Abb Rmu
Abb Rmu
Abb Rmu
Content
Applications SafeRing
SafeRing
RMU type
SafeRing
CCV / CCF
SafeRing
RMU type
SafeRing
CCVV /
CCFF
SafeRing
RMU type
SafeRing
DeV / DeF
SafeRing
RMU type
SafeRing
CCCV /
CCCF
Applications SafeRing
DeF
CCCF
CCF
CCFF
CCC
CCCC
DeV
CCCV
CCV
CCVV
Available modules:
C
Cable Switch
De
Direct Cable Connection with Earthing Switch
F
Switch Fuse-Disconnector
V
Vacuum Circuit-Breaker
Applications SafePlus
De
CB
Sl
Sv
Be
Mt
3
A
3
V
Applications SafePlus
SafePlus
CC
REF541
SafePlus
SafePlus
SafePlus
SafePlus
FF
REF541
SafePlus
REF541
SafePlus
SafePlus
Design philosophy
SafeRing configurations
General
SafeRing is a ring main unit for the secondary distribution
network. SafeRing can be supplied in 10 different configurations suitable for most switching applications in 12/24 kV
distribution networks. SafeRing can as an option be delivered
as extendable rong main unit.
SafeRing combined with the SafePlus concept, which is
ABBs flexible, modular compact switchgear represent a complete solution for 12/24 kV secondary distribution networks.
SafeRing and SafePlus have identical user interfaces.
SafeRing is a completely sealed system with a stainless steel
tank containing all the live parts and switching functions. A
sealed steel tank with constant atmospheric conditions ensures a high level of reliability as well as personnel safety and
a virtually maintenance-free system.
The SafeRing concept offers a choice of either a switch fuse
combination or circuit breaker with relay for protection of the
transformer. SafeRing can be supplied with an integrated
remote control and monitoring unit.
SafeRing is supplied with the following standard equipment
Earthing switches
Operating mechanisms with integral mechanical inter locking
Operating handle
Facilities for padlocks on all switching functions
Bushings for cable connection in front with cable covers
Lifting lugs for easy handling
All 3- and 4-way units are designed for the subsequent
fitting of an integral remote control and monitoring unit
Optional features
Bushings for connection of external busbar on top of RMU
Bushings for side connection (400A) (C-, F- and De modules only)
Bushings for cable testing, incl. earthing device (C- and
De- modules only)
Cable bushings (Interface A, B, C and D)
Cable compartment front cover interlocked with earthing
switch
Interlocking of compartment for cable test bushings
Arc suppressor with signal (1NO) wired to terminals
(only one each SF6 tank)
Signal (1NO) from internal pressure indicator wired to
terminals (only one each SF6 tank)
Latched single spring mechanism for ring cable switch
Optional features also available as retrofit
Manometer for SF6 pressure monitoring
(temperature compensated)
Integrated control and monitoring unit (ICMU)
Integrated battery and charger
Motor operation
Trip coil open
Trip coil open and close
SafeRing configurations
SafeRing
SafeRing
SafeRing
SafeRing
SafeRing
DeF
Depth: 765 mm
Width: 696 mm
Height: 1336 mm
CCF
Depth: 765 mm
Width: 1021 mm
Height: 1336 mm
CCCF
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
CCFF
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
DeV
Depth: 765 mm
Width: 696 mm
Height: 1336 mm
SafeRing configurations
SafeRing
SafeRing
SafeRing
SafeRing
SafeRing
CCV
Depth: 765 mm
Width: 1021 mm
Height: 1336 mm
CCCV
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
CCVV
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
CCC
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
CCCC
Depth: 765 mm
Width: 1346 mm
Height: 1336 mm
SafeRing
C-module
Switch
F-module
Earthing switch
disconnector
V-module
Switch-fuse
Downstream
Vacuum
Earthing
disconnector
earthing switch
circuit-breaker
switch/
12/17,5/24
12/17,5/24
disconnector
Rated voltage
kV
12/15/17,5/24
12/15/17,5/24
12/15/17,5/24
12/15/17,5/24
kV
28/38/38/50
28/38/38/50
28/38/50
28/38/50
28/38/38/50
28/38/38/50
kV
95/95/95/125
95/95/95/125
95/95/125
95/95/125
95/95/95/125
95/95/95/125
630/630/630/630
- active load
630/630/630/630
- closed loop
630/630/630/630
135/135/135/135
- earth fault
200/150/150/150
115/87/87/87
kA
Making capacity
kA
200/200/200/200
see1)
Breaking capacities:
1)
2)
3)
4)
5)
3)
20/20/20
16/16/16/16
see2)
52,5/52,5/40/40
52,5/52,5/40/40
see2)
12,5/12,5/12,5
kA
4)
kA
5)
kA
40/40/40/40
40/40/40/40
16/16/16/16
16/16/16
21/21/16/16
21/21/16/16
5/5/5
16/16/16/16
16/16/16/16
16/16/16/16
SafeRing is tested according to IEC publications IEC 60265-1, IEC 6227-1, EC 62271-100, -102, -105, -200 and IEC 60529.
SafePlus modules
General
SafePlus is a metal enclosed compact switchgear system for
up to 24 kV distribution applications. The switchgear has a
unique flexibility due to its extendibility and the possible combination of fully modular and semi-modular configurations.
SafePlus combined with SafeRing, which is ABBs standard
ring main unit, represent a complete solution for 12/24 kV
distribution networks.
SafePlus and SafeRing have identical user interfaces.
SafePlus is a completely sealed system with a stainless steel
tank containing all live parts and switching functions.
A sealed steel tank with constant atmospheric conditions
ensures a high level of reliability as well as personnel safety
and a virtually maintenance-free system. As an option external
busbars can be provided to obtain full modularity.
The external busbar kit has to be mounted to the switchgears
on site. It is fully insulated and screened to ensure the reliability and climatic independence.
The SafePlus system offers a choice of either a switch-fuse
combination or a circuit-breaker with relay for protection of
the transformer.
SafePlus accommodates a wide selection of protection relays
for most applications.
SafePlus can also be supplied with remote control and monitoring equipment
SafePlus (except M- and Mt-modules) is supplied with
the following standard equipment:
Earthing switches (not for D module)
Operating mechanisms with integral mechanical
interlocking
Operating handle
Facilities for padlocks on all switching functions
Bushings for cable connection in front (not for Sl, Sv and
Be modules)
Cable compartment cover
Manometer for SF 6 pressure monitoring (temperature
compensated)
Lifting lugs for easy handling
C - Cable switch
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Standard features
Three position load break switch with disconnector and
earthing switch
Operating mechanism with two separate operating shafts
for load break function and earthing function
Switch position indication for load break switch and
earthing switch
Cable bushings horizontal in front, Interface C (400 series
bolted) with integrated voltage divider for voltage indication
Cable compartment cover allowing surge arrestor or
double cable connection
Busbar, 630A
Earthing bar
Optional features
Bushings for connection of external busbar on top of the
unit
Bushings for side extension (400 A)
Bushings for cable testing (incl. earthing device test points)
Cable bushings:
Interface B (400 series plug-in, In = 400 A)
Interface C (400 series bolted) combisensors with
integrated capacitor for voltage indication and sensors for
current and voltage monitoring
Interface D (600 series bolted)
Cable compartment front cover interlocked with earthing
switch
Interlocking of compartment for cable test bushings
Arc proof and interlocked cable covers
Arc suppressor with signal (1NO) wired to terminals
(only one each SF6 tank)
Technical data
Switch disconnector
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- active load
- closed loop
- off load cable charging
- earth fault
- earth fault cable charging
Making capacity
Short time current 1 sec.
Short time current 3 sec.
Number of mechanical operations
Earthing switch
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 1 sec.
Short time current 3 sec.
Number of mechanical operations
kV
kV
kV
A
12
28
95
630
15
38
95
630
17,5
38
95
630
24
50
125
630
A
A
A
A
A
kA
kA
kA
1000
630
630
135
200
115
62,5
25
21
close /
630
630
630
630
135
135
150
150
87
87
52,5
50
21
21
open manual
630
630
135
150
87
50
21
kV
kV
kV
kA
kA
kA
1000
12
28
95
62,5
25
21
close /
15
17,5
38
38
95
95
52,5
50
21
21
open manual
24
50
125
50
21
F - Switch-fuse-disconnector
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Standard features
Three position switch-fuse-disconnector with upstream
earthing switch mechanically linked with downstream
earthing switch
Switch position indication for switch-fuse-disconnector and
earthing switches
Operating mechanism with double spring for switch-fuse-
disconnector function
Common mechanism for earthing functions
Fuse canisters for DIN type fuse. Only accessible when
earthing switches are closed
Fuse-link / transformer rating:
12 kV, max 125 A CEF fuses
24 kV, max 63 A CEF fuses
Fuse tripping arrangement
Optical fuse trip indication
Cable bushings horizontal in front, Interface A (200 series
plug-in) with integrated capacitor for voltage indication
Cable compartment cover allowing surge arrestor or
double cable connection
Busbar, 630 A
Earthing bar
Optional features
Bushings for connection of external busbar on top of unit
Bushings for side extension (400 A)
Cable bushings:
Interface B (400 series plug-in, In = 400A)
Interface C (400 series bolted)
Interface C (400 series bolted) combisensors with in
tegrated screen for voltage indication and sensors for
current and voltage monitoring
14 F - Switch-fuse-disconnector | Product Catalogue
Technical data
Switch-fuse-disconnector
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- off load transformer
Making capacity
Number of mechanical operations
Earthing switch downstream
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 1 sec.
Number of mechanical operations
1)
kV
kV
kV
A
17,5
38
95
200
24
50
125
200
A
20
20
20
1)
1)
1)
kA
1000 close / open manual
20
kV
kV
kV
kA
kA
1000
12
28
95
200
12
28
95
12,5
5
close /
15
38
95
200
15
17,5
38
38
95
95
12,5 12,5
5
5
open manual
1)
24
50
125
12,5
5
V - Vacuum circuit-breaker
Technical data
Vacuum circuit-breaker
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- short-circuit breaking current
Making capacity
Short time current 0,5 sec. 1)
Short time current 1 sec. 2)
Short time current 3 sec.
Number of mechanical operations
Earthing switch downstream
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 3 sec.
Number of mechanical operations
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
1)
2)
Standard features
200 A vacuum circuit-breaker for transformer protection or
630 A vacuum circuit-breaker for feeder protection
Two position double spring mechanism for vacuum circuit-
breaker
Three position disconnector/earthing switch downstream
vacuum circuit-breaker
Three positioning single spring mechanism for
disconnector/earthing switch
Interlocking between vacuum circuit-breaker and
disconnector/earthing switch
Switch positioning indication for vacuum circuit-breaker
and disconnector/earthing switch
Self powered electronic protection relay with ring core CTs
on cables (only standard on 200 A)
Trip coil (for relay tripping)
Cable bushings horizontally in front; Interface A (200 series
plug-in) for 200 A vacuum circuit-breaker with integrated
capacitor for voltage indication and Interface C (400 series
bolted) for 630 A vacuum circuit-breaker with integrated
capacitor for voltage indication
Cable compartment cover allowing surge arrestor or
double cable connection
Busbars, 630 A
Earthing bar
Optional features
Bushings for connection of external busbar on top of unit
Cable bushings:
Interface B (400 series plug-in)
Interface D (600 series bolted)
kV
kV
kV
A
12
28
95
kA
kA
kA
15
38
95
200 /
17,5
38
95
630
24
50
125
21
52,5
16
16
kA
21
2000 close /
21
16
52,5
40
16
16
16
16
21
16
open manual
16
40
16
16
16
kV
kV
kV
kA
kA
1000
15
17,5
38
38
95
95
52,5
40
21
16
open manual
24
50
125
40
16
12
28
95
52,5
21
close /
Maximum rating for bushings Interface A (200 series plug-in) with rated curretn 200 A
Maximum rating for bushings Interface B (400 series plug-in)
Technical data
Vacuum circuit-breaker
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- short-circuit breaking current
Making capacity
Short time current 1 sec. 1)
Short time current 3 sec.
Number of mechanical operations
Earthing switch downstream
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 1 sec.
Number of mechanical operations
REJ603
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
1)
Standard features
630 A vacuum circuit-breaker for feeder protection
Mechanism with operating sequence;
O 0,3 s CO 3 min CO
Auto-reclosing capability
Vacuum circuit-breaker with downstream three-position
disconnector/earthing switch
Three-position single spring mechanism for
disconnector/earthing switch
Interlocking between vacuum circuit-breaker and
disconnector/earthing switch
Switch position indication for vacuum circuit-breaker
and disconnector/earthing switch
Mechanical counter
Self-powered electronic protection relay with ring core CTs
on cables
Trip coil (for relay tripping)
Cable bushings horizontally in front Interface C (400 series
bolted) with integrated capacitor for voltage indication
Cable compartment cover allowing surge arrestor or
double cable connection
Busbars, 630 A
Earthing bar
Optional features as factory mounted
Bushings for connection of external busbar on top of unit
Cable bushings:
Interface B (400 series plug-in)
Interface C (400 series bolted) combisensors with
integrated voltage divider for voltage indication and
integrated sensor for current and voltage monitoring
kV
kV
kV
A
12
28
95
630
24
50
125
630
kA
25
20
kA
62,5
50
kA
25
21
kA
21
21
2000 close / open manual
kV
12
24
kV
28
50
kV
95
125
kA
62,5
50
kA
25
21
1000 close / open manual
Sl - Busbar sectionalizer
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Depth: 765 mm
Width: 650 mm
Height: 1336 mm
Busriser is needed when
Sl-module is on right
hand side of SF6-tank
Standard features
Three positioning load break switch with disconnector and
earthing switch
Operating mechanism with two separate operating shafts
for load break function and earthing function
Switch position indication for load break switch and
earthing switch
Busbars, 630 A
Earthing bar
Technical data
Busbar sectionalizer Sl
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- active load
- closed loop
- off load cable charging
- earth fault
- earth fault cable charging
Making capacity
Short time current 1 sec.
Short time current 3 sec.
Number of mechanical operations
Earthing switch
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Making capacity
Short time current 1 sec.
Short time current 3 sec.
Number of mechanical operations
kV
kV
kV
A
12
28
95
630
15
38
95
630
17,5
38
95
630
24
50
125
630
A
A
A
A
A
kA
kA
kA
1000
630
630
135
200
115
62,5
25
21
close /
630
630
630
630
135
135
150
150
87
87
52,5
50
21
21
open manual
kV
kV
kV
A
kA
kA
kA
1000
12
28
95
630
62,5
25
21
close /
15
17,5
24
38
38
50
95
95
125
630
630
630
52,5
50
50
21
21
21
open manual
630
630
135
150
87
50
21
Optional features
Bushings for connection of external busbars on top of the
unit
Latched single spring mechanism
Sv - Busbar sectionalizer
Depth: 765 mm
Width: 650 mm
Height: 1336 mm
Sv is always in combination
with busrise module (Br)
Standard features
630 A vacuum circuit-breaker
Two position double spring mechanism for vacuum circuit-
breaker
Three position disconnector / earthing switch downstream
vacuum circuit-breaker
Three position single spring mechanism for disconnector /
earthing switch
Interlocking between vacuum circuit-breaker and
disconnector / earthing switch
Switch position indication for vacuum circuit-breaker and
disconnector / earthing switch
Busbars, 630 A
Optional features
Bushings for connection of external busbar
Technical data
Busbar sectionalizer Sv
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- short-circuit breaking ccurrent
Making capacity
Short time current 3 sec.
Number of mechanical operations
Earthing switch
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 3 sec.
Number of mechanical operations
kV
kV
kV
A
12
28
95
630
15
38
95
630
17,5
38
95
630
24
50
125
630
kA
kA
kA
2000
21
52,5
21
close /
21
16
52,5
40
21
16
open manual
16
40
16
kV
kV
kV
kA
kA
1000
12
28
95
52,5
21
close /
15
17,5
38
38
95
95
52,5
40
21
16
open manual
24
50
125
40
16
REJ603
Depth: 765 mm
Width: 650 mm
Height: 1336 mm
Sv is always in combination
with busrise module (Br)
Standard features
630 A vacuum circuit-breaker
Mechanism with operating sequence;
O 0,3 s CO 3 min CO
Vacuum circuit-breaker with downstream three-position
disconnector/earthing switch
Three position single spring mechanism for disconnector /
earthing switch
Interlocking between vacuum circuit-breaker and
disconnector / earthing switch
Switch position indication for vacuum circuit-breaker and
disconnector / earthing switch
Busbars, 630 A
Technical data
Busbar sectionalizer Sv
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
- short-circuit breaking ccurrent
Making capacity
Short time current 3 sec.
Number of mechanical operations
Earthing switch
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Making capacity
Short time current 3 sec.
Number of mechanical operations
kV
kV
kV
A
12
28
95
630
24
50
125
630
kA
25
20
kA
62,5
50
kA
21
21
2000 close / open manual
kV
12
24
kV
28
50
kV
95
125
kA
62,5
50
kA
25
21
1000 close / open manual
Optional features
Bushings for connection of external busbar
Technical data
Direct cable connection
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Short time current 1 sec.
Short time current 3 sec.
kV
kV
kV
A
kA
kA
12
28
95
630
25
21
15
38
95
630
21
17,5
38
95
630
21
24
50
125
630
21
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Standard features
Cable bushings horizontally in front, Interface C (400 series
bolted) with integrated capacitor for voltage indication.
Cable compartment cover allowing surge arrestor or
double cable connection
Busbars, 630 A
Earthing bar
Optional features
Bushings for connection of external busbars
Cable bushings:
Interface B (400 series plug-in) (In = 400 A)
Interface C (400 series bolted) combisensors with
integrated capacitor for voltage indication and sensors for
current and voltage monitoring
Interface D (600 series bolted)
Arc suppressor with signal (1NO) wired to terminals
(only one each SF 6 tank)
Signal (1NO) from internal pressure indicator wired to
Technical data
Direct cable connection with earthing
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Making capacity
Short time current 1 sec
Short time current 3 sec.
Number of mechanical operations
switch
kV
12
kV
28
kV
95
A
630
kA
62,5
kA
25
kA
21
1000 close /
15
38
95
630
52,5
17,5
38
95
630
50
21
21
open manual
24
50
125
630
50
21
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Standard features
Earthing switch
Two positioning single spring mechanism
Switch position indication
Cable bushings horizontal in front, Interface C (400 series
bolted) with integrated capacitor for voltage indication
Cable compartment cover allowing surge arrestor or
double cable connection
Busbars, 630 A
Earthing bar
Optional features
Bushings for connection of external busbars
Bushings for cable testing, incl. earthing device
Cable bushings:
Interface B (400 series plug-in) (In = 400 A)
Interface C (400 series bolted) combisensors with
integrated capacitor for voltage indication and sensors for
current and voltage monitoring
Interface D (600 series bolted)
Cable compartment front cover interlockied with earthing
switch
Interlocking of compartment for cable test bushings
Arc suppressor with signal (1NO) wired to terminals (only
one each SF 6 tank)
Signal (1NO) from internal pressure indicator wired to
terminals (only one each SF 6 tank)
Be - Busbar earthing
Technical data
Busbar earthing
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Making capacity
Short time current 1 sec
Short time current 3 sec.
Number of mechanical operations
Depth: 765 mm
Width: 325 mm
Height: 1336 mm
Standard features
Earthing switch
Two position single spring mechanism
Switch position indication for earthing switch
Busbars, 630 A
Earthing bar
Optional features
Bushings for connection of external busbars
Signal (1NO) from internal pressure indicator wired to ter
minals (only one each SF 6 tank)
Optional features also available as retrofit
Low voltage compartment / Top entry box
Base frame (290 or 450 mm
Auxiliary switches, earthing switch position 2NO+2NC
Ronis key interlock
kV
kV
kV
A
kA
kA
kA
1000
12
28
95
630
62,5
25
21
close /
15
38
95
630
52,5
17,5
38
95
630
50
21
21
open manual
24
50
125
630
50
21
CB - Circuit-breaker module
REF541
SafePlus
M
VD4
Technical data
Circuit-breaker module
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Breaking capacities:
Short-circuit breaking current
Making capacity
Short time current 1 sec
Short time current 3 sec.
Number of mechanical operations
kV
kV
kV
A
12
28
95
630 / 1250
24
50
125
630 / 1250
kA
25
20
kA
62,5
50
kA
25
20
kA
25
20
30000 close / open manual
Depth: 800 mm
Width: 696 mm
Height: 1336 mm
Standard features
630/1250A vacuum circuit breaker
Disconnector
Earthing switch
Bushings for connection of external busbars
Auto reclosing sequence
Closing and tripping coil
Combisensors with Interface C (400 series bolted)
Low voltage compartment with different protection relays
Optional features
Signal (1NO) from internal pressure indicator wired to
terminals
Optional features also available as retrofit
Base frame (290 or 450 mm)
Motor operated disconnector / earthing switch
Motor operating mechanism, circuit-breaker
M - Metering module
Technical data
Metering module
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Short time current 1 sec
Short time current 3 sec.
SafePlus
3
A
kV
kV
kV
A
kA
kA
12
28
95
630
25
21
15
38
95
630
17,5
38
95
630
24
50
125
630
21
21
21
The M-module is a factory assembled type tested air insulated metering cubicle with conventional CTs and VTs. The
M-module is designed for CTs and VTs with dimensions according to DIN 42600 Narrow type.
The M-module is also designed for tariff metering.
Depth: 802 mm
Width: 696 mm
Height: 1806 mm
Standard features
2 or 3 pcs (has to be specified) DIN 42600 Narrow type
current transformers with ribs
3 pcs DIN 42600 Narrow type single pole voltage trans
formers
6 pcs bushings Interface C (400 series bolted) with con
nections and external busbars for SafePlus modules on left
and right hand side
3 pcs bushings Interface C (400 series bolted) only re
quired if the M-module is left hand side or right hand side
end module
Internal layout with CTs and VTs on left hand side or right
hand side dependent of power direction (has to be speci
fied)
Padlock interlocking to prevent access to live parts
Voltage transformers
Single pole insulated with measuring and earth fault
windings
Primary voltage and frequency (50 or 60 Hz) has to be
specified
Secondary windings --/110:V3/110:3V or --/100:V3/100:3V
has to be specified
Note: VTs can also be delivered without open Delta Earth
fault windings
Burden / class has to be specified
M - Metering module
Current transformers
Single-core or double-core design
Secondary side reconnectable possible
Primary current max. 600 Amp., has to be specified
Secondary current 5 Amp or 1 Amp. has to be specified
Burden / class has to be specified
Low voltage compartment
Terminals for voltage transformers secondary connection
3-pole MCB for measuring voltage
1-pole MCB for earth fault voltage
Damping resistor for voltage transformers open delta earth
fault windings, to avoid ferro resonance
Separating terminals for current transformers secondary
windings
Space for electronic kWh-meter
Optional features
Primary fuses for voltage transformers
Voltmeter with selector switch, 6 positions +0
A-meter with selector switch, 3 positions +0
Additional meters
Ronis key interlocking to prevent access to live parts
Cable bottom entry for outgoing cable
Metering module delivered for voltage measuring only
Metering module delivered without low voltage equipment
and wiring
Metering module delivered without VTs and CTs, with
connections only
Optional features also available as rtrofit
Base frame (290 or 450 mm)
SafePlus
SafePlus
12
28
95
630
20
24
50
125
630
20
SafePlus
kV
kV
kV
A
kA
The Mt-module is a factory assembled type tested air insulated non arc proof metering cubicle with conventional CTs and
VTs. The Mt-module is designed for CTs and VTs with dimensions according to DIN 42600 Narrow type and for installation
of transformers locally.
Depth: 1047 mm
Width: 800 mm
Height: 1806 mm
Technical data
Metering tariff module
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated normal current
Short time current 1 sec.
SafePlus
Standard features
3 pcs DIN 42600 Narrow type current transformers with
ribs
3 pcs DIN Narrow type single pole voltage transformers
Padlock interlocking to prevent access to live parts
MV cable connection to SafePlus cubicle using Elastimold,
3M, Pirelli, Raychem, Kabeldon, etc. connectors
MV cable connection inside Mt-module by conventional
cable lugs
Voltage transformers
Single pole insulated with measuring and earth fault wind
ings
Primary voltage and frequency (50 or 60 Hz) has to be
specified
Secondary windings --/110:V3/110:3V or --/100:V3/100:3V
has to be specified
Note: VTs can also be delivered without open Delta Earth
fault windings
Burden / class has to be specified
Current transformers
Single-core or double-core design
Secondary side reconnectable possible
Primary current max 600 Amp, has to be specified
Secondary current 5 Amp or 1 Amp has to be specified
Outer assembly
5
17
8
9
SafePlus
2
3
4
18
10
11
12
13
15
14
16
The cable switch (C-Module) is a three positioning switchdisconnector and earthing switch using SF6 gas as an arc
quenching medium.
The switch positioning is close open earthed. In the open
position the switch satisfies the disconnector requirements.
Switch-fuse module
Cable bushings
Arc suppressor
The arc suppressor is an optimal quick-make short circuit device with a mechanical pressure detector that can be installed
with each incoming feeder inside the sealed SF6 tank of the
SafeRing and SafePlus switchgear.
If an arc fault should occur inside the SF6 tank the pressure
detector of the arc suppressor will automatically trip the short
circuit device of the incoming feeder(s) within milliseconds,
thereby transforming the arc fault into a bolted fault.
The arc is extinguished without any emission of hot gases and
the bolted short circuit will be interrupted by the upstream
circuit-breaker.
No links or release mechanisms are installed outside the tank.
Corrosion and any environmental influences are therefore
prevented, giving optimum reliability.
The pressure detector is insensitive to pressure changes due
to variation in atmospheric temperature or pressure as well as
external phenomena such as vibrations or shocks.
The arc suppressor will operate for short-circuit currents in
the range of 1kArms to 21kArms and it will reduce the generated arc energy to less than 5% of the arc energy released
during an arcing time of 1 sec.
A signalling device (1NO) will indicate local or remote the tripping of one or more arc suppressors.
Since the system is self-contained, an internal arc fault will
have no impact on the surroundings. No arc fault tests have
to be repeated in combination with channel release systems
or transformer stations.
The costs of the cleaning work which has to be done after
an internal arc fault when the release flap has opened, are
reduced to zero.
C-module
F-module
V-module
All operating mechanisms are equipped with position indicators for all switches. In order to achieve true indication,
indicators are directly connected to the operating shafts of the
switches inside the SF6-tank, please see shafts shown with
red colour on next page.
Operating handle has an anti-reflex system which prevents an
immediate re-operation of the switch.
SF6
Air
C-mechanism
SF6
Air
Switch-fuse module
The mechanism (3PAE) has two operating shafts; the upper
one for the load break switch and the lower one for the earthing switch.
The upper one operates two springs; one for closing and one
for opening. Both springs are charged in one operation. By
means of mechanical push buttons it is then possible to close
and open the load break switch.
F-mechanism
SF6
Air
Vacuum circuit breaker and busbar sectionalizer with circuit
breaker
These two modules have two mechanisms; the upper one
(2PA) with one operating shaft is for circuit breaker and the
lower one (3PKE) with two operating shafts is for disconnector and earthing switch.
The upper mechanism has two operating springs; one for
closing and one for opening.
Both springs are charged in one operation. By means of
mechanical push buttons it is then possible to close and open
the circuit breaker.
V-mechanism
The opening spring is always charged when the circuit breaker is in closed position and will be ready to open immediately
if the protection relay gives a trip signal.
However a quick reclosing is not possible. If the mechanism is
equipped with a motor operation a reclosing will take approx.
10 seconds.
The lower mechanism is identical to the one described above
for cable switch module.
There is a mechanical interlock between these two mechanisms which prevents operating of the disconnector and
earthing switch when the circuit breaker is in closed position.
When the earthing switch is in closed position it will be impossible to operate the disconnector, but the circuit breaker
can be closed for testing purpose.
On the top of all SafeRing and SafePlus switchgears it is possible as an option to have bushings for connection of external
busbars on the left and / or right side.
SafePlus
SafePlus
SafeRing
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
The complete extension kit and the dead end receptacles are
fully screened, earthed and insulated with EPDM rubber.
This makes a safe and reliable switchgear extension.
In addition protection covers are available as an option.
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
Top view
Side extension
SafeRing
SafePlus
SafePlus
SafePlus
SafePlus
SafePlus
Base frame
REF 610
REF 610
REF 610
SafePlus
SafePlus
SafePlus
Front view
Side view
Rear view
SafeRing
The top entry box allows entrance of the customers low voltage wiring from the rear side, left hand side and right hand
side.
Furthermore the top entry box gives the opportunity to install
ammeters with position switches, local/remote switch for motor operation etc.
Additionally all SafePlus switchgears can be supplied with low
voltage compartment.
This compartment may be equipped with protection relays,
meters, position switches, terminal blocks etc.
Side view
Top entry box seen from above when front / top covers have
been removed
REF541
SafePlus
Motor operation
Power consumption
(V)
(W) or (VA)
Operation times
Opening time (s)
current (A)
Peak start
Fuse
24
90
6-9
6-9
14
F 6,3 A
48
150
4-7
4-7
13
F4A
60
90
6-9
6-9
F4A
110
90
6-9
6-9
F2A
220
90
6-9
6-9
1,7
F1A
Peak start
Fuse
Power consumption
(V))
(W) or (VA)
Operation times
Opening time (ms)
current (A)
24
160
9-14
40-60
14
F 6,3 A
48
200
5-9
40-60
13
F4A
60
140
8-13
40-60
F4A
110
140
8-13
40-60
F2A
220
140
8-13
40-60
1,7
F1A
Peak start
Fuse
Power consumption
(V)
(W) or (VA)
Operation times
Charge/Closing time (s)
current (A)
24
180
10-17
40-60
14
F 6,3 A
48
220
5-9
40-60
13
F4A
60
150
9-13
40-60
F4A
110
170
9-13
40-60
F2A
220
150
9-14
40-60
1,7
F1A
Characteristics of shunt trip coils, closing coils and opening cioils for F-and V-module
Rated voltage
Power consumption
Peak start
(V)
(W) or (VA)
Operation times
Opening time (ms)
current (A)
24 V DC
150
40-60
40-60
F 3,15 A
48 V DC
200
40-60
40-60
F2A
60 V DC
200
40-60
40-60
F 1,6 A
110 V DC
200
40-60
40-60
F1A
220 V DC
200
40-60
40-60
F 0,5 A
110 V AC
200
40-60
40-60
F1A
230 V AC
200
40-60
40-60
F 0,5 A
Motor operation
12
5
13
7
10
11
1
3
14
3
15
6
16
18
17
Transformer protection
SafeRing
100%
Un (kV)
3
CEF
25
50
75
100
125
160
200
250
315
400
500
630
16
25
25
40
40
50
50
80
100
125
160
160
800
16
25
25
40
40
50
50
63
80
100
125
160
10
16
25
25
40
40
50
50
63
80
100
125
160
10
16
25
25
25
40
40
50
50
63
80
100
160
1250
1600
7,2 kV
3,3
4,15
1000
160
16
25
25
25
40
50
50
63
80
100
125
160
16
16
25
25
25
40
40
50
50
80
100
125
160
160
6,6
16
16
25
25
25
40
40
50
50
63
80
100
125
160
10
10
10
16
16
25
25
25
40
40
50
50
80
80
125
11
10
16
16
25
25
25
25
40
50
50
63
80
100
125
12
10
16
16
16
25
25
25
40
40
50
63
80
100
125
13,8
10
10
16
16
25
25
25
25
40
50
50
63
80
100
15
10
10
16
16
16
25
25
25
40
40
50
63
80
100
17,5
10
10
16
16
16
25
25
25
40
50
50
63
80
20
10
10
16
16
16
25
25
25
40
40
50
63
63
22
10
10
16
16
16
25
25
25
40
50
50
63
24
10
10
16
16
16
25
25
25
40
40
50
63
125
24 kV
16
17,5 kV
12 kV
5,5
120%
Un (kV)
CEF
25
50
75
100
125
160
200
250
315
400
500
16
25
25
40
40
50
63
80
100
125
160
3,3
16
25
25
40
40
50
63
80
80
100
125
630
800
10
16
25
25
40
40
50
63
80
80
100
125
10
16
25
25
25
40
40
50
63
80
80
125
160
5,5
16
16
25
25
25
40
50
50
80
80
100
125
1250
1600
7,2 kV
4,15
1000
160
16
16
25
25
25
40
40
50
63
80
100
125
160
16
16
25
25
25
40
40
50
63
80
80
100
125
10
10
10
16
16
25
25
25
40
40
50
63
80
80
125
10
16
16
25
25
25
25
40
50
50
80
80
100
125
10
16
16
16
25
25
25
40
40
50
63
80
100
125
13,8
10
10
16
16
25
25
25
25
40
50
50
80
80
100
100
10
10
16
16
16
25
25
25
40
40
50
63
80
10
10
16
16
16
25
25
25
40
50
50
63
80
20
10
10
16
16
16
25
25
25
40
40
50
63
80
22
10
10
16
16
16
25
25
25
40
50
50
63
24
10
10
16
16
16
25
25
25
40
40
50
63
24 kV
15
17,5
17,5 kV
11
12
12 kV
6
6,6
Fuse-links
Fuse-link
Fuse holder
Fuse adapter
Type
Rated voltage kV
Rated current A
e / D mm
Type
Rated voltage kV
Rated current A
e / D mm
CEF
3,6/7,2
192/65
CEF
17,5
292/65
CEF
3,6/7,2
10
192/65
CEF
17,5
10
292/65
CEF
3,6/7,2
16
192/65
CEF
17,5
16
292/65
CEF
3,6/7,2
25
192/65
CEF
17,5
25
292/65
CEF
3,6/7,2
40
192/65
CEF
17,5
40
292/87
CEF
3,6/7,2
50
192/65
CEF
17,5
50
292/87
CEF
3,6/7,2
63
192/65
CEF
17,5
63
292/87
CEF
3,6/7,2
80
192/87
CEF
17,5
80
442/87
CEF
3,6/7,2
100
192/87
CEF
17,5
100
442/87
CEF
3,6/7,2
125
292/87
CEF
3,6/7,2
160
292/87
CEF
12
292/65
CEF
24
442/65
CEF
12
10
292/65
CEF
24
10
442/65
CEF
12
16
292/65
CEF
24
16
442/65
CEF
12
25
292/65
CEF
24
25
442/65
CEF
12
40
292/65
CEF
24
40
442/65
CEF
12
50
292/65
CEF
24
50
442/87
CEF
12
63
292/65
CEF
24
63
442/87
CEF
12
80
292/87
CEF
12
100
292/87
CEF
12
125
442/87
Product catalogue | Fuse-links 47
Relays
Relays
Relay
IEEE
IEC symbol
Protection function
REX
521
device no.
REF
REF
610
615
Short circuits
51
3I>
Short circuits
50/51/51B
3 I >>
Short circuits
50/51B
3 I >>>
Short circuits
51
2I>
Short circuits
50/51
2 I >>
Earth fault
51N
Io >
Earth fault
51N
Io >/SEF
Earth fault
50N/51N
Io >>/Io-o>
Earth fault
67N
Io >-->/SEF
Earth fault
67N
Io >-->/SEF
Earth fault
67N
Io >> -->
Earth fault
59N
Uo >
Residual overvoltage
Additional functions
46
I>
Phase discontinuity
Additional functions
62BF
CBFP
Circuit-breaker failure
31/21
Io
Neutral current
Degree of unbalance
Uo
Residual voltage
1)
79
X
X
Self-powered relays
Functionality
Features
1)
Relay
Description
IEEE
device no.
REJ 603
WIC 1
Protection functions
50/51
Protection functions
Short-curcuit protection
50/51
Protection functions
50/51B
Protection functions
50N/51N
Protection functions
Characteristic curves
Overcurrent element
DEFT,INV
2
1)
Characteristic curves
DEFT,INV
1)
DEFT,INV
1)
DEFT
Additional functions
Trip indication
Additional functions
Electro-impulse
Additional functions
115VAC/230VAC
Additional functions
Measuring circuit
wide range
wide range
special CT
special CT
Measuring circuit
7,2
14,4
Climatic withstand
-40 +85
-40 +85
Climatic withstand
-40 +85
-40 +85
X (option)
Relays
Current range
Transformer type
W2
16 - 56 A
Transformer type
W3
32 - 112 A
Transformer type
W4
64 - 224 A
Transformer type
W5
128 - 448 A
Current range
Transformer type
CT1
8 - 28 A
Transformer type
CT2
16 - 56 A
Transformer type
CT3
32 - 112 A
Transformer type
CT4
64 - 224 A
Transformer type
CT5
128 - 448 A
Ration - burden
SVA 100-100-45
50-100-200/1 A 1,5/3/6 VA
SVA 100-100-45
150/1 A 4 VA
SVA 100-100-45
100-200/1 A 4 - 7 VA
SVA 100-100-45
300-600/1 A 4 - 7 VA
SVA 100-100-45
400-600/1 A 4 - 7 VA
Multi-tap secondary:
KOLMA 06A1 (90 mm)
50-150/1 A or 50-750/5 A
Multi-tap secondary:
50-150/1 A or 50-750/5
Relays
Relays
REF541
REF 541
SafePlus
Depth:
Width:
Height:
765 mm
325 mm
1806 mm
REF542plus
REF 542plus
Menu
SafePlus
Depth:
Width:
Height:
765 mm
325 mm
1806 mm
Optional functionality:
Capacitor bank protection
Capacitor bank control
Power quality
Measurement:
3-phase current
neutral current
3-phase voltage
residual voltage
3-phase power and energy incl. cos phi
transient disturbance recorder
Combisensor
Sensor variants
Two versions could be selected: one providing voltage
measurement together with voltage indication capability
(KEVCY 24 RF1), or a second one, providing, in addition to
these, also the possibility of current measurement
(KEVCY 24 RE1).
Linearity
Due to the absence of a ferromagnetic core the sensor has
a linear response over a very wide primary current range, far
exceeding the typical CT range.
Current sensor
Current measurement in KEVCY 24 RE1 sensors is based on
the Rogowski coil principle. A Rogowski coil is a toroidal coil,
without an iron core, placed around the primary conductor in
the same way as the secondary winding in a current transformer.
Voltage sensor
Voltage measurement in KEVCY 24 RE1 and KEVCY 24 RF1
sensors is based on the capacitive divider principle
Sensor application
KEVCY 24 RE1 & RF1 are compact and very small bushing
type sensors designed to be used in SF6 gas insulated
switchgear type SafeRing and SafePlus.
The external cone type of the sensor is designed according to
the standard EN 50181, Interface C (400 series 630 A,
M16 bolt), and therefore enables connection of all compatible
cable plugs.
Secondary cables
The sensor is equipped with two cables:
Cable for coupling electrode with BNC connector
Current and voltage signal cable with RJ-45 connector for
connection with the IED
The cable connector for connection with the IED is type
RJ-45. The sensor accuracy classes are verified up to the
RJ-45 connector, i.e. considering also its secondary
cable. This cable is intended to be connected directly to
the IED, and subsequently neither burden calculation nor
secondary wiring is needed. Every sensor is therefore
accuracy tested when equipped with its own cable and
connector.
Standard cable length for connection with IED: 2.2 m
Standard cable length for connection with coupling
electrode: 0.45 m
up to 630 A
up to 24 kV
24 kV
50 kV
125 kV
Value
22/V3 kV
22/3V kV
Rated frequency, fn
50/60 Hz
Accuracy class
0.5/3P
10 MOhm
10 000 : 1
1.9/8h
80 A
80A /0.150 V at 50 Hz
80 A/0.180 V at 60 Hz
3mV/Hz
i.e 150 mV at 50 Hz
or 180 mV at 60 Hz
Rated continuous thermal current, Icth
630 A
25 kA / 3 s
63 kA
Rated frequency, fr
50/60 Hz
7.875
100
10 MOhm
Cables
Current and voltage sensing:
Length
2.2 m
Connector
RJ-45 (CAT-6)
Coupling electrode:
Length
0.45 m
Connector
BNC
Cable termination
Cable termination
All bushings are situated in the same height from the floor and
are protected by cable compartment cover. The three drawings below show typical arrangements with cable connectors
for single and double cables.
Interface B
Interface C
Interface D
Standard
400
361
360
369
With window
392
354
353
362
Arc proof
377
338
337
346
Double cables
595
556
555
564
Cable termination
CSE-A 12250
CSE-A 24250
CSE-A 12400
CSE-A 24400
CSE-A 12630
CSE-A 24630
Designation
XLPE/EPR
Conductor cross
mm2
section mm2
Elbow cable connector with capacitive test point, 12kV
Rated current
Bushing type
Weight kg/unit
CSE-A 12250-01
10 - 12
10 - 16
250 A
2.2
CSE-A 12250-02
CSE-A 12400-01
CSE-A 12400-02
13 - 22
13 - 20
18.5 - 30.5
25 - 95
25 - 70
95 - 300
250 A
400 A
400 A
2.2
6.1
6.6
CSE-A 12630-01
13 - 20
25 - 70
630 A
5.1
CSE-A 12630-02
18.5 - 30.5
95 - 300
630 A
5.5
CSE-A 12630-03
30.5 45.0
400 - 630
630 A
7.7
250 A
2.2
CSE-A 24250-02
250 A
2.2
17.0 - 25.5
25 - 95
CSE-A 24400-01
17 - 24
25 - 70
400 A
6.1
CSE-A 24400-02
22.5 - 35.0
95 - 300
400 A
6.6
CSE-A 24630-01
17 - 24
25 - 70
630 A
5.1
CSE-A 24630-02
22.5 - 35.0
95 - 300
630 A
5.5
CSE-A 24630-03
30.5 - 45.0
400 - 630
630 A
7.7
Cable termination 12 kV
Designation
93-EE 605-2/-95
Conductor
XLPE / EPR
[mm2]
[mm]
25-95
12.2-25.0
3M
92-EE 615-2/-120
120
19.8-22.8
3M
92-EE 615-2/-150
150
21.3-24.3
ABB Kabeldon
CSE-A 12250-01
10-16
10.0-12.0
ABB Kabeldon
13.0-22.0
CSE-A 12250-02
25-95
Euromold
158LR/G
16-70
12.6-18.7
Euromold
158LR
70-95
18.4-26.4
nkt cables
EASW 10/250
25-95
12.7-19.2
nkt cables
CE 12-250
95-120
16.9-25.0
Prysmian
FMCE-250
16-95
10.0-21.3
Sdkabel
SEW 12
25-150
12.2-25.0
RSES
16-120
13.5-33.5
Tyco Electronics
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the different
suppliers
12 kV: Separable connectors interface B with earthing shield, Ir = 400 A
Arrester
[mm2]
[mm]
with
arrangement
3M
93-EE 605-4/-95
25-95
15.0-23.5
3M
93-EE 605-4/-240
95-240
21.8-32.6
None
MUT 23
ABB Kabeldon
CSE-A 12400-01
25-70
13.0-20.0
None
None
ABB Kabeldon
CSE-A 12400-02
95-300
18.5-30.5
None
None
Euromold
400LR/G
50-240
12.0-37.5
None
None
Euromold
400TE/G
70-240
12.0-37.5
400CP-SC+400TE/G
156SA +
Double cables
Distance A = 556 mm
Additional equipment
Arc proof
Distance A = 338 mm
Double cables
Distance A = 556 mm
MUT 23
EPR
With window
Distance A = 354 mm
Arc proof
Distance A = 338 mm
Designation
Conductor
Standard
Distance A = 361 mm
With window
Distance A = 354 mm
None
Surge
XLPE /
Manufacturer
Dual cables
Standard
Distance A = 361 mm
surge arrester
400RTPA
nkt cables
CE 24-400
25-300
12.7-34.6
None
None
nkt cables
CB 36-400
25-300
12.7-40.0
CC 12-630
CSA 12
Prysmian
FMCE-400
70-300
18.5-30.4
None
None
Prysmian
FMCT-400
70-300
18.5-30.4
None
None
Sdkabel
SEHDT 12.1
70-300
17.7-30.4
None
None
Sdkabel
SET 12-B
50-300
15.0-32.6
MUT 23
RSES
25-240
12.7-34.6
None
None
Tyco Electronics
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers
Cable termination 12 kV
Arrester with
MUT 23
Double cables
Distance A = 555 mm
arrangement
KU 23.1+93-EE 705-
Arc proof
Distance A = 337 mm
With window
Distance A = 353 mm
15.0-23.5
Surge
Standard
Distance A = 360 mm
[mm]
50-95
Double cables
Distance A = 555 mm
3M
Additional equipment
Dual cables
Arc proof
Distance A = 337 mm
Manufacturer
EPR
With window
Distance A = 353 mm
[mm2]
93-EE 705-6/-95
XLPE /
Conductor
surge arrester
Standard
Distance A = 360 mm
Designation
Single cable +
6/95
3M
93-EE 705-6/-240
120-240
21.8-32.6
93-EE 718-6/150-240
MUT 23
ABB Kabeldon
CSE-A 12630-01
25-70
13.0-20.0
CSEP-A 12630-01
CSAP-A 12
ABB Kabeldon
CSE-A 12630-02
95-300
18.5-30.5
CSEP-A 12630-02
CSAP-A 12
ABB Kabeldon
CSE-A 12630-03
400-630
30.5-45.0
CSEP-A 12630-03
CSAP-A 12
Euromold
400TB/G
25-300
12.0-37.5
400CP-SC+400TB/G
400PB-XSA
Euromold
400LB
25-300
12.0-37.5
400CP-SC+400TB/G
400PB-XSA
X
X
Euromold
400TB-630
25-300
12.0-37.5
300PB-630
300PB-10SA
Euromold
400TB/G
185-630
23.5-56.0
440CP+440TB/G
400PB-XSA
nkt cables
CB12-630
25-300
12.7-34.6
CC 12-630
CSA 12
X
X
X
X
nkt cables
AB12-630
25-300
12.7-34.6
AC 12-630
ASA 12
nkt cables
CC24-630(1250)
400-630
34.0-45.6
CC24-630(1250) or
CSA 12
Prysmian
FMCTs-400
70-300
18.5-30.4
FMPCs-400-12+
CC 12-630
Yes
1)
Yes
1)
FMCTs-400
Prysmian
FMCTs-400/1250
70-300
18.5-42.0
FMPCs-400-12+
FMCTs-400/1250
Sdkabel
SET 12
50-300
15.0-32.6
SEHDK 13.1
MUT 23
Sdkabel
SET 12
50-300
15.0-32.6
KU 23.2/22 +SET 12
MUT 23
Sdkabel
SEHDT 13
400-500
31.3-36.4
None
KU33+MUT 23
RSTI-L
25-300
12.7-34.6
RSTI-CC-L
RSTI-SA
Tyco Electronics
Tyco Electronics
RICS
25-300
Flexible
None
RDA
Tyco Electronics
RSTI-36Lxx
400-630
28.9-45.6
RSTI-66CP-M16+
None
X
X
X
X
RSTI-36Lxx
1)
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers
Cable termination 12 kV
[mm2]
[mm]
arrangement
with
676LRA/G
50-630
16.0-56.0
680CP+676LRA/G
156SA +
Double cables
Distance A = 564 mm
Designation
Euromold
Arc proof
Distance A = 346 mm
Manufacturer
With window
Distance A = 362 mm
Arrester
Dual cables
Standard
Distance A = 369 mm
Surge
Double cables
Distance A = 564 mm
Additional equipment
EPR
Arc proof
Distance A = 346 mm
XLPE /
With window
Distance A = 362 mm
Conductor
Standard
Distance A = 369 mm
surge arrester
676RTPA
Prysmian
FMCTs- 600/1250
120-630
19.7-42.0
FMPCs-600-12 +
None
FMCTs-600/1250
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers
Cable termination 24 kV
Designation
Conductor
XLPE / EPR
[mm2]
[mm]
3M
93-EE 605-2/-95
25-95
12.2-25.0
3M
93-EE 615-2/-120
120
24.0-27.0
3M
93-EE 615-2/-150
150
25.5-28.5
ABB Kabeldon
CSE-A 24250-01
10-16
13.0-22.0
ABB Kabeldon
CSE-A 24250-02
25-95
17.0-25.5
K158LR/G
16-25
12.6-18.7
Euromold
Euromold
K158LR
25-95
18.4-26.4
nkt cables
EASW 20/250
25-95
17.0-25.0
nkt cables
CE 24-250
25-120
16.9-25.0
Prysmian
FMCE-250
35-95
18.6-26.0
Sdkabel
SEW 24
25-95
17.3-25.0
RSES
16-120
13.5-33.5
Tyco Electronics
15.0-23.5
None
MUT 23
3M
93-EE 605-4/-240
95-240
21.8-32.6
None
MUT 23
ABB Kabeldon
CSE-A 24400-01
25-70
17.0-24.0
None
None
ABB Kabeldon
CSE-A 24400-02
95-300
22.5-35.0
None
None
[mm2]
[mm]
Arrester
dual cable
with
arrangement
Euromold
K400LR/G
25-240
12.0-37.5
None
None
Euromold
K400TE/G
25-240
12.0-37.5
K400CP-SC + K400TE/G
156SA +
Double cables
Distance A = 556 mm
25-95
Designation
Arc proof
Distance A = 338 mm
Double cables
Distance A = 556 mm
93-EE 605-4/-95
Manufacturer
EPR
With window
Distance A = 354 mm
Arc proof
Distance A = 338 mm
3M
Surge
XLPE /
Conductor
Standard
Distance A = 361 mm
With window
Distance A = 354 mm
Dual cables
Standard
Distance A = 361 mm
surge arrester
K400RTPA
nkt cables
CE 24-400
25-300
12.7-34.6
None
None
nkt cables
CB 36-400
25-300
12.7-40.0
CC 24-630
CSA 24
Prysmian
FMCE-400
35-300
18.5-35.3
None
None
Prysmian
FMCT-400
35-300
18.5-35.3
None
None
Sdkabel
SEHDT 22.1
25-240
18.0-32.6
None
None
Sdkabel
SET 24-B
25-240
15.0-32.6
MUT 23
RSES
25-240
12.7-34.6
None
None
Tyco Electronics
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers.
Cable termination 24 kV
Arrester with
Arc proof
Distance A = 337 mm
Double cables
Distance A = 555 mm
15.0-23.5
KU 23.1+93-EE 705-6/-95
MUT 23
3M
93-EE 705-6/-240
95-240
21.8-32.6
93-EE 718-6/150-240
MUT 23
X
X
dual cable
Surge
ABB Kabeldon
CSE-A 24630-01
25-70
17.0-24.0
CSEP-A 24630-01
CSAP-A 24
ABB Kabeldon
CSE-A 24630-02
95-300
22.5-35.0
CSEP-A 24630-02
CSAP-A 24
ABB Kabeldon
CSE-A 24630-03
400-630
30.5-45.0
CSEP-A 24630-03
CSAP-A 24
Euromold
K400TB/G
25-300
12.0-37.5
K400CP-SC+K400TB/G
400PB-XSA
Euromold
K400LB
25-300
12.0-37.5
K400CP-SC+K400TB/G
400PB-XSA
Euromold
K430TB-630
25-300
12.0-37.5
K300PB-630
300PB-10SA
Euromold
K440TB/G
185-630
23.5-56.0
K440CP+K440TB/G
400PB-XSA
nkt cables
CB24-630
25-300
12.7-34.6
CC 24-630
nkt cables
CC24-630(1250)
400-630
34.0-45.6
CC24-630(1250) or
Prysmian
FMCTs-400
35-300
18.5-35.3
FMPCs-400-24 +
CSA 24
CSA 24
Double cables
Distance A = 555 mm
arrangement
50-95
EPR
Arc proof
Distance A = 337 mm
[mm]
93-EE 705-6/-95
Manufacturer
XLPE /
With window
Distance A = 353 mm
[mm2]
3M
Conductor
Standard
Distance A = 360 mm
Designation
With window
Distance A = 353 mm
Dual cables
Standard
Distance A = 360 mm
surge arrester
X
X
X
X
X
CC24-630
Yes
1)
Yes
1)
FMCTs-400
Prysmian
FMCTs-400/1250
35-630
18.5-47.1
FMPCs-400-24 +
FMCTs-400/1250
Sdkabel
SET 24
25-240
15.0-32.6
SEHDK 23.1
MUT 23
Sdkabel
SET 24
25-240
15.0-32.6
KU 23.2/23 + SET 24
MUT 23
Sdkabel
SEHDT 23.1
300
31.9-34.6
MUT 23
Sdkabel
SEHDT 23
300-500
31.9-40.6
None
KU33+ MUT 23
Tyco Electronics
RSTI-L
25-300
12.7-34.6
RSTI-CC-L
RSTI-SA
Tyco Electronics
RSTI-56Lxx
400-630
34.0-45.6
RSTI-66CP-M16 +
None
X
X
X
X
RSTI-56Lxx
1)
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers.
Cable termination 24 kV
[mm2]
[mm]
arrangement
K676LRA/G
35-630
16.0-56.0
K680CP+K676LRA/G
with
156SA+
Double cables
Distance A = 564 mm
Designation
Euromold
Arc proof
Distance A = 346 mm
Manufacturer
With window
Distance A = 362 mm
Arrester
Standard
Distance A = 369 mm
Surge
Dual cables
Double cables
Distance A = 564 mm
Additional equipment
EPR
Arc proof
Distance A = 346 mm
XLPE /
With window
Distance A = 362 mm
Conductor
Standard
Distance A = 369 mm
surge arrester
K676RTPA
Prysmian
FMCTs- 600/1250
50-630
19.7-42.0
FMPCs-600-24 +
None
FMCTs-600/1250
Separable connectors without earthing shield are not recommended.
For dynamic and thermal short-circuit currents, please compare the values
expected in your nework with the rated values of the connector from the
different suppliers.
VPIS
PCM
Special features
No external power supply required.
Voltage indication by flashing LED.
Fully insulated system (IP 68) with cast resin.
Function test 230 V AC or test-equipment MAXTEST - S
Technical data PCM
VIM 3
Rated frequency
50 Hz
1,4 m
Operating temperature
-25 - +55 oC
43 x 22 x 20 mm
Enclosure protection
IP 68
Weight
40 g
VIM 1
Technical data VIM 1 and VIM 3
Rated frequency
50 / 60 Hz
Treshold voltage U
70 - 90V
Treshold current I
1,62 - 2,5 uA
74 - 88 pF
36 - 43,2 MOhm
Operating temperature
-25 - +55 oC
Enclosure protection
IP 68
43 x 22 x 30 mm
144 x 28 x 30 mm
Weight VIM 1
40 g
Weight VIM 3
110 g
Short-circuit indicator
Response time
40 ms or 80 ms
Timed reset
after passage of 1, 2, 4 or 8 h
Temperature range
Energy supply
Relay contact
Timed reset
after passage of 1, 2, 4 or 8 h
Temperature range
Energy supply
internal:by long-life lithium cell, life expectancy 20 years, total flashing time >1000h; external:by 12-60VDC (optional feature)
Relay contact
Short-circuit indicator
50 A - 2000 A / 20 A - 1000 A
40 ms < t < 60 ms
Time reset
1 min - 24 h
Temperature range
Energy supply
Relay contact
100 ms
Timed reset
after passage of 2 or 4 h
12 - 60 V AC/DC
Temperature range
Energy supply
Relay contact
B
1)
B
2)
B
4)
2) First you have to operate the load break switch in switchgear A to open position.
Then it will be possible to operate the key interlock and turn
the key which extends the locking bolt. This will prevent the
access to the operating shaft of the load break switch.
Then withdraw the key and insert it into the identical key interlock on the earthing switch of switchgear B.
3) When the key is inserted, you will be able to operate the
key interlock and turn the key which will withdraw the extended locking bolt.
Then there will be access to operate the earthing switch to
closed position. As long as the earthing switch is in closed
position, the key will be captured and make it impossible to
close the load break switch in switchgear A.
3)
Packages
All standard packages include:
Power supply backup source for automation devices
(24V DC batteries and battery charger)
Wire (Ethernet) and/or wireless (GSM/GPRS) communi-
cation interfaces (SIM card is not part of delivery)
IEC 60870-5-104 host (slave) communication protocol
Three levels of automation packages are defined below.
There are additional options which can be selected for each
package.
Main selections and their options are (*) default values)
1. Automation level
Remote Monitoring package
Remote Control package* )
Remote Measurement package
2.
3.
4.
7.
Options description
1. Automation level
The three automation levels (packages) are described below.
Remote Monitoring
This package provides remote monitoring of:
The position of load break switches in C modules
(-> grid topology supervision)
Fault passage indicator fault signalization
(-> fast fault localization, reduced outage time, efficient use
of manpower)
Faults in the transformer feeders
Remote Control
This package includes the features from the Remote
Monitoring package and in addition provides:
Remote control of load break switches in C modules
(-> fast fault isolation, fast restoration of healthy part of the
MV network , operator safety)
Remote Measurement
This package includes the features from the Remote Control
package and in addition provides:
MV network analog data values such as: currents,
voltages, frequency, power, energy, load flow direction etc.
(-> improved notification of overloaded equipment, better
maintenance planning, improved power quality).
Note: There are spare inputs (1 5 pieces) which can be used
for additional customer specified digital/binary signals such
as: SF 6 gas pressure signal, low voltage fuses tripped signal,
transformer overheating signal, etc. The number of spare inputs depends on configuration of Ring Main Unit (CCF, CCCF
etc.) and on the type of fault detection for the MV network.
2. Feeder automation device
Compact Feeder Automation devices secure remote
monitoring and control of the secondary substations in the
distribution network. It enables the network control centers to
monitor and control the field devices over the different
communication infrastructure.
REC603
The Wireless Controller REC603 is a compact, solution based
device for the remote control and monitoring of secondary
substations such as network disconnectors, load break
switches and Ring Main Units in distribution networks.
REC603 enables the network control system to monitor and
control the field devices over the public communication infrastructure (GPRS). The Wireless Controller REC603 utilizes the
built-in GPRS for reliable and secure end-to-end communication providing remote monitoring and control of up to three
objects.
RTU560CIG10
The RTU560 DIN rail provides advanced functionality and
makes it the perfect fit for existing and future Grid Automation solutions. The compact housing with the possibility to
integrate hardwired information fulfills complex requirements
and space restrictions at the same time.
REC615
REC615 is a dedicated grid automation IED designed for
remote control and monitoring, protection, fault indication,
power quality analyzing and automation in medium-voltage
secondary distribution systems, including networks with distributed power generation, with secondary equipment such as
medium-voltage disconnectors, switches and ring-main units.
3. MV network fault types
Different signals from Fault Passage Indicators can be
transmitted to the control centers. These are selected based
on type of the MV network (isolated neutral, compensated
neutral, high resistance earthing, low resistance earthing or
solidly earthing).
Available options are:
OC and EF directional
With this selection, two different types of events can be
transferred to the remote control centers:
Fault in forward direction (does not differentiate over-
current and earth fault)
Fault in backward direction (does not differentiate over-
current and earth fault)
OC and EF non directional
With this selection, two different types of events can be
transferred to the remote control centers:
Over-current fault (does not differentiate fault direction)
Earth fault (does not differentiate fault direction)
Fault
With this selection, one type of event can be transferred to
the remote control centers:
Fault (does not differentiate over-current and earth fault nor
fault direction)
Product catalogue | Smart Grid applications 71
Dimensions
371
696
SafePlus
1021
SafeRing
SafeRing
79
107
107
107
107
107
325
1346
595
325
1671
SafeRing
SafePlus
107
Dimensions
696
REF541
SAFEPLUS
SafePlus
VD4
VD4
150
244
150
152
595
CB modul
696
802
56
SafePlus
1806
1336
Dimensions
260
696
124
SafeRing
1460
280
1021
110
20
REF541
470
SafePlus
1806
30
Dimensions
1466
1561
430
280
315
1591
1651
External busbars
Busbar cover
Dimensions
56
195
33
660
1626
1786
1045
885
Dimensions
100
14
751
81/87 *)
1336
1248
8/14 *)
595
Distance between two units which are connected to each
other by means of external busbars
475
138
*) Top extension - 8 mm / 81 mm
Side extension - 14 mm / 87 mm
138
238
100
37
Unit
238 207
284
500
15 (6x)
40
1-way
281
371
2-way
606
696
3-way
931
1021
4-way
1256
1346
5-way
1581
1671
475 537
251
138
79
107
79
107
107
107
325
325
B
3-way unit with cable bushings Interface C (400 series bolted) for module
1 and 2 and cable bushings Interface A (200 series plug-in) for module 3
Technical data
IEC 62271-1
IEC 62271-100
IEC 62271-102
High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches
IEC 62271-105
High-voltage switchgear and controlgear - Part 105: Alternating current switch-fuse combinations
IEC 62271-200
High-voltage switchgear and controlgear - Part 200: A.C. metal-enclosed switchgear and controlgear for rated voltages above
1 kV and up to and including 52 kV
IEC 60265-1
High-voltage switches- Part 1: Switches for rated voltages above 1 kV and less than 52 kV
IEC 60529
Technical data
Rated voltage
Ur
kV
12
15
17,5
24
Ud
kV
kV
kV
kV
28
32
95
110
38
45
95
110
38
45
95
110
50
60
125
145
Rated frequency
fr
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
2)
Up
Hz
50/60
50/60
50/60
50/60
Ir
630
630
630
630
Ir
630
630
630
Ir
200
Ir
200
200
200
200
Ik
kA
21
21
16
16
tk
Ip
kA
52,5
52,5
40
40
I1
n
630
630
630
630
100
100
100
100
I2a
630
630
630
630
I3
20
20
20
20
I4c
135
135
135
135
I6a
200
150
150
150
I6b
A
kA
115
52,5
87
52,5
87
40
87
40
I1
n
200
200
200
200
100
100
100
100
I3
20
20
20
20
Isc
kA
21
21
16
16
Ima
kA
12,5
12,5
12,5
12,5
Ik
kA
tk
I1
Ima
1)
3)
200
1)
3)
200
630
1)
3)
200
1)
3)
200
200
200
200
Isc
kA
16
16
16
16
Ic
31,5
31,5
31,5
31,5
Ik
kA
16
16
16
16
Ima
kA
40
40
40
40
Pre
MPa
0,04
0,04
0,04
0,04
4)
33
Maximum value
+40
+40
+40
+40
34
+35
+35
+35
+35
35
Minimum value
-25
-25
-25
-25
36
1500
1500
1500
1500
37
Relative humidity
max 95%
max 95%
max 95%
max 95%
5)
1)
2)
3)
4)
5)
Technical data
Rated voltage
3
4
Rated frequency
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
2)
kV
12
15
17,5
24
kV
kV
kV
kV
28
32
95
110
38
45
95
110
38
45
95
110
50
60
125
145
fr
50/60
Ur
Ud
Up
Hz
50/60
50/60
50/60
Ir
630
630
630
630
Ir
1250
1250
1250
1250
Ir
Ir
Ir
200 / 630
Ik
kA
25 / 21
tk
Ip
kA
I1
n
I 2a
630
200
630
200
1)
3)
1)
200 / 630
21
3)
630
200
1)
200 / 630
21
3)
630
200
1)
200 / 630
21
3)
1/3
62,5 / 52,5
52,5
52,5
52,5
630
630
630
630
100
100
100
100
630
630
630
630
I3
20
20
20
20
I 4c
135
135
135
135
I 6a
200
150
150
150
I 6b
115
87
87
87
I ma
kA
62,5
52,5
50
50
I1
n
I3
200
200
200
200
100
100
100
100
20
20
20
20
Isc
kA
25
21
20
20
I ma
kA
12,5
12,5
12,5
12,5
Ik
kA
tk
I1
200 / 630
200 / 630
200 / 630
200 / 630
I sc
kA
21
21
16
16
Ic
31,5
31,5
31,5
31,5
Ik
kA
21
21
16
16
I ma
kA
52,5
52,5
40
40
P re
MPa
0,04
0,04
0,04
0,04
4)
34
Maximum value
+40
+40
+40
+40
35
+35
+35
+35
+35
36
Minimum value
-25
-25
-25
-25
37
1500
1500
1500
1500
38
Relative humidity
max 95%
max 95%
max 95%
max 95%
5)
1)
2)
3)
4)
5)
Technical data
Number of phases
Yes
Yes
Insulating gas
SF6
0,1%
30 years
10
11
12
Busbars
240 mm2 Cu
13
100 mm2 Cu
14
M10
Height mm
Depth mm
15
2-way unit
1336
765
696
16
3-way unit
1336
765
1021
17
4-way unit
1336
765
1346
Width mm
CSG (2, 3 and 4 way units as RMU) with additional height for
optional low voltage compartment (470 mm)
18
1-way unit
1336
765
371
19
20
5-way unit
Distance between units when external extension is used
1336
765
8 mm
1671
21
14 mm
Weight table
Maximum weights for standard SafeRing
2-way DeV
300 kg
2-way DeF
300 kg
3-way CCV
450 kg
3-way CCF
450 kg
4-way CCCV
600 kg
4-way CCCF
600 kg
4-way CCVV
600 kg
4-way CCFF
600 kg
3-way CCC
450 kg
4-way CCCC
600 kg
SafePlus
Standard 1-way
150 kg
as for SafeRing
5-way
750 kg
M - metering module
250 kg
Technical data
separate handle
O 3 min CO 3 min CO
O 0,3 s CO 3 min CO
approx. 75 ms
approx. 40 60 ms
1000 CO
1000 CO
2000 CO
10
30000 CO
11
13
100
Degree of protection:
14
IP 67
15
IP 2XC
16
Cable covers
IP 3X
17
IP 67
Colours:
18
Front covers
RAL 7035
19
RAL 7035
Standard dimensions
125 A
63 A
107 mm
54,5 mm
120 mm
Elbow or T-connector
SafeRing/SafePlus V module
2000
1000
No. of operations
No. of operations
Technical data
SafeRing/SafePlus C module
10000
800
8000
600
6000
400
4000
200
2000
100
1000
80
800
60
600
40
400
20
200
10
100
80
60
40
12 kV
20
2
24 kV
1
10
8 10 16 21
30 40 (kA)
Breaking current
8 10
8 10 3
3 4 (A)
Breaking current
Environmental Certification
Environmetal Certification
Life expectancy of product
The product is developed in compliance with the requirements
denoted by IEC 298. The design incorporates a life span under
indoor service conditions exceeding 30 years (IEC 298 annex
GG).
The switchgear is gas-tight with an expected diffusion rate of
less than 0.1 % per annum. Referring to the reference-pressure of 1.4 bar, the switchgear will maintain gas-tightness and
a gas-pressure better than 1.3 bar* throughout its designed
life span. *) at 20oC.
Recycling capability
Weight (kg)
Raw Material
% of total
weight
Recycle
Iron
132,80
42,53
Yes
Stainless steel
83,20
24,93
Yes
Copper
43,98
14,09
Yes
Brass
2,30
0,74
Yes
Aluminium
8,55
2,74
Yes
Zinc
3,90
1,25
Yes
Silver
0,075
0,024
Yes
Thermoplastic
5,07
1,63
Yes
26,75
8,35
Yes
Rubber
1,35
0,42
Yes
Dielectric coil
0,21
0,066
Yes
SF6 gas
3,24
1,04
Yes
311,44
97,25
Total recycleables
Not specified*)
Total weight
**)
9,00
320,00
*)
100 %
Packing foil
0,20
Yes
Wooden pallet
21,50
Yes
**)All figures are collected from CCF 3-way unit with arc suppressor
End-of-life
ABB is committed to the protection of the environment and
adhere to ISO 14001 standards. It is our obligation to facilitate
end-of-life recycling for our products.
There exist no explicit requirements for how to handle discarded switchgears at end-of-life.
ABB AS
Power Products Division
Medium Voltage
P.O.Box 108, Sentrum
N-3701 Skien, Norway
Phone: +47 35 58 20 00
Fax:
+47 35 52 41 08
www.abb.com
Contact us