HVAC - Overview of Space Heating Systems PDF
HVAC - Overview of Space Heating Systems PDF
HVAC - Overview of Space Heating Systems PDF
2012
www.PDHcenter.com
www.PDHonline.org
SECTION 1
Page 1 of 67
www.PDHcenter.com
www.PDHonline.org
slows the flow of heat. R-value is a measure of insulation; the larger the R-value, the lesser is
the heat loss. U factor is the inverse of R factor, (U = 1 / R); the lower the U factor, the
less ability of the material to transfer heat, therefore, the lower the heat loss.
2) Temperature difference between the inside and outside of the building is the primary cause of
heat loss in the winter months. The greater this difference, the higher the rate of heat loss.
Since most buildings are controlled to a constant inside temperature by the occupants, higher
heat loss occurs when it is colder outside.
3) Wind and infiltration - The U-values and indoor-outdoor temperature differential alone do not
describe the extent of heat loss; the wind & infiltration has a great influence on the heat loss.
High winds can occur on the cold nights and when they do, heat loss can be higher because of
air scrubbing the outside of the space covering. Winds can also force their way through cracks
in the structure, causing infiltration and drafts. In fact, the studies indicate that up to one-third of
the annual heating energy goes to heat this moving infiltration air. Shrubs and windbreaks to
keep the high winds from impacting the walls will help reduce this energy loss.
d. Inside design temperature for most commercial and residential spaces is 65F.
2) U = Heat transfer coefficient in Btu/hr-ft -F; the value dependent on the materials of
construction
2
3) A = Area of exposed surface in ft ; the value measured from building plan and elevation
drawings
4) Ti = Inside design temperature in F; the recommended value is 65F
5) To = Outside design temperature in F; look up for geographical location and refer ASHRAE
handbook
Page 2 of 67
www.PDHcenter.com
www.PDHonline.org
2) The inside design temperature (Ti) is traditionally taken as 65F, because most buildings
have people, lights, and equipment that will reduce the occupied heating requirement in
comparison to the unoccupied winter night loads. But there are numerous exceptions such as
warehouses and hospitals.
3) The net area (A) of each building section is determined from the drawings (in new construction)
or from field measurements (in retrofit situations). In addition to the areas of the four walls, floor,
and ceiling, we must also consider heat loss from doors and windows. Finally, we will need to
determine the volume of the building as an easy way to estimate the rate of infiltration into the
building measured in air changes per hour.
4) The heat transfer coefficient (U-factor) is a measure of the rate of heat loss or gain through
construction of materials. The lower the U-factor, the greater the material's resistance to heat
flow and the better is the insulating value. U-value is the inverse of R-value (hr sq-ft F /Btu).
Mathematically, the U-value of a construction consisting of several layers can be expressed as
U=1/R
Where
R is the sum of the thermal resistances for each component used in the construction of the
wall or roof section. The R-value of the single layer can be expressed as:
R = 1 / C = 1 / K lt
Where
1) C = layer conductance (Btu/hr sq-ft F)
2) K = layer conductivity (Btu in/hr sq-ft F)
3) lt = thickness of layer (inches)
As an example, consider a section of standard wall construction below:
Page 3 of 67
www.PDHcenter.com
www.PDHonline.org
Adding the values gives a total resistance, R = 14.43 (hr-ft -F / Btu) and therefore U-factor is
2
determined by taking the reciprocal of the R-value i.e. U = 1/ R = 1 / 14.43 = 0.07 Btu / hr-ft -F.
Here are a few of the most common covering materials and their associated U factors:
U Value
Material
Glass, single
1.13
.70
1.20
.70
1.20
Corrugated polycarbonate
1.20
.58
8 mm thick
.65
6 mm thick
.72
.51
Page 4 of 67
www.PDHcenter.com
www.PDHonline.org
Page 5 of 67
www.PDHcenter.com
www.PDHonline.org
about 0.5 air changes per hour; an average building is about 1.0 air change per hour and a leaky
older space can lose well over 2.0 air changes per hour.
Consumption of natural gas is measured in cubic feet (ft ). This is the amount that the gas meter
registers and the amount that the gas utility records when a reading is taken. One cubic foot of
natural gas contains about 1,007 Btu of energy.
Propane: Propane, or liquefied petroleum gas (LPG), can be used in many of the same types of
equipment as natural gas. It is stored as a liquid in a tank, so it can be used anywhere, even in
areas where natural gas hookups are not available. Consumption of propane is usually measured in
gallons; propane has an energy content of about 92,700 Btu per gallon.
Fuel Oil: Several grades of fuel oil are produced by the petroleum industry, but only # 2 fuel oil is
commonly used for space heating. The heating (bonnet) capacity of oil heating appliances is the
steady-state heat output of the furnace, measured in Btu/h. Typical oil-fired central heating
appliances have heating capacities of between 56,000 and 150,000 Btu/h. Oil use is generally billed
by the gallon. One gallon of #2 fuel oil contains about 140,000 Btu of potential heat energy.
Electricity: The watt (W) is the basic unit of measurement of electric power. The heating capacity
of electric systems is usually expressed in kilowatts (kW); 1 kW equals 1,000 W. A kilowatt-hour
(kWh) is the amount of electrical energy supplied by 1 kW of power over a 1-hour period. Electric
systems come in a wide range of capacities, generally from 10 kW to 50 kW.
When converted to heat in an electric resistance heating element, one kWh produces 3,413 Btu of
heat.
Page 6 of 67
www.PDHcenter.com
www.PDHonline.org
Since the actual heat content of different types of fuels varies, the approximate average values are
often used. The table below provides a list of typical heating fuels and the Btu content in the units
that they are typically sold in the United States. The figures below are for guidance only; commercial
and industrial users should obtain more precise values from their fuel vendors.
No. of Btu/Unit
#2 Fuel Oil
140,000/gallon
#6 Fuel Oil
150,500 /gallon
Diesel
137,750/gallon
Kerosene
134,000/gallon
Electricity
3,412/kWh
Natural Gas*
Propane
91,330/gallon
20,000,000/cord or 8,000/pound
16,500,000/ton
Kerosene
135,000/gallon
Coal
28,000,000/ton
*Natural gas is a mixture of several gases and can vary in composition from supplier to supplier. For
this and other reasons it is often sold on the basis of "therms" (1 therm equals 100,000 Btu) rather
than "per cubic foot".
*A cord of wood is a rough measuring unit; it is a stack of wood 4 feet high, 8 feet long, and 4 feet
wide. A "good" cord of wood will be tightly packed. Pellet fuels are usually made from sawdust. The
Btu content will therefore vary depending on the type of wood that the sawdust is from. Pellet fuels
typically have a moisture content of around 10 percent.
Note that the energy content values may vary drastically, especially for wood and coal. As an
energy system designer, you must learn the purchasing units associated with each energy source.
Rounding things off can make it a little bit easier. For example, natural gas contains about 1000 Btu
per cubic foot. So, one hundred cubic feet (CCF) contains about 100,000 Btu. A gallon of fuel oil
delivers almost 100,000 Btu per gallon. Knowing the unit efficiency allows you to calculate the
original content.
Page 7 of 67
www.PDHcenter.com
www.PDHonline.org
combustion process when hydrogen in the fuel is combined with oxygen to form water vapor. In
general, this difference can range from as little as 2 percent to as much as 60 percent, depending
on the hydrogen or moisture content of specific fuels. The heat energy contained in the water vapor
is generally lost as the combustion gases leave the appliance vent or chimney. Some types of
combustion appliances, however, such as high efficiency "condensing" forced-air furnaces, are able
to capture much of the heat contained in the water vapor before it leaves the furnace vent (thus the
term "condensing"). Since electricity is not burned in a heating appliance, the two values are equal.
Wood heating values can vary significantly. The most important factor affecting useful Btu content is
the moisture content of the wood. Well-seasoned, air-dried wood will typically have a moisture
content of around 20 percent (when compared to a "bone dry" sample of the wood). A very rough
approximation of the effect of moisture content on the heating value is for every percent increase in
moisture content (relative to a bone-dry sample) there is a one percent decrease in heating value.
Efficiency (%)
Coal (bituminous)
Central heating, hand-fired
45.0
60.0
14.5
Oil
Cast iron head burner
60.0
70 - 78
75 - 82
78 - 86
83 -89
Page 8 of 67
www.PDHcenter.com
www.PDHonline.org
85 - 95
80 -85
60
Gas
Conventional furnace
60.0
62 - 67
78 -84
89 - 97
85.0
78.0
note 1
99.0
note 1
65.0
62.0
Electricity
Baseboard, resistance
100
100
note 2
200+
note 2
300+
30.0 - 40.0
40.0 - 70.0
Catalytic stoves
65.0 - 75.0
Pellet stoves
85.0 - 90.0
Note 1*: Most of the appliance efficiencies given in the table above roughly account for the net heating value
fuels used in a vented appliance (i.e. one that has a chimney). An un-vented space heater, such as a kerosene
heater or a natural gas fireplace insert, delivers nearly all of the heating value of a fuel to the space in which it
is located. It also puts all the products of combustion including carbon dioxide, water vapor, and small amounts
Page 9 of 67
www.PDHcenter.com
www.PDHonline.org
of carbon monoxide, sulfur dioxide, and nitrous oxides into the room. These types of heating units generally
require that a window be opened (slightly) for safe operation, which reduces their overall heating capability.
Note 2*: Heat pumps are measured by coefficient of performance (COP). A COP of 1.5 means that the
equipment has an efficiency of 150%.It can be over 100% because heat pumps move heat from outside to
inside, instead of creating it.
Fuel
Fuel Cost
(Note #1)
Fuel energy
content (in
millions Btu
per unit)
Heating
System
Efficiency
Heat Cost in $
per million
Btu
(Note #2)
(Note #3)
Resistance
Baseboard
Electric
$0.086 per
kWh
0.003412
0.99
= $25.46
Heat Pump
Electric
$0.086 per
kWh
0.003412
= $12.60
Medium
Efficiency
Furnace
Natural
Gas
$9.96 per
thousand
cubic feet
1.03
0.90
= $10.74
Medium
Efficiency
Furnace
Fuel Oil
$1.25 per
gallon
0.14
0.85
= $10.5
Medium
Efficiency
Furnace
Propane
$1.09 per
gallon
0.0913
0.85
= $14.05
Note #1: The fuel costs used are the national annual average residential fuel prices in 2001 according to the
Energy Information Administration (EIA), U.S. Department of Energy. Prices will vary by location and season.
Note #2: The system efficiencies used are assumed examples only.
Note #3: Energy cost ($ per million Btu) = Cost per unit of fuel [Fuel energy content (in millions Btu per unit)
Heating system efficiency (in decimal)]
Page 10 of 67
www.PDHcenter.com
www.PDHonline.org
For simplicity, consider all energy will cost exactly $10 per million Btu. At today's energy prices, this
average value is high for gas heat (by about a factor of 2), about right for fuel oil, and low for electric
resistance heat (by about a factor of 2). The reason for this is that natural gas, for all practical
purposes, is a raw commodity, while electricity is a value-added commodity. In other words,
electricity is generated by raw commodities, including natural gas.
Even these prices vary substantially across the nation. Natural gas in New York sells for almost
three times the price in Colorado and Louisiana. Electricity on Long Island costs almost ten times
more than the price that Bonneville Power Administration gets for their hydroelectric power in
Montana.
So in the Pittsburgh example we have discussed earlier using 71 million Btu/yr, we would calculate
the heating cost to be 71 x $10 = $710 per year. But in reality the heating cost might range from
under $350 for gas heat to over $1400 for electric resistance heat.
Page 11 of 67
www.PDHcenter.com
SECTION - 2
www.PDHonline.org
There are almost endless variations and combinations that can be utilized to create the best
system. Every type of heating equipment has its strength and limitations. Depending on the level of
comfort and the operating costs, youll need to choose the style of system that integrates best with
your facility requirements. Its simply a matter of determining your requirements and researching the
best options with expert design professionals.
In this section, we will examine
1) Heating System Choices
2) Factors influencing the choice of heating system
3) Heating Systems Ranking
4) System Design Decisions
Page 12 of 67
www.PDHcenter.com
www.PDHonline.org
3) Comfort: Comfort is defined by uniformity, heat response control and noise levels. A
comfortable heating system may incorporate some radiant heating as well as convective. It may
be difficult to obtain comfort levels if a purely radiant system is used (such as radiant panels) so
a mixture of convective and radiant heating is desirable.
Heat Response factor means how quickly the system will supply heat to the space. A
heating system with a good "heat response" time brings a room up to the human
comfort zone more quickly. A convective heater has much quicker heat response when
compared to the radiant heaters.
If noise levels in a room such as a library are to be at a minimum then fan convectors is
not a good option. Quieter form of heating options can be radiators, underfloor heating,
natural convectors or a radiant ceiling.
4) Application & type of Building: There are many types of buildings each having different
application. Here are few notes that require architects or heating system designers attention:
In some applications (e.g., theaters and churches) noise and vibration control are primary
considerations.
In other buildings (refineries, chemicals or spray paint booths), explosion prevention may be
the primary consideration.
In textile facilities fire is the major concern and in food facilities, the need for sanitary
conditions can eliminate several options.
Hospitals require clean environment; thus filtered air heating may be necessary, usually in a
full air conditioning system.
For warehouse radiant heating may be a suitable option since the air temperature need not
be high.
Museums and Archive Stores require constant control of room temperature and humidity air-conditioning may be necessary.
In some buildings it is difficult to run services through e.g. stone walls, solid concrete slabs,
therefore electrical heating may be used.
In some buildings like nursery schools and nursing spaces, if radiators are utilised, it is
advisable that low surface temperature radiators are used.
In wet areas like shower rooms and bathrooms underfloor heating has an advantage in that
it keeps the floor dry.
Some buildings like churches may be intermittently used so electrical heating may not
completely ruled out. High temperature roof mounted quartz electric heaters have been
used in this type of building.
Schools have limited wall space so underfloor heating or low temperature ceiling heating is
sometimes used.
In general, large areas benefit from the quick warm-up of air heating. In buildings with large
occupancy a ventilation system may be necessary to provide adequate fresh air for
occupants e.g. concert hall, auditoria. Ventilation systems with ductwork require ceiling void
space.
5) Plant Space: Room for plant and equipment, storage space for fuel etc. are some of the
considerations for selection of heating systems. While natural gas may be piped and electricity
lines are fixed, space is required for storing the fuel oil and solid fuels. Decision needs to be
made on putting the central heating unit in the basement (check if the unit is not prone to
flooding) or rooftop unit (RTU) (if noise below is not an issue). Factory assembled RTU is
Page 13 of 67
www.PDHcenter.com
www.PDHonline.org
cheaper option, which provides better quality control, does not require valuable building floor
space, and provides direct access to interior spaces via the ceiling plenum.
In very large facilities, all utility equipments such as air-conditioning plant, heating and cooling
equipment, the emergency electrical generator, the fire safety systems, and often the electrical
supply transformer and Motor Control Center (MCC) and Lighting Control Center (LCC) can be
located in a remote mechanical room. This allows for better central management of the system
operation, but is more expensive to build.
6) Let Buildings: Most landlords prefer the tenant to look after payment of their own heating bills.
Individual meters for gas or electricity in a block of flats means that the tenants are responsible
for the payment of bills. In a large office building with several tenants electrical or natural gas
heating is easy to measure in zones. Hot water heating system is cumbersome to divide. In let
buildings, some form of billing arrangement needs to be in place to charge tenants. This
essentially requires study on the quality of available instrumentation, ease of measurement and
reliability of readings.
7) Appearances: In some buildings, the designer may require the heating system to be totally
hidden e.g. underfloor heating, heated ceiling or air heating. In some buildings the designer
may wish to make a feature of the heating system or heat emitters e.g. warm air ductwork
system painted a bright color or concealed in a reflected ceiling plan. In some areas like
parametric lengths of building cast iron radiators may be the choice. For Rooftop units (RTUs)
the designer need to integrate the unit into the architectural theme of the building so that it looks
like it is supposed to be there, not just added as an after-thought!
8) Efficiencies of heating equipment are rated by different methods such as Heating System
Performance Factor (HSPF) and Annual Fuel Utilization Efficiency (AFUE) or Thermal
Efficiency/Combustion Efficiency Factor (Et/Ec). In all cases, the higher is the rating number, the
more efficient the unit.
The Federal Energy Agency requires all gas and oil fired furnaces be given operating efficiency
ratings -- the annual fuel utilization efficiency (AFUE). For combustion furnaces such as gas or
oil, an AFUE rating of 8.1 or higher is considered good.
For electric resistance heating though heat is generated almost at 100 percent efficiency, it is
very costly on $ per Btu heat release compared to other options. This is because first we
generate electricity by thermal energy at 35 to 50% efficiency and than using it again for
heating. The high operating cost of electricity must be considered to get an accurate picture of
the system economics.
An efficient method of using electric energy as heating source is the use heat pump. For air-toair heat pumps (the heat exchanger is cooled or heated by air), a rating of 3.2 is considered
good. For water-source heat pumps where the heat exchanger is heated or cooled by water, a
rating of 3.8 is considered good. If rated by the HSPF method, 6.8 or better is considered good
for heat pumps.
9) Transport Media: Another way of grouping heating systems is by the transport media used to
get the heating energy to the distribution point. Heating fuels are normally handled in one of the
following ways. Some fuels are stored or warehoused (such as fuel oil in a tank or coal in a
bunker), while other fuels such as natural gas or electricity are point-of-use fuels. Point-of-use
fuels are delivered through utility piping or wiring networks, and are metered and billed after
consumption. Stored fuels are paid for when purchased. Stored fuel suppliers are not regulated
as closely or carefully compared to point of-use fuel suppliers. As a result, prices for stored
fuels tend to fluctuate more widely with market conditions. Point-of-use suppliers are normally
regulated by state agencies and are restricted to rate schedules that tend to lag the market
response of stored fuels. Electricity can be transported directly via wires.
10) Environmental impact factor considers air pollution and the best use of resources. The
products of combustion of oil, coal and gas pollute the atmosphere.
Coal is probably the worst offender since carbon dioxide contributes to the greenhouse
effect and sulphur dioxide causes acid rain. Smoke causes urban smog and soot and ash
add to the problem. Oil produces contaminants to a lesser extent and gas is probably the
best of the three.
Page 14 of 67
www.PDHcenter.com
www.PDHonline.org
Using electricity is of little benefit because power stations burn fuel to produce electricity.
For example, to generate one kilowatt hour of electricity in a coal-fired plant will require
burning one pound of coal. This produces about three pounds of carbon dioxide (a
greenhouse gas) and four ounces of sulfur dioxide (contributes to acid rain).
A totally 'green' source of heat may be solar energy if you live in an area with plenty of
sunshine.
11) Safety: Ensure all apparatus is approved and meets standards and regulations. You should be
aware of the following hazards when considering heating system:
Fires and burns caused by contact with or close proximity to the flame, heating element, or
hot surface area.
Some open gas and coal fires and paraffin heaters have a poor safety record.
12) Security of Supply of Heat Source: Some fuels at certain times may be liable to unsecured
supply e.g. oil prices can fluctuate. It may be advisable to have a dual fuel system so that
burners can easily be changed over to burn the cheaper or more readily available fuel.
Alternative sources of energy are not always secure e.g. the wind doesn't always blow on a
wind farm. The sun doesnt always shine if the system relies on solar panels. A hybrid system is
more secure or back-up boilers can be used.
13) Fluctuating Heat Demand: In some buildings the demand for heat fluctuates widely throughout
the day. To meet this demand economically, a modular system such as multiple unit heaters or
electrical units may be a good option. This means that the required number of boilers is
automatically switched on to meet the demand.
14) Industrial Waste Heat: In some industrial units, heat is available from the process e.g.
condensate, a by-product of steam or high temperature exhaust flue gases. Waste heat
recovery equipment could be utilized to generate hot water or steam, which can be used to
warm air in a heat exchanger. There are many ways in which waste heat can be utilized to preheat water or up-grade in heat pumps for further use in space heating.
15) Maintenance: Maintenance is very important with the heating systems because there are many
pieces of equipment that can cause problems. With fuel fired equipment, the heat exchanger
surfaces have to be cleaned and the burner has to be maintained and adjusted. In case of hot
water system, the water quality needs to be assured to prevent scaling. The electrical system
does not have such problems other than routine switchgear maintenance.
16) Financial Rebates/Subsidies: Some gas and electric utilities offer rebates or low interest
loans if certain systems are installed. Electric utilities prefer high efficiency heat pumps using
heat recovery units to improve water heating. Gas utilities prefer efficient combinations of gas
space and water heating systems. If rebates or low interest loans are offered, it could make the
"equipment cost" factor more favorable.
Page 15 of 67
www.PDHcenter.com
www.PDHonline.org
have electronic ignition as opposed to pilot lights. Natural gas is the most popular heating
source for locations where it is available.
2) Ranked second is the air to air heat pump systems:
Air to air heat pump systems are generally efficient to operate, but initial equipment cost is
usually higher and heat response is slow. A heat recovery unit can be added to improve the
performance of the water heater. Where resistance costs more than fuel fired systems on a Btufor-Btu basis, heat pumps may be a more cost-effective alternative, especially where the heat
pump can also provide space cooling, dehumidification, or recover building or waste-water
waste heat.
3) Ranked third is the geothermal heat pump systems:
Water source or geothermal heat pump systems use a heat exchanger to recover heat from or
release heat to ground water or earth. Systems using pumped well water may not be allowed in
some water districts and may have scaling problems. The cost of these systems is generally
highest, but comparable to natural gas in terms of efficiency and cost effectiveness to operate.
Environmental impact is moderate; heat response is usually better than air to air heat pumps.
4) Ranked fourth is the fuel oil systems:
Fuel oil heating systems have moderately high efficiencies, moderate initial costs, relatively
high environmental impact, and high heat recovery response. Fuel oil shares many of the same
characteristics as gas, but requires on-site storage of fuel and a fuel unloading site.
5) Ranked fifth is the liquefied petroleum gas systems:
Liquid petroleum gas systems, such as propane and butane, have a moderately low initial cost,
relatively high fuel cost, moderate environmental impact and high heat response. In general, the
same technologies and comments apply to propane as to natural gas, with slight differences in
the efficiencies. Propane has a lower hydrogen level than natural gas. About 3% less energy is
tied up in the form of latent heat with propane systems than with natural gas. This means that
conventional and mid-efficiency propane furnaces can be expected to be slightly more efficient
than comparable natural gas units. On the other hand, propane's lower hydrogen content
makes it more difficult to condense the combustion products, so that propane-fired condensing
furnaces will be 2%-3% less efficient than the same unit fired with natural gas. While all current
heating equipment has built-in safety features and are installed to rigid code requirements, LPG
systems are less safe than others as this gas is heavier than air.
6) Ranked sixth is the wood stove systems:
Wood stove systems have a wide range of ratings depending on efficiency. Catalytic wood
stoves with combustion efficiencies near 90 percent are considerably more expensive than
standard wood stoves with combustion efficiencies of 20 to 40 percent. Handling wood and
ashes is an inconvenience. Wood stoves have a high initial cost and, with the exception of
catalytic stoves, the environmental impact is higher than gas, oil or heat pump heating systems.
The heat response of wood stoves is moderate. Coal and wood-burning systems are only used
in very large installations, where the lower fuel costs can justify the higher installation costs and
higher operating costs.
7) Ranked seventh is the wood burning fireplaces:
Wood burning fireplaces have negative or very low efficiencies unless properly designed. The
fireplaces are mainly used for aesthetics. Handling wood, disposing of ashes and increased risk
of fire due to sparks and chimney fires are problem areas.
8) Ranked eighth is the electric resistance heating systems:
Electric resistance heating is costly to operate and has tremendous impact on environment.
Though the electrical heating offer number of advantages to consumer such as they are cheap
to buy, least expensive to install, 100% efficient i.e. all the energy is converted into heat, safer
than fuel fired systems, a clean form of heating and easy to control with a thermostat but it has
a set of problems. The environmental impact of using resistance heating is high and heat
response is moderate. Since most electricity is produced from oil, gas, or coal generators that
convert only about 30% of the fuels energy into electricity and after accounting losses due to
Page 16 of 67
www.PDHcenter.com
www.PDHonline.org
transmission & distribution, converting electricity back to heating doesnt make sense. The use
of electric resistance heating should never be recommended as a policy measure.
Table below may serve as a decision-making guide.
Heating System
Equipment
Cost
Efficiency &
Fuel Cost
Environmental
Impact
Heat
Response
Overall
Rank
Natural Gas
1-3
2-4
10
1-3
Heating Oil
2-5
LPG (Propane/Butane)
4-8
2-6
2-4
Wood Fireplaces
5-10
6-10
5-8
Electric Resistance
(Strip)
10
10
Wood Stoves
Efficiency Terminology
When shopping for heating equipment, it is important that you understand the common terminology
used to describe different types of equipment. There are several types of efficiency terms used
when describing heating equipment. The most common terms used to describe heating equipment:
1) Combustion Efficiency: This term is the most basic description of efficiency. It denotes the
percentage of fuel burned and turned into heating energy.
2) Thermal Efficiency: This term is a measurement of the actual amount of available energy that
transfers into the heating medium. It is derived by operating a piece of equipment at a steady
state and measuring how much fuel is used vs. how much useable heat comes out. It is most
typically used in reference to boilers.
3) Distribution Efficiency: This is the measure of efficiency of how well the heating equipment
actually delivers the heat energy (BTUs) to your space and structure. This expression
addresses how energy is distributed and transferred to the objects requiring heat.
Distribution efficiency is greatly affected by the system(s) you select, and how you utilize your
equipment. Some examples:
1) Forced hot air systems distribution efficiency is largely dependent upon the means of air
circulation used in the space.
2) Infrared systems, properly installed, can transfer heating energy very well to crops without
the necessity of air circulation.
3) With hot water, distribution efficiency is affected tremendously if the supply and return lines
are poorly installed or are not insulated.
4) Some hot water systems deliver heat much more efficiently than others. Finned pipes heat
faster than bare pipes.
5) With hot water, a high efficiency distribution system coupled to a poor efficiency boiler may
be better than a high efficiency boiler with poor efficiency distribution.
Page 17 of 67
www.PDHcenter.com
www.PDHonline.org
Look at all facets of heating system efficiency when making heating equipment purchases along
with other selection factors. In the following sections we will discuss some design aspects of
commercially installed Gas Fired Heating Systems, Hot Water Heating Systems and Electric
Heating Systems in detail.
Another form of central system is pipe system using multiple radiators. Instead of circulating warm
air through a ductwork, hot water is circulated from boiler to the floor or ceiling mounted baseboard
units.
Page 18 of 67
www.PDHcenter.com
www.PDHonline.org
Description
Approx.
Annual Heating Costs
purchase/install price (note 1)*
$4,000 - $6,000
Reverse-cycle air
conditioner
$8,000 - $12,000
$120-$220
Hydronic Heating
Water is heated in a
boiler (fuelled by natural
gas, LPG, wood or offpeak tariff electricity) and $5,000+
circulated to radiator
panels that heat the
room.
$100-$350(natural gas)
Electric in-slab
$100-$1352
Electric thin-film
$150-$2203
Note 1: Heater use for the winter quarter (90 days), for 8 hours per day, in an average temperature of 8 - 18C
Zoned Systems
In contrast, zoned systems are designed to heat a zone, rather than a whole space. The space
heaters are placed throughout the space, allowing you to adjust the temperatures in different area.
Space heaters tend to be more economical than central heating simply because the units are
smaller with lower running costs and these allow greater flexibility and individual control.
Electric baseboard heaters and radiant heating panels are examples of zoned heating.
Types of Zoned Space Heaters
The most economical space heaters in terms of running costs are either:
1) High efficiency (5-6 star rated) natural gas heaters;
2) High efficiency (3-6 star rated) reverse cycle air conditioners; or
3) Off-peak electric storage fan heaters
Page 19 of 67
www.PDHcenter.com
www.PDHonline.org
When choosing gas systems or reverse cycle zone air conditioners, look for the energy rating label the more stars you see, the better the performance, and the more money you'll save on your energy
bill!
The table below compares various space heaters per 600sq-ft space.
Approx.
Annual
purchase & Heating Costs
install price (note-1)
Space Heating
Description
System(600 sq-ft)
$50 - $90
$55 -$120
Reverse-cycle air
conditioner (4 - 5
star rated)
$20+
$160 - $200
$600+
$100 - $300
Slow combustion
wood heater
$85 - $110
Note 1: Heater use for the winter quarter (90 days), for 8 hours per day, in an average temperature of 8 to - 18C
Page 20 of 67
www.PDHcenter.com
www.PDHonline.org
Then..
Bathrooms/ensuites
Free Convection systems rely on the buoyancy of heated air to provide circulation
throughout the space. The most common examples are the steam radiator and the
baseboard unit.
Forced Convection systems have a fan to force the air to circulate. Unit heaters and other
fan/coil units are the common examples. These units allow the introduction of outside air
and provide air filtration.
To maximize efficient use of the heat energy, it is important to force the mixing and circulation
of these warm air layers.
The Advantages of Convective Heating:
The convective units ensure that warm air is evenly distributed throughout the structure.
The air heaters attempt to heat the entire space including people, hardware and all of the
air within the space.
The high discharge air volumes can cause unwelcome draughts which may reduce the
perceived heating effect.
Because of their usual overhead location severe vertical temperature stratification can
occur with ceiling temperatures as much as 30C above floor temperature.
Page 21 of 67
www.PDHcenter.com
www.PDHonline.org
High volume air movement can also cause dust problems which could affect product quality
particularly in product coating operations.
2) Conduction: Conduction utilizes direct application of heat transfer to the space. Conduction of
heat is generally a small proportion of the total heat output from equipment and is not useful
heat transfer since most of the conducted heat ends up in ceiling voids or through external
building fabrics as a heat loss.
3) Radiant Heating: Radiant heating systems utilize infra red radiation to heat objects, people and
surfaces. Anyone who has warmed themselves by a hot wood stove or warmed their hands at a
camp fire has experienced radiant heat. It is also demonstrated by standing in the sun on a
winters day; or walking near a brick wall that has been exposed to the sun during the day. In
both examples, although the air may not be warm, you are able to feel the heat energy radiating
from these surfaces.
Radiant heat directly heats objects in the room, but does not directly warm the room air.
Radiant heaters can be appropriate if your rooms have large open spaces or high ceilings, or
are particularly draughty.
Advantages of Radiant Heating
No air movement is caused by the system itself, therefore unwelcome draughts are
minimized and dust movement is reduced.
Lower operating costs should be achieved because of the localization of heating compared
to convection systems.
An unobstructed space above floor level is necessary for an effective installation. The
presence of ductwork, pipes, overheard conveyors and other equipment may sometimes
limit full utilization of radiant heating.
Emitter
Media
Heat Transfer
1.
air
Convective
2.
Unit Heaters
water
Convective
3.
direct
Mainly Convective
4.
Radiators
water
Mainly Convective
5.
Convectors
water
Mainly Convective
6.
Direct
Mainly Convective
7.
Underfloor Heating:
Underfloor Heating
water
Mainly Convective
Electrical Underfloor
Heating
direct
Mainly Convective
Page 22 of 67
www.PDHcenter.com
Sno.
Emitter
8.
Skirting/Baseboard Heating
9.
10.
www.PDHonline.org
Media
Heat Transfer
water
Mainly Convective
Direct
Mainly Radiant
Direct
Radiant
water
Radiant
11.
water
Radiant
12.
Direct
Radiant
Infra-red heater
High Temperature
Panels
Page 23 of 67
www.PDHcenter.com
SECTION - 3
www.PDHonline.org
Gas fired heating systems normally offer the most cost effective way to heat large buildings. Gas or
fuel burning furnaces work on the same basic principle; the fuel is burned inside an enclosed metal
container, generally referred to as a fire box and the exhaust gases are vented to the exterior of the
building. The burning of the fuel warms the heat exchanger, which radiates the heat into the air in
the living area. This heated air is circulated by gravity or pumped through the living area with a fan.
Electric and oil fired heaters are sometimes useful for very specific space heating applications when
gas is not available.
In this section, we will examine
1) Codes & Standards
2) Classification & type of fired heating equipment
3) Furnace efficiencies
4) Combustion air requirements
5) Factors affecting combustion efficiency
6) Ventilation air requirements
7) Air Intake configurations
8) Rules for proper venting
9) Heating systems & indoor air quality
10) Installation, Operation & Maintenance guidelines
Page 24 of 67
www.PDHcenter.com
www.PDHonline.org
Thermal efficiency can be up to 70 to 80%, depending on the number of air turnovers per hour.
Indoor air is circulated continuously through the system, so a furnace filter is used to contain dust,
pollen and other airborne particles. These units can also be fitted with cooling coils for use in the
summer.
When a furnace is installed in a basement it is considered an "Up flow" furnace, meaning the
cooler air is drawn at the base of the furnace, and the warm air exits out the top of the furnace. If a
furnace is installed on the main floor of a space and the heat comes from floor registers, it is a
"Down flow" furnace: In a down flow furnace, the cool air enters the furnace at the top and the
warmed air exits at the bottom.
Page 25 of 67
www.PDHcenter.com
www.PDHonline.org
quantities of heated air into the exhaust. A circulation fan passes indoor air from the return
ducts over the furnace heat exchanger. The warmed air then flows into the ductwork for
distribution around the indoor space. These older natural gas systems usually have seasonal
efficiencies of about 60%.
A minor improvement in efficiency comes with adding a vent damper in the flue exhaust. By
closing off the vent during the off cycle, the damper prevents some of the warm air from being
drawn up the flue and lost to the outdoors. These furnaces usually have an electric or electronic
ignition. Fuel savings are generally in the 3%-9% range, relative to a conventional furnace.
2) Conventional oil furnace is similar to a natural-gas furnace, but the dilution device is a
barometric damper--a plate that acts as a valve on the side of the flue pipe. The damper
isolates the burner from changes in pressure at the chimney exit by pulling varying quantities of
heated room air into the exhaust. The quantity of air drawn through the barometric damper is
much greater than the quantity required for combustion and can represent 10% to 15% of the
total heat loss. The burner is a high-pressure gun type, with a blower fan to help mix the oil and
air for good combustion. A conventional oil furnace with a cast-iron head burner has a seasonal
efficiency about 60%. Replacing the conventional burner with a flame retention head burner will
save 10%-15% on the fuel bill.
3) Mid-efficiency gas furnaces usually have a naturally aspirating burner like conventional units.
They do not have a continuous pilot, however, and instead of a draft hood, they are equipped
with a powered exhaust--usually a built-in induced draft fan. They save 15%-25% of the energy
used by conventional gas furnaces.
One word of caution: do not buy a mid-efficiency furnace that is more than 82% efficient. These
systems often have condensation problems in the furnace or venting system. There is also
some concern about the longevity of high temperature plastic pipe used to vent many of these
mid-efficiency units. For higher efficiency, get a condensing furnace.
4) Mid-efficiency oil furnaces use a more efficient high-static retention burner. This type of
furnace also features an improved low-mass combustion chamber (usually ceramic fiber) and
passes the hot combustion gases through a superior heat exchanger that enables the
circulating space air to extract more heat. The barometric damper, with its large requirement for
air to dilute the combustion gases, has been eliminated in the most efficient of these designs.
Benefits of a good mid-efficiency furnace are much lower combustion and dilution air
requirements as well as more power to exhaust the combustion products (both advantages in
new, tighter housing); a safety shutoff in case of draft problems; and a more effective venting
system. Mid-efficiency oil furnaces can have seasonal efficiencies of 85%-89% and use 25%30% less fuel than a conventional oil furnace producing the same amount of heat.
5) Gas condensing furnace condenses the water vapor produced in the combustion process and
uses the heat from this condensation. An enlarged heat exchanger surface lowers the
temperature of the exhaust gases, making the furnace more efficient. The exhaust gas
temperature drops to the dew point of the water vapour in the gas, causing the vapour to
condense to water and give up 970 Btu for every pound of water condensed. Natural gas can
yield more than 1 gallon (8 lbs) of water per 100,000 Btu (one therm) burned, giving up about
7,760 Btu. Condensing furnaces achieve AFUE rating up to 96 percent. Because the flue gas
temperature is low, plastic piping can be used for venting out the side wall of the building.
Although a condensing unit costs more than a non-condensing unit, the condensing unit can
save you money in fuel costs over the 15 to 20-year life of the unit. Condensing gas furnaces
are the most energy efficient furnaces available, with seasonal efficiencies between 90% and
96%.
6) Oil condensing Furnace: While a natural-gas condensing furnace has a significant efficiency
advantage over a mid-efficiency gas furnace, a condensing oil furnace is only marginally more
efficient than a well-designed mid-efficiency oil furnace. Oil produces only half the water vapor
of gas, and so has much less energy tied up in the form of latent heat; the furnace must work
harder to condense less. In addition, the condensate is much more corrosive than with natural
gas, so the condensing oil heat exchanger must be made of special materials. For these
reasons, a mid-efficiency oil furnace is a better bet than a condensing oil furnace.
Page 26 of 67
www.PDHcenter.com
www.PDHonline.org
Classification of Furnaces
There are three types of furnaces: Single-Stage, Two-Stage, and Two-Stage Variable.
1) Single-Stage: Single stage implies the furnace control is simply on or off. Since every facility
has a unique "heat load which varies through out the day, the manufacturers wisely put options
in the furnace fan speed. A single-stage furnace may have multiple speeds. If the heat load
requires significantly less than the amount of heat that the furnace would provide - the furnace
fan speed should be hard wired to its medium high option.
2) Two-Stage: Two-Stage furnaces were developed with comfort in mind. Here is how they
function. When the thermostat activates the furnace, it comes on at 2/3 rd strength (burning gas
at 65% of maximum). If, after 10 minutes of operation, the thermostat is still calling for heat - the
furnace will switch to 100%. What that accomplishes is a uniform heating of entire space. If a
furnace kicks on at full power and dumps hot air into the space to satisfy the thermostat - it will
shut off leaving cool air still circulating the space; meaning that the furnace will have to kick in
again. Two-Stage furnaces are more efficient and more effective at heating the space.
Furnaces are like light bulbs, they operate better if they are turned on and left on. If you flick a
light switch on and off, over and over - that bulb is toast. The same goes for furnaces. Running
at 65% for 9 minutes is better than 100% for 3 minutes several times an hour. It uses less gas
and is easier on the machine.
3) Two-Stage Variable: Two-Stage Variables were developed with the knowledge that subtle
circulation of heated air is the most effective way to heat a space. The furnace part is the same
as a Two-Stage; the difference is in the blower motor. In a Single-Stage, if you want your fan on
for circulation, that fan is on high. It is the only option it has. Not only is that hard on the utility
bill, but a fan on high means the warm air is moving fast, warm air moving fast is a cool breeze.
In a Variable, the fan turns over slowly to maintain air circulation while being easy on the utility
bill. By the way, most air cleaners and filtration devices are only active when the furnace blower
is on. So the best way to utilize these accessories is to have a variable speed blower. By
switching its blower fan from AC current to DC current, it only draws 1/10 the electricity.
Furnace Efficiencies
Furnaces are often classified according to efficiencies. You'll often hear furnaces being referred to
as standard, mid and high efficient units. A standard furnace is one whose efficiency is below 70%,
a mid efficient furnace is one whose efficiency is between 71% and 82% and a high efficient furnace
is one with efficiency above 90%.
When a furnace is 80% efficient - it means that of the gas or fuel oil that is ignited to create heat 80% of the heat energy is captured by your heating system. The remaining 20% escapes up the
flue or emanates out the face of the furnace. For example, if the rating of old furnace is 100,000
BTU @ 60% efficiency, the effective heat delivery shall be 60,000 BTU and for new furnace of
80,000 BTU rating @ 80% efficiency, the effective heat delivery shall be 64,000 BTU of heat. So, a
new 80% furnace should be smaller than your old one. But lets back up a bit to "heat load."
Lets say the heat load is 60000 BTU. An 80,000 @ 80% efficiency furnace provides 64,000 BTU.
That is a good fit. It is a good idea to fudge a little on the side of enough heat. An 80,000 @ 90%
efficiency furnace provides 72,000 BTU. That is overkill. The space will never reach optimal comfort
because the heat will rise faster than it takes to cycle all of the cold air through the furnace. Your
furnace would ""short cycle." That is bad. Over the long haul, a 90% efficient furnace will save you
money on your utilities, but it might take 7 to 10 years. In either case, one size does not fit all.
AFUE Ratings (Efficiency)
The Federal Energy Agency requires all furnaces and boilers be given operating efficiency ratings -the annual fuel utilization efficiency (AFUE). The AFUE tells how much heat the system extracts
from the fuel it burns during a single heating season. The higher the AFUE, the more efficient is the
equipment. The minimum efficiency standard for new furnaces is 78% AFUE. This factor includes
on-and-off cycling, the energy embodied in combustion air, and jacket losses.
Page 27 of 67
www.PDHcenter.com
www.PDHonline.org
A high efficiency furnace or boiler has special efficiency features which raise the AFUE. These
features may include electronic ignition, power draft system, improved burner, vent damper, high
efficiency heat exchangers, and secondary heat exchangers in the highest efficiency models.
Combustion Efficiency
In order to understand the basics of combustion efficiency, the combustion process must be
understood. Stable combustion conditions require three inputs: fuel, oxygen, and a source of
ignition. If the combustibles themselves can provide this third element as they burn, the source of
ignition can be turned off. The products of complete combustion are heat energy, carbon dioxide,
water vapor, nitrogen, and other gases (excluding oxygen). In theory, there is a specific amount of
oxygen that will completely burn a given amount of fuel. In practice, burning conditions are never
ideal. Therefore, more air must be supplied to completely burn all fuel. The amount of air above the
theoretical requirement is referred to as "excess air."
If an insufficient amount of air is supplied to the burners, unburned fuel, soot, smoke, and carbon
monoxide are exhausted out the stack. This results in heat transfer surface fouling, pollution, lower
combustion efficiency, flame instability (the flame blows out) and the potential for an explosion. To
avoid these costly and unsafe conditions, furnaces are normally operated at an excess air level.
This excess air level also provides operating protection from an insufficient oxygen condition
caused by variations in fuel composition and "operating slop" in the fuel-air control system. Typical
optimum values of excess air levels (and equivalent percentage of oxygen by volume) are shown in
the table below:
Firing Method
Optimum
Excess Air
Equivalent
Percent O2
(by Volume)
Natural Gas
5%- 10%
1% - 2%
Propane
5%- 10%
1% - 2%
5%- 10%
1% - 2%
No #2 Oil
Steam atomized
10%- 15%
2% - 3%
Page 28 of 67
www.PDHcenter.com
www.PDHonline.org
No #6 Oil
Steam atomized
10%- 15%
2% - 3.5%
Coal
Pulverized
15%- 20%
3% - 3.5%
Coal
Stoker
20%- 30%
3.5% - 5%
It is important to understand that "excess air" and "excess oxygen" is not the same. Because air is
roughly 21% oxygen by volume, 50% excess air is approximately equal to 10.5% oxygen remaining
in the exhaust stack.
While insufficient air to the burners can be dangerous, airflows in excess of those needed for stable
flame propagation needlessly increase flue gas heat losses and consequently lower efficiency.
Minimizing these losses monitoring for two variables: the percentage of O2 (or CO2), and the stack
temperature. Very high percent of O2 in the flue stack means lower efficiency. The percentage of O2
(or CO2) can be measured by using simple devices containing gas-absorbing analyzers.
These figures show the relationship between proper tune-up, proper heat transfer and efficiency.
As fuel is such a dominant cost factor, the boiler efficiency needs to be kept high to keep operating
costs low. Decreases in efficiency over time can indicate the need for minor adjustments or repairs.
In some cases, only control linkages, a fuel valve, or an air damper may need to be adjusted. In
other cases, a worn burner tip or control cam may need replacing. High stack temperatures may
also indicate the need for cleaning. In any situation, decreases in efficiency indicate the need for
professional maintenance.
Page 29 of 67
www.PDHcenter.com
www.PDHonline.org
Unless outside air is brought into the space for combustion, negative pressure (outside pressure is
greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent
pipe or chimney. As a result, combustion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, you must consider
combustion air needs and requirements for exhaust vents and gas piping in accordance to the
National Fuel Gas Code (ANSI- Z223.1/NFPA 54).
*Unconfined Space: An unconfined space is an area such as a basement or large equipment room
3
with a volume greater than 50 cubic feet (1.42 m ) per 1,000 Btu (29 kW) per hour of the combined
input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not separated by a door. Though an area may
appear to be unconfined, it might be necessary to bring in outdoor air for combustion, if the
structure does not provide enough air by infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the
procedures in the air from outside section (discussed below).
3
Confined Space: A confined space is an area with a volume less than 50 cubic feet (1.42 m ) per
1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This definition includes furnace closets or small equipment rooms.
2) Air from Outside: If air from outside is brought in for combustion and ventilation, the confined
space shall be provided with two permanent openings. One opening shall be within 12"
(305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings
must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input
rating of all equipment in the enclosure. When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu
(645mm2 per .59kW) per total input rating of all equipment in the enclosure. Refer figures
below:
Page 30 of 67
www.PDHcenter.com
www.PDHonline.org
If air from outside is brought in for combustion and ventilation, the confined space must have
two permanent openings. When ducts are used, they shall be of the same cross-sectional area
as the free area of the openings to which they connect. The minimum dimension of rectangular
air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of
louvers, grilles, or screens must be considered. If the design and free area of protective
covering is not known for calculating the size opening required, it may be assumed that wood
louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75
percent free area. Louvers and grilles must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during equipment operation.
Venting Requirements
There are several rules to follow to assure proper venting of gravity vented equipment:
1) Keep vent runs as straight as possible with few turns or bends.
2) Never use a vent size smaller than the size recommended by the equipment manufacturer.
3) All vents must terminate with a proper wind proof vent cap
4) Limit horizontal vent runs to a maximum of 75% of the vertical run. Example, if the vertical run is
10 ft. The horizontal run must not exceed 7.5 ft.
5) Horizontal runs must be pitched with a minimum upward slope of .25 inch per foot of run
6) Vents must terminate a minimum of 2 1/2 ft above any obstructions within a 10 ft radius of the
vent pipe.
7) Always provide a drip leg as near to the equipment as possible. This to prevent condensation of
flue gases in the vent pipe from entering the equipment.
8) Keep combustible material 6 inches away from single wall vent pipe
9) When venting into a common vent, the area of the common vent should be equal to or greater
than the area of the largest vent plus 50% of the area of all additional vents
10) When venting into a common vent, the individual vents should enter at different levels
Rules for Power Vents
The rules for power vented equipment generally are the same as gravity vented equipment with the
following exceptions:
1) Approved power exhausted equipment may have its vent system terminate horizontally out of a
wall. A proper vent cap must still be installed.
Page 31 of 67
www.PDHcenter.com
www.PDHonline.org
2) Horizontal run lengths may exceed vertical run lengths. The combined total run length must not
exceed the manufacturers recommendations.
3) If elbows are used in the vent system you must attribute 6 ft. of equivalent length of run for each
90 degree elbow.
4) If a vent terminates horizontally out a wall make sure it does not terminate near an air inlet
opening. A minimum of 3 ft. is recommended.
5) Make sure the horizontal vents are sufficiently high enough, or guarded so as to prevent
accidental contact by people or equipment.
6) No common venting should be utilized.
Installation Guidelines
1) When the furnace is installed in an attic or other insulated space, keep insulation away from the
furnace.
2) For installation in a residential garage, the furnace must be installed so that the burner(s) and
the ignition source are located no less than 18 (457 mm) above the floor. The furnace must be
located or protected to avoid physical damage by vehicles.
3) The furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms
in the upflow position. When a furnace is installed in an attic, the passageway to and service
area surrounding the equipment shall be floored.
4) The furnace shall not be installed directly on carpeting, tile, or other combustible material other
than wood flooring.
5) Place the furnace as close to the center of the air distribution system as possible. The furnace
should also be located close to the chimney or vent termination point
6) When the furnace is installed in non-direct vent* applications; do not block the furnace
combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion
and safe unit operation.
7) When the furnace is installed in an unconditioned space, consider provisions required to
prevent freezing of condensate drain system.
8) When this furnace is used with cooling units, it shall be installed in parallel with, or on the
upstream side of cooling units to avoid condensation in the heating compartment.
9) The furnace must be installed so that its electrical components are protected from water. The
furnace must be electrically grounded according to the current National Electric Code,
ANSI/NFPA No. 70.
These instructions are intended as a general guide and do not supersede local codes in any way.
Consult authorities having jurisdiction before installation. Typical commercial terminology is
indicated below:
*In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
*In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged
outdoors.
* In Un-vented installations, combustion air is taken from indoors and the flue products are discharged
Page 32 of 67
www.PDHcenter.com
www.PDHonline.org
Unit heaters are the most commonly used form of heating due to the following reasons:
1) they provide the air circulation needed
2) they can be used in conjunction with ventilation systems
3) they are comparably the least expensive
4) they provide quick response to temperature changes
5) they are easy to install
6) they offer inexpensive expansion for additions
7) they can be used in conjunction with waste heat applications
8) they provide snow load protection which facilitates solar gain
1) Gas fired unit heaters: Gas fired unit heaters provide a reliable and energy efficient low cost
heating system and are available for use with natural or propane gas. Gas fired unit heaters
have evolved in three generations.
a. The initial design utilized a natural gravity vented system where the combustion air is taken
from inside of space and has a flue pipe terminated above the ridge of the space.
b. The second generation of gas fired space equipment answered the need for efficiency and
is power vented. Modifications to the venting system increased the efficiency 20% by
adding a fan unit that actively expels the products of combustion. This enhancement
eliminates thermal siphoning of heated air out the flue pipe between heating cycles.
c.
The most recent generation is called the separated combustion style. They capitalize on the
efficiency gained and increased longevity offered by utilizing air from outside the space for
the combustion process. These products eliminate most of the concerns of combustion air
quality and corrosion.
Gas fired units heaters are available with propeller fan or blower wheel air delivery systems.
Propeller fan gas unit heaters are most common. The propeller model is used to deliver the
heated air directly to the space or in conjunction with a fan jet system. Blower units have the
capability to be used in high static systems like large duct distribution systems.
2) Direct Un-vented gas fired unit heaters: Direct un-vented gas fired heaters do not vent hot
flue products out of the space; instead, a direct fired heater expels all heated combustion
products into the space. Products of combustion are carbon dioxide (CO2), water (H2O), and
carbon monoxide (CO). Direct-fired heaters require intermittent ventilation to dilute their
products of combustion. It is recommended that direct-fired heaters use outside air to optimize
combustion.
3) Oil fired unit heaters: This style is utilized regionally. The northeast region of the U.S. utilizes
oil fired equipment more than other areas. Oil fired equipment is available for suspended or
floor mounted installation. Oil fired equipment normally requires more annual maintenance by a
service company.
Safety
Page 33 of 67
www.PDHcenter.com
www.PDHonline.org
All unvented gas-fired space heaters (manufactured after 1983) should be equipped with an oxygen
depletion sensor (ODS). An ODS detects a reduced level of oxygen in the area where the heater is
operating and shuts off the heater before a hazardous level of carbon monoxide accumulates.
These heaters also have labels that warn users about the hazards of carbon monoxide. Always
have your gas heater and venting system professionally installed and inspected according to local
codes.
Safety Warning: Unit heaters that vent products of combustion directly into the space structure
should be used only in areas where adequate ventilation is available to avoid exposure to personnel
from combustion byproducts such as carbon monoxide and ethylene.
Page 34 of 67
www.PDHcenter.com
www.PDHonline.org
10) Check the control wiring to make sure the connections are tight.
11) Check to make sure the manual valves are opened.
12) If your space has an alarm system, make sure it is operational.
It is recommended that a record be kept of the date the heating equipment service was performed.
It is also recommended that these same service checks be performed on a periodic basis
throughout the heating season. By keeping a service record and updating it, it is less likely that this
important maintenance will be overlooked.
Page 35 of 67
www.PDHcenter.com
SECTION - 4
www.PDHonline.org
Hot Water Heating (sometimes called hydronic heating) systems use water or a water-based
solution as a medium to transport heat from a heat source to one or several heat emitters. The hot
water then radiates heat and warms the air within the space. As the water circulates it begins to
cool and is then circulated back to a boiler for reheating.
These systems are useful as centralized heating systems in large building complexes and can be
designed as forced air or radiant heating systems. In a forced air application the heated water is
passed through a coil (much like an automobile radiator) and a blower pushes (or pulls) the cool air
across the coil. At the coil the air picks up the heat energy and the warm air is directed to the living
area. In radiant systems the heated water is run through pipes in the floor (or walls) and the floor
gets warm and the heat radiates into the living area. Both these design options require specific
engineering knowledge and the installation is complex. However, the energy efficiency advantages
and flexibility they offer and the potential to enhance evenness make them attractive alternative.
This section provides design and installation guidelines for both floor and space heating systems. The topics
include:
1)
2)
3)
4)
5)
Secondary components such as expansion tank, safety devices, instrumentation & control
6)
Page 36 of 67
www.PDHcenter.com
www.PDHonline.org
Alternatively, hydronic water system may use forced air handling units using blower, heating coil,
and ducting to distribute heater air to various zones of the building. These systems are well suited
for buildings where such a system already exists for cooling. The force air circulation system
typically mixes 20% outside air with the space return air. In buildings where air cleanliness is
imperative, the force air systems make use of appropriate air-filtering equipment to prevent ingress
of dust indoors. In the regions where both cooling and heating is required, a forced air heating
system is a sensible choice for cooling and heating, since the heating and cooling systems can
share the ductwork and air handling unit. The air handling unit in such cases shall contain both the
chilled water and hot water coil.
Page 37 of 67
www.PDHcenter.com
www.PDHonline.org
3) Hot water can be transported from a heat source to a space over great distances using
insulated pipelines.
4) Hot water can be proportionately controlled to operate at various flow rates and temperatures
all from the same heat source.
5) When properly equipped, a hydronic heating system can also be used to heat domestic water
for things like cooking, cleaning and bathing. Some heating systems can even be adapted to
heat other structures such as greenhouses, garages, swimming pools and snow-melting
systems in the driveway.
6) Exterior water heating and snow-melting systems use a heat exchanger placed between the
boiler and a secondary fluid such as an anti-freeze solution.
7) A properly designed and installed hydronic system can operate with virtually undetectable
sound levels in the occupied areas of a space.
8) Noninvasive Installation: It is often very difficult to conceal ducting out of sight within a typical
house. The best that can be done in many cases is to encase the ducting in exposed soffits.
Such situations often lead to compromises in duct sizing and / or placement. By comparison,
hydronic heating systems are easily integrated into the structure of most small buildings without
compromising their structure or the aesthetic character of the space. The underlying reason for
this is the high heat capacity of water. A given volume of water can absorb almost 3500 times
more heat as the same volume of air for the same temperature change. The volume of water
that must be moved through a building to deliver a certain amount of heat is only about 0.03
percent that of air! This greatly reduces the size of the distribution conduit. Heres an
example of what that means: A 3/4-inch diameter tube can carry the same amount of heat as a
14 x 8 duct. Hydronic systems using small flexible tubing are much easier to retrofit into
existing buildings than is ducting. The tubing can be routed through closed framing spaces
much like electrical cable. Other benefit is that not only shall a -inch diameter tube shall
require considerably less material for insulation, the heat loss of the 14 x 8 inch duct is almost
ten times greater than that of the 3/4 inch tube when insulated with the same material. For
buildings where utility space is minimal, small wall-hung boilers can often be mounted in a
closet. In many cases, these compact boilers supply the buildings domestic hot water as well
as its heat. The entire system might occupy less than ten square feet of floor area.
Disadvantages
The installed cost of hydronic systems is higher than that of direct fired forced-air systems, they can
be slow to warm up, and there is no capability for central air conditioning, air filtering, or ventilation.
Unless your hydronic heating system also has a fan installed, it cannot provide the cooling,
humidification, air filtration or forced air circulation that alternative heating systems can. In addition,
excessive heat gains from sources such as sunlight cant be easily transferred to other areas within
the home.
Another factor to consider when installing a hydronic heating system is its vulnerability to damaging
impacts and leaks. The system will only function correctly if all piping is in full working order. If the
piping becomes damaged, water leaks can rot the flooring and structure of the building.
Design Alternatives
Hot water heating system design can be either gravity heating systems or forced heating systems.
1) Gravity Circulation: In a hot water gravity heating system, the circulation of water is a result of
the difference in density between the hot water in the supply line and the cold water in the
return line. The hot water tends to flow upwards and cold water tends to flow downwards. The
elevation of the supply and return lines are therefore important for proper functionality. Gravity
systems have many disadvantages:
The low differential pressure in the system demands increased pipes and valves
dimensions. They require very large diameter piping for supply and return mains.
Page 38 of 67
www.PDHcenter.com
www.PDHonline.org
The gravity system will also have a relative low heating capacity because of low medium
temperatures in the heating elements. The low temperature water provided a heat
emission rate of only around 150 BTUs per square foot of radiation per hour.
Consequently, radiators had to be large.
Temperature
drop (C)
50 - 90
10 - 15
90
20
Medium Pressure
90 - 120
15 -35
High Pressure
120 - 200
27 - 85
Page 39 of 67
www.PDHcenter.com
www.PDHonline.org
Bare pipes: Perhaps the simplest means of transferring heat from hot water is through
bare pipes of steel, black iron, copper, or aluminum. Black steel pipe is most commonly
used; this is easy to clean, least affected by dust and not easily damaged. Galvanized pipe
should not be used since the galvanizing restricts heat transfer. Black steel pipe is usually
mounted under air inlets or on wall brackets at least one pipe diameter from the wall to
permit free air circulation. Heat output for bare steel pipe, and the length of pipe needed
can be determined from the standard tables or heating equipment vendor catalogues.
Finned pipes: The addition of finned elements to the surface of a pipe enhances its ability
to transfer heat by expanding the pipes surface area. This reduces water volume to heat
and less actual footage of piping is required to do the same work. There are many
variations in the design of finned pipes. There are black pipes with steel fins attached,
copper tubes with aluminum fins, and completely aluminum products. All of them seek to do
the same job, enhance heating potential while minimizing footage and the water volume
required.
These are particularly suitable where there is not enough room for bare pipe. Where less
heat is required, short sections of convector can be spaced along a wall. The main
drawbacks to finned-tube systems are that they collect dust (reducing performance), require
frequent cleaning and can easily be damaged. They are not recommended for dusty
atmospheres.
3) Cast-iron baseboard systems include low-profile convector radiators that have lower heat
output and substantially higher initial cost than baseboard convectors. These heating systems
operate at the same temperatures as cast-iron radiators and can also overheat.
4) Fan Coils: Fan coils transfer heat mainly by forced convection. In a typical fan coil system the
air in a room is drawn into the system and is heated over a heat exchanger, composed of hotwater finned-tube coils. The effectiveness of a fan coil to heat depends on the surface area,
size of heat exchanger, spacing and thickness of coil fins, the number of tubes and the
performance of the fan. The temperature of the entering water as well as the temperature of the
entering air will also influence the heat capacity of the fan-coil.
The heat output of the fan coil is approximately proportional to the difference between the
entering water temperature and the entering air temperature;
Increasing the rate of water flowing through the coil will increase the heating capacity of the
fan coil;
The increase of the air flow rate flowing through the coil will also increase the heating
capacity of the fan coil;
A fan coil unit running with lower water temperatures will have the same heat capacity of
another similar heat coil with smaller coil surfaces and/or less tubes.
5) Radiators: These are large cast-iron heating units usually found in older buildings. They are
designed to provide full heating capacity at a lower temperature than baseboard convectors.
Caution should be used with these radiators as they can overheat.
Page 40 of 67
www.PDHcenter.com
www.PDHonline.org
6) Unit heaters: These are excellent for areas where a concentrated heat source is desired. They
can also be incorporated with ventilation air ducts or other types of air circulation systems. In
dusty buildings, these radiators should be inspected and cleaned regularly to maintain heating
effectiveness. Hydronic unit heaters are often used as a way to supplement another hydronic
heating system, like a heated slab floor system heating system. Hot water unit heaters are very
reliable, inexpensive and very responsive to control inputs.
7) Kick-space heaters are designed to be installed horizontally under kitchen cabinets or
bathroom vanities. Kick-space heaters are best suited to smaller rooms.
8) Radiant floors have hot water piping or tubing installed in or under the floor.
Page 41 of 67
www.PDHcenter.com
www.PDHonline.org
In fire tube boilers, hot combustion gases pass through tubes submerged in water. These
systems are simple and easy to construct and are generally used in low-pressure applications.
The main components that make firetube boilers energy efficient is the four-pass design, the
forced-draft design, the heating surface area and updraft construction.
!"Four-pass design: The number of passes indicates the amount of time the flue gases pass
through the tubes. It has been proven that the efficiency of the boiler is directly proportional
to the number of passes. The four-pass design is based on the velocity of the gases being
directly proportional to the ratio of the volume of the gases and the flow area. The flue gas
has to maintain high flow velocity. The temperature of the exhaust gas is lower, leading to
an increase of the overall efficiency of the boiler.
!"Forced-draft design: The forced-draft design uses a fan to pressurize the combustion air
before it is mixed with the fuel, which improves combustion. This design provides air in the
required quantities and at the proper pressure, thus reducing excess air.
!"Heating surface area: Heat transfer is fundamental for efficient and long lasting
2
equipment. Packaged units can offer a heating surface area of 0.047 m /kW which helps
increasing the life of the boiler, reduces maintenance requirements and increases the
efficiency of the boiler.
!"Updraft construction: Updraft construction involves placing the furnace at the lower end of
the boiler and running the gases towards the higher end of the boiler. The furnace contains
the hottest combustion gases and is designed with a significant clearance from the bottom
shell to enable full fluid circulation in the system. Such a construction offers a safer
operation and better combustion.
In water-tube boilers, the water is contained in tubes located inside a furnace and hot flue gases
pass over the tubes, heating the water, and then exit out the stack. Small watertube boilers are
usually available in packaged units while larger tubes are assembled in the field. Packaged
watertube boilers, using oil or natural gas, have various designs and can have any capacity. They
are usually categorized according to their burner, which can be an atmospheric burner (standing
pilot of spark ignition) or a forced convection burner, which has a higher efficiency and better overall
combustion.
For boilers to run at peak efficiency, operators must attend to boiler staging, water chemistry,
pumping and boiler controls, boiler and pipe insulation, fuel-air mixtures, burn-to-load ratio, and
stack temperatures.
3) Circulator, or the circulating pump, is an electrically driven pump that forces water through
the boiler and/or the piping system. Some heating systems have more than one circulator in
order to serve separate areas of the building. The circulator pump is selected for the flow rate
and the head requirements. A pump must develop enough pressure to overcome the resistance
(friction) created in the boiler, piping, fittings, heat distributing units and other parts of the
system. When making your selection, do not add the static head pressure (due to the height of
the system) to the head pressure rating of the circulator. The following facts may be noted:
!"Centrifugal pumps, in the form of wet rotor circulators or three-piece circulators, are most
commonly used in hydronic heating systems.
!"There are four possible pump selections: a large and small pump, either of which can run in
high or low speed. Obviously the large pump in high speed offers the maximum
performance, but it would be both the most expensive to buy and the most expensive to
run. The small pump in low speed is at the other extreme. Again we see the trade-off
between initial cost and operating cost ("pay me now, or pay me later").
Pumps can also be placed in parallel or in series. It is a good idea to use two pumps connected
in parallel in case one should fail, or to have a spare on hand.
4) Isolation Valves at all Zones or Flow Circuits are often used as an alternative to having
separate circulating pumps for each different zone in the building. Individual zone valves are
electric and are controlled by their own thermostat so each zone or room in the home can be
individually controlled for comfort and energy savings. Manually operated valves are sometimes
needed to balance the system in multi-zoned installations, for system shut down, or if a
thermostat fails. Valves can usually be one or two sizes smaller than the line they serve. If the
Page 42 of 67
www.PDHcenter.com
www.PDHonline.org
pipe is larger than the flow requires (as is often the case for bare pipe systems), know the flow
rate and select a valve of the required capacity.
5) Automatic Temperature Control and Zone Control: These are desirable, using
thermostatically controlled flow regulators. Automatic valves regulate the hot water circuit in
each room or zone and are actuated by the thermostat for that room. The circulating pump
usually runs continually and the valves open or close as required. Alternatively, the pump can
be started by thermostat or aquastat, as one or more zones calls for heat. Three-speed pumps
or pumps equipped with variable speed drive are also available, which increase or decrease the
flow as needed.
6) Relief Valve: Every hot water boiler must have a safety relief valve that will keep the pressure
at or below the boilers working pressure. The A.S.M.E. (American Society of Mechanical
Engineers) code states: Every hot water heating boiler shall have at least one officially rated
pressure relief valve set to relieve at or below the maximum allowable working pressure of the
boiler. Relief valves shall be connected to the top of boilers with the spindle vertical if possible.
No shutoff of any description shall be placed between the relief valve and the boiler, or on the
discharge pipe between such valve and the atmosphere.
The discharge of steam through a relief valve is an emergency condition and places a critical
demand on the valve. Whenever the temperature of the water in the boiler is about 212F or
above, and the relief valve discharges, the sudden pressure drop causes the water to flash and
to steam. The capacity of the relief valve must handle this. There is a vast difference between
discharging water and discharging steam. A pound of water occupies 27.7 cubic inches of
space. A pound of steam, at atmospheric pressure, occupies 26.8 cubic feet; over 1600 times
more space than water! Thus, an A.S.M.E. relief valve is tested and rated on steam, even
though it is a valve for a hot water boiler. The smallest pressure relief valve available is
probably rated at 15,000 Btu/hr, which is also more than adequate.
7) Low Water Cut-Off: Most boiler manufacturers recommend putting low water cut-offs on hot
water boilers. Many local codes will require this. Even though a boiler may be protected from
exploding because it has an A.S.M.E. relief valve, dry firing can still ruin it. Most hot water
boiler damage can be traced to low water conditions.
There is a misconception that the pressure reducing fill valve will keep a system full under all
circumstances. This is not true. To illustrate the problem, a typical system will have a pressure
reducing fill valve set around 12 to 18 lbs and a relief valve set to open at 30 lbs and close at 26
lbs. Should the relief valve open to discharge water due to excess pressure, it is obvious the fill
valve wont make up the water lost. Without make-up water replacing the loss through the relief
valve, a low water condition can result. There are many other reasons a system can lose water
so that a low water condition will result such as leaks in the boiler, piping, or through the pump
seals. Carelessness, such as draining a boiler for repair and forgetting to refill the system is yet
another common reason for a low water condition. A low water cut-off will save the boiler by
not allowing the burner to come on until the low water condition is corrected.
Under certain circumstances, a low water cut-off may not be enough protection. A fuel valve
could stick open; contacts could weld closed due to an overload or short circuit making the lowwater cut-off ineffective. The best recommendation to cover all installations is to use a
combination water feeder and low water cut-off. The feeder portion is usually capable of
feeding water into the boiler as fast as it can be discharged through the relief valve. While the
feeder cut-off combination will add to the cost of an installation, when compared to the cost of
replacing a boiler, it is cheap insurance. Remember, codes are minimum requirements, the
at least, that must be done. It is always good practice to exceed the code requirements,
especially where safety is concerned.
8) Expansion tanks are used as a reservoir or overflow tank. Water expands about 4% as it
heats from room temperature to near boiling. The expansion tank is an essential component of
the hydronic heating system used to accommodate an increased volume of water in order to
avoid damage and accidents due to high pressure. The expansion tank contains a quantity of
air that is compressed as the volume of water rises in the system. In essence, the expansion
tank performs two key functions: 1) Accept the extra water produced by heating the water in a
sealed system and 2) Prevent the circulator from changing the static pressure in the sealed
system. The three parameters to take into consideration when designing an expansion tank are
Page 43 of 67
www.PDHcenter.com
www.PDHonline.org
its location, its height and its volume. As a general rule, the expansion tank should also be
located near the inlet port of the circulator and the volume of the tank should not be larger than
the calculated volume value.
Expansion tanks are sized from the volume of water in the loop and the difference between the
maximum and minimum operating temperatures. Generally the required volume is less than
10% of the system volume. System water volume and temperature determine tank size. The
compression tank acts like a spring on the system, keeping pressure on it at all times.
!"If the tank is too small, or becomes waterlogged, the relief valve will open when the boiler is
heating and discharge water. When the heating cycle is over, the water will cool, system
pressure will drop, and the feed valve will open and feed water until system pressure is
back to normal. On the next call for heat, the water will again expand, causing the relief
valve to open. The cycle will repeat over and over until the too small tank is replaced,
another expansion tank is added, or the waterlogged tank drained and properly refilled with
the correct air and water charge.
!"If the tank is too large, the system pressure increase may not be enough as the system
heats up and approaches boiling, especially at the high point of the system where low static
head exists. Proper compression tank sizing is very important for trouble-free system
operation, whether it is a pre-charged tank with a bladder separating the water and air, or a
standard expansion tank.
9) Air elimination devices should be installed at each high point in the hydronic system where air
can gather. Trapped air must be expelled from the heating system to ensure optimum heating
performance and to prevent noisy operation, blockage or even complete damage to the system.
Manual air vents at high points, automatic air vents, float-type air vents, air purgers and microbubble absorbers are used to solve the problem. There are two basic types of air vents;
automatic and manual. Automatic air vents come in two styles. Float type and fiber disc type.
!"Float vents have a float attached to a valve, all contained in a shell. When the shell is full of
water, the float keeps the valve closed. When enough air accumulates in the shell, the float
drops, opening the valve and air passes out until water again fills the shell, closing the
valve.
!"Fiber disk type automatic vents are physically very small, the same size as manual loose
key or coin vents. They use special discs that swell when water touches them. As air
accumulates and replaces the water around the discs, the discs dry out, shrink, and open a
small vent port.
!"The best air vents are the manual vents which require a small key to open or close them.
These are just a small needle valve, metal to metal seat and are virtually indestructible and
cheap. Their only drawback is that they must be manually opened and closed. Air vents for
residential heating systems typically have a 1/8" NPT (National Pipe Thread) connection
and require no further sizing.
10) Heat transfer devices such as radiators, convectors, fan-coil units and radiant floors transfer
the heat from piped water to the living space.
11) Heat exchangers are the elements in the hydronic system that transfer heat to the piped water,
or in the case of snow melting systems, the heat is transferred to an anti-freeze solution.
12) Mixing valves blend cooler return water with hot boiler water to obtain the desired thermostat
temperature.
13) Controls: Standard low-voltage or newer programmable electronic thermostats can be used to
provide temperature control for the hydronic system. Thermostats are usually connected to, and
control, the zone valves. When the valve is fully open, an end switch on the zone valve turns
the boiler and circulator on. Thermometers and pressure gauges are handy for balancing the
system and also to monitor the efficiency of the system. Pressure gauge cocks and
thermometer wells shall be installed at appropriate locations to make the routing checks.
14) Pressure regulator: The pressure regulator which is actually a pressure reducing valve must
be provided on the cold water supply connection. It is used to fill the system initially and will add
water when system pressure falls below the valve setting. The standard factory setting is
Page 44 of 67
www.PDHcenter.com
www.PDHonline.org
usually 12 lbs. This setting is the correct setting for a static height up to about 18 feet, good for
most two-story buildings. For higher static heads, the valve can be adjusted up to 25 lbs. Most
systems work best under a moderate pressure of about 15 PSI (100 kPa) for better circulation
and to avoid vapor locks (just like automobile systems).
A 0-100 PSI pressure gage would be specified if the water tank is connected to the domestic
water supply, since most city water systems operate in that range. If it is a stand-alone loop,
specify a 0-30 PSI pressure gage, since residential heating equipment is generally required by
ASME Pressure Vessel Code to operate in that range.
15) Piping materials for the hydronic system will vary depending on how the system is used and
installed. Copper piping is typically used to distribute the hot water throughout the system,
however, if the piping is embedded in concrete it may be made of iron, steel, synthetic rubber or
plastic. Take changes in pipe size into account when choosing supports and planning layout.
Provide sleeves or adequate clearance where pipes pass through walls or floors. Pipe supports
should allow movement. Allow for expansion at the end of along pipe line or loop by stopping
short of the end wall. For a 100C change in temperature, steel expands 0.12% in length;
various plastics expand 5 to 15 times as much.
16) Draining and Venting: Both are facilitated if heating lines slope uniformly to one end (or one
point). Install drain cocks at the low points and air vents at the high points. One of each may be
all that is required for simple systems; others may require several.
17) Pipe insulation is used to prevent heat loss and to ensure heat is delivered to the living space
where it is required. Pipes running through unheated areas, such as crawlspaces, should be
insulated with moulded fibreglass pipe insulation.
18) Antifreeze and Corrosion Protection: This protection is important. Antifreeze should be used
if there is any danger of freezing. Use an ethylene glycol solution specially formulated for hot
water heating systems. This contains corrosion inhibitors to maintain long-term performance of
systems and components. Check the antifreeze solution every year, and add inhibitor if needed.
= density, (lb/ft )
T = temperature difference (F)
The basic equation can be modified for the actual units - SI or imperial - and the liquids in use.
For water with temperature 60F flow rate can be expressed as:
3
or
q = h / (500 * T)
Fluid Velocity: The acceptable range for water velocity in most applications is between three and
seven feet per second (3-7 fps). Velocities lower than 3 fps represent large diameter pipe that is uneconomical to install, and velocities higher than 7 fps represent too small pipe that will cause large
Page 45 of 67
www.PDHcenter.com
www.PDHonline.org
pressure drops and un-economical sizing of circulator pump. Going outside of this acceptable
design range can also cause problems with air entrapment in the water (if too slow) and pipe
erosion and noise (if too fast).
Pipe Size: The pipe size is determined from the standard selection charts based on equation q = A
2
* V where A = area of the pipe, * d /4 and V is velocity of flow in fps. When two parameters GPM
and velocity range is fixed, the optimum pipe diameter can be selected. For example, if a system
requires 90 GPM, we can select either 2-" diameter pipe at 6 fps velocity or 3" diameter pipe at 4
fps both within the acceptable velocity range. Most flow rates will offer a choice between a couple of
pipe diameters within the acceptable velocity range.
Page 46 of 67
www.PDHcenter.com
www.PDHonline.org
Case #1 Direct Return System: Consider a system comprising of hot water generator, circulator
and hot water distribution system serving 4 branches. As the water moves away from the circulator,
the pressure differential across each circuit becomes less and less. On branch 1, the system has
10 of head pressure on the supply and 3 on the return side of the zone. That means there is a
pressure differential of 7 , and this 7 differential will cause a certain amount of flow to take place in
that zone. At the farthest zone which has 7 of head pressure on the supply and 6 on the return
side, only 1 of pressure differential exists across this zone. A difference in pressure is what causes
water flow and greater the pressure differential, the greater shall be the flow rate. In the scheme
above the farthest circuit might have no-flow or very scarce flow.
How do we solve this imbalance problem?
Case #2 (Reverse Return System): The reverse-return piping provides answer to this problem.
Reverse-return maintain equal pressure drop throughout the entire piping system and ensures
adequate flow to all the branch circuits. There is a bit more piping involved but maintaining water at
every point makes it well worth installing.
Notice the length of circuit via branch 4 from pump discharge back to the hot water generator and
via branch 1 is same resulting in somewhat equivalent pressure drop in both the circuits. Consider
putting balancing valves on the return side of each circuit. By appropriate setting, the pressure drop
in each circuit shall be the same. With equal pressure drops in each circuit, there is no path of least
resistance, and so there will be adequate flow in each circuit.
Note that the two pipe systems are more expensive than either of the one-pipe systems but water in
each of the pipes travels shorter distances, returns to the boiler more quickly and allows greater
heat control in individual rooms or zones.
Control Strategies
When a boiler is used for space heating, the simplest control strategy is to have the thermostat
control the burner and circulator together. This easily adjusts the heat to your needs and provides
the lowest operating costs. Programmable thermostats can be purchased and set up with the boiler
and circulator to allow you to control the time and temperature settings of your heating system. A
programmable thermostat is one of the most energy efficient items you can add to your heating
system.
A second control strategy is to always keep the boiler hot and have the thermostat turn the
circulator on and off. Operating costs for this strategy will be higher due to continual heat losses.
A third method of space heating is to adjust the boiler temperature to compensate for the
temperature outside on the north side of the house. In this system, an externally mounted
Page 47 of 67
www.PDHcenter.com
www.PDHonline.org
thermostat records outdoor temperatures and an internal thermostat adjusts interior zone valves to
comfortable heating levels. This method is more energy efficient than the other temperature control
strategies.
If your boiler is also used to heat domestic water it must be maintained at full temperature, even
when living space heating isnt needed. This leads to increased operating costs from high stand-by
heat losses. Separate water heating is recommended for energy efficiency.
Installation hints
1) Install a programmable thermostat with the heating system. Set it to turn heat down when your
home is empty and to turn the heat up before you return home.
2) Install extra heating capacity in the bathroom, most people prefer a warmer bathroom.
3) Install a floor heater or recessed tube piping in front of glass patio doors to offset the chill
caused by the large glass area. Allow at least 20 cm between the heater and the window.
4) Install a return air grille in the floor at the opposite side of the room from the heating device to
improve cold air removal.
5) Clean heating devices regularly to remove dust and keep air circulating properly.
6) Install hot water to anti-freeze heat exchangers and piping systems under steps, sidewalks and
driveways to melt snow and ice improving safety outside your home during winter.
7) As a minimum, bedrooms should be zoned separately from living and dining areas.
8) Rooms with southern exposure should be zoned separately from those with other exposures.
9) Radiant floors have lower water temperature requirements than convection units and these
must be on separate zones.
System Startup
Most air problems can be eliminated by careful design, good maintenance, and proper initial startup
of the system. The most often overlooked part of a forced hot water system is proper startup. Once
a system has been installed, flushed, and filled to the proper static head, the boiler should be fired
and slowly heated to at least 225F water temperature and held there for about one-half hour. This
will liberate the entrained air in the water and send it to the expansion tank. The hotter the water,
the more air it will liberate. The circulating pump(s) should be off during this initial heating. Now,
allow the boiler to cool to normal operating temperature and start all circulators and open all the
zone valves, if used. Again, run the water temperature back up to at least 225F and circulate all
the water for 15 to 30 minutes. This will drive most of the air out of the fresh water, and as long as
there are no leaks in the system, air problems will be prevented. Anytime the system is drained,
say for some repairs, and re-filled, the startup procedure should be repeated.
Page 48 of 67
www.PDHcenter.com
www.PDHonline.org
stratification effect. The main disadvantage is their slow response time compared to other hydronic
systems.
Radiant floor systems can be installed in one of three ways:
Slab-on-grade system
Pipe
Diameter
Up to100 ft
0.5
Up to 200 ft
0.75
Up to 325 ft
1.0
Up to 500 ft
1.25
Water flow should be higher than for space heat to keep the temperature more uniform. Use a
temperature drop of 10-15F for calculating flow rates.
Floor heat has a number of advantages:
1) Warm floor dries quickly
Page 49 of 67
www.PDHcenter.com
www.PDHonline.org
System Design
The best floor temperature is 77 - 86F; warmer floors are uncomfortable and cooler ones are less
effective. The amount of heat transferred from the concrete floor depends on both floor and the air
temperatures. Heat input to the floor will depend on the inlet water temperature, pipe spacing and
water flow, provided that the heating unit has enough capacity to keep up to the floor heat loss.
Heat output from floor to air is given by the following equation:
h = 2.11 * (Tf - Ta)
Where
h = heat output from the floor, Btu/sq-ft
Tf = floor slab temperature, F
Ta = room air temperature, F
For a floor at 86F and air temperature of 58F, heat output would be 2.11 x 28F = 59 Btu/sq-ft. As
the building cools below 58F, the heat output will increase accordingly. Design for 60 Btu/sq-ft and
size the heating unit slightly larger to account for system losses.
It is possible to get by with a smaller heating unit, down to about 50 Btu/sq-ft, if cooler floors are
acceptable. This heat output will keep a reasonably well-insulated shop at 50 - 58F but does not
have extra capacity for reserve heat. It is not feasible, however, to obtain greater capacity from the
floor system, since this would require a floor temperature too high for comfort. The system will have
to be larger if auxiliary unit heaters are supplied from the same boiler system.
Water flow and pump capacity are calculated as outlined earlier; using equation
q = h / (500 * T)
Where
q = water flow rate (gal/min)
h = heat flow rate (Btu/h)
T = temperature difference (F)
The T is usually taken as 9-16F to maintain uniform conditions. Floor heating pipe is usually
placed in loops running from a supply and back to a return header. Flow through each loop, for the
purpose of checking pressure drop and sizing valves, is thus the total flow divided by the number of
loops. Pipe may also be laid out in a continuous spiral around the building but this will require larger
pipe owing to the longer loop length. The header system is normally of steel pipe, with T-fittings or
nipples welded on for attaching the floor lines. The header should be sized for the total water flow in
the system. Valves are recommended on each floor line to balance or control flow; one on the
supply and another on the return are best in case one loop springs a leak.
Page 50 of 67
www.PDHcenter.com
www.PDHonline.org
Example:
Design a floor heating system for a room 32 x 50. Floor area inside the foundation is about 30 x
48 = 1440 sq-ft. Calculate system size based on 70 Btu/sq-ft heat input.
Solution
Room floor area = 1440 sq-ft
1) Calculate system size based on 70 Btu/sq-ft heat input.
Total Heat input = 70 Btu/sq-ft x 1440 sq-ft = 100800 Btu (or ~ 30 kW capacity)
2) Determine flow rate for an inlet- outlet hot water temperature change of 10F across the system
q = h / (500 * T)
q = 96600 / (500 * 10)
q = ~ 20 GPM
3) Determine number of loops and water quantity per loop
Each loop is about 100 ft ( ~2 x 48) long, thus pipe will be adequate (Note: double loops of 184
ft length could be run to reduce valves and connections).
Room width = 30 ft
Pipe spacing = 1.5 ft
Number of lines = 30 / 1.5 = 20
Therefore, use 20 lines or 10 loops
Water flow in each loop = 20/ 10 GPM = 2 GPM
4) Size the header system:
For a flow of 20 GPM, 2 (50 mm) pipe is more than adequate.
5) Estimate the volume of the system
1000 ft* of floor pipe x 0.025 gallons per ft = 25 gallons {Note *.100 ft loop x 10 loops; the
pipe has a holding capacity of 0.0.25 gallons per ft of pipe}
60 ft* of 2 mm header x 0.16 gallons per ft = 9.6 gallons {Note*.2 x 30 ft of supply & return
header; the 2 pipe has a holding capacity of 0.16 gallons per ft of pipe}
Boiler unit volume (estimated) = 5 gallons
Total = 39.6 gallon
Minimum expansion capacity required is 5% of 39.6 gallon = 1.98 gallon; obtain an expansion tank
with at least 2 gallon net expansion capacity.
Page 51 of 67
www.PDHcenter.com
www.PDHonline.org
3) Floor reinforcement: There are three basic methods used, re-bar, re-mesh, and fiber-mesh.
The latter is an additive to the wet concrete and reportedly can offer the most integrity and
longevity. Spend some time researching the best means of reinforcement for your project.
Remember that you will need to secure your heating tubing to something and a reinforcement mesh
might be the best choice.
4) Insulate! It cannot be stressed enough that a heated concrete slab floor should be insulated
around the perimeter and as deep as the frost line in your area. Some reports indicate that up to
50% of your heat can be lost out the perimeter of a heated slab if no below grade insulation is
installed. The best type of insulation to use is one of the extruded styrene boards, usually 1.5 - 2
inches thick.
5) Engineering: A good design and plumbing plan are the keys to a well designed heated concrete
slab floor. A well designed system will include an appropriate boiler and pump sized to handle the
load. Also important is a means of balancing the flow of hot water to achieve even floor
temperatures.
The factors to take into consideration during the design of a radiant floor system are:
the hottest fluid should be routed first along the exterior wall(s) of a room
Page 52 of 67
www.PDHcenter.com
SECTION- 5
www.PDHonline.org
ELECTRICAL HEATING
Electric furnace using resistance heating converts nearly 100% of the energy in the electricity to
heat. From energy management and environment conservation point of view, electric heating is not
a recommended choice for heating. Since most electricity is produced from oil, gas, or coal
generators that convert only about 30% of the fuels energy into electricity and after accounting
losses due to transmission & distribution, converting electricity back to heating doesnt make sense.
Page 53 of 67
www.PDHcenter.com
www.PDHonline.org
6) Heating Cable: These are insulated resistance heating elements manufactured in various
lengths and wattage's and are suitable for installation in ceiling plaster or in/under concrete
slabs. This method of heating evenly distributes the heat source and produces a low
temperature radiant heat surface. This method has been used in large open buildings such as
warehouses, garages, hangars, etc.
7) Unit Heaters: These heating elements are used with a fan or blower to force air into the
conditioned space. Certain types are classified as heater-ventilators and perform the function of
both controlled heating and ventilating. These units have been used primarily in schoolroom
heating, but can be used for many commercial/industrial applications where ventilation is
required.
8) Electrical Tabular Heaters: These are steel or aluminum tubes usually round or oval in
section. They consist of an electrical heating element, which extends from end to end and is
surrounded by air. The surface temperature is about 80C. A single tube at 50mm diameter has
an output of about 180 Watts per meter length and tubes may be mounted in banks, one above
the other, for higher outputs. An electrical skirting heater with an output of 400 Watts per meter
run is typical of some installations requiring background or low level heating. Tubular heaters
are used in churches, under pews, in greenhouses, conservatories and foyers. They can be
placed at the bottom of high windows to prevent downdraughts of cold air or be set to prevent
frost in greenhouses or conservatories.
9) Radiant Heating: Instead of circulating heat by moving the air in the room, a radiant system
heats objects including people. There are several types of electrical radiant heaters:
Infrared Radiant Heaters: These heaters generate infrared radiation, heating all objects in
their "line of sight," or radiation path. The electrical elements used are similar to those fitted
to luminous fires but, for a given rating, are commonly longer as shown below, and
arranged to operate at about 900C. Equipment is available with either metal sheath
enclosed element, quartz tubes, and reflector lamps. They are all used with a directional
reflector. Wall or ceiling models of these are suitable for kitchens and bathrooms, ratings
are up to 3 kW. Infrared heating is used in areas where heating the entire space through
convection would be difficult or expensive in comparison to keeping people comfortable
such as warehouses, garages, etc.
Quartz Lamp Heater: The elements of this type of heater operate at about 2000oC and
consist of a tungsten wire coil sealed within a quartz tube containing gas and a suitable
halide rating of elements about 1.5kW. These are used in large spaces either where the
requirement is intermittent or where only local areas require spot heating.
High Temperature Panels: These consist of either a vitreous enameled metal plate or a
ceramic tile behind which a resistance element is mounted within a casing. Panels of this
type operate at a temperature of about 250C and have ratings in the range 750 W to 2 kW;
they are normally used in washrooms in industrial situations. These low-density radiant
heaters which can be mounted in wall or ceiling to provide spot heating.
Heat Pumps
Many forced-air systems use a heat pump instead of an electric furnace because of its high
efficiency and capability to air-condition. A heat pump is an electrical device that functions by
moving (or pumping) heat from one place to another. Like a standard air-conditioner, a heat pump
takes heat from inside a building and dumps it outside. The difference is that a heat pump can be
reversed to take heat from a heat source outside and pump it inside. Thus heat pump can be used
for both summer cooling and winter heating cycles. Note the following facts:
1) In the heating mode, heat pumps are far more "efficient" at converting electricity into usable
heat because the electricity is used to move heat, not to generate it.
2) Because they move heat rather than generating heat, heat pumps can provide up to 4 times the
amount of energy they consume.
3) If you heat with electricity, a heat pump can trim the amount of electricity you use for heating by
as much as 30% to 40%.
Page 54 of 67
www.PDHcenter.com
www.PDHonline.org
4) High-efficiency heat pumps also dehumidify better than standard central air conditioners,
resulting in less energy usage and more cooling comfort in summer months.
The heat pumps are divided into two major groups: air source (air-to-air) systems, which draw heat
from the air, and ground source (earth energy) systems, which draw heat from the ground or
underground water.
Page 55 of 67
www.PDHcenter.com
www.PDHonline.org
refrigerant. The refrigerant is then pumped to the warm heat exchanger, where the refrigerant is
condensed, releasing heat in the process. This sequence is reversed for operation in the cooling
mode.
Although these cost more to install, these have low operating costs because they take advantage of
relatively constant ground temperatures. However, the installation depends on the size of your lot,
the subsoil and landscape. Ground-source or water-source heat pumps can be used in more
extreme climatic conditions than air-source heat pumps, and customer satisfaction with the systems
is very high.
The efficiency or coefficient of performance (COP) of ground-source heat pumps is significantly
higher than that of air-source heat pumps because the heat source is warmer during the heating
season and the heat sink is cooler during the cooling season. Ground-source heat pumps are
environmentally attractive because they deliver so much heat or cooling energy per unit of electricity
consumed. The COP is usually 3 or higher.
Page 56 of 67
www.PDHcenter.com
www.PDHonline.org
Annexure # 1
Gas Furnaces
Typical
Available
Output
Ranges
40000 to 150000
Btuh
Advantages
Oil Furnaces
72800 to 168000
Btuh
Favourable alternative to
electricity in colder climate
Disadvantages
Electric Furnaces
17065 to 136520
Btuh
(5 kW to 40 kW)
No flue required
18000 to 60000
Btuh
(1 to 5 tons)
No flue required
Small space required
similar to electric furnace
Same unit often adaptable
to upflow, downflow and
horizontal configurations
Economical operation
compared to electric
resistance furnace
Use same equipment for
both heating and cooling
Page 57 of 67
www.PDHcenter.com
Equipment
Type
Typical
Available
Output
Ranges
Advantages
www.PDHonline.org
Disadvantages
combinations
Servicing more sophisticate
than furnace
Heat Pump
(water to air)
18000 to 60000
Btuh
(1 to 5 tons)
No flue required
Small space required
similar to electric furnace
80000 to 200000
Btuh
Provide abundance of
warm heat utilizing
economical fuels
Ideal for retrofit in poorly
insulated older homes
Coal furnace can burn coal,
wood and even trash
Operation not dependent
on electric supply, hence
not affected by outages
Page 58 of 67
www.PDHcenter.com
www.PDHonline.org
Annexure # 2
APPLICATION CONSIDERATIONS FOR VARIOUS SYSTEMS
A general guide to select an appropriate heating system for different buildings is presented below,
based on experience. This can be amended judiciously for specific users needs.
Heating/Cooling Systems and Buildings
BUILDING
Hospital Ward
HospitalOperating Theater
Large Workshop,
Industrial
Building, Factory
Small Workshop,
Garage
Office Building,
Public Building
HEATING SYSTEM /
EMITTERS
HEATING
MEDIA
COMMENTS
Air
Plenum heating
Air
Radiant ceiling
Water
Air
Chilled ceiling /
beams.
Chilled water
Oil/gas fired
Unit heaters
Steam, HTHW,
MTHW, LTHW
Radiant tubes
Steam, HTHW,
MTHW or
direct gas
fired.
Radiant panels
Steam, HTHW,
MTHW
Oil/gas fired
Unit heaters
MTHW, LTHW
Fan convectors
MTHW, LTHW
Air conditioning
central plant
Air
Hot/chilled
water
Page 59 of 67
www.PDHcenter.com
BUILDING
HEATING SYSTEM /
EMITTERS
HEATING
MEDIA
COMMENTS
Room air
conditioners/ cassette
units
Hot/chilled
water
Plenum heating
Air
Radiators
LTHW
Natural convectors
LTHW
Fan convectors
LTHW
May be noisy.
Underfloor heating
LTHW
Storage heaters
E7 electricity to
air
Air conditioning
central plant
Air
Plenum heating
Air
Radiators
LTHW
Underfloor heating
LTHW
Electric quartz
tube
High temperature
panels
Electric metal
plate
Low temperature
panels
Electric
elements in
plate
Skirting heating
Electric
element
Tubular heaters
Electric
element
Pipe coils
LTHW
Air conditioning
central plant
Air
Church, Library
Department Store,
Supermarket
www.PDHonline.org
Page 60 of 67
www.PDHcenter.com
BUILDING
School, College,
University
HEATING SYSTEM /
EMITTERS
HEATING
MEDIA
House
COMMENTS
Room air
conditioners/ cassette
units
Hot/chilled
water
Plenum heating
Air
Radiators
LTHW
Fan convectors
LTHW
Radiators
LTHW
Radiators LST
Warm water
Radiant ceiling
Water
Underfloor heating
LTHW
air
Radiators
LTHW
Air conditioning
central plant
Air
Room air
conditioners/ cassette
units
Hot/chilled
water
Plenum heating
Air
Fan convectors
LTHW
Natural convectors
Electric
element
Radiators
LTHW
Underfloor heating
LTHW
Invisible system.
Air conditioner
Electrically
operated
refrigerant
(Low Surface
Temperature)
Hotel
www.PDHonline.org
Page 61 of 67
www.PDHcenter.com
BUILDING
Apartment
HEATING SYSTEM /
EMITTERS
HEATING
MEDIA
www.PDHonline.org
COMMENTS
Storage heaters
Electricity
Underfloor heating
Electric cables
Underfloor heating
Water
Radiators
Page 62 of 67
www.PDHcenter.com
www.PDHonline.org
Annexure # 3
ENERGY CONSERVATION & LOAD REDUCTION STRATEGIES
Heating requirements can be reduced through passive solar design and attention to tightening the
building envelope. The following tips may be useful for energy conservation:
General Tips on Energy Conservation
1)
Use a correctly sized heater for the space you are heating.
2)
3)
4)
Don't overheat. Every one-degree increase in temperature is a 10% increase in heating bills
and emissions.
5)
Minimize heat loss through poor insulation by repairing faulty door seals, hanging curtains
that sit close to the window frames and laying rugs on bare floors.
6)
7)
Always light gas heaters in accordance with manufacturer instructions, turning the setting
down to a comfortable level after the burners are lit.
8)
Keep all doors closed so that the warm air is restricted to the area requiring heating.
9)
10)
Install draught seals and weather stripping around doors and windows. Air leaks can account
for 15-25% of heat loss from an uninsulated space and create uncomfortable draughts.
11)
Protect your windows - up to 40% of total heat loss from a space occurs through uncovered
windows. Close-fitting, heavy drapes or blinds, or double-glazed windows reduce heat loss.
12)
Zone your space: being able to close off different areas of your space allows you to heat only
those areas in use at any one time.
13)
Open up curtains to north-facing windows on sunny winter days to let in the natural warmth.
14)
Wear warmer clothing - it's free, easy and will let you turn down your heater just those few
degrees more.
15)
A wall-mounted heater is the safest to use in the bathroom. It should be mounted at least 1.4
meters above the floor, well away from water taps and shower outlets.
16)
Don't leave the heater running on low overnight or while you are out.
17)
Use a programmable thermostat. This simple, inexpensive device may provide better savings
than any other efficiency measure.
18)
19)
20)
On dark winter days, cover windows with close fitting, floor length heavy curtains - up to 30%
of total heat loss from a home occurs through uncovered windows. Leaving curtains open can
increase your heating bill by up to $80 per quarter for the average home!
21)
On sunny winter days, open up the curtains to north-facing windows for free natural solar
energy to warm your home.
22)
Lower your thermostat setting at night and when there will be no one home for at least 4
hours; a 10 setback can give you significant savings. Setback thermostats save energy by
automatically turning the thermostat down and up on a preset schedule.
23)
drapes, furniture or carpet obstructing the supply and/or return registers or grilles
Page 63 of 67
www.PDHcenter.com
www.PDHonline.org
Page 64 of 67
www.PDHcenter.com
www.PDHonline.org
Annexure # 4
TYPICAL REQUIREMENTS & STANDARD SPECIFICATIONS FOR BOILER HYDRONIC SYSTEMS
Where the Boiler Safety Division will not be informed or required to inspect.
1.0
1.1
The installer shall be responsible to compile and provide to the owner and/or the operator all
installation, operating and service instruction manuals and information.
1.2
The installer shall instruct the owner/operator on the use, maintenance and service
requirements of the system and associated equipment as in the CSA B149.1 Natural Gas and
Propane Installation code, Responsibilities of the Installer.
2.0
General Requirements
2.1
All boilers shall be approved by a recognized Canadian certification agency and have all the
required markings on the name/rating plate attached to the boiler.
2.2
Installations shall meet the requirements of the most recent version of the CSA B214
Installation Code for Hydronic Heating Systems.
2.3
2.4
Boiler controls and safeties can not be located or piped in such a way as to be isolated from
the boiler by manual or automatic valves or controls.
2.5
All boilers shall have two limit controls. One shall act as an operating control and one shall
act as a high limit safety control.
2.6
Pressure relief valves shall be installed with the discharge outlet facing down or horizontal and
the discharge outlet piped down towards the floor. The ends of the discharge pipe shall not
be threaded or provided with a fitting, which could allow the discharge pipe to be blocked or
restricted.
3.0
3.1
Unless regulated by other jurisdictions, boilers installed with a heat distribution system at a
level below the boiler shall be provided with an approved low water cut-off device.
3.2
Low water cut-off controls shall be installed as specified by the manufacturers certified
installation instructions and shall be capable of shutting off the fuel supply to the burner(s).
3.3
Low water cut-off safety devices shall be installed and piped in the same manner as required
by the Boiler and Pressure Vessels Act to allow for inspection and testing.
4.0
4.1
Boilers designed to have burner operation with no flow conditions present shall be installed as
per the manufacturers certified installation instructions and any other requirements set forth
by any national or local codes and jurisdictions.
4.2
Boilers sensitive to low return water temperatures shall be installed and controlled in such a
way as to maintain the minimum return water temperature during normal operation as
required by the manufacturer. Owners and/or operators shall be instructed of any minimum
return water temperature requirements.
4.3
Boiler installations shall include a minimum of two thermometers located to accurately sense
the water temperature inside (or leaving) the boiler and the return water temperature entering
the boiler. Installations shall have a minimum of one pressure gauge located at or on the
boiler.
5.0
Page 65 of 67
www.PDHcenter.com
www.PDHonline.org
5.1
When used in residential applications and in heating applications of three family and less
housing:
The heating system shall be installed in such a manner that the boiler has constant flow
conditions when in use.
The boiler shall be equipped with a flow switch installed so that with reduced or no flow, the
burner must shut off.
The boiler shall be equipped with two limit controls. One to act as an operating (primary)
control and the second shall act as a high limit (secondary) control. Both of which must shut
down the fuel supply to the burner when the respective set point has been reached.
5.2
When used in commercial applications or residential applications of more than three families:
The heating system shall be installed in such a manner that the boiler has constant flow
conditions when in use.
In accordance with the Boiler Safety Division a flow switch shall be installed. The flow switch
must be capable of being tested in service. When flow is reduced or stopped, the burner
must shut off.
The boiler shall be equipped with two limit controls. One to act as an operating (primary)
control and the second shall act as a high limit (secondary) control. Both of which must shut
down the fuel supply to the burner when the respective set point has been reached.
6.0
Hydronic Boilers Other Than Fin Tube (Cast Iron Sectional etc)
6.1
When used in residential applications and in heating applications of three family and less
housing:
6.2
The boiler shall be equipped with two limit controls. One to act as an operating (primary)
control and the second shall act as a high limit (secondary) control. Both of which must
shut down the fuel supply to the burner when the respective set point has been reached.
When used in commercial applications or residential applications of more than three families:
The boiler shall be equipped with two limit controls. One to act as an operating (primary)
control and the second shall act as a high limit (secondary) control. Both of which must
shut down the fuel supply to the burner when the respective set point has been reached.
Boilers with inputs of 400,000 Btu/hr or less shall have either a flow switch or a low water
cut-off safety device installed.
Boilers with inputs over 400,000 Btu/hr shall have a low water cut-off device installed.
The flow switch must be capable of being tested in service and when flow is reduced or
stopped, it must shut down the flow of fuel to the burner.
7.0
7.1
7.2
Steam boilers shall have a minimum of one operating pressure control and one high limit
pressure control approved for use on steam boilers.
8.0
8.1
Page 66 of 67
www.PDHcenter.com
www.PDHonline.org
8.2
8.3
Minimum return water temperatures to boilers must be maintained and identified in the
owner's operating instructions.
8.4
When outdoor temperature compensation is used, boiler minimum return water temperatures
must be considered.
8.5
In multiple boiler installations, the method of installation of the boilers must allow for
recommended design flow through all boilers using piping design, pumping methods or
balancing devices.
8.6
Use design approved valves for flow balancing. (Ball and gate valves are not approved for
flow regulation.)
8.7
Installations with continuous flow conditions may require a pressure relief bypass valve or a
piping arrangement to provide adequate flow if the system flow conditions can drop to 30% or
less of design flow conditions. The pressure relief bypass valve or piping arrangement must
be sized to suit the needs of the system.
8.8
Boilers sensitive to high or low flow conditions shall be installed as required by the
manufacturers certified installation instructions.
8.9
The maximum operating pressure of a boiler must be at least 10 psi below the relief valve
discharge pressure.
8.10 It is not recommended to pipe a relief valve discharge to the outdoors, pipe vertical above the
outlet of the relief valve or pipe through a wall to another room. The discharge must be no
more than 12 or less than 1 above the floor. The distance above the floor must be at least
twice the diameter of the discharge pipe.
8.11 Any secondary heating loops isolated from the primary loop by means of a heat exchanger
must have a separate expansion compensator, relief valve, thermometers, pressure gauges
and controls as required by design, manufacturer's installation instructions and good piping
practices.
8.12 Steam boiler replacements with units of a smaller water storage capacity must give
consideration to the needs of a condensate receiving/holding tank to prevent the system from
flooding the boiler or cycle on the low water cut-off.
8.13 Automatic feed water supply systems must comply with local or provincial plumbing codes.
8.14 Ventilation requirements as indicated in the National Building Code must be met.
8.15 When heat exchangers are used for secondary heating loops or when heat exchangers are
used to heat domestic (potable) water, the installer must ensure the heat exchanger(s) is
approved to suit the needs of the installation. The installation must meet the requirements of
all national and local codes as well as the requirements of all jurisdictions having authority.
_______________________________________________________________________________
Page 67 of 67