Schneider Short Circuit Calculation
Schneider Short Circuit Calculation
Schneider Short Circuit Calculation
currents
B. de Metz-Noblat
F. Dumas
C. Poulain
no. 158
Calculation of short-circuit
currents
Benot de METZ-NOBLAT
Frdric DUMAS
Christophe POULAIN
Lexicon
Abbreviations
Ra
MLVS
RL
Scc
BC
Symbols
A
cos
Breaking capacity.
Sn
tmin
u
usc
U
XL
iac
idc
ip
I
Ib
Ik
Ik"
Ir
Is
Isc
Un
Xa
Xsubt
Z(1)
Z(2)
Z(0)
ZL
Zsc
Zup
Subscripts
Short-circuit power
Negative-sequence
impedance
Zero-sequence impedance
of a network
or an
element.
Line impedance.
k or k3
k2
k1
Phase-to-earth or phase-to-neutral
short circuit.
SO
T
Transformer.
Summary
1 Introduction
p. 4
p. 5
p. 11
p. 11
4 Conclusion
Bibliography
p. 7
p. 10
p. 12
p. 13
p. 18
p. 19
p. 23
p. 27
p. 28
p. 23
p. 24
p. 32
p. 32
1 Introduction
Electrical installations almost always require
protection against short-circuits wherever there
is an electrical discontinuity. This most often
corresponds to points where there is a change
in conductor cross-section. The short-circuit
current must be calculated at each level in the
installation in view of determining the
characteristics of the equipment required to
withstand or break the fault current.
Upstream Ssc
HV / LV
transformer rating
b Power factor
b Coincidence factor
b Duty factor
b Foreseeable expansion
factor
b Feeder current
ratings
b Voltage drops
Load
rating
usc (%)
Conductor characteristics
b Busbars
v Length
v Width
v Thickness
b Cables
v Type of insulation
v Single-core or multicore
v Length
v Cross-section
b Environment
v Ambient temperature
v Installation method
v Number of contiguous circuits
Isc
at transformer
terminals
Isc
of main LV switchboard
outgoers
Isc
at head of secondary
switchboards
Isc
at head of final
switchboards
Isc
at end of final
outgoers
Breaking capacity
Main
ST and inst. trip setting circuit breaker
Main LV
switchboard
ST and inst. trip setting distribution
circuit breakers
Breaking capacity
Secondary
distribution
ST and inst. trip setting circuit breakers
Breaking capacity
Breaking capacity
Inst. trip setting
Final
distribution
circuit breakers
Fig. 1 : Short-circuit (Isc) calculation procedure when designing a low-voltage electrical installation (ST = short time; Inst. = instantaneous)
Cable or I2t
characteristic
Design
current
Transient
overload
Circuit breaker
time-current
curve
IB Ir Iz
Isc BC
(tri)
Cable or I2t
characteristic
5s
I2t = k2S2
I2t
Fig. 2 : The
characteristics of a conductor depending
on the ambient temperature (1 and 2 represent the rms
value of the current in the conductor at different
temperatures 1 and 2, with 1 > 2; Iz being the limit of
the permissible current under steady-state conditions).
Characteristics of short-circuits
The primary characteristics are:
c Duration (self-extinguishing, transient and
steady-state)
Transient
overload
Furse time-current
curve
IB
Ir
Iz
Fig. 4 : Circuit protection using an aM fuse.
c Origin
Consequences of short-circuits
The consequences are variable depending on
the type and the duration of the fault, the point in
the installation where the fault occurs and the
short-circuit power. Consequences include:
c At the fault location, the presence of electrical
arcs, resulting in
v Damage to insulation
v Welding of conductors
a) Three-phase short-circuit
L3
L3
L1
L1
L2
L2
I"k2
I"k3
c) Phase-to-phase-to-earth short-circuit
d) Phase-to-earth short-circuit
L3
L3
L1
L1
L2
L2
I"k2EL3
Ik" 2EL2
Ik" E2E
Ik" 1
Short-circuit current,
Partial short-circuit currents in conductors and earth.
Fig. 5 : Different types of short-circuits and their currents. The direction of current is chosen arbitrarily
(See IEC 60909).
R + X2
However, the transient conditions prevailing
while the short-circuit current develops differ
depending on the distance between the fault
location and the generator. This distance is not
necessarily physical, but means that the
generator impedances are less than the
impedance of the elements between the
generator and the fault location.
where I =
Zsc =
R2 + X2
idc = - 2 sin ( ) e
Zsc
Zs
iac = I sin (t + )
idc = - I sin ( ) e
I
-
R
t
L
R t
L
t
i = iac + idc
Fault initiation
Fig. 7 : Graphical presentation and decomposition of a short-circuit current occuring far from the generator.
a) Symmetrical
i
Ir
i =
b) Asymmetrical
i
idc
ip
E 2
sin t
Z
which, from the initiation, has the same shape as for
steady state conditions with a peak value E / Z.
R
t
E 2
sin (t - ) + sin e L
Z
i =
Fig. 8 : Graphical presentation of the two extreme cases (symmetrical and asymmetrical) for a short-circuit current .
= 1.02 + 0.98 e
R
X
2.0
1.8
1.6
1.4
1.2
1.0
0.2
0.4
0.6
0.8
1.0
1.2
R/X
a) 0
t (s)
b) 0
t (s)
c) 0
t (s)
d) 0
t (s)
0.1
e) 0
Subtransient
0.3
Transient
0.5
Steady-state
t (s)
Fig. 10 : Total short-circuit current isc (e), and contribution of its components:
a) subtransient reactance = Xd
b) transient reactance = Xd
c) synchronous reactance = Xd
d) aperiodic component.
Note that the decrease in the generator reactance is faster than that of the aperiodic component. This is a rare
situation that can cause saturation of the magnetic circuits and interruption problems because several periods
occur before the current passes through zero.
1
1 t / Td'' 1
1 t / Td'
1
E 2
i(t ) = E 2 '' ' e
+ '
e
+
cos t '' e t / Ta
Xd
Xd
X d X d
X d Xd
Where:
c In LV power distribution and in HV applications,
however, the transient short-circuit current is often
E: Phase-to-neutral rms voltage across the
used if breaking occurs before the steady-state
generator terminals
stage,
in which case it becomes useful to use the
X"d: Subtransient reactance
short-circuit
breaking current, denoted Ib, which
X'd: Transient reactance
determines the breaking capacity of the timeXd: Synchronous (steady-state) reactance
delayed circuit breakers. Ib is the value of the
T"d: Subtransient time constant
short-circuit current at the moment interruption is
T'd: Transient time constant
effective, i.e. following a time t after the beginning
Ta: Aperiodic time constant
of the short-circuit, where t = tmin. Time tmin
(minimum time delay) is the sum of the minimum
Practically speaking, information on the
operating time of a protection relay and the shortest
development of the short-circuit current is not
opening time of the associated circuit breaker, i.e.
essential:
the shortest time between the appearance of the
c In a LV installation, due to the speed of the
short-circuit current and the initial separation of the
breaking devices, the value of the subtransient
pole contacts on the switching device.
short-circuit current, denoted I"k , and of the
Figure 11 presents the various currents of the
maximum asymmetrical peak amplitude ip is
short-circuits defined above.
sufficient when determining the breaking capacities
of the protection devices and the electrodynamic
forces
Symmetrical
Asymmetrical
2r I"k
Subtrans.
Transient
Steady-state
ip
2r Ik
Isc =
Un
.
3 (Z )
U/ 3
Zcc
where U (phase-to-phase voltage) corresponds
to the transformer no-load voltage which is 3 to
5% greater than the on-load voltage across the
terminals. For example, in 390 V networks, the
phase-to-phase voltage adopted is U = 410 V,
and the phase-to-neutral voltage is
U / 3 = 237 V .
Calculation of the short-circuit current therefore
requires only calculation of Zsc, the impedance
equal to all the impedances through which Isc
flows from the generator to the location of the
sc3 =
Three-phase fault
+ X
where
ZL
ZL
Zsc
V
sc 3 =
U/ 3
Zsc
sc 2 =
U
2 . Zsc
ZL
Phase-to-phase fault
ZL
ZL
Phase-to-neutral fault
ZL
Zo
Zsc
Zsc
ZL
ZLn
Phase-to-earth fault
Zsc
ZLn
sc1 =
U/ 3
Zsc + ZLn
sco =
U/ 3
Zsc + Z o
Zsc
V
Zo
sc 2 =
U
=
2 Zsc
3
sc 3 0.86 sc 3
2
sc1 =
U/ 3
Zsc + ZLn
U2
Ssc
where U is the no-load phase-to-phase voltage
of the network.
The upstream resistance and reactance may be
deduced from Rup / Zup (for HV) by:
Rup / Zup 0.3 at 6 kV;
Rup / Zup 0.2 at 20 kV;
Zup =
Xup
2
= 1 - (0.2) = 0.980
Zup
Xup = 0.980 Zup at 20kV,
hence the approximation Xup Zup .
c Internal transformer impedance
The impedance may be calculated on the basis
of the short-circuit voltage usc expressed as a
percentage:
u
U2
,
3 Z T = sc
100 Sn
U = no-load phase-to-phase voltage of the
transformer;
Sn = transformer kVA rating;
usc
= voltage that must be applied to the
100
primary winding of the transformer for the rated
current to flow through the secondary winding,
when the LV secondary terminals are
shortcircuited.
For public distribution MV / LV transformers, the
values of usc have been set by the European
Harmonisation document HD 428-1S1 issued in
October 1992 (see Fig. 13 ) .
Network impedances
c Upstream network impedance
Generally speaking, points upstream of the
power source are not taken into account.
Available data on the upstream network is
therefore limited to that supplied by the power
distributor, i.e. only the short-circuit power Ssc in
MVA.
The equivalent impedance of the upstream
network is:
Rup
1 -
Zu p
Za2 - Ra 2 ,
630
4
800
4.5
1,000
1,250
5.5
1,600
6
2,000
sc =
U
3 ( Zup + Z T )
U2
sc
' sc - sc
Zup
Ssc
=
=
=
sc
sc
ZT
usc U2
i.e. :
100 Sn
sc
=
sc
usc Ssc
100 Sn
where
A
S = cross-sectional area of the conductor;
= conductor resistivity, however the value used
varies, depending on the calculated short-circuit
current (minimum or maximum).
6 The table in Figure 15 provides values for
each of the above-mentioned cases.
Practically speaking, for LV and conductors with
cross-sectional areas less than 150 mm2, only
the resistance is taken into account
(RL < 0.15 m / m when A > 150 mm2).
v The reactance per unit length of overhead
lines, cables and busbars may be calculated as
d
XL = L = 15.7 + 144.44 Log
r
Isc/Isc
(%)
12
10
5
0
500
1,000
1,500
2,000
Sn
(kVA)
Fig. 14 : Resultant error in the calculation of the short-circuit current when the upstream network impedance Zup
is neglected.
),
cables (flat
or triangular
);
(
) and spaced, single-conductor cables
(
) ; For sandwiched-phase busbars
(e.g. Canalis - Telemecanique), the reactance is
considerably lower.
Notes :
v The impedance of the short lines between the
distribution point and the HV / LV transformer
may be neglected. This assumption gives a
conservative error concerning the short-circuit
current. The error increases in proportion to the
transformer rating
v The cable capacitance with respect to the earth
(common mode), which is 10 to 20 times greater
than that between the lines, must be taken into
account for earth faults. Generally speaking, the
capacitance of a HV three-phase cable with a
cross-sectional area of 120 mm2 is in the order
Resistitivity
(*)
Resistivity value
( mm2/m)
Concerned
conductors
0.01851
0.02941
PH-N
2 = 1,5 0
1 = 1,25 0
1 = 1,25 0
0.028
0.023
0.044
0.037
PH-N
PH-N (**)
1 = 1,25 0
1 = 1,25 0
0.023
0.037
PH-N
Copper
0,023
Aluminium
0,037
0.023
PH-N
PE-PEN
0.037
(*) 0 = resistivity of conductors at 20C = 0.01851 mm2/m for copper and 0.02941 mm2/m for aluminium.
(**) N, the cross-sectional area of the neutral conductor, is less than that of the phase conductor.
Fig. 15 : Conductor resistivity values to be taken into account depending on the calculated short-circuit current
(minimum or maximum). See UTE C 15-105.
Wiring system
Busbars
Diagram
Reactance per unit length,
values recommended in
UTE C 15-105 (m/m)
Average reactance
per unit length
values (m/m)
Extreme reactance
per unit length
values (m/m)
0.08
0.13
0.08
0.09
0.13
0.13
0.15
0.08
0.15
0.085
0.095
0.145
0.19
0.12-0.18
0.06-0.1
0.1-0.2
0.08-0.09
0.09-0.1
0.14-0.15
0.18-0.20
Examples :
v First case: Consider a three-phase cable, at
20C, with copper conductors. Their reactance
is 0.08 m / m. The RL and XL curves
(see Fig. 17) indicate that impedance ZL
approaches two asymptotes, RL for low cable
cross-sectional areas and XL = 0.08 m / m for
high cable cross-sectional areas. For the low and
high cable cross-sectional areas, the impedance
ZL curve may be considered identical to the
asymptotes.
The given cable impedance is therefore
considered, with a margin of error less than
5.1%, comparable to:
- A resistance for cable cross-sectional areas
less than 74 mm2
m/m
1
0.8
0.2
ZL
0.1
0.08
0.05
XL
0.02
0.01
10
20
50
100 200
RL
Turbo-generator
Salient-pole generators
x
In
=
(where x is the equivalent of the
100 Isc
transformer usc).
Consider:
x
U2
where
100 Sn
U = no-load phase-to-phase voltage of the
generator,
Sn = generator VA rating.
11 What is more, given that the value of R / X is
low, in the order of 0.05 to 0.1 for MV and 0.1 to
0.2 for LV, impedance Z may be considered
comparable to reactance X. Values for x are
given in the table in Figure 18 for
turbogenerators with smooth rotors and for
hydraulic generators with salient poles (low
speeds).
In the table, it may seem surprising to see that
the synchronous reactance for a shortcircuit
exceeds 100% (at that point in time, Isc < In) .
However, the short-circuit current is essentially
inductive and calls on all the reactive power that
the field system, even over-excited, can supply,
whereas the rated current essentially carries the
active power supplied by the turbine
(cos from 0.8 to 1).
c Synchronous compensators and motors
The reaction of these machines during a
shortcircuit is similar to that of generators.
12 They produce a current in the network that
depends on their reactance in % (see Fig. 19 ).
c Asynchronous motors
When an asynchronous motor is cut from the
network, it maintains a voltage across its
terminals that disappears within a few
hundredths of a second. When a short-circuit
occurs across the terminals, the motor supplies a
current that disappears even more rapidly,
according to time constants in the order of:
10 Z =
Subtransient
reactance
Transient
reactance
Synchronous
reactance
15-25
25-35
70-120
10-20
15-25
150-230
Other impedances.
c Capacitors
A shunt capacitor bank located near the fault
location will discharge, thus increasing the
shortcircuit current. This damped oscillatory
discharge is characterised by a high initial peak
value that is superposed on the initial peak of the
shortcircuit current, even though its frequency is
far greater than that of the network.
Depending on the timing between the initiation of
the fault and the voltage wave, two extreme
cases must be considered:
v If the initiation of the fault coincides with zero
voltage, the short-circuit discharge current is
asymmetrical, with a maximum initial amplitude
peak
v Conversely, if the initiation of the fault
coincides with maximum voltage, the discharge
current superposes itself on the initial peak of
the fault current, which, because it is
symmetrical, has a low value
It is therefore unlikely, except for very powerful
capacitor banks, that superposition will result in
an initial peak higher than the peak current of an
asymmetrical fault.
High-speed motors
Low-speed motors
Compensators
Subtransient
reactance
Transient
reactance
Synchronous
reactance
35
50
100
15
25
25
40
80
160
U2
Zsc
This means of expressing the short-circuit power
implies that Ssc is invariable at a given point in
the network, whatever the voltage. And the
equation
Ssc = U 3 =
U
implies that all impedances
3 Zsc
must be calculated with respect to the voltage at
the fault location, which leads to certain
complications that often produce errors in
calculations for networks with two or more
voltage levels. For example, the impedance of a
HV line must be multiplied by the square of the
reciprocal of the transformation ratio, when
calculating a fault on the LV side of the
transformer:
sc 3 =
UBT
17 ZBT = ZHT U
HT
R
X
and XCR = 2 with R and X in
2
U
U
ohms and U in volts.
c For transformers, the impedance is expressed
on the basis of their short-circuit voltages usc and
their kVA rating Sn:
RCR =
1 usc
Sn 100
c For rotating machines, the equation is
identical, with x representing the impedance
Z TR =
expressed in %.
1
x
Sn 100
c For the system as a whole, after having
calculated all the relative impedances, the
shortcircuit power may be expressed as:
ZMR =
Ssc =
ZR
sc =
Ssc
=
3 U
3 U
ZR
Hence, Ssc =
ULV 2
U
Z T LV
UHV
+ ZL
1
ZT
ZL
+
UHV 2
ULV 2
UHT
ZT
UBT
ZC
A
2.4 Calculation example (with the impedances of the power sources, the upstream network
and the power supply transformers as well as those of the electrical lines)
Problem
Consider a 20 kV network that supplies a HV /
LV substation via a 2 km overhead line, and a
1 MVA generator that supplies in parallel the
busbars of the same substation. Two 1,000 kVA
parallel-connected transformers supply the LV
busbars which in turn supply 20 outgoers to
20 motors, including the one supplying motor M.
All motors are rated 50 kW, all connection cables
are identical and all motors are running when the
fault occurs.
Upstream network
U1 = 20 kV
Ssc = 500 MVA
Overhead line
3 cables, 50 mm2, copper
length = 2 km
Generator
1 MVA
xsubt = 15%
3L
2 transformers
1,000 kVA
secondary winding 237/410 V
usc = 5%
Main LV
switchboard
3 bars, 400 mm2/ph, copper
length = 10 m
10 m
Cable 1
3 single-core cables, 400 mm2,
aluminium, spaced, laid flat,
length = 80 m
LV sub-distribution board
neglecting the length of the busbars
Cable 2
3 single-core cables 35 mm2,
copper 3-phase,
length = 30 m
Motor
50 kW (efficiency = 0.9 ; cos = 0.8)
x = 25%
3L
C
3L
D
M
Solution
Section
Calculation
Results
(the circled numbers X indicate where explanations may be found in the preceding text)
20 kV
1. upstream network
Zup = 20 x 103
Xup = 0.98 Zup
X ()
/ 500 x 106
3. generator
20 kV
Xc o = 0.4 x 2
Rc o = 0.018 x
XG
20 x 103
15
=
x
100
106
ZT =
1
2
0.78
0.8
6
2
RG = 0.1 XG
Fault A
4. transformers
ZT on LV side
2, 000
50
1
5
4102
x
x
2
100
106
X T ZT
10
60
11
X (m)
4.2
5. circuit-breaker
X cb = 0.15
15
0.15
6. busbars
(one 400 mm2 bar per
phase)
XB = 0.15 x 10-3 x 10
1.5
RB = 0.023 x
Fault B
7. circuit-breaker
X cb = 0.15
8. cable 1
(one 400 mm2 cable per
phase)
Xc1 = 0.15 x 10
9. circuit-breaker
X cb = 0.15
10. cable 2
(35 mm2)
Xc 2 = 0.09 x 10 3 x 30
Fault C
Fault D
11. motor 50 kW
Rc 2 = 0.023 x
Xm =
25
4102
x
100 (50 / 0.9 x 0.8) 103
Rm = 0.2 Xm
30
35
R (m)
0.84
0.57
0.15
x 80
80
Rc1 = 0.036 x
400
10
400
0.15
0.72
RT = 0.2 X T
410 V
R ()
12
7.2
0.15
2.7
19.3
12
605
121
20 x 103
6,415 A
3 x 1.80
IA is the steady-state Isc and for the purposes
of calculating the peak asymmetrical IpA:
C =
2
2
RC
+ XC
= 20.7 m
410
11,400 A
3 x 20.7 x 10 3
RC
= 0.48 hence = 1.25 on the curve in
XC
A =
RA
= 0.55 hence = 1.2 on the curve in
XA
figure 9 and therefore ipA is equal to:
[(XA
XB = 6.51 m and
RB =
[(RA
RB = 1.77 m
These calculations make clear, firstly, the low
importance of the HV upstream reactance, with
respect to the reactances of the two parallel
transformers, and secondly, the non-negligible
impedance of the 10 meter long, LV busbars.
ZB =
B =
410
35,070 A
3 x 6.75 x 10-3
RB
= 0.27 hence = 1.46 on the curve in
XB
and
1.25 x
and
D =
2
2
RD
+ XD
= 35.5 m
410
6, 700 A
3 x 35.5 x 10-3
RD
= 1.31 hence 1.04 on the curve in
XD
c Fault at C
The current produced by the motor may be
calculated on the basis of the motor + cable
impedance:
XM = (605 + 2.7)10 3 608 m
M =
410
3 x 624 x 10 3
379 A
c Fault at D
The impedance to be taken into account is 1 / 19th
of ZM (19 parallel motors), plus that of the cable.
XMD
608
=
+ 2.7 10-3 = 34.7 m
19
140
RMD =
+ 19.3 10-3 26.7 m
19
ZMD = 43.8 m hence
MD =
410
= 5, 400 A
3 43.8 103
c Fault at B
As for the fault at C, the current produced by the
motor may be calculated on the basis of the
motor + cable impedance:
XM = (605 + 2.7 + 12) 10-3 = 620 m
IM =
410
372 A
3 637 103
410
= 152.5 A
20 103
X =
X =
R =
Z'D =
' D =
4.2 + 1.5 + 12
17.7 m = X'D
410
7,430 A
3 x 31.9 x 10-3
2 x 7,430 10,500 A .
a = e
I1(1)
I2(1)
I2(2)
I3(2)
Geometric construction of I1
I1
I1(1)
I1(2) I1(0)
I1(2)
I3(0)
Geometric construction of I2
I2 I1(1)
I1(0)
a I1(2)
I1(2)
a2 I1(1)
1
3
between I 1, I 2,
+ j
2
2
Zero-sequence
I1(0)
I2(0)
= -
Negative-sequence
2
3
and I 3.
This principle, applied to a current system, is
confirmed by a graphical representation
(see fig. 23). For example, the graphical addition
of the vectors produces, for, the following result:
Positive-sequence
I3(1)
I3
I2
I1
t
Geometric construction of I3
a2 I1(2)
I1(1)
I1(2)
I3
I1(1)
Fig. 23 : Graphical construction of the sum of three balanced three-phase systems (positive-sequence, negative-sequence and zero-sequence).
V(1)
(1)
, Z (2) =
V(2)
(2)
and Z (0) =
V(0)
(0)
Elements
Transformer
(seen from secondary winding)
No neutral
Yyn or Zyn
Dyn or YNyn
Dzn or Yzn
free flux
forced flux
Machine
Z(0)
10 to 15 X(1)
X(1)
0.1 to 0.2 X(1)
Synchronous
0.5 Z(1)
Line
3 Z(1)
Asynchronous
Rated
voltage
Un
Voltage factor c
for calculation of
Isc max. Isc min.
If tolerance + 6%
1.05
0.95
1.1
LV (100 to 1000 V)
If tolerance + 10%
MV and HV
1 to 550 kV
1.1
0.95
breaking current,
idc, aperiodic component,
Ik, rms value of the steady-state short-circuit
current.
I"k
Type
of short-circuit
Fault occuring
far from rotating machines
General situation
c Un
I"k3 =
c Un
I"k3 =
3 Z (1)
3 Z(1)
In both cases, the short-circuit current depends only on Z(1). which is generally replaced by Zk
the short-circuit impedance at the fault location, defined by Zk =
" =
Ik2
Phase-to-earth
I"k1 =
Phase-to-phase-to-earth
I"kE2E =
c Un 3
k2EL3
I"k1 =
"
Ik2EL2
=
I"
" =
Ik2
Z (1) + Z (2 )
c Un 3 Zi
Rk 2 + Xk 2 where:
c Un
2 Z (1)
c Un 3
2 Z(1) + Z( 0)
I"kE2E =
I"k2EL2 =
c Un Z (0) a 2 Z( 2 )
I"k2EL3 =
c Un 3
Z (1) + 2 Z(0)
Z
c Un (0) a
Z (1)
Z (1) + 2 Z( 0)
Z
c Un (0) a 2
Z (1)
Z(1) + 2 Z(0 )
Fig. 26 : Short-circuit values depending on the impedances of the given network (see IEC 60909).
RL = 1 +
(e - 20 C) x RL20
K T = 0.95
Cmax
1+ 0.6x T
SrT
2
UrT
ZS = K S tr2ZG + Z THV
2
UnQ
U2
cmax
2rTLV
2
UrQ UrTHV 1+ x''d xT sin rG
and tr =
UrTHV
UrTLV
UnQ
U
cmax
rTLV (1 p T )
UrG (1+ pG ) UrTHV
1+ x''dsin rG
I''kG =
where:
cUrG
3K G,S ZG
cmax
1+ x''dsin rG
K G,S =
KG =
cmax
Un
UrG 1+ x''dsin rG
K T, S =
I''kG =
cmax
1 x T sin rG
where:
K T,SO =
cUrG
3K G,SOZG
KG,SO =
1
cmax
1+ pG 1+ x''dsin rG
1
cmax
1+ pG 1 x T sin rG
2 k" where
= 1.02 + 0.98 e
-3
R
X
Ib = . I"k where:
Ikmin = min Ir
is a factor defined by the saturated
synchronous reactance Xd sat.
1.0
0.9
0.05 s
0.8
0.1 s
> 0.25 s
0.7
0.6
0.5
Fig. 27 : Factor used to calculate the short-circuit breaking current Ib (see IEC 60909).
2.4
Xd sat
max
2.2
6.0
1.2
1.4
2.0
1.6
1.8
2.0
2.2
1.8
1.6
1.4
5.0
4.5
Xd sat
max
4.0
0.6
3.5
1.2
0.8
3.0
1.0
1.0
1.2
2.5
0.8
0.6
1.7
2.0
2.0
1.5
min
0.4
min
1.0
0.5
0.2
0
5.5
Supply network
UnQ = 20 kV
I"kQ = 10 kA
SrT = 400 kVA
UrTHV = 20 kV
UrTLV = 410 V
Ukr = 4%
PkrT = 4.6 kW
R(0)T / RT = 1.0
X(0)T / XT = 0.95
Fig. 30
Solution:
c Three-phase fault at F1
v Impedance of the supply network (LV side)
ZQt =
c QUnQ
3 I''kQ
2
U
1.1 20 0.41
rTLV =
= 0.534 m
3 10 20
UrTHV
2
RQ
= 0.1, hence:
XQ
T (Dyn5)
Cable L
l=4m
F1
Un = 400 V
X Qt = 0.995ZQt = 0.531 m
100
SrT
100 400 103
RTLV = PkrT
2
UrTLV
2
SrT
= 4, 600
(410)2
(400 10 )
3 2
= 4.83 m
SrT
2
UrTLV
= 16.10
400
= 0.03831
4102
cmax
1.05
= 0.95
= 0.975
1+ 0.6x T
1+ (0.6 0.03831)
I''k =
cUn
1.05 400
=
= 14.12 kA
3 Zk
3 17.17
R Rk
5.18
=
=
= 0.316
X Xk 16.37
= 1.02 + 0.98e
ip = 2
I''k
R
X
= 1.4
c Phase-to-earth fault at F1
v Determining the zero-sequence impedances
For transformer T (Dyn5 connection), the manufactures indicates:
R(0 )T = RT and X (0)T = 0.95X T
with the impedance-correction factor KT, the zero-sequence impedance is:
Z (0)TK = K T (RT + j0.95X T ) = (4.712 + j14.913) m
For cable L:
The initial phase-to-earth short-circuit current can be calculated using the equation below:
cUn 3
1.05 400 3
I''k1 =
=
= 14.35 kA
50.70
Z(1) + Z( 2) + Z(0)
The peak short-circuit current ip1 is calculated with the factor obtained via the positive-sequence:
ip1 = 2 I''k1 = 1.4 2 14.35 = 28.41 kA
F2
SrT = 250 MVA
UrTHV 240 kV
=
UrTLV
21 kV
Ukr = 15%
PkrT = 520 kW
UnQ = 220 kV
F1
Fig. 31
Solution:
c Three-phase fault at F1
v Impedance of the transformer
Z THV =
2
ukr UrTHV
15 2402
= 34.56
100
SrT
100 250
RTHV = PkrT
2
UrTHV
2
SrT
2402
= 0.479
2502
= 0.52 x
2
x''d UrG
17 212
= 0.2999
100 SrG 100 250
SrG > 100 MVA, therefore RGf = 0.05 X"d, hence ZGf = 0.015 + j0.2999
KS =
2
UnQ
2
UrG
2
UrTLV
2
UrTHV
1+
x''d
cmax
x T sin rG
2202
212
1.1
= 0.913
2
21
2402 1+ 0.17 0.15 0.6258
240 2
ZS = 0.735 + j67.313
I''kS =
cUnQ
3 ZS
I''kS = 2.08 kA
11
, 220
= 0.023 j2.075
3 (0.735 + j67.313)
Based on impedance ZSf, it is possible to calculate RSf / XSf = 0.033 and S = 1.908
The peak short-circuit current ipS is calculated by:
ipS = S 2 I''kS
IbS = I''kS
Factor is a function of radio I"kG / IrG and the minimum dead time tmin.
Ratio I"kG / IrG is calculated by:
I''kG I''kS UrTHV 2.08 240
=
=
= 3.46
IrG IrG UrTLV 6.873 21
UrTLV
21
= 1.65 6.873
= 0.99 kA
UrTHV
240
Factor max = 1.65 is obtained in figure 28 for the ratio I"kG / IrG = 3.46 and xdsat = 2.0
c Three-phase fault at F2
I''kG =
where:
K G,S =
I''kG =
cUrG
3K G,SZG
cmax
1.1
=
= 0.994
1+ x''dsin rG 1+ (0.17 0.626)
cUrG
3KG,SZG
1.1 21
= 44.74 kA
3 0.994 0.2999
Based on impedance ZGf, it is possible to calculate RGf / X"d = 0.05, hence G = 1.86
ipG = 1.86 2 44.74 = 117.69 kA
IbG = I''kG
Factor is a function of ratio I"kG / IrG and the minimum dead time tmin.
Ratio I"kG / IrG is calculated by:
I''kG 44.74
=
= 6.51
IrG 6.873
Factor max = 1.75 is obtained in figure 28 for the ratio I"kG / IrG = 6.51 and xdsat = 2.0
4 Conclusion
Various methods for the calculation of shortcircuit currents have been developed and
subsequently included in standards and in this
Cahier Technique publication as well.
Bibliography
Standards
Other publications
c Electrical Installation Guide
In English in accordance with IEC 60364:
2005 edition.
In French in accordance with NF C15-100:
2004 edition.
Published by Schneider Electric
(Schneider Training Institute).
E-mail : [email protected]
DTP: Axess
Transl.: Cabinet Harder - Grenoble - France
Editor: Schneider Electric
Schneider Electric