Bus Bar Protection: External Faults
Bus Bar Protection: External Faults
Bus bar protection relays depends mainly on khirchoffs current law, which states that the sum of
current inter to any node must be equal to the sum of the currents leaving it.
Figure
(50)
direction
shows
of
two
current
equipments
normal
condition
(without
the
differential
current
This case is similar to the pervious healthy case in that the two current will increase to very high
values but still equal in magnitude and opposite in direction and the relay will not operate due to
the zero current in the differential relay coil as shown in figure (51).
Internal Fault
In the internal fault case shown in figure (52), There are two expected situation:
1.
Non redial system, then I2P has a non zero value. In this case the differential current is
equal to (I1S+ I2S) and this value is sufficient to operate the relay and trip all the equipments
connected.
2.
In this case the differential current is equal to i1S and this value is also sufficient to operate the
relay and trip all equipments connected to the bus bar.
Note
All equipments current transformers must have the same transformer ratio, if different ratios are
exist Aux current transformers (matching current transformers) must be used to compensate
these difference. These matching may be internally in the relay (Taps) or externally by separate
matching current transformers.
There are different types of bus differential protection relays. Low impedance and high
impedance relays may be considered there is some difference between them, but it is not
considered in this study.
Each
equipment
contains
one
CT1 (of the coupler) is connected between circuit breaker and bus1 and for equilibrium it is
added to CT3, and Ct4 which are connected to bus2, and CT2 (of the coupler) is connected
between circuit breaker and bus2 and for equilibrium it is connected to CT5, CT6 which are
connected to bus1.
The advantage of these connections is to protect the zone between circuit breaker and current
transformer of the coupler. If one CT is installed for the coupler, the zone between circuit breaker
and current transformer is not protected by bus protection.
At fault, sum of I3+I4 not equals 0, so the differential coil will operate and transfer a trip signal to
a trip bus and so to trip coils of equipments connected to the same bus.A similar circuit for bus1
(equipment 5,and 6) is exist .
Note
The previous examples assumes that the coupler is not connected . If the coupler is connected
before fault occurrence, the circuit breaker of it is disconnected at the beginning of the fault to
isolate bus1 From Bus2 and then identify which bus from1 and 2 is faulted and then trip all
equipments connected to it and leave the healthy bus as it is.