Proservo NMS5
Intelligent Tank Gauge with High Accuracy Performance
Liquid Level, I/F, Density & Density Profile Application
Oil (fuels)
LPG/LNG
Chemicals
Water / chemical interface measurement
Alcohols
Tank mounted intelligence makes the NMS5 ideal for single
or multi-task installation, converting a wide range of
measurement functions including:
Liquid level
Interface level
Spot density
SIL2 Certified
Measures liquid to an accuracy of +/- 0.7 mm
Measures two clear interface levels and specific gravity of
Density profile
Tank bottom
Water dip
TI 00452G/08/EN/05.13
71240040
Software Ver. V.4.27G
Proservo NMS5
Table of Contents
Storage Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Liquid Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Degree of Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Application Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Displacer Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Displacer Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Recommended Displacer by Application . . . . . . . . . . . . . . . . . . . 8
Point to Confirm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Custody Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Material Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Process Connection Size: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Mechanical Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Design and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Housing Materials of Construction . . . . . . . . . . . . . . . . . . . . . . 24
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Flange Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Measuring Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Displacer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Input for Local Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Human Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Operating Concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Display (LCD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Memo Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Output Parameters based on Communication Protocol . . . . . . .10
RS485 Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Bidirectional Serial Pulse (V1 Protocol). . . . . . . . . . . . . . . . . . . 11
HART Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Whessoematic 550 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Mark/Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Enraf Bi Phase Mark (BPM) . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Analogue Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Auxiliary Energy/Electrical for Primary Output . . . . . . . . . 15
V1 Serial Pulse Modbus RS 485 HART Enraf BPM . . . . . . . . . . .15
Whessoematic 550 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Mark/Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Safe Electrical Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Performance Characteristics . . . . . . . . . . . . . . . . . . . . . . . . 19
Maximum Measured Error . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Operating Conditions: Environment . . . . . . . . . . . . . . . . . . 20
Modbus (RS485 Output) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Sakura V1 Serial Pulse Ouput . . . . . . . . . . . . . . . . . . . . . . . . . .20
Enraf Bi Phase Mark Output . . . . . . . . . . . . . . . . . . . . . . . . . . 21
HART Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Whessoematic 550 (WM 550) Output . . . . . . . . . . . . . . . . . . .21
Varec Mark Space (M/S) Output . . . . . . . . . . . . . . . . . . . . . . . 22
Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Advanced Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Prediction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Proactive Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
27
27
27
32
32
34
35
37
Supplementary Documentation. . . . . . . . . . . . . . . . . . . . . .
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional Safety Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
38
38
38
38
38
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Stainless Steel Conversion Table . . . . . . . . . . . . . . . . . . . . . . . 39
Endress+Hauser
Proservo NMS5
NMS5 is an intelligent tank gauge for measuring liquid levels with high precision, and employing the latest
microprocessor technology. In addition to gauging level, NMS5 can measure the interfaces between up to three
liquids, specific gravity of each and discern tank bottom. To enable accurate volume calculation or simple indication, NMS5 will accept input from either an average temperature probe NMT 53x series (via twisted pair
cables, HART protocol) or spot temperature element (via 3 wire Pt. 100 RTD signal). Once installed, all calibration and operating functions can be done via the user friendly Matrix program and touch sensitive keypad.
Tank side monitoring and operation can be performed by the Promonitor NRF 560.
NMT539
NMS5
HART
Temp.
Level
Interface
Density
Water Dip
Bottom
NRF560
Power
(AC / DC)
HART
HART
to HOST System
in Control Room
Figure 1:
Endress+Hauser
Measuring System
Proservo NMS5
System Configuration
From single tank level measurement to the largest oil refinery applications, NMS5 can be an integral part of
tank farm management solutions. A wide variety of data output protocols are available for seamless
integration into many commonly used systems.
A primary example is Endress+Hausers revolutionary Tankvision., A scalable concept, offering local tank
management for up to 225 tanks via Modbus, V1 or Whessomatic 550 protocols. Accumulated data is
available to DCS and other plant management systems via a Host Link.
Output protocols
Modbus, RS485 or current loop
V1 serial pulse
Whessomatic 550
local HART
Mark/Space
Enraf BPM
Modbus
SCADA
DCS/PLC
Host Link
$EVICE#ONlG
LAN
TCP/IP
Data Concentrator
Data Scanner
Data Scanner
(Field Protcol)
V1, Modbus
HART
Figure 2:
Major Application
HART
HART
The number of measuring functions and output options as well as the lightweight compact design enables
NMS5 to be installed in a wide range of applications at minimal cost.
Petroleum Industry
From oil production to storage at an oil depot, there exists an extensive need to measure and manage a wide
variety of products. Remote tank gauging and an inventory management system combined into NMS5 and a
receiving computer is an ideal way to measure and manage tank contents.
Chemical Industry
A wide choice of products are available in the wetted parts construction manufacturing industry, to ensure
chemical compatibility and long life.
Power Plant
Fuel oil levels are a major applications where precise measurement is required to ensure safe operation.
Endress+Hauser
Proservo NMS5
Operating Principle
Hall Element
Weight Data
Measurement
Wire
Displacer
Position
Data
CPU
Motor
Displacer
Figure 3:
Endress+Hauser
Proservo NMS5
NMS5
E
E-+
NMT539
NMT539
Ball Valve
Reducer
Measuring Wire
Measuring Wire
Displacer
Displacer
Stilling Well
Figure 4:
Stilling Well
Note!
When NMS5 is installed in the floating roof tank,
ensure to use a stilling well.
NMS5
E
NMS5
+
E
NMT
Measuring Wire
Measuring Wire
Displacer
Displacer
Stilling Well
Figure 5:
Endress+Hauser
Proservo NMS5
Measurement Terminology
Level
Upper
Density
Upper I/F
Middle
Density
Middle I/F
Lower
Density
Tank Bottom
Figure 6:
NMS5 with standard level, I/F x 2, Tank bottom and spot density x 3 measurement
I/ F Projle
True Average Density
within Upper Layer
Tank Projle
True Average Density
throughout Tank
Level
Oil
Upper I/F
Emulsion
Water
Figure 7:
Endress+Hauser
Tank Floor
Density Profile measurement "I/F (Interface) Profile" (Left) "Tank Profile" Measurement Range (Right)
Proservo NMS5
Application Selection
Displacer Selection Guide
A wide variety of displacers are available to meet your applications. Proper displacer selection ensures optimal
performance and longevity. The following guidelines will assist you in selecting the ideal displacer for your
application.
Displacer Types
30mm
40mm
50mm
70mm
110mm
Alloy C
PTFE
Recommended Displacer by
Application
Application
Surface
Interface
Density
Viscous
50mm PTFE
Not
Recommended
Not
Recommended
Crude
50mm 316
50mm PTFE
50mm 316
50mm PTFE
50mm 316
50mm PTFE
Black oil
50mm 316
50mm 316
50mm 316
White oil
50mm 316
50mm 316
50mm 316
70mm 316
70mm 316
50mm 316
50mm Alloy C
50mm PTFE
50mm Alloy C
50mm PTFE
50mm Alloy C
50mm PTFE
70mm 316
110mm 316
N/A
N/A
Aggressive
Custody Transfer
Note!
The above table is for 80A (3") mounting flange or larger.
Endress+Hauser
Proservo NMS5
Point to Confirm
Application:
What will be the primary measurement function in your application? Most applications can be generalized into
three classifications: level data, density data, or both. NMS5 is primarily a highly accurate level measurement
gauging instrument, with the added ability to measure density. Level is derived by determining fluid surface
level, interface level(s) between different liquids, as well as finding tank floor or datum plate. Density served
from single-point (called spot measurements), as well as profile measurements of all liquid(s) in a tank.
Surface Level:
In general, larger diameter displacers have better accuracy under similar conditions.
Interface Level(s):
Cylindrical-shaped displacers, with rounded top and bottom, reduce resistance while moving through liquid(s).
Thus, providing smoother movement and faster interface measurements, compared to flat-based displacers,
particularly in density profile measurements that span the full tank height. Note that, in order for a displacer
to travel down through liquid(s), displacer density (its weight divided by its volume) must be higher than liquid(s) density.
Tank-bottom/Datum Plate Level:
(same as for Interface Levels)
Density:
Since the density is the calculated result of two of more measurements, a displacer with higher volume will
usually yield the most accurate density measurement. In most cases we recommend our 50mm diameter
displacer for density measurement.
Level and Density:
When an application calls for equal importance placed on measuring both level and density, the 50mm
diameter, cylindrical displacer will give the best all-around performance.
Custody Transfer
Material Compatibility
What are the liquid(s) characteristics of your application? Displacers are available in three different standard
materials. Material compatibility should be confirmed to ensure safe operation and optimal NMS5
performance.
316:
Stainless steel is a highly versatile industrial material and provides good compatibility with a wide range of
chemicals, including most white and black oils.
Alloy C:
This high-performance material is harder than 316, and provides excellent resistance to many of harshest
corrosive chemical applications.
PTFE:
One of the most well-known and versatile polymer materials, this high-performance material has one of the
lowest friction coefficients. It provides excellent performance in viscous/sticky liquids, and also has excellent
chemical resistance to a wide range of corrosives
Process Connection Size
Endress+Hauser
The process connection defines the tank process entry, and may affect displacer size. The standard NMS5
process connections start at 3/DN80 and fit most tank gauging applications. Accordingly, most applications
can be covered with one of the 50mm or 70mm displacer options. Smaller diameter displacers are available
when the process connection is smaller. Note that, when the 110mm diameter custody transfer approval (PTB)
displacer is selected, a separate calibration and maintenance chamber is recommended between the NMS5 and
tank process connection.
Proservo NMS5
Input
Input for Local Devices
Signal
Power supply
DC 24V
Additional units
Output
Output Parameters based on
Communication Protocol
V1(new)
V1 (old)
MODBUS
HART
WM550
ENRAF
M/S
Level
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Temperature (Product)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Vapor Temperature
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Middle I/F
Yes
Yes
Yes
Upper Density *2
Yes
Yes
Yes
Yes
Middle Densuty*3
Yes
Yes
Yes
Lower Density*4
Yes
Yes
Yes
Average Density *5
Yes
Yes
Yes
Yes
Yes
Multi-Element Temperature
Yes
Yes
Yes
Yes
--
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Alarm data
Yes
Yes
Yes
Yes
Yes
Yes
KA0002N
KA001N
Protocol Documentation
Note!
Upper I/F output value can be either selected from the Proservos own displacer measurement or Water
Bottom measured value via the Prothermo NMT 539.
A single point density measurement within the upper layer liquid in the tank. The measurement position is
configured to 150mm below the liquid surface at default.
A single point density measurement within the middle layer liquid in the tank. The measurement position is
configured to 150mm below the upper interface level at default.
A single point density measurement within the lower layer liquid in the tank. The measurement position is
configured to 150mm below the middle interface at default
The value of this Average Density is based on the calculation after performing the Density Profile operation
at the Proservo.
All of the selected number of density measured value from 1 ~ 16 points can be transmitted.
10
Endress+Hauser
Proservo NMS5
RS485 Modbus
Module name
No. of unit
Baud rate
Parity
Cable
Topology
Transmission distance
Instrument address
Isolation
Module name
COM - 1
No. of units
Baud rate
3,300 BPS
Cable
Topology
Transmission distance
Maximum 6,000 m
Instrument address
Isolation
Module name
No. of units
Baud rate
1,200 BPS
Cable
Transmission distance
Maximum 1,200 m
Instrument address
Isolation
HART Protocol
Endress+Hauser
11
Proservo NMS5
Whessoematic 550
Module name
No. of units
Baud rate
Cable
Topology
20 mA current loop
Transmission distance
Instrument address
Isolation
Module name
No. of units
Baud rate
Cable
Four wire
Topology
Transmission distance
Instrument address
Isolation
Module name
COM - 3
No. of units
Baud rate
Cable
Topology
Transmission distance
Maximum 10 km
Instrument address
Isolation
Mark/Space
12
Endress+Hauser
Proservo NMS5
Analogue Output
Module name
I/O - 5
Output
On alarm
Electrical isolation
Maximum load
500 ohm
Load effect
Negligible
Module name
I/O - 3
Relay
Open
Closed
On Alarm
Closed
Open
On Device Error
Closed
Open
Custody
Transfer
Closed
Custody
Transfer
Open
Power Outage
Endress+Hauser
13
Proservo NMS5
Alarm output ,
Overspill prevention
(Order Code position 050=4)
Closed
On Alarm
Open
On Device Error
Open
Open
Power Outage
Open
Switching capacity
Umax. 200VDC/200VppAC
Imax. 0.5AC, DC or peak AC
Pmax. 15W
Operation Input
14
CTR1
CTR2
LEVEL
0 (OFF)
0 (OFF)
UP
1 (ON)
0 (OFF)
STOP
0 (OFF)
1 (ON)
INTERFACE LVEL
1 (ON)
1 (ON)
Input voltage
Input current
Approximately 5mA
Endress+Hauser
Proservo NMS5
Auxiliary Energy
Electrical for Primary Output
V1 Serial Pulse
Modbus RS 485
HART Enraf BPM
L
L
N
Power Supply
AC 85...264V 50/60Hz
or
DC 20...62V
AC 20...55V
Alarm Contact
Alarm Contact
4 ... 20mA
Channel 2
Port_A +
Local HART
Port_A (see Caution!.)
G
Alarm Contact
0TSPOTTEMP
Port_B +
Non IS HART to NRF or others
Port_B Digital Output
RS485,
V1 Serial Pulse
or Remote HART
Alarm Contact
Terminals 4 & 5
Digital Output:
Terminals 6 & 7
- V1 serial pulse
- Modbus (RS485)
- HART
- Enraf BPM
Operation
Contact
Input
4 ... 20mA
Channel 1
Ex ia local (slave) HART, or
Pt100 3 wire spot RTD (see Caution!.)
4 to 20mA Output:
Terminals 20 & 21, 22 & 23
Note:
Terminals 22 & 23 will be used as Status 1 Input
WHENSIGNALINPUTFROMlELDUNIT/RDERCODEPOSITION IS
4: HART and Status 1 input
5: HART, Pt100 Spot and Status 1 input
6: HART, Pt100 Spot temp., Operation cntact, and Status 1 input
Refer to ordering information.
Caution!
Terminal connection for Whessoe Matic 550 (WM550) and Mark Space, refer to the next few pages.
4ERMINALSANDFOR(!24DEVICESAREINTER
CONNECTEDON%XPLOSIONPROOF%XD CERTIlEDVERSION
Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
ONLYWHENINTRINSICALLYSAFECERTIlEDVERSIONISSELECTED
Figure 8:
Endress+Hauser
15
Proservo NMS5
Whessoematic 550
WM550
Channel 2
Ex d Local HART
(see Caution!.)
WM550
Channel 1
Ex d local (slave) HART or
Pt100 3 wire spot RTD (see Caution!.)
Terminals 4 & 5
Caution!
4ERMINALSANDFOR(!24DEVICESAREINTER
CONNECTEDON%XPLOSIONPROOF%XD CERTIlEDVERSION
Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
ONLYWHENINTRINSICALLYSAFECERTIlEDVERSIONISSELECTED
Figure 9:
16
Endress+Hauser
Proservo NMS5
Mark/Space
L
L
N
Mark
Power Supply
AC 85...264V 50/60Hz
or
DC 20...62V
AC 20...55V
Space
Port_A +
Local HART
Port_A (see Caution!.)
G
G
N
Port_B +
Non IS HART to NMT or other
Port_B -
Operation
Contact
Input
04SPOTTEMP
Mark/Space
Terminals 4 & 5
M/S output:
Terminals 20 &21, 22 & 23
M/S is the serial pulse digital data transmission along with separate
power supply circuit. Since these 4 terminals are occupied by M/S
terminal connection, 4 - 20mA output and status 1 input function
are no longer available.
Caution!
4ERMINALSANDFOR(!24DEVICESAREINTER
CONNECTEDON%XPLOSIONPROOF%XD CERTIlEDVERSION
Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
ONLYWHENINTRINSICALLYSAFECERTIlEDVERSIONISSELECTED
Endress+Hauser
17
Proservo NMS5
Cable Entry
Thread: G , ,
NPT , ,
M20, 25
*TIIS: G only, CSA: NPT only
Supply Voltage
Caution!
Allowable voltage supply is specifically stated depending on each Ex approval. Refer to the designated
certification
Power Consumption
Between power supply and signal output, CPU, RS 485, relay and other electronics
18
Endress+Hauser
Proservo NMS5
Performance Characteristics
Maximum Measured Error
Level
Interface
Density
0.005 g/cm3 *3
Sensitivity
Displacer
Automatic compensation of displacer weight
Tank Wall
Compensation of depression and distortion
Endress+Hauser
19
Proservo NMS5
Termination Resistors
Set terminators as required in specific enviroments.
Bus Address
Each transmitter has an individual bus address configured in the software of the transmitter.
Bus Cabling
The bus cabling is galvanically isolated from the transmitter and the PC plug-in board or the interface adapter.
The screening must be grounded and have electrical continuity throughout.
Bus Topology
When planning a system, attention should be paid to possible segmentation of the bus according to individual
plant sections. Suitable topologies are:
Tree of total length 1200 m
The bus is connected to a RTU8, Tankvision or other Endress+Hauser V1- type receiver. The interface or
receiver must be configured accordingly.
Termination Resistors
It is not necessary to set any termination resistors for serial pulse output.
Bus Address
Each transmitter on a signal loop has an individual bus address. This is defined within the transmitter software.
Bus Cabling
The bus cabling is electrically isolated from the transmitter and from the interface receiver.
Standard communication cable (non-shielded twisted pair cable) can be used for the data transmission.
Bus Topology
The suitable topologies for the serial pulse output are:
Serial max. 6000 m (Sakura V1)
Tree of total length 6000 m. (Sakura V1)
20
Endress+Hauser
Proservo NMS5
The bus is connected to an Enraf I/F CIU or RTU8 to transmit measured value to upper host system as Entis
(Enraf TG program) or Fuels Manager. These interface must be configured accordingly.
Termination Resistors
It is not necessary to set any termination resistors for serial pulse output.
Bus Address
Each transmitter on a signal loop has an individual bus address. This is defined within the transmitter software.
Bus Cabling
The bus cabling is electrically isolated from the transmitter and from the interface receiver. Standard
communication cable can be used for the data transmission.
Bus Topology
The suitable topologies for Enraf BPM serial pulse output are:
Serial max. resistance: 400 ohm at 3 bus loops or less (10 transmitters per 1bus loop)
Serial max. capacitance: 1 micro F or less
Data Transmission & Operation
NMS5 is capable to transmit following sensory data as well as gauge operation command via Enraf BPM serial
pulse output.
Data: level, temperature, operation status
Gauge command: STOP, UP, LEVEL, I/F
HART Output
The bus is connected to a HART master. The HART master must be configured accordingly.
Bus Address
Each transmitter on a signal loop has an individual bus address. This is defined within the transmitter software
and / or auxiliary configuration environment such as host system or Field Communicator 375.
Bus Cabling
The bus cabling is galvanically isolated from the transmitter and the PC plug-in board or the interface adapter.
The screening must be grounded and have electrical continuity throughout. EMC tests indicate the best result
when the grounding at both ends and each transmitter is established. If there is a potential difference in
between the grounds, measurement must be taken to equalize whilst observing a relevant hazardous area.
Bus Topology
The suitable topologies are:
Serial max. 1000 m
Tree of total length 1000 m.
The bus is normally connected to Whessoe 1098, RTU 8 or other upper host system via dual channel (can be
single) WM550 current loop.
Termination Resistors
Admissible termination resistance should be calculated as follow.
R = [Va - {n x (Vb + Vc)}] / 0.02
R = terminal resistance in the system
n = number of transmitter in the system
Va = max. available voltage at receiver
Vb = voltage drop across transmitter
Vc = voltage drop across receiver
Endress+Hauser
21
Proservo NMS5
Bus Address
Each transmitter on a signal loop has an individual bus address. This is defined within the transmitter by
mechanical dip switch on com board.
Bus Cabling
The bus cabling is galvanically isolated from the transmitter and the PC plug-in board or the interface adapter.
BS5308 or equivalent 1.5sq.mm screened twisted pairs are recommended for bus cabling.
Bus Topology
The suitable topologies for the WM550 current output are depending on number of transmitter & cable quality
on the loop. Recommended number of transmitter on single loop shall be less than 15 units to achieve the
maximum performance.
Varec Mark Space
(M/S) Output
The bus is normally connected to Interface Unit (IFU), Data acquisition Processor (DAP), RTU 8 or other upper
host system via 4 wire M/S serial bus link.
Termination Resistors
Admissible termination resistance should be calculated as follow.
R = (48 - 33) / {60mA + N (2.0mA)}
R = terminal resistance in the system
N = number of transmitter in the system
48 = supply voltage to receiver
33 = minimum M/S board operation voltage
60mA = required current for system operation
2.0mA = required current per transmitter
Bus Address
Each transmitter on a signal loop has an individual bus address. This is defined within the transmitter by
mechanical dip switch on com board.
Bus Cabling
The bus cabling is galvanically isolated from the transmitter and the PC plug-in board or the interface adapter.
The total length of field wiring shall be determined by calculation of maximum resistance within the system &
required operation current. Once the total length is determined, distance has to be reduced by half because
of current flow in both B+ & B- leads.
Bus Topology
The suitable topologies for the M/S serial pulse output are depending on number of transmitter & cable quality
on the loop.
Ambient Temperature
Storage Temperature
Liquid Temperature
Degree of Protection
IP 67 with closed housing and cable glands of equal protection type... (ATEX/TIIS)
NEMA 4X...(FM/CSA)
22
Endress+Hauser
Proservo NMS5
NMS5-1
NMS5-2
NMS5-4
NMS5-5
NMS5-6
Measuring Range
Level
28m
Standard Option
36m
Standard Option
47m
Standard Option
Density
0.430 to 2.000 g/cm3
Endress+Hauser
23
Proservo NMS5
Mechanical Construction
Design and Dimensions
NMS5 - 1/ NMS5 - 4
Max. 39.7mm
Travel Distance of Displacer
34.6mm for 28m Wire (0.15mm)
39.7mm for 36m Wire (0.15mm)
$ISPLACERPOSITIONATTOPOFTANKCENTEROFmANGE
Displacer position at bottom of tank
Max. 41.6mm
Travel Distance of Displacer
34.6mm for 28m Wire (0.15mm)
39.7mm for 36m Wire (0.15mm)
41.6mm for 47m Wire (0.15mm)
Electrical Compartment
Terminal Box
Display (LCD)
Cable Entery (A, B, C, D)
Wire Drum Husing
Flange
Measuring Wire
Displacer
Calibration Window
Window Cover
Touch Control
$ISPLACER0OSITIONAT4OPOF4ANK#ENTEROF&LANGE
Displacer Position at Bottom of Tank
Housing Materials of
Construction
Weight
NMS 5-1/5-4 : 12 kg
NMS 5-2/5-5/5-6 : 27 kg
Flange Type
ANSI, JIS, DIN 3" and 6" (standard) or equivalent. Refer to order code for full selection.
Flange for NMS5-1/5-4: aluminum
Flange for NMS5-2/5-5/5-6: stainless steel 304
Measuring Wire
Material (standard)
Note!
When liquid level in a tank becomes turbulent condition, use a stilling well pipe or a guide wire for installation.
24
Endress+Hauser
Proservo NMS5
Displacer
Feature: 070
Horizontal Movement
Distance (mm/m) on
Drum Wire
1.24
1.34
1.57
1.10
1.57
0.88
Cable Entry
Cable Entry A
Cable Entry B
Cable Entry C
Cable Entry D
Caution!
When ordering TIIS Ex d specification, cable glands are attached with NMS5. Ensure to use the cable glands.
Endress+Hauser
25
Proservo NMS5
Human Interface
Operating Concept
NMS5 is furnished with a four line illuminated liquid crystal display. With the E+H matrix driven operation,
configuration is simple. Using only three keys, all parameters can be selected and modified. For example:
Operation - level; interface; spot & profile density, water dip, & tank bottom
Current output
Relay output
Maintenance prediction
Calibration, etc.
The display can be configured to be displayed in English, Japanese or Chinese. Measurement unit & decimal
point can be also configured within NMS matrix.
Operational Security
The programming information can be protected by software access codes that disable all programmable
parameters or by a hardware switch to prevent changes from remote transmission or the touch control keypad.
A self-diagnosis function checks for any operational failures.
Display (LCD)
IIluminated LCD
Infrared Transmitting
Diaode
Infrared Receiving
Diaode
3 Optical Operating Elements
" Touch Control"
Figure 13: Display (LCD)
Memo Function
26
Endress+Hauser
Proservo NMS5
Advanced Maintenance
Maintenance Prediction
NMS 5 will provide advance warning of required maintenance such as replacement of worn wire etc. The
operating life-span of electrical and mechanical parts of the NMS 5 are factory set within the instruments
memory. This information is checked involving with the built-in clock and compared and registered in the
instrument.
Maintenance
The maintenance record can be accessed via the matrix and will provide information of alarm data (e.g. date,
time, alarm type). A memo function allows the user or an E+H Service Engineer to enter maintenance data
manually.
Proactive Safety
Proactive safety diagnostic function warns of mechanical failure, and outputs maximum level value, e.g. 99999
to local display and fieldbus.
Endress+Hauser
27
Proservo NMS5
PTB: Germany
NMi: Netherlands
Overspill Prevention
TV: Germany
SIL
TV: Germany
EMC-Directive 89/336/EC
PE-Directive 97/23/EC
EN 10204-3.1B
OIML-R85/1998
OIML-R85/2008
SIL IEC61508, IEC61511
ISO 9001:2008
28
Endress+Hauser
Proservo NMS5
Order Information
NMS5
010
0 5.88bar/588kPa/85.28psi; Alu
9
020
030
040
050
NMS5-
Endress+Hauser
Approval:
0 Weather proof, IP 67 NEMA 4X
1 TIIS Ex d IIB T4
5 FM XP Cl. I Div. 1 Gr. C-D
N FM XP-AIS Cl. I Div.1 Gr. C-D
6 CSA Cl. I Div. 1 Gr. C-D
O CSA Ex d[ia] Cl. I Div. 1 Gr. C-D
G ATEX II 1/2G Ex d IIB T6...T3
Q ATEX II 1/2G Ex d IIC T6...T3
S ATEX II 1/2G Ex d IIB T6...T3, -40C
J ATEX II 1/2G Ex d (ia) IIB T6...T3
U ATEX II 1/2G Ex d (ia) IIB T6...T3, -40C
A IEC Ex d ia IIB T6...T3 Ga/Gb
B IEC Ex d IIB T6...T3 Ga/Gb
C IEC Ex d IIC T6...T3 Ga/Gb
D IEC Ex d ia IIB T6...T3 Ga/Gb, -40C
E IEC Ex d IIB T6...T3 Ga/Gb, -40C
9 Special version, TSP-no. to be spec.
Application:
A Liquid Level
B PTB (<1mm) type approval, liquid level
C NMi (<1mm) type approval, liquid level
D Multi measurement, liquid level, I/F level, bottom, density
E PTB (<1mm) type approval, liquid level, I/F level, bottom, density
F NMi (<1mm) type approval, liquid level, I/F level, bottom, density
G Density profile multi measurement, liquid level, I/F level, bottom, density
H PTB (<1mm)type approval, density profile, liquid level, I/F level, bottom, density
J NMi (<1mm) type approval, density profile, liquid level, I/F level, bottom, density
Y Special version, TSP-no. to be spec.
Output 1:
F Not selected
A 2-way 2-wire (V1 protocol)
J 2-way 2-wire (MDP protocol)
B 2-way 2-wire (BBB protocol)
C 2-way 2-wire (MIC, RS232C protocol)
D 2-way 2-wire (MIC protocol)
G HART active
H HART passive
L Whessmatic 550, overvoltage protection
M Mark Space
N Enraf BPM
P Modbus RS 485
Y Special version, TSP-no. to be spec.
Output 2:
0 Not selected
1 4 x relay SPST
2 2 x 4-20mA
3 4 x relay SPST, 2 x 4 - 20mA
4 2 x relay SPST, Overspill prevention TV
5 4 x relay SPST, 1 x 4 - 20mA
9 Special version, TSP-no. to be spec.
29
Proservo NMS5
060
070
080
090
100
110
Input:
0 HART (NMT5xx, NRF560, pressure transmitter)
1 1 x spot temperature Pt100, HART (NRF560, pressure transmitter)
2 2 x operation contact, HART (NMT5xx, NRF560, pressure transmitter)
3 1x spot temperature Pt100, 2x operation contact, HART (NRF560, pressure transmitter)
4 1 x status, HART (NMT5xx, NRF560, pressure transmitter)
5 1x spot temperature Pt100, 1x status, HART (NRF560, pressure transmitter)
6 1x spot temperature Pt100, 1x status, 2x operation contact, HART
(NRF560, pressure transmitter)
9 Special version, TSP-no. to be spec.
Measuring Range; wire:
C 0 - 28m; SUS316L, 0.15mm
L 0 - 36m; SUS316L, 0.15mm
N 0 - 47m; SUS316L, 0.15mm
H 0 - 16m; PFA>SUS316, 0.4mm
K 0 - 16m; Alloy C, 0.2mm
M 0 - 22m; Alloy C, 0.2mm
Y Special version, TSP-no. to be spec.
Cable entry:
E 4 x thread G1/2
F 4 x thread G3/4
G 4 x thread NPT1/2
H 4 x thread NPT3/4
L 4 x thread M20
M 4 x thread M25
Y Special version, TSP-no. to be spec.
Process connection:
A 10K 80A RF, flange JIS B2220
C 10K 80A FF, flange JIS B2220
U 10K 150A RF, flange JIS B2220
E 20K 80A RF, flange JIS B2220
G 3" 150Ibs RF, flange JIS B2220
J 3" 300lbs RF,flange ANSI B16.5
W 4" 300lbs RF, flange ANSI B16.5
T 6" 150lbs RF, flange ANSI B16.5
L DN80 PN10 B1, flange EN1092-1 (DIN2527 B)
N DN80 PN25 B1, flange EN1092-1 (DIN2527 B)
Q 80A 150lbs RF, flange JPI 7S-15
S 80A 300lbs RF (apply for NMS5-6), flange JPI 7S-15
Y Special version, TSP-no. to be spec.
Power supply:
3 85 - 264 VAC, 50/60 Hz
4 20 - 62 VDC, 20 - 55 VAC, 50/60 Hz
9 Special version, TSP-no. to be spec.
Displacer:
N Cylindrical 30 mm, SUS316
K Cylindrical 40 mm, SUS316
D
W
V
U
T
B
R
S
Y
NMS5-
30
Endress+Hauser
Proservo NMS5
120
Endress+Hauser
130
Options:
A not selected
C Rc3/8 cleaning nozzle
D Rc3/8 gas purging nozzle
E Guide wire installation
G Relief valve
H Relief valve, pressure gauge
J Sunshade
L Rc3/8 gas purging nozzle, sunshade
M Rc3/8 cleaning nozzle, sunshade
N Rc3/8 gas purging nozzle, guide wire installation
P Rc3/8 cleaning nozzle, guide wire installation
Q Guide wire installation, sunshade
R Relief valve, guide wire installation
S Relief valve, pressure gauge, guide wire installation
T Relief valve, sunshade
U Relief valve, pressure gauge, sunshade
Y Special version, TSP-no. to be spec.
NMS5-
31
Proservo NMS5
Accessories
Calibration Chamber
Calibration Chamber
8 hole
Flange
300
172
Flange
150
Calibration chamber is recommended for use with tank level gauges in order to allow maintenance (removing
displacers), while tank is in service.
Standard chamber is 6" flange, with bolts & packing for NMS connection.
Note!
The dimensions differ depending on material, flange size. Contact Endress+Hauaser for details.
NHC4HP (high pressure version)
10
20
30
40
NHC4HP-
32
Process Connection:
A 10K 150A RF, flange JIS B2220
C 10K 150A FF, flange JIS B2220
E 20K 150A RF, flange JIS B2220
G 6" 150lbs RF, flange ANSI B16.5
J 6" 300lbs RF, flange ANSI B16.5
L DIN 150 PN10 B1, flange EN1092-1(DIN2527 B)?
N DIN 150 PN25 B1, flange EN1092-1(DIN2527 B)
Q 150A 150lbs RF, flange JPI 7S-15
S 150A 300lbs RF, flange JPI 7S-15
Y Special version, TSP-no. to be spec.
Pipe Material; Flange Material:
2 STPG370; SS400
3 SUS304TP; SUS304
9 Special version, TSP-no. to be spec.
Bolts, Packing:
0 not used
1 SUS304, Valker #6502
9 Special version, TSP-no. to be spec.
Pressure Gauge, Relief Valve:
1 Selected
9 Special version, TSP-no. to be spec.
Complete product designation
Endress+Hauser
Proservo NMS5
020
Process Connection:
A 10K 150A RF, flange JIS B2220
C 10K 150A FF, flange JIS B2220
G 6" 150lbs RF, flange ANSI B16.5
L DN150 PN10 B1, flange EN1092-1(DIN2527 B)
Q 150A 150lbs RF, flange JPI 7S-15
Y Special version, TSP-no. to be spec.
Pipe Material; Flange Material:
1 AC4AAC4A
3
9
030
NHC4LP-
Endress+Hauser
SUS304TPSUS304
Special version, TSP-no. to be spec.
Bolts, Packing:
0 not used
1 SUS304, Valker #6502
9 Special version, TSP-no. to be spec.
Complete product designation
33
Proservo NMS5
Power+Control Switch
Power + Control Switch
3PECIlCATIONS
Rated Voltage
AC110/220V
Rated Current
6A/5A
INST
Terminal Box
Iron Casting
Structure
LIFT
120
Housing
STOP
OFF
.OOF#ERTIlCATE4
Grounding
65
2 - 7
113
Connection Diagram
NHS8
Term.No
NMS
Term.No
Power Supply
2 Power N
Power L
193
4
5
16 COM
17 CRT1
18 CRT2
Handle
Position
Wiring
INST
OFF
LIFT
STOP
INST
STOP
Cable entry
7
LIFT
OFF
Cable Entry
PF (G)1/2
PF (G) 3/4
PF (G)1
h (mm)
17
20
24
B
140
140
145
Power & Control Switches are used for field mounted tank gauges. This provides additional gauge operation
contact switching in order to control gauges operation, such as hoisting up displacer.
NHS8
010
020
NHS8-
34
Approval:
1 Weather proof IP67
2 Flame proof (JIS d3aG5)
Cable entry:
0 2 x thread G3/4
1 2 x thread G1
2 2 x thread NPT3/4
3 2 x thread NPT1
9 Special version, TSP-no. to be spec.
Complete product designation
Endress+Hauser
Proservo NMS5
Ball Valve
Body Cap
Ball
Body
Figure 16: Parts Name of Ball Valve
Ball valves are recommended for use with tank level gauges in order to allow such maintenance as removing
displacers, while tank is in service.
Standard ball valve with ANSI flanges. Ball material is SS304, seat material is PTFE.
Note!
The dimensions vary depending on material, flange size. Contact Endress+Hauser for details.
NHV4A (ANSI flanges)
Standard ball valve with ANSI flanges. Ball material is SS304, seat material is PTFE.
10
20
NHV4A-
Endress+Hauser
35
Proservo NMS5
20
Ball Type:
A Full bore
B Reduced bore
Y special version, TSP-no. to be spec.
NHV4J-
36
Endress+Hauser
Proservo NMS5
Reducing Flange
High Pressure (ANSI Example)
Stud Bolt
Stud Bolt
Flange
Flange
Use reducing flange when NMS5 connection 80A(30")and mounting nozzle is 150A(6").
NHF4
10
20
NHF4-
Note!
NHF4 is not required if NMS5 is ordered with "Order Information; Guide Wire Installation (130-E)".
When ordered as NMS5-xxxxxxxxxxxxE with Guide Wire Installation, all the required mounting equipment
is included.
Endress+Hauser
37
Proservo NMS5
Supplementary Documentation
Technical Information
TI00042G
Prothermo NMT 539
TI00462G
Promonitor NRF 560
Operating Manual
BA00401G
Proservo NMS5
Compact Instructions
KA001N
Whessoemtric 550
KA002N
RS485 Modbus
Safety Instructions
XA00578G
Proservo NMS5 - ATEX
XA00582G
Proservo NMS5 - IECEx
38
SD00337G
Proservo NMS5 - (4-20mA Output, Overspill prevention)
Endress+Hauser
Proservo NMS5
Appendix
Stainless Steel Conversion
Table
The stainless steel material used in products of Endress + Hauser Yamanashi normally have expressions
according to Japanese industrial standards, such as JIS. Each country or region may have different expressions
place to place.
The following conversion table contains the expression of equivalent stainless steel material based on the
chemical composition and mechanical properties.
Country
Standard
Expressions
Japan
JIS
SUS304
SUS304L
SUS316
SUS316L
Germany
DIN 17006
X5 CrNi 18 10
X5 CrNi 18 12
X2 CrNi 18 11
X5 CrNiMo 17 12 2 /
1713 3
X2 CrNiMo 17 13 2
W.N. 17007
1.4301 1.4303
1.4306
1.4401 / 1.4436
1.4404
France
AFNOR
Z 6 CN 18-09
Z 2CN 18-10
Z 6 CND 17-11 / 17 12
Z2 CND 17-12
Italy
UNI
X5 CrNi 1810
X2 CrNi 1911
X5 CrNiMo 1712 /
1713
X2 CrNiMo 1712
U.K.
BSI
304S15 / 304S16
304S11
316S31 / 316S33
316S11
U.S.A.
AISI
304
304 L
316
316L
U.E.
EURONORM
X6 CrNi 1810
X3 CrNi 1810
X6 CrNiMo 17 12 2 /
17 13 3
X3 CrNiMo 17 12 2
Spain
UNE
X6 CrNi 19-10
X2 CrNi 19-10
X6 CrNiMo 17-12-03
X2 CrNiMo 17-1203
Russia
GOST
08KH18N10
06KH18N11
03KH18N11
03KH17N14M2
ISO
11
10
20
19
ASME
S30400
S30403
S31600
S31603
Note!
Since each standard carries its own mechanical and scientific definition, some expressions on the list above may
not have a straight conversion from the Japanese standard. Consult a local authority or legislature to ensure
proper comparison of the applied standard prior to determining specifications.
Endress+Hauser
39