Electrical Thumb Rules-(Part-5) | Electrical Notes & Articles

1 of 5

https://electricalnotes.wordpress.com/2013/09/01/electrical-thumb-rules-...

Electrical Notes & Articles


Sharing Abstracts,Notes on various Electrical Engineering Topics.

Electrical Thumb Rules-(Part-5)


SEPTEMBER 1, 2013
7 COMMENTS (HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2013/09/01/ELECTRICAL-THUMBRULES-PART-5/#COMMENTS)

Standard Size of Transformer (IEEE/ANSI 57.120):


Single Phase Transformer

Three Phase Transformer

5KVA,10 KVA,15 KVA,25 KVA,37.5


KVA,50 KVA,75 KVA,100 KVA,167
KVA,250 KVA,

3 KVA,5 KVA,9 KVA,15 KVA,30 KVA,45 KVA,75


KVA,112.5 KVA,150 KVA,225 KVA,300 KVA,500
KVA,750 KVA,1MVA,1.5 MVA,2 MVA,2.5
MVA,3.7 MVA,5 MVA,7.5MVA, 10MVA
,12MVA,15MVA,20MVA ,25MVA,
30MVA,37.5MVA ,50MVA
,60MVA,75MVA,100MVA

333 KVA,500 KVA,833 KVA,1.25


KVA,1.66 KVA,2.5 KVA,3.33
KVA,5.0 KVA,6.6 KVA,8.3 KVA,10.0
KVA,12.5 KVA,16.6 KVA,20.8
KVA,25.0 KVA,33.33 KVA

Standard Size of Motor (HP):


Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000

Approximate RPM of Motor


HP

RPM

< 10 HP

750 RPM

10 HP to 30 HP

600 RPM

30 HP to 125 HP

500 RPM

125 HP to 300 HP

375 RPM

11/30/2015 7:55 PM

Electrical Thumb Rules-(Part-5) | Electrical Notes & Articles

2 of 5

https://electricalnotes.wordpress.com/2013/09/01/electrical-thumb-rules-...

Standard Size of Motor (HP):


Electrical Motor (HP)
1,1.5,2,3,5,7.5,10,15,20,30,40,50,60,75,100,125,150,200,250,300,400,450,500,600,700,
800,900,1000,1250,1250,1500,1750,2000,2250,3000,3500,4000

Motor Line Voltage:


Motor (KW)

Line Voltage

< 250 KW

440 V (LV)

150 KW to 3000KW

2.5 KV to 4.1 KV (HV)

200 KW to 3000KW

3.3 KV to 7.2 KV (HV)

1000 KW to 1500KW

6.6 KV to 13.8 KV (HV)

Motor Starting Current:


Supply

Size of Motor

Max. Starting Current

1 Phase

< 1 HP

6 X Motor Full Load Current

1 Phase

1 HP to 10 HP

3 X Motor Full Load Current

3 Phase

10 HP

2 X Motor Full Load Current

3 Phase

10 HP to 15 HP

2 X Motor Full Load Current

3 Phase

> 15 HP

1.5 X Motor Full Load


Current

Motor Starter:
Starter

HP or KW

Starting Current

Torque

DOL

<13 HP(11KW)

7 X Full Load Current

Good

Star-Delta

13 HP to 48 HP

3 X Full Load Current

Poor

Auto TC

> 48 HP (37 KW)

4 X Full Load Current

Good/ Average

0.5 to 1.5 X Full Load


Current

Excellent

VSD

Motor > 2.2KW Should not connect direct to supply voltage if it is in Delta
winding

11/30/2015 7:55 PM

Electrical Thumb Rules-(Part-5) | Electrical Notes & Articles

3 of 5

https://electricalnotes.wordpress.com/2013/09/01/electrical-thumb-rules-...

Impedance of Transformer (As per IS 2026):


MVA

% Impedance

< 1 MVA

5%

1 MVA to 2.5 MVA

6%

2.5 MVA to 5 MVA

7%

5 MVA to 7 MVA

8%

7 MVA to 12 MVA

9%

12 MVA to 30 MVA

10%

> 30 MVA

12.5%

Standard Size of Transformer:


Standard Size of Transformer

KVA

Power Transformer (Urban)

3,6,8,10,16

Power Transformer (Rural)

1,1.6,3.15,5

Distribution Transformer

25,50,63,100,250,315,400,500,630

FILED UNDER UNCATEGORIZED


About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical) from Gujarat University. He has more than 13 years
experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical
Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Deputy
Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical
Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for Electrical Mirror and Electrical India Magazines. He is
Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and
help technical enthusiasts to nd suitable solutions and updating themselves on various Engineering Topics.

11/30/2015 7:55 PM

Electrical Thumb Rules-(Part-5) | Electrical Notes & Articles

4 of 5

https://electricalnotes.wordpress.com/2013/09/01/electrical-thumb-rules-...

7 Responses to Electrical Thumb Rules-(Part-5)


Kaustubh Wasave says:
September 4, 2013 at 6:03 am
Hello Sir,
I am a huge fan of yours. I recently ran into your blog and have been hooked since. Your blog contains all vital information that
an electrical engineer, like me, needs to know and I thank you for the pain that you took to make it available for everyone. I have
one request, if its not too much for you, can you please explain relay coordination in an industry or substation using an example?
Thank you and keep up the good work. Well always look up to you for inspiration.
Reply
Sandeep Ayyagari says:
September 22, 2013 at 5:53 am
Hello Sir,
Thanks for your great support in Electrical ,please let me know the Magnetizing current in a Transformer and basic tests to be
conducted before charging the Transformer ,and Standard Tolerances to be followed for Transformer Selection ,and General
Transformer Erection Procedure, and Pre Commissioning Checks,Check List for Smother Maintenance.
Reply
Luis Zorrilla says:
September 27, 2013 at 3:06 pm
Jignesh,
Thanks a lot for your Blog. I have a question for you:
What is the impact of modeling or not modeling the static wire in a Transmission, Distribution line? I am doing a model for a
transmission line and I want to know how much details I need to have to have reasonable results.
Regards
Reply
P.Ashokan says:
November 8, 2013 at 11:20 am
Hello Sir,
could you say Which Standards You are used in above All the details.
Thanking you,
P.Ashokan
Chennai
Reply
Mintu kumar pandit says:
September 9, 2014 at 12:55 pm
why in a.c power cable like to delta shape? please tel me sir.
thanking you,
Mintu kr. pandit
Howrah/ W.B
Reply
Mintu Kumar Pandit says:
September 9, 2014 at 1:00 pm
why in a.c power cable like to delta shape? please tel me sir,
thanking you
mintu kr. pandit
Howrah / W.B
Reply
Engr. Ghazanfar Ali Khan says:
January 23, 2015 at 2:51 pm
How rating of tertiary winding winding is formulated, calculated?