SE40.4B
Thermostats for Pipeline and Vessel Heating Circuits
Table of Contents
1.
2.
3.
4.
5.
6.
Scope...................................................................................................................................................................2
Applicability........................................................................................................................................................2
Benefits ...............................................................................................................................................................2
General ................................................................................................................................................................2
Application..........................................................................................................................................................2
References..........................................................................................................................................................3
List of Tables
Table 1. Manufacturers and ratings..........................................................................................................................4
Page 1 of 5
1.
SE40.4B
Thermostats for Pipeline and Vessel Heating Circuits
Scope
This specification describes the DuPont requirements for weatherproof and explosionproof
thermostats used to control heating circuits installed on pipelines or vessels. Although other
enclosures are available, their use is limited within DuPont for this application, so they are not
described in this specification.
For further design and application information, see DE6H.
2.
Applicability
The thermostats described in this specification are for use in pipeline heating applications in
ordinary (nonhazardous) and classified (hazardous) areas. Listings are provided for North
America and European equipment for global use.
3.
Benefits
Use of this specification provides a ready cross-reference of thermostats available from Alliance
Suppliers that will simplify and improve accuracy of the selection process.
4.
General
A thermostat may be used in some pipeline and vessel heating installations to control system
temperature by turning the heat-tracing system on or off. The contact(s) of the thermostat opens
when a preset temperature is reached and closes at some lower temperature depending on the
temperature differential (deadband) of the unit.
Thermostats can also be used where process fluid temperatures must not be exceeded and to
limit the pipe maximum temperature in hazardous area applications (refer to Controlled design
as defined in IEEE-515, clause 6.5(b) and DE1H.
Depending on the load requirements, the thermostat may be used to control the heat-tracing
circuit directly. However, when the circuit current or voltage exceeds the thermostats rating, the
thermostat is used to switch a power control device (e.g., a magnetic contactor).
5.
Application
For ambient temperature-sensing applications, locate the thermostat in a protected location away
from direct sunlight, wind, or influences of external heat.
Contact the manufacturer for availability of longer capillary lengths. These are required to locate
thermostats at easily accessible locations.
Aluminum heat transfer tape, readily available from Thermon and Tyco Thermal Controls,
provides an effective method of attaching the thermostat capillary or resistance thermal detector
(RTD) to the pipeline or equipment.
For manufacturers and applicable ratings, see Table 1. Listings are provided for standard catalog
thermostats from the two DuPont Strategic Alliance Suppliers for electric heat-tracing systems
(Thermon and Tyco Thermal Controls). Information is provided for both U.S. and European
installations.
Page 2 of 5
SE40.4B
6.
References
DuPont Design Standards
Links to the following standards are only available from this section.
DE1H
DE6H
Other References
ANSI/IEEE 515
7.
Manufacturers
Refer to the DuPont Intranet, Sourcing/Best Acquisition Process for additional information.
Tyco Thermal Controls
300 Constitution Avenue
Menlo Park, CA 94205-1164
Thermon Industries
100 Thermon Drive
P.O. Box 609
San Marcos, TX 78667-0609
Page 3 of 5
Enclosure
rating
Copyright 2001, 2008 E.I. du Pont de Nemours and Company. All Rights Reserved. Used under Copyright License.
NEMA 4X
E4X - 25325
NEMA 4X
JBS-100-ECW-A
(wall mounted)
NEMA 4X
NEMA 4X
JBS-100-ECP-A
(pipe mounted)
E4X - 35235
NEMA 4X
Raystat-EX-03-A
NEMA 4X
NEMA 4X
AMC - F5
E4X - 1
NEMA 4X
AMC - 2B-2
NEMA 4X
NEMA 4X
AMC - 1B
B4X - 15140
NEMA 4X
AMC - 1A
Note:
a
AB indicates air break contact
(continued)
Thermon
Tyco Thermal
1.1C to
6.7C
1.1C to
6.7C
1.1C to
6.7C
1.1C to
6.7C
-4C to 163C
(25F to 325F)
2C to 113C
(35F to 235F)
2C to 113C
(35F to 235F)
-9C to 60C
(15F to 140F)
-0C to 218C
(32F to 425F)
-0C to 218C
(32F to 425F)
SPDT
DPST
SPST
DPDT
External knob
w/cover
Fixed at
4.4C(40F)
Internal
thumbwheel
switches
3.9C
5C
5C
SPDT
SPST
SPST
SPDT
Internal w/dial
Internal w/dial
Internal w/dial
Internal w/dial
3.3. C
SPDT
480 V ac
480 V ac
480 V ac
480 V ac
240 V ac
480 V ac
240 V ac
480 V ac
480 V ac
22 A
30 A
30 A
22 A
16 A
22 A
22 A
22 A
22 A
S/S
Nickel
plated
copper
Nickel
plated
copper
S/S
Ambient
sensing
thermostat
Comment
Fixed amb.
sensing
thermostat
T-Stat &
power conn.
kit
T-Stat &
power conn.
kit
1.8 m
(6ft)
1.7 m
(5.5 ft)
Amb sensing
thermostat
Pipe maint or
ambient
sensing
controller
0. 8 m
(30 in.)
(Not included)
S/S
S/S
Tinplated
copper
S/S
S/S
S/S
Std.
Length
Capillary/RTD
External knob
w/cover
External knob
w/cover
Temp.
adjustment
1% of
-40C to 40C
(-40F to 105F) setpoint
4.4C (40F)
Nonadjustable
-4C to 163C
(25F to 325F)
-4C to 163C
(25F to 325F)
-9C to 60C
(15F to 140F)
Temp. range,
C (F)
Switch (es)
Table 1.
Temp.
differential
(deadband)
SE40.4B
Page 4 of 5
Enclosure
Rating
Temp. range,
C (F)
Temp.
differential
(dead-band)
Temp.
adjustment
Poles
and
throw
External knob
w/cover
3.3. C
3.9C
5C
5C
5C
4X/7 350235JB
E4X/7 35235JB
E4X/7 200600JB
Copyright 2001, 2008 E.I. du Pont de Nemours and Company. All Rights Reserved. Used under Copyright License.
EX 03-A
IP66
0C to 499C
Internal Digital
thumbwheel
Internal w/dial
Internal w/dial
Internal w/dial
External knob
w/cover
DPDT
SPST
SPST
DPST
SPDT
SPDT
DPST
SPDT
SPDT
277 V ac
480 V ac
480 V ac
277 V ac
480 V ac
480 V ac
240 V ac
480 V ac
480 V ac
Notes:
a
Rated EEX e m ia II C T6, intrinsically safe RTD sensor, encapsulated electronics and power relay
b
AB indicates air break contact
Tyco Thermal
Min 1C
External knob
w/cover
1.1C to
6.7C
E507S 2LS-2
External knob
w/cover
1.1C to
6.7C
External knob
w/cover
1.1C to
6.7C
AMC - 1H
Thermon
Tyco Thermal
16 A
30 A
30 A
25A
22 A
22 A
22 A
22 A
22 A
Maximum Maximum
Volts
Amps
S/S
Nickel
plated
copper
Nickel
plated
copper
Nickel
plated
copper
S/S
S/S
Line sensing
thermostat
2 m (6 ft)
Line sensing
thermostat
3 m (10 ft)
S/S
Line sensing
thermostat
Ambient sensing
thermostat
Comment
2.7 m (9ft)
Std. Length
S/S
S/S
Material
Capillary/RTD
Table 1.
Hazardous/nonhazardous area Applications / U.S (Class I Group B,C, and D/Class II, Groups E,F, and G/Class III)
Manufacturer
Catalog
number
Switch (es)
SE40.4B
Page 5 of 5