PLC Input - Output Wiring Methods
PLC Input - Output Wiring Methods
PLC Input - Output Wiring Methods
Experiment #2
PLC Input Output Wiring Methods
OBJECTIVES
After successfully completing this laboratory, you should be able to:
Read and explain the nameplate of DELTAs PLC DVP Series Model.
Make different types of PLC input wiring.
Make different types of PLC output wiring.
1. Basic Information
1.1.
Nameplate Explanation
Model Explanation
Fig. 2.2 Delta programmable logic controller name plate model explanation.
1.2.
9
10
11
12
13
14
15
Output indicators
Status indicators, POWER, RUN ERROR
I/O terminal cover
I/O terminal cover
I/O terminal nameplate panel
I/O terminal nameplate panel
RS-485 Communication port
1.3.
Wiring Guidelines
AC Input Type
The +24V supply output is rated at 0.4 Amperes. DO NOT connect external power
supply to this terminal.
FUSE Protection: there are internal fuses on all DVP PLCs. However, the fuse does
not guarantee the prevention of DVP PLC damage, but it will provide added
protection.
DC Input Type
For example, we simply connect the common terminal S/S to the supply source(+).
By adding the switch, between the supply(-) and the input, we have completed the
circuit. Below are two circuit diagrams showing both the sinking and sourcing inputs.
Be careful with the connection of the common terminals when wiring output
terminals. For example, when wiring DVP14ES00R, note that there are six
normally-open SPST relays available. They are organized into 4 groups with
individual commons. The figure below shows the relays and the internal wiring of
the PLC. Note that each group is isolated from the other groups:
10
C0
Y0 C1
Y1 C2
Y2
C3
Y3
Y4
Y5
Fig. 2.10 relays groups and the internal wiring of the PLC.
11
1.
2.
3.
4.
DC supply.
Emergency stop.
Fuse.
If Y0 is used as a pulse train output with PLSY, use a pull up resistor to ensure the
output current is greater than 0.01A for correct operation.
5. If Y1 is used with PWM, use a pull up resistor to ensure the output current is greater
than 0.01A for correct operation.
6. Mutually exclusive outputs: use external hardware interlocks, as well as those in the
PLC program, for maximum safety.
7. Unused terminal: do not connect.
2. Equipments
DVP14ES00R
1x10A mcb.
230V(coil), 50Hz, 10A Relay
Green and red indicator lamp.
NO and NC pushbuttons.
ON-OFF switch.
Flexible wires.
Single phase power source.
Control board.
3. Procedure
1. Assemble the components of the control circuit on the control board and make the
required wiring and connections as shown in figure 2.13.
12
SW3
SW2
SW1
mcb 1x10A
PB2
PB1
Pulser
N
220V/50Hz L
S/S
X4
X5 X6 X7
X0 X1
X2 X3
N
DVP-14ES
+24V
Y0
24G
Y1
Y2
Y3
Y4
C0
C1 C2
C3 Y5
+24VDC
L1
R1
L2
R2
220V/50Hz
COIL
220V/50Hz
COIL
220V/50Hz
220V/50Hz
24GND
Fig. 2.13 The power circuit diagram for a direct on line starter
2. Make the required wiring and connections for the power circuit as shown in figure
2.14.
+24V
R2
R1
Left
D1
D2
LSL
LSR
R2
R1
GND
3. Once you are finished with the connections, call the instructor to check it for you
and make sure that it is correct.
13