Basic Principles
The availability of an acceptable building is
an important requirement for the
operation of the school.
To be acceptable, a building shall be safe,
sanitary and adequate.
A safe school building is structurally stable
to resist lateral forces, such as strong
winds, earthquakes, etc.
Gabaldon Type
Army Type
Magsaysay Type
Marcos Type
Bagong Lipunan
RP-US Bayanihan
ESF Bldg.
Imelda Type
Pagcor Bldg.
(7X9) minimum
(6X7)
(6X7)
(6X7)
(6X8)
(7.35X6)
(6X8)
(6X8)
(6X8)
GOJ-TRSBP Bldg.
(8X6.25)
GOJ-EFIP Bldg.
(8X7)
SEDP Bldg. (CarinoType)
(8X7)
Multi-Purpose Workshop Bldg. (7X18)
DECS 1 room Bldg.
(7X8)
FVR 2000 (Fabricated Vigorous Room
2000) (7X8)
Federation of Filipino Chinese Chamber of
Commerce and Industry Inc. (FCCCII)
(7X7)
CURRENT DESIGN
STANDARDS for
EDUCATIONAL FACILITIES
BUILDING
DESIGN
BASIC
FEATURES:
TYPE I
TYPE II
TYPE III
With toilets
(male/female)
at the ground
floor only
With toilets
(male/female)
for every
floor; steel
casement
window type
With toilets
(male/female
) for every
floor; jalousie
window type
I
TYPE II
REVISED DESIGN
160mm x 400mm
COLUMN SIZE (single
storey
200mm x 300mm
COLUMN SIZE (single
storey)
1. Roof
PRE-PAINTED LONGSPAN
Corrugated G.I. Sheet
0.40mm PRE-PAINTED
LONGSPAN Corrugated
G.I. Sheet
2. Eaves
3. Windows
4. Windowsill
5. Doors
B. Exterior Finish
REVISED DESIGN
C. Interior Finish
1. Flooring
Reinforced concrete
The floor must be of
slab with plain cement non-skid finish
finish
2. Ceiling
thk Ordinary
Plywood
No standard design
for blackboards
With Blackboards as
specified
No exterior ceiling
vent (Single Storey,
Type II)
2 - 9000mm X
275mm reqd area
for 1 classroom
E. OTHERS
1. Ceiling Vents
dimension
2. Balcony
railing
REVISED DESIGN
E. OTHERS
4. Ramps
No railings on single
storey
Provision of Railings
1. Toilet for
Persons w/
disabilities
(PWD)
2. Lavatory
E. TOILETS
REVISED DESIGN
F. Electrical
Provisions
4 units of 2-40watt
Fluorescent Lamp
4 units of 2-40watt
Fluorescent Lamp or
Light Emitting Diode
(LED) lamps
G. Plumbing
Provisions
2 chambers only
3 chambers
2. Waterline
piping system
Polypropylene
Random (PPR) type
3 pipe and ASTM
A120
3. Drainage
system
No rainwater collector
Provision shall be
made for the
installation of
rainwater collection
system in compliance
with RA 6716
1. Septic vault
Classroom
-1.40 sq.m./place
Science Laboratory
-2.10 sq.m./place
School Shops - will vary on the subject
area with a minimum of 2.50 sq.m to a
maximum of 7.00 sq. m./place
900mm
900mm
STANDARD
TOILET DESIGNS
ONE SEATER
(DETACHED)
(ATTACHED)
TWO SEATER
(DETACHED)
(ATTACHED)
THREE SEATER
TYPE I (Standard,
2cubicle(1male/1female), 1-cubicle
for DAP)
TYPE II (2 cubicle(1male/1female),
1-cubicle for DAP, 4-unit of faucets on
the hand washing
TYPE III (1 cubicle for male, 2 cubicle
for female, 4-unit of faucets)
FOUR SEATER
1cubicle for male
2cubicle for female
1cubicle for Differently
Abled Persons (DAP)
CURRENT DESIGN OF
HANDWASHING
GREEN SCHOOL
BUILDING DESIGNS
1CL ON-STILT
TYPE
4CL ON-STILT
TYPE
ACTUAL PHOTO
DOORS
ACTUAL PHOTO
Floor
ACTUAL PHOTO
PAINTING &
FINISHES
ACTUAL PHOTO
EXISTING
DEPED
STANDRAD
SPECIFICATIO
NS
MINIMUM
PERFORMANCE
STANDARD &
SPECIFICATIONS
(MPSS)
CHALCKBOARDS
ACTUAL PHOTO
The minimum
horizontal clear length
of eaves (excluding
gutter, if introduced)
shall be: front = 1.50
m; rear = 1.0 m; and
sides = 0.6 m i.e. no
interior gutter. For the
2-storey building,
maintenance access to
the roof cavity must be
through the corridor.
ACTUAL PHOTO
EXISTING DEPED
STANDRAD
SPECIFICATIONS
MINIMUM
PERFORMANCE
STANDARD &
SPECIFICATIONS
(MPSS)
CIRCULATION &
EMERGENCY
EGREES
CORRIDOR
The minimum
corridor width shall
be 2.50 m for multistorey school
building types
ACTUAL PHOTO
ACTUAL PHOTO
PLUMBING WORKS
Waterline piping
system
The system must be
according to E DIN1988 for
Polypropylene Random
Copolymer (PP-R) type 3
pipe and ASTM A53/A53M.
The system must provide
for a waterline service
entrance.
ACTUAL PHOTO