RL User Manual
RL User Manual
USER MANUAL
MTE Series RL Line/Load Reactors are components designed to improve the reliability of
adjustable frequency drives, DC drives and a wide variety of other types of power
electronic equipment. In addition they provide limited input line current harmonic
mitigation and aid in long lead protection for inverter fed motors. Note: (See MTE
harmonic filters and motor protection products for guaranteed results.) MTE reactors are
available in a large number of current ratings and a variety of inductance values. The
suitability of a line/load reactor for a specific application must therefore be ultimately
determined by the customer. In no event will MTE Corporation assume responsibility or
liability for any direct or consequential damages resulting from the use or application of
reactors. Nor will MTE Corporation assume patent liability with respect to the use of
information, circuits or equipment described in this instruction manual.
This manual includes recently redesigned performance enhanced reactors. These reactors are
physically smaller and weigh less than the reactors they replace. Enhanced reactors have base
mounting brackets with additional slotted holes to accommodate past mounting hole centers. You
may uses your existing drill pattern or choose the new layout. The tables contained in this manual
reflect historical mounting dimensions for previous reactors.
This document supports computer searches and is best viewed with Adobe Acrobat
PDF viewer (6 or 7). Click links are incorporated throughout the document to speedup
document navigation.
2 of 32
Table of Contents
3 of 32
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to avoid contact with high
voltage when operating, installing or repairing equipment containing line/load reactors
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback
lethal voltages. Follow the safety instructions in the equipment used with the reactor in addition to the
safety instruction in this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been
interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and
replaced if damaged.
WARNING
An upstream disconnect/protection device must be used as required by the National Electrical Code
(NEC).
WARNING
Even if the upstream disconnect/protection device is open, a drive or inverter down stream of the
line/load reactor may feed back high voltage to the reactor. The inverter or drive safety instructions
must be followed.
INJURY OR DEATH MAY RESULT IF THE DRIVE SAFETY PRECAUTIONS ARE NOT
OBSERVED.
WARNING
The frame of line/load reactors must be grounded at least at one of the reactors mounting holes.
WARNING
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used
4 of 32
INTRODUCTION
This manual was specifically developed to
assist in the installation, interconnection and
operation of MTE Corporation Series RL
Line/Load Reactors
This manual is intended for use by
personnel experienced in the operation and
maintenance of electronic drives, inverters
and similar types of power electronic
equipment. Because of the high voltages
required by the equipment connected to
line/load reactors and the potential dangers
presented by rotating machinery, it is
essential that all personnel involved in the
operation and maintenance of line/load
reactors know and practice the necessary
safety precautions for this type of
equipment. Personnel should read and
understand the instructions contained in this
manual before installing, operating or
servicing line/load reactors and the drive to
which the reactor is connected.
Repair/Exchange Procedure
MTE Corporation requires a Returned
Material Authorization Number before it can
accept any reactors that qualify for return or
repair. If problems or questions arise during
installation, setup, or operation of the filter,
please call us for assistance at:
Phone: 1-262-253-8200
FAX: 1-262-253-8222
5 of 32
MOV
option
RL
blank
208 Volts
A
C
E
G
J
X
Z No.
1
2
3
4
Option
suffix
none
240 Volts
Style
Open Frame
NEMA 1
OVERSIZE NEMA 1
NEMA 3R
0
1
2
3
none
6 of 32
blank
B
B1
B5
B6
B7
B8
B9
B11
B10
B14
B18
T
T1
T2
T5
T6
T7
Spare Parts
For standard type RL AC Line / Load Reactors
Description
Part No.
Terminal Blocks
Description
Part No.
36-822-049
36-825-004
TERMBLK-013
7 of 32
B8 Terminal Modification
SLU Lug Option
Wire range:
2 - 0000
8 of 32
9 of 32
PRODUCT SPECIFICATIONS
Standard impedance values
Impedance basis
Service Factor
(Continuous)
Reactors rated 1 to 750 Amps
Reactors rated above 750 Amps
rating
Overload Rating
20 KHz
Insulation system
Class N (200 C)
Temperature rise
Open or enclosed reactors
135 C (average)
Ambient temperature
Open or enclosed reactors
45 C (maximum)
Altitude (maximum)
1000 meters
Fundamental frequency
Line or Load
50/60 Hz
Approvals:
Inductance tolerance
+/- 10%
Impregnation:
Dielectric Strength
dv/dt Protection
motors)
Protection:
meet IP20
10 of 32
Sheet Insulation:
Epoxy:
CONSTRUCTION:
CORE:
WINDINGS:
Meet 3000 volts rms dielectric strength (coil to coil and coil- to core).
ASSEMBLY:
COLOR:
Royal Blue
TESTING:
11 of 32
AUDIBLE NOISE:
Guard-AC Line/Load Reactors offer low noise operation. Core and coil
construction, flux density control, harmonic compensation as well as our epoxy impregnation process
assure minimal audible noise radiation. Although our reactors are typically quiet, waveforms vary by
drive type and application and therefore reactor audible noise may vary by application. Noise levels may
be affected by type of motor and motor conductor as well as motor conductor length.
Typical audible noise levels for units selected from our catalog by HP rating are:
2 thru 12 amps
18 thru 100 amps
130 thru 400 amps
500 thru 1200 amps
55 dBA
65 dBA
70 dBA
75 dBA
Service Factor:
Guard-AC reactors are compensated for the additional currents and high
frequencies caused by the presence of harmonics. The reactor fundamental current rating indicates the
typical full load motor current and is also the basis of impedance rating. Standard reactors rated 1 amps
thru 750 amps offer a full 1.5 service factor rating which allows them to carry overload current up to 150%
of their fundamental rating when applied as an input line reactor. Since the nameplate ratings of motor
drives (ASD) varies widely by manufacturer, this helps to assure that the reactor maximum current rating
is compatible with the nameplate current rating on the ASD. The service factor rating compensates for
ASD manufacturer variances in motor drive current ratings and for harmonic currents. Nominal
inductance is assured all the way up to the service factor current rating.
PWM / IGBT PROTECTION: Guard-AC reactors are protected against the high peak voltage and fast
rise time voltage pulses associated with PWM waveforms. The dielectric strength is 4000 volts rms and
Guard-AC reactors meet the ratings of an inverter duty motor (NEMA MG-1, part 31). For convenience,
they can be located either at the motor or at the drive.
HARMONIC ATTENUATION: Our unique harmonic compensation assures maximum circuit inductance
in the presence of complex waveforms and can be relied upon to minimize input total harmonic current
distortion (THID). Additionally it offers superior absorption of transient voltage spikes. Our standard
reactors will typically reduce 6-pulse rectifier input current harmonics to the following levels at full load
operating conditions:
3% reactor alone
5% reactor alone
3% AC reactor + 3% DC link choke
5% AC reactor + 3% DC link choke
(DC link choke inductance is equivalent ac impedance).
12 of 32
DE-RATING CURVES
3300
6600
9900
13200
16500
Altitude (Feet)
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
40
45
50
55
60
65
70
75
80
85
13 of 32
90
Dimension Reference
Open Type
Visit the MTE web for reactor detail drawings www.mtecorp.com
IS THE CATOLOG.
14 of 32
Mounting Compatibility
15 of 32
A
Inches
3.8
3.8
3.8
3.8
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
8.1
7.2
7.2
7.2
7.2
7.2
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
10.8
9.0
9.0
10.8
9.0
9.0
11.0
9.0
10.8
mm
97
97
97
97
112
112
112
112
112
112
112
112
152
152
152
152
152
152
152
152
152
206
183
183
183
183
183
229
229
229
229
229
229
229
229
229
274
229
229
274
229
229
279
229
274
B
Inches
3.5
3.5
3.5
3.5
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.8
4.8
4.8
4.8
5.0
5.0
5.0
5.3
5.3
6.1
5.8
5.8
5.8
5.8
5.8
7.4
7.4
7.4
7.3
7.3
7.0
7.0
7.2
7.2
8.5
7.3
7.3
8.3
7.0
7.2
8.5
7.2
8.3
mm
89
89
89
89
104
104
104
104
104
104
104
104
122
122
122
122
127
127
127
135
135
155
147
147
147
147
147
188
188
188
185
185
178
178
183
183
216
185
185
210
178
183
216
183
211
C
Inches
1.2
1.2
1.2
1.2
2.8
2.8
2.8
2.5
2.8
2.8
3.4
3.4
3.0
3.0
3.4
3.4
3.3
3.3
3.9
3.2
3.5
4.0
3.5
3.5
4.3
4.0
4.0
4.7
4.7
4.7
5.3
5.3
5.3
6.0
6.3
6.5
6.8
6.5
6.8
6.2
4.7
6.8
6.2
6.8
6.0
mm
30
30
30
30
71
71
71
64
71
71
86
86
76
76
86
86
84
84
99
81
89
102
89
89
109
102
102
119
119
119
135
135
135
152
160
165
173
165
173
156
118
173
156
173
152
D
Inches
2.40
1.98
1.98
1.98
1.98
1.98
1.98
1.73
1.98
1.98
2.35
2.60
2.10
2.10
2.62
2.48
2.10
2.10
2.75
2.10
2.48
2.60
2.35
2.35
3.10
2.60
2.75
3.16
3.16
3.16
3.66
3.16
3.16
3.91
3.47
3.47
4.16
3.30
3.66
4.16
3.16
3.66
4.16
3.16
3.47
mm
61.0
50.3
50.3
50.3
50.3
50.3
50.3
43.9
50.3
50.3
59.7
66.0
53.3
53.3
66.5
63.0
53.3
53.3
69.9
53.3
63.0
66.0
59.7
59.7
78.7
66.0
69.9
80.3
80.3
80.3
93.0
80.3
80.3
99.3
88.1
88.1
105.7
83.8
93.0
105.7
80.3
93.0
105.7
80.3
88.1
E
Inches
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.63
3.63
3.63
3.63
3.63
3.63
3.00
3.63
3.63
3.63
3.63
mm
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.8
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
92.2
92.2
92.2
92.2
92.2
92.2
76.2
92.2
92.2
92.2
92.2
Weight
Lbs
4
4
3
3
4
4
4
3
4
4
5
6
7
8
11
13
9
10
18
9
12
16
11
14
20
14
16
30
23
28
39
24
27
41
25
33
61
29
37
74
29
43
64
41
50
See www.mtecorp.com Line load Reactors for current dimensions and CAD details
16 of 32
Mass
Kg
1.8
1.8
1.4
1.4
1.8
1.8
1.8
1.4
1.8
1.8
2.3
2.7
3.2
3.6
5.0
5.9
4.1
4.5
8.2
4.1
5.4
7.3
5.0
6.3
9.1
6.3
7.3
14
10
13
18
11
12
19
11
15
28
13
17
34
13
20
29
19
23
RL-50001
RL-50002
RL-50003
RL-60001
RL-60002
RL-60003
RL-75001
RL-75002
RL-75003
RL-85001
RL-85002
RL-85003
RL-100001
RL-100002
RL-100003
RL-120001
RL-120002
RL-120003
RL-140001
RL-140002
RL-140003
RL-150001
RL-150002
RL-150003
RL-180001
RL-180002
RL-180003
RL-210001
RL-210002
A
Inches
9.0
9.0
10.8
9.0
10.8
14.4
10.8
10.8
14.4
10.8
15.0
14.4
10.8
14.4
14.4
14.4
14.4
14.4
14.4
14.4
14.4
20.3
22.0
22.5
21.6
20.3
20.3
22.5
21.5
16.8
22.0
19.0
22.0
22.0
16.9
22.0
22.0
22.0
22.0
24.0
24.0
B
C
D
E
Weight Mass
mm Inches mm Inches mm Inches mm Inches mm
Lbs
Kg
229
7.5
191
7.3
185 4.16
105.7 3.63
92.2
38
17
229
7.5
191
8.3
211 4.41
112.0 3.63
92.2
54
24
274
8.3
211 10.0 254 5.91
150.1 3.63
92.2
100
45
229
7.5
191
9.0
229 4.19
106.4 3.63
92.2
47
21
274
8.5
216
9.0
229 5.16
131.1 4.60 116.8
80
36
366 11.2 284 10.3 262 5.82
147.8 4.60 116.8
125
57
274
9.0
229
8.3
211 5.16
131.1 4.60 116.8
80
36
274
9.0
229 10.0 254 5.88
149.4 4.60 116.8
102
46
366 11.3 286 10.5 267 7.13
181.1 4.60 116.8
160
73
274 10.0 254 10.0 254 5.16
131.1 4.60 116.8
84
38
381 11.3 286 11.5 292 6.76
171.7 4.60 116.8
118
54
366 11.3 286 12.5 318 7.26
184.4 4.60 116.8
149
68
274
9.0
229 10.5 267 5.50
139.7 4.60 116.8
93
42
366 11.5 292 11.5 292 6.76
171.7 4.60 116.8
118
54
366 11.5 292 13.3 338 9.76
247.9 4.60 116.8
210
95
366 11.5 292 10.0 254 5.26
133.6 4.60 116.8
120
54
366 11.3 286 12.0 305 8.00
203.2 4.60 116.8
175
79
366 11.3 286 15.0 381 9.26
235.2 4.60 116.8
270
122
366 11.5 292 11.0 279 6.63
168.4 7.20 182.9
140
63
366 11.5 292 12.5 318 8.01
203.5 7.20 182.9
190
86
366 14.5 368 14.0 356 9.26
235.2 7.20 182.9
265
120
514 16.8 425 13.0 330 7.60
193.0 7.20 182.9
285
129
559 16.8 425 13.0 330 8.00
203.2 7.20 182.9
370
168
572 16.8 427 18.0 457 9.00
228.6 7.20 182.9
452
205
549 16.8 425 11.0 279 7.26
184.4 7.20 182.9
320
145
514 16.8 425 13.0 330 8.50
215.9 7.20 182.9
408
185
514 16.8 425 15.0 381 10.76 273.3 7.20 182.9
589
267
572 17.0 432 13.0 330 11.00 279.4 7.20 182.9
425
193
546 17.0 432 20.0 508 10.76 273.3 7.20 182.9
440
200
427 17.0 432 18.5 470 11.00 279.4 7.20 182.9
560
254
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
500
227
483 17.0 432 19.0 483 11.00 279.4 7.20 182.9
525
238
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
850
385
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
635
288
429 17.0 432 16.0 406 11.00 279.4 7.20 182.9
675
306
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
900
408
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
700
317
559 17.0 432 22.0 559 10.38 263.7 7.20 182.9
860
390
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
1090
494
610 18.0 457 24.0 610 11.00 279.4 7.20 182.9
800
363
610 18.0 457 24.0 610 11.00 279.4 7.20 182.9
970
440
See www.mtecorp.com Line load Reactors for current dimensions and CAD details
17 of 32
Cabinet
Number
CAB-8
CAB-13V
Weight
Lbs
11
11
11
10
11
11
12
13
14
15
18
20
16
17
25
16
19
34
29
32
38
32
34
48
41
46
57
42
45
59
43
51
79
47
55
92
47
61
82
59
68
85
18 of 32
Mass
Kg
5
5
5
5
5
5
5
6
6
7
8
9
7
8
11
7
9
15
13
15
17
15
15
22
19
21
26
19
20
27
20
23
36
21
25
42
21
28
37
27
31
39
Cabinet
Number
CAB-13V
CAB-17V
CAB-26C
CAB-30B
CAB-42C
19 of 32
Weight
Lbs
56
72
118
65
107
152
107
129
187
111
145
176
120
262
354
264
319
414
299
349
424
444
529
611
479
567
748
584
599
719
803
828
1153
938
978
1203
1003
1163
1393
1103
1273
1573
Mass
Kg
25
33
54
30
49
69
49
59
85
50
66
80
54
119
161
120
145
188
136
158
192
202
240
277
217
257
340
265
272
326
365
376
523
426
444
546
455
528
632
501
578
714
Note: The entry locations shown above are for reference only. The electrician installing the reactor
guided by the local codes determines the final entry wiring. MTE does not pre- punch entry holes or
provide wiring hardware with the standard product.
20 of 32
ENCLOSURE DIMINSIONS
CAB-8
CAB-12C
21 of 32
ENCLOSURE DIMENSIONS
CAB-13V
CAB-17V
22 of 32
ENCLOSURE DIMENSIONS
CAB-17C
CAB-26C
23 of 32
ENCLOSURE DIMENSIONS
CAB-30B
CAB-42C
24 of 32
TECHNICAL DATA
Catalog
Number
RL-00101
RL-00102
RL-00103
RL-00104
RL-00201
RL-00202
RL-00203
RL-00204
RL-00401
RL-00402
RL-00403
RL-00404
RL-00801
RL-00802
RL-00803
RL-00804
RL-01201
RL-01202
RL-01203
RL-01801
RL-01802
RL-01803
RL-02501
RL-02502
RL-02503
RL-03501
RL-03502
RL-03503
RL-04501
RL-04502
RL-04503
RL-05501
RL-05502
RL-05503
RL-08001
RL-08002
RL-08003
RL-10001
RL-10002
RL-10003
RL-13001
RL-13002
RL-13003
RL-16001
Watts Loss
(watts)
13.5
12.8
11.9
9.6
8
12
16
11
15
20
20
21
20
29
26
28
26
31
41
36
43
43
48
52
61
49
54
54
54
62
65
64
67
71
82
86
96
94
84
108
108
180
128
116
Wire Range
(AWG)
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
22 10
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
14 - 6
18 4
18 4
18 4
18 4
60
60
60
60
60
60
60
60
60
2 0000
2 0000
2 0000
2 0000
Terminal Torque
(in lbs)
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
150
150
150
150
25 of 32
Ind.
mH
100
50
36
18
12
20
32
6
3
6.5
9
12
1.5
3
5
7.5
1.25
2.5
4.2
0.8
1.5
2.5
0.5
1.2
1.8
0.4
0.8
1.2
0.3
0.7
1.2
0.25
0.5
0.85
0.2
0.4
0.7
0.15
0.3
0.45
0.1
0.2
0.3
0.075
Fund
Amps
1
1
1
1
2
2
2
2
4
4
4
4
8
8
8
8
12
12
12
18
18
18
25
25
25
35
35
35
45
45
45
55
55
55
80
80
80
100
100
100
130
130
130
160
Max
Amps
1.5
1.5
1.5
1.5
3
3
3
3
6
6
6
6
12
12
12
12
18
18
18
27
27
27
37.5
37.5
37.5
52.5
52.5
52.5
67.5
67.5
67.5
82.5
82.5
82.5
120
120
120
150
150
150
195
195
195
240
RL-50001
RL-50002
RL-50003
RL-60001
RL-60002
RL-60003
RL-75001
RL-75002
RL-75003
RL-85001
RL-85002
RL-85003
RL-90001
RL-90002
RL-90003
RL-100001
RL-100002
RL-100003
RL-120001
RL-120002
RL-120002
RL-140001
RL-140002
RL-140003
RL-150001
RL-150002
RL-150003
Watts Loss
(watts)
149
138
124
168
146
154
231
219
224
264
351
231
333
293
266
340
422
307
414
406
427
630
552
798
930
1133
860
1020
1365
940
1090
1500
980
1130
1550
1523
1680
1432
1671
1815
Wire Range
(AWG)
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Terminal Torque
(in lbs)
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Ind
mH
0.15
0.23
0.055
0.11
0.185
0.045
0.09
0.15
0.04
0.075
0.125
0.03
0.06
0.105
0.025
0.05
0.085
0.02
0.04
0.065
0.015
0.029
0.048
0.015
0.027
0.042
0.013
0.025
0.04
0.011
0.022
0.038
0.009
0.019
0.03
0.008
0.016
0.027
0.008
0.015
0.025
Fund
Amps
160
160
200
200
200
250
250
250
320
320
320
400
400
400
500
500
500
600
600
600
750
750
750
850
850
850
900
900
900
1000
1000
1000
1200
1200
1200
1400
1400
1400
1500
1500
1500
Max
Amps
240
240
300
300
300
375
375
375
480
480
480
600
600
600
750
750
750
900
900
900
1125
1125
1125
1063
1063
1063
1125
1125
1125
1250
1250
1250
1500
1500
1500
1750
1750
1750
1875
1875
1875
26 of 32
INSTALLATION INSTRUCTIONS
Open Line/Load Reactor Installation
WARNING
27 of 32
WARNING
If a line reactor or a line reactor and a load
reactor are used with a drive equipped with a
bypass circuit, the reactors must be removed
from the motor circuit in the bypass mode.
Damage to the motor and other equipment will
result if this warning is not observed.
Grounding
A stud is provided on enclosed reactors for
grounding the enclosure. The enclosure must be
grounded. Open reactors must be grounded at
the designated grounding terminal or the reactor
mounting holes if no designated grounding
terminal is provided.
WARNING
Reactor are designed for use with copper
conductors with a minimum temperature rating
of 75 degrees C. Table 2 lists the wire range and
terminal torque requirements for the power input
and output connections by reactor part number.
Refer to Figure 4 for typical electrical diagrams
describing the application of reactors in both line
and load applications. For reactors supplied as a
component part of a drive system or a
component part of power electronic apparatus
follow the interconnection diagram supplied by
the System Engineer.
28 of 32
29 of 32
Sequence of Operation
1. Read and follow safety precautions.
2. After installation, ensure that:
All Reactor ground terminals are connected to ground.
Power wiring to the utility, drive and motor is in accordance with the
interconnection diagrams supplied by the System Engineer.
3. Check that moisture has not condensed on the Reactor. If moisture is
present, do not proceed with startup until the moisture has been removed.
4. Proceed with startup according to the instructions provided by the system
supplier.
WARNING
Reactors are a component part of an electrical system. Do not proceed with startup until
the system startup instructions provided by the System Engineer are understood and
followed. Injury, death and damage to equipment may result if the system startup
instructions are not followed.
WARNING
Use extreme caution to avoid contact with line voltage when checking for
power.
30 of 32
STARTUP
Safety Precautions
Before startup, observe the following warnings and instructions:
WARNING
A Reactor is at line potential when the Reactor is connected to the utility. This voltage
is extremely dangerous and may cause death or severe injury if you come in contact
with it.
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to
avoid contact with high voltage when operating, installing or repairing equipment
containing line/load reactors. Line/load reactors are used in conjunction with
inverters, or other electrical equipment that may feedback lethal voltages.
Follow the safety instructions in the equipment used with the reactor in addition
to the safety instruction in this manual.
31 of 32