Access Control Testing
Access Control Testing
and Commissioning Of
Security Access Control
Testing.
Document Control
Contract No:
Contract
Description:
Document Title:
Document No:
Rev. Date
SN15005
Citibank - South Quarter Jakarta - Office Fit Out
Method Statement for Security Access Control Testing
Comments:
23 October 2015
Prepared by:
Checked by:
Approved by:
VG
SDA
DFA
Prepared by:
Checked by:
Approved by:
Name
Initials
Name
Initials
Contents
Introduction.
Reference Standards
Test Procedures.
Test Execution...
1.0
Introduction.
1.1
The following test procedure has been prepared as a guideline for the Testing Of
Access Control systems for this project.
1.2
1.3
1.4
1.5
2.0
3.0
All instrumentation used for the testing of Access Control Equipment, must have
up to date (with at least 6 months validity) calibration certificates that is traceable
to international standards
2.2
The following test instrumentation & tools will be required to undertake the tests
detailed within this procedure: Details to be recorded on equipment record sheets
at annex A.
Reference Standards.
The Contractor is to confirm all Local and International codes relevant to this
installation.
Ensure all wiring is 100% complete, and that all ancillaries have been installed
correctly.
4.2
4.3
The contractor shall carry out and submit test records on the testing equipment
record sheet included within the electrical test sheets. Tests to include
Insulation tests.
Visual Checks
5.
Test Execution.
The contractor shall carry out and submit all test records on the Testing &
Commissioning Report Forms for all applicable equipment. Test to be conducted will
include the following:
Citibank Jakarta
Location:
INDONESIA, JAKARTA
Contractor:
Make
Model
Serial No.
Date of
Calibration
Issued By:
Contractor
Signature:
Name:
Date
Signature
Name:
Date
Received By:
Commtech Asia
Certificate
attached
Door Name:
)
Single Door
Wood
Double Door
Glass
Sliding Door
Steel
Other:
Electromagnetic
Surface Mount
At Door Entry
Strike
Concealed
At Door Exit
Drop-bolt
Other:
Other Location
Reader
Release Button
Exit Alarm
Break-glass
Key-switch
Yes /
No
Yes /
No
Yes /
No
Device Layout is conformed to the requirement as set out in floor plans and door schedules
TESTS
Door Lock
Door Contact
Card Readers (Touchpad)
Release Button
Audible Door Alarm/Strobe
Emergency Break-glass
Tested by:
Name:
Signature:
Date:
Contractor
Witnessed By
Name:
Commtech Asia
Signature:
Date;