Manual Scu m520s v1.1
Manual Scu m520s v1.1
User Manual
Version
Revision date
BOM
V1.1
July 14, 2010
31012224
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Contents
Chapter 1 Overview ............................................................................................................................................................ 1
1.1 Appearance .......................................................................................................................................................... 1
1.2 Main Functions...................................................................................................................................................... 1
1.2.1 Background Communication...................................................................................................................... 1
1.2.2 Multiple Monitoring Functions .................................................................................................................... 1
1.2.3 Setting Dry Contact Alarm Types .............................................................................................................. 2
1.2.4 Different Authorities Protected By Different Password Levels ................................................................... 2
Chapter 2 Connection ......................................................................................................................................................... 3
2.1 Connecting Signal Terminals ................................................................................................................................ 3
2.2 Connecting Dry Contacts ...................................................................................................................................... 3
Chapter 3 Use Of Monitoring Module .................................................................................................................................. 5
3.1 Front Panel ........................................................................................................................................................... 5
3.2 Main LCD Pages ................................................................................................................................................... 5
3.2.1 System Information Page .......................................................................................................................... 5
3.2.2 Enter Password Page ................................................................................................................................ 6
3.2.3 MAINMENU Page ...................................................................................................................................... 6
3.2.4 STATUS Page ........................................................................................................................................... 7
3.2.5 Settings Page ............................................................................................................................................ 7
3.2.6 Maintenance Page ..................................................................................................................................... 7
3.2.7 Energy Saving Page .................................................................................................................................. 8
3.2.8 Fast Settings Page .................................................................................................................................... 8
3.3 Querying System Main Information ....................................................................................................................... 8
3.4 Querying Rectifier Status .................................................................................................................................... 10
3.5 Querying Alarms ................................................................................................................................................. 10
3.5.1 Querying Active Alarm ............................................................................................................................. 10
3.5.2 Querying History Alarm............................................................................................................................ 12
3.6 Maintenance ....................................................................................................................................................... 12
3.7 Setting System Parameters ................................................................................................................................ 13
3.7.1 Alarm Settings ......................................................................................................................................... 13
3.7.2 Battery Settings ....................................................................................................................................... 16
3.7.3 AC Settings .............................................................................................................................................. 20
3.7.4 DC Settings ............................................................................................................................................. 20
3.7.5 Rectifier Settings ..................................................................................................................................... 21
3.7.6 System Settings ....................................................................................................................................... 22
3.7.7 Communication Settings .......................................................................................................................... 23
3.8 Setting Energy Saving ........................................................................................................................................ 23
3.9 Fast Settings ....................................................................................................................................................... 24
Chapter 1 Overview
Chapter 1 Overview
This chapter introduces the appearance and main functions of the M520S monitoring module (monitoring module for
short).
1.1 Appearance
The appearance of the monitoring module is shown in Figure 1-1.
Figure 1-1
User Manual
Chapter 1 Overview
Remote acquiring analog signals: The monitoring computer can obtain the analog signal of the system in real time
through the monitoring module.
Remote acquiring digital signals: The monitoring computer can obtain the digital signal of the system in real time
through the monitoring module.
Remote control function: The monitoring computer can realize the rectifier on/off, system boost charge/float charge,
system control mode changeover, alarm silence and start/stop battery test.
Operation authority
All maintenance operation, without resetting system, resetting password and
changing system type, modifying password and controling alarm volume pages
All the users authorities, resetting system, resetting password and changing system
type pages, without modifying password and controling alarm volume pages
All the engineers authorities, resetting system, resetting password and changing
system type and modifying password pages, browsing serial No., version and DI
status of the monitoring module
User Manual
Default password
1
2
640275
Chapter 2
Connection
Chapter 2 Connection
This chapter introduces the connection description of the monitoring module.
J424
J412
J411
J408
J409
J407
J416
J427
J426
D2
D1
J419 J422
J433 J404
J403
J402
J420
32
31
Figure 2-1
J421
5
2
1
J3
The definitions of the terminals and connection descriptions are given in Table 2-1. Connect signal cables according
to Table 2-1.
Table 2-1
Terminal
Definition
Connection description
J402 ~ J404
J417
J418
J420
RS232 port
J426
J427
J430
DO8
DO6
DO4
DO2
DO7
DO5
DO3
DO1
Figure 2-2
User Manual
Chapter 2
Connection
Connection method:
Peel the signal cables and insert it into the specialized connectors, fasten the screws on the terminals and insert the
connectors into J402 ~ J404 terminals.
The functions of dry contacts are given in Table 2-2.
Table 2-2
Terminal
J402_1 (DO1)
Function
Terminal
Function
Mains failure
J402_2 (DO2)
DC over/ under-voltage
Reserved
Rectifier failure
J404_1 (DO7)
Reserved
BLVD
J404_2 (DO8)
Reserved
Note:
The above functions are default settings. You can change them through the monitoring module
User Manual
LLVD
Chapter 3
Functional keys
ESC
Alarm indicator
Critical alarm indicator
ENT
Figure 3-1
Color
Normal state
Fault state
Green
On
Off
Alarm indicator
Yellow
Off
On
Red
Off
On
Run indicator
Fault cause
The monitoring module uses a 128 64 LCD, and a keypad with six keys (listed in Table 3-2). The interface language
is Chinese/English optional.
Table 3-2
Key
Function
ESC
Return to the upper level menu. When the audible alarm tone is generated, press ESC to cancel the alert
ENT
Enter the main menu or confirm the menu operation. When changing or inputting parameters, press ENT to get
into editing state. After any change is made, press ENT to validate the change
and
Shift among parallel menus. For a character string, these two keys can be used to shift among different options
and
Change values at a value setting interface. For a character string, these two keys can move the cursor left or right
User Manual
Chapter 3
Figure 3-2
Normal
Figure 3-3
1. To input the password, use or to modify numbers, and use or to move the cursor. After the input, press
ENT to confirm.
2. If the password is incorrect, the system will prompt Password incorrect.
3. Press ESC to return to MAINMENU page.
4. The system has three different password levels: user level (default: 1), engineer level (default: 2) and administrator
level (default: 640275).
Once you enter the correct password, you never need to enter the password again during the operation. While the
interval time for adjacent operation is more than four minutes, the system will prompt you to input the password again.
If you want to enter senior setting pages, you need to wait four minutes and cannot do any operation during waiting,
and then the system will enter the senior setting pages after you input the higher level password. If the two level
passwords are the same, the system will display the senior menus after you enter the password.
Figure 3-4
Energy Saving
Fast settings
MAINMENU page
1. At any system information page, press ENT to enter the MAINMENU page.
2. At any sub-menu of the MAINMENU page, press ESC repeatedly to return to the higher-level menu, and ultimately
to the MAINMENU page.
User Manual
Chapter 3
STATUS page
1. At the MAINMENU page, press or to select the STATUS menu, and press ENT to confirm.
2. At any sub-menu of the STATUS page, press ESC repeatedly to return to the higher-level menu, and ultimately to
STATUS page.
Settings
Alarm Setting
Bat. Settings
AC Settings
Figure 3-6
DC Settings
Rect Settings
Sys Settings
Comm Settings
Settings page
1. At the MAINMENU page, press or to select the Settings menu, and press ENT to confirm. System will then
prompt you to input the password.
2. Input the correct password and press ENT to enter the Settings page. Press or to scroll to the operation page
you need.
Users with different password level have different authorities. See Table 3-3.
Table 3-3
Level
Authority
Default password
User
Engineer
Users authority, plus resetting system, resetting password and modifying system type
Administrator
Engineers authority, plus modifying password of all levels, controling alarm volume,
browsing system parameters configured by host
640275
Once you enter the correct password, you never need to enter the password again during the operation. While the
interval time for adjacent operation is more than four minutes, the system will prompt you to input the password again.
If you want to enter senior setting pages, you need to wait four minutes and cannot do any operation during waiting,
and then the system will enter the senior setting pages after you input the higher level password. If the two level
passwords are the same, the system will display the senior menus after you enter the password.
FC
ReConnect
DisConn
Figure 3-7
RectTrim:
53.5V
RectLimit:
121%
Maintenance page
User Manual
Chapter 3
1. At the MAINMENU page, press or to select the Maintenance menu, and press ENT to confirm. The system
will prompt you to input the password when the battery management mode is set to Manual (see 3.7.2 Battery
Settings).
2. Input the correct password and press ENT to enter the Maintenance page. Press or to scroll to the operation
page you need.
Figure 3-8
1. At the MAINMENU page, press or to select Energy Saving, and press ENT to confirm. The system will
prompt you to input the password.
2. Input the correct password and press ENT to enter the Energy Saving page. Press or to select the
parameters you need.
Figure 3-9
1. At the MAINMENU page, press or to select Fast Settings, and press ENT to confirm. The system will prompt
you to input the password.
2. Input the correct password and press ENT to enter the Fast Settings page. Press or to select the parameters
you need.
Figure 3-10
Normal
The date and time are displayed at the interval of 2s. System operation state contains No Alarm and Alarm. Battery
management mode includes Auto and Manual. Battery state includes Float charge, Temp Comp, Boost charge, Cyclic
Boost, Batt. Test, ShortTest and TimeTest.
M520S Monitoring Module
User Manual
Chapter 3
Figure 3-11
The first line displays the save state. The second line displays the percentage between the output power and rated
power of the rectifier. The lower line displays the BC prompt information, they will be different for different states of
the system, including:
1. Prompt the time of the next Cyclic BC according to the battery state.
2. If BC is going on or prohibited, --- will be prompted.
Battery information
At the first system information page, press to query the battery information, as shown in Figure 3-12.
Batt1:
0A
Remain: 100%
Batt2:
0A
Remain: 100%
Figure 3-12
As shown in the preceding page, they represent respectively the current of the battery that battery shunt 1 and shunt
2 is connected to. Because the Shunt Coeff of battery group is set to No, the battery information page is not
connected and no actual capacity will be displayed.
The remaining battery capacity can be displayed in the mode of percentage, remaining Ah or remaining time. The
default is the percentage.
AC information
At the battery information page, press to display AC information page, as shown in the following page. The system
will display AC voltage of the A, B and C phases, as shown in Figure 3-13.
AC 1 Volt
Phase A:
Phase B:
Phase C:
0V
0V
0V
Figure 3-13
AC 2 Volt
Phase A:
Phase B:
Phase C:
0V
0V
0V
AC information page
If the temperature sensor is not connected or is faulty, the system will prompt ---. Meanwhile, alarm information page
will display Temperature sensor not connected or Temperature sensor failures. If the monitoring module bans BC and
no temperature sensor is configured, this page will not be displayed.
User Manual
10
Chapter 3
Note
If the monitoring module has not detected rectifiers, you cannot query the rectifier information.
The rectifier information includes the rectifier serial No., voltage, current, current limit, AC input voltage, mains
situation, rectifier power limit and temperature power limit.
At the STATUS page (see Figure 3-5), press or to select the Rectifiers sub-menu, as shown in Figure 3-15.
Press ENT to confirm.
Rect 1:
ID: 01060700584
Out Volt: 53.5V
Out Curr: 38.5A
Figure 3-15
In Volt:
220V
AC State:
On
DC State:
On
AC Derated:
N
Temp Derated: Y
The information of every rectifier is displayed in three pages. Press to scroll to the next page, or to return to the
last.
At most 24 pieces of rectifier information can be displayed. When selecting one rectifier, the green indicator of the
corresponding rectifier will blink. If the rectifier communication is interrupted, the information will be displayed in high
light.
The preceding page includes alarm serial No., alarm name, alarm level and time. The alarm raising time determines
the sequence it is displayed, with the latest alarm displayed first. Use or to view all active alarms.
While querying rectifier alarms, press to view rectifier ID, and the Run indicator of the corresponding rectifier will
blink.
In the case of battery test alarm or maintenance time alarm, press to display the prompt information, then press
ENT to confirm that the alarm is cleared. The active alarms in the monitoring module are given in Table 3-4.
User Manual
Chapter 3
No.
1
2
3
4
5
6
7
8
Alarm type
Rectifier
Alarm
Rect AC Fail
Rect Over temp
Rect Fault
Rect Protect
Rect Fan Fails
Rect Derated
Rect Not Respond
Rectifier Lost
Multi-Rect Alarm
1
2
3
4
5
6
AC SPD Fault
Digital Alarm
AC High
AC LOW
AC PH Fail
Mains Failure
DC Volt High+ , DC
Volt High
DC Volt Low
DC Volt LowBatt Over temp
Batt Temp High
Alarm
Batt Temp Low
Alarm
Ambient Temp
High Alarm
Ambient Temp Low
Alarm
T1 No Probe
T2 No Probe
Sensor 1 Fault
Sensor 2 Fault
LVD
BLVD
Load Fuse Alarm 1
Load Fuse Alarm 2
Load Fuse Alarm 3
Load Fuse Alarm 4
Load Fuse Alarm 5
Load Fuse Alarm 6
Load Fuse Alarm 7
Load Fuse Alarm 8
Load Fuse Alarm 9
Aux Load Fails
Batt Fuse Alarm 1
Batt Fuse Alarm 2
Batt Fuse Alarm 3
Batt Fuse Alarm 4
Batt 1 Curr High
Non Float Status
Batt Discharge
Load share Alarm
Batt Test Fail
Short Test Fail
Save Power
Save Power Fault
AC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
1
2
3
4
5
6
7
DC
Battery
management
Description
Press to confirm the alarms. If yes, the interfered rectifiers are reduced, you
can clear this alarm manually
AC SPD fault is the alarm of Digital 1
Press to prompt you to clear this alarm
-
User Manual
11
12
Chapter 3
No.
1
2
3
4
5
Monitoring
self-detect
Alarm
SelfDetect Fail
Manual Mode
Volt Discrepancy
Maintain Alarm
Alarm Block
Description
-
If the alarm is a rectifier related alarm, the first line in Figure 3-17 will display the latter 10 number of the rectifier ID.
The history alarms of the monitoring module are stored in cyclic order. Up to 200 alarms will be recorded. Above that,
the earliest alarm will be cleared automatically.
2. Use or to view other history alarms.
3. At any History Alarm page, press ESC repeatedly to return to the first system information page.
3.6 Maintenance
Note
FC
ReConnect
DisConn
RectTrim: 53.5V
RectLimit: 121%
Rect 1: DC On
Rect 1: AC On
Figure 3-18
Rect 1: Reset
Maintenance page
4. Use or to select the needed action. After the input, press ENT to confirm or ESC to cancel.
1) Start: The options include FC, BC and Test. Press or to select the needed action. If there is AC power off
alarm, or the busbar voltage is too low, the BC and battery test control will not be executed by the system. No battery
test control can be conducted when the rectifier communication is interrupted. Finally, after the battery test, the
battery management mode will be changed from Manual to Auto automatically.
2) Battery: The options include Reconnect and Disconnect. If there is a battery alarm, the battery operations will be
invalid.
3) Load: The options include Reconnect and Disconnect.
4) RectTrim: Range: 42V ~ 58V. If the value of this parameter cannot exceed the over-voltage alarm point, otherwise,
the parameter will be invalid.
User Manual
Chapter 3
13
Figure 3-19
Figure 3-20
Press or to move the cursor to the needed option. Press or to select the corresponding content and press
ENT to confirm.
The monitoring module alarms are classified into four types: critical alarm, major alarm, observation and no alarm.
Critical alarm, major alarm: These two types of alarms have strong impacts on the system performance. Whenever
these alarms are generated, you are supposed to handle them immediately. The alarm indicators will be on and
audible indication will be given.
Observation: When this type of alarm is raised, the system maintains normal output for a while. If the alarm occurs
during watch time, it should be handled immediately. If the alarm occurs during non- watch- time, handle it during
watch time. The alarm indicators will be on when observation alarm occurs.
No alarm: The system will not generate a visible or audible indication.
User Manual
14
Chapter 3
The alarm default value of the monitoring module is listed in Table 3-5.
Table 3-5
No.
Alarm
SPD Fault
DI
AC Voltage High
AC Voltage Low
Mains Failure
DC Volt High
DC Volt Low
DC Volt Under
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
SPD failure
Defined the alarm name by user, at most 10 letters. In
this system, eight DIs can be defined. Among which, the
first DI is defined as SPD Fault, the remained seven DI
can be defined freely
AC input voltage higher than the setting of AC input overvoltage alarm point
AC input voltage lower than the setting of AC input
under- voltage alarm point
All the AC input voltages from the rectifier are less than
80V
DC output voltage higher than the setting of DC output
over- voltage alarm point
DC output voltage lower than the setting of DC output
low- voltage alarm point
DC output voltage lower than the setting of DC output
under- voltage alarm point
Major
Major
Major
Critical
Major
Major
No alarm
Critical
Observation
Observation
Observation
Observation
User Manual
None
None
No alarm
Related
parameter
Major
Major
Major
Major
Major
Major
Major
None
None
1
2
2
None
None
None
Over- voltage
alarm
Low- voltage
alarm
Over- voltage
alarm
Low- voltage
alarm
Under- voltage
alarm
Over Temp
alarm point
High Temp
alarm point
None
Low Temp
alarm point
None
High Temp
alarm point
None
Low Temp
alarm point
-
None
None
None
None
5
4
None
LLVD enabled
BLVD enabled
-
Major
None
Major
None
Observation
None
Observation
None
Critical
Observation
Major
Observation
Critical
Observation
Critical
Major
No alarm
No alarm
No alarm
No alarm
Over (over
current point)
Over (over
current point)
-
3
3
3
3
3
3
3
None
None
None
None
None
Chapter 3
No.
38
39
40
41
42
43
44
Alarm
Description
Related
parameter
15
3
No alarm
Observation
Observation
None
None
None
Observation
Observation
Major
No alarm
None
None
None
Figure 3-21
Voice Sign option: open/ off/ 3min/ 10min/ 1h/ 4h. You can set according to you requirement.
Clear: His Alarm option: His Alarm, Rect Lost, TestFail, ShortTest, ESaveFail and Maintain. Press ENT to clear the
saved alarm information in the monitoring module.
DI settings
At the Alarm Settings page, press or to select DI Settings menu. Then press ENT to enter the DI Settings page,
as shown in Figure 3-22.
DI Settings
DI NO: 1
SPD Alarm
Active: High
Figure 3-22
DI Settings page
Press or to select the needed option. Press or to select the parameter value and press ENT to confirm.
Press or to modify the number and letter of DI name on the third line after pressing the ENT to confirm, press
or to move the cursor left or right and input # to end. Finally, press ENT to confirm.
Use or to change the number, and or to move the cursor left or right. Press ENT to confirm.
The value description of the parameter is listed in Table 3-6.
Table 3-6
Parameter
DI No.
DI Name
Alarm Mode
Range
1~8
Figures or letters,
10 at most
High, Low
Factory setting
8
SPD
High
Value description
The eighth corresponding connecting terminals, queued up in the
order that the hardware switches are put
When there are DI alarms, this parameter shows the alarm name you
have actually defined.
High: alarm upon high level; Low: alarm upon low level
User Manual
16
Chapter 3
BAT Settings
Basic Setting
LVD Settings
Charge
Figure 3-23
Battery Test
Temp. Comp
BAT Settings page
The battery parameters are divided into 5 kinds: basic, LVD, charging management, battery test and temperature
coefficient parameters.
Basic parameters
1. At the BAT Settings page, press or to select Basic Setting menu. Then press ENT to enter the battery basic
parameter setting page, as shown in Figure 3-24.
Sys Mode: Auto
Bat. Fuse: 0
Capacity: 600Ah
Bat. Shunt 1: Y
Figure 3-24
Bat. Shunt 2: N
Shunt Coeff:
-Current:
500A
-Volt:
75mV
2. Press or to select one page or one of the parameters, and or to select the parameter value. Then press
ENT to confirm and save.
The value description of the basic battery parameters is listed in Table 3-7.
Table 3-7
Parameter
Range
Sys Mode
Auto, Manual
Auto
Bat. Fuse
0~4
Capacity
50Ah ~ 5000Ah
600Ah
Bat. Shunt1
Bat. Shunt2
Shunt Coeff
Current
Shunt Coeff Volt
Y, N
Factory setting
Value description
In the Auto mode, you can manage the system through the monitoring
module.
In the Manual mode, you can manage the system manually, as well as
calculate battery BC time protection and capacity automatically. Upon the
system DC under-voltage alarm, system can automatically switch to the
Auto mode
You should set this parameter according to the actual battery
configuration
The capacity of the total battery strings. You should set this parameter
according to the actual battery configuration
Y
N
You can set shunt parameters when System Type is SET
1A ~ 5000A
500A
1mV ~ 500mV
75mV
LVD parameters
At the BAT Settings page, press or to select LVD Setting menu. Then press ENT to enter LVD settings page, as
shown in Figure 3-25.
LVD1 Enable: Y
LVD2 Enable: Y
LVD1 Volt: 44.0V
LVD2 Volt: 43.2V
Figure 3-25
User Manual
Chapter 3
17
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
LVD1 means the monitoring module opens the LLVD contactor, so that the non-priority load will be powered off. In
this way, the battery remaining capacity can sustain the priority load longer.
LVD2 means the monitoring module opens the BLVD contactor. In this way, the battery will stop powering the load,
preventing over-discharge.
The value description of the LVD parameters is listed in Table 3-8.
Table 3-8
Parameter
LVD1 Enable
LVD2 Enable
LVD1 Volt
LVD2 Volt
Range
Factory setting
Value description
Y
Select Y to enable LVD1/ LVD2 function
Select N to disable the LVD1/ LVD2 function
Y
44.0V
Select Voltage, when the monitoring module detects that the battery
voltage is lower than the preset LVD1 Volt, the load will be disconnected,
and so is the battery when the battery voltage is lower than the preset
43.2V
LVD2 Volt
Y, N
40V ~ 60V
Auto Boost:
-Enable: Yes
-Current: 0.060C
-Cap:
80.0%
Const Boost:
-Current: 0.010C
-Time:
180min
Cyc Boost:
-Enable: Yes
-Period: 2400h
-Time: 720min
Figure 3-26
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
The charging management parameter value description is listed in Table 3-9.
Table 3-9
Parameter
Range
Float
53.5V
42V ~ 58V
Boost
56.4V
0.1C10 ~ 0.25C10
0.1C10
0.3C10 ~ 1.0C10
0.3C10
Y, N
0.050C10 ~
0.080C10
0.06C10
10% ~ 99%
80%
0.002C10 ~
0.01C10
0.02C10
30min ~ 1440min 180min
Value description
In the FC state, all rectifiers output voltage
according to the set Float
The Boost must be
higher than the Float
In the BC state, all rectifiers output voltage
according to the set Boost
When the monitoring module detects that the battery charging current is
higher than the Limit, it will control the current of the rectifiers, through
which it can limit the battery charging current.
C10 is the battery rated capacity, generally set to 10% ~ 20% of the rated
capacity of one battery string
When the monitoring module detects that the battery charging current is
higher than the Over, it will raise the battery charge over-current alarm
Select Y to enable this function
Select N to disable this function
The monitoring module will control the system enter the BC state when
the battery capacity decreases to the value of To Boost Capacity, or
when the charge current reaches the To Boost Current. The charge
voltage will be the Boost
The system in the BC state will enter the FC state when the charge
current decreases to the Constant BC Curr and after the Duration. The
battery charge voltage then will be the Float
User Manual
18
Chapter 3
Parameter
Range
Factory setting
2400h
Value description
Select Y to enable this function
Select N to disable this function
Select Y, and the monitoring module will control the system to enter the
Cyclic Boost when the FC time reaches the Cyclic Boost Interval. The
battery charging voltage is the preset Boost, and the time is the preset
Cyclic Boost Time
To ensure safety, the monitoring module will forcefully control the
system to enter the FC state if during the BC state, the BC time reaches
the Boost Limit, or abnormalities occur (such as AC failure, battery route
faulty, and rectifier communication failure)
BC
FC
Constant BC
time-up
Constant
BC
Charge current
smaller than
'Constant BC
Curr'
Figure 3-27
End Test:
-Volt: 45.2V
-Time: 300min
-Cap: 0.70C
07-01-00:00
10-01-00:00
Figure 3-28
Short Test:
-Enable: No
-Alarm: 10A
-Period: 720h
-Time: 5min
Stable Test
-Enable: No
-Current: 9999A
2. Press or to select one page or one of the parameters, and or to select the parameter value. Then press
ENT to confirm and save.
User Manual
Chapter 3
19
The monitoring module can do battery test, and record 10 sets of test data (accessible only through the host). The
battery test has to be started manually, then the monitoring module will control the rectifier output voltage, make it
lower than the battery voltage, and the battery discharge will begin. The monitoring module will stop the test if the
battery voltage reaches the Battery Test Voltage, or the discharge time reaches Battery Test Time, or the battery
capacity reaches Test End Cap. Afterwards, it will restore the rectifier output voltage to the normal FC voltage, begin
the battery charge and switch the system to battery auto-management.
Meanwhile the test start time/voltage and end time/voltage and battery remaining capacity will be recorded. The
records can be queried through the host. During the battery test, if abnormalities occur, the monitoring module will
stop the battery test automatically.
The value description of the parameters is listed in Table 3-10.
Table 3-10
Parameter
End Test Volt
End Test Time
End Test Cap
Cyc Test En
Range
Factory setting
Value description
43.1V ~ 57.9V 45.2V
The monitoring module will stop the test and change to FC if the battery
5min ~ 1440min 300min
voltage reaches the Battery Test Voltage, or the discharge time reaches
0.01C10 ~
Battery Test Time, or the battery capacity reaches Test End Cap
0.7C10
0.95C10
Select Y to enable this function
Y, N
Y
Select N to disable this function
01-01-00:00
04-01-00:00
Month, day,
When the parameter Cyc Test En is set to Y, the monitoring module will
time
test the battery according to the 4 sets of test time
07-01-00:00
10-01-00:00
Y, N
Y
Whether using Short Test function
1A ~ 100A
10A
If the battery is not discharged within the ShortTest Cycle, the monitoring
module will start a short test, whose operation time is set by the
24h ~ 8760h
720h
parameter ShortTest Duration. By the end of the test, if the difference in
the discharge currents of batteries is bigger than the Alarm Current, the
1min ~ 60min
5min
battery discharge imbalance alarm will be raised. This alarm will
automatically end after 5min of delay. Also you can end it by confirming it
Y, N
Y
The stable test is conducted with constant battery current, whose value is
set through the parameter StableTest Current. If the parameter
StableTest Enable is set to Y, and the test will be started once the battery
0 ~ 9999A
9999A
satisfies the test condition
Manually/
Scheduled start
Rectifier output
voltage lower than
battery voltage
battery test
Figure 3-29
Battery
Auto-management
Temperature coefficient
1. At the BAT Settings page, press or to select Temp. Comp menu. Then press ENT to confirm.
There are two pages, as shown in Figure 3-30.
C
Center Temp: 25
C
Coeff: 72mV/
Temp1: No
Temp2: No
Figure 3-30
C
Batt T H2: 50
C
Batt T H1: 50
C
Batt T L1: 0
2. Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm and
save.
User Manual
20
Chapter 3
Range
10C ~ 40C
Value description
25C
0 ~ 500mV/C
Ambient
Temp, None,
Battery Temp
None
Batt T H2
-40C ~ 100C
50C
Batt T H1
-40C ~ 100C
50C
Batt T L1
-40C ~ 100C
0C
Coeff
Temp1
Temp2
3.7.3 AC Settings
At the Settings page, press or to select AC Settings menu. Then press ENT to enter the AC Settings page, as
shown in Figure 3-31.
Over Volt: 280V
Low Volt: 180V
Under Volt: 80V
AC In:
Auto
AC PH: 3-PH
Figure 3-31
AC Settings page
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 3-12.
Table 3-12
Parameter
Range
Factory setting
Over Volt
50V ~ 300V
280V
Low Volt
50V ~ 300V
170V
Under Volt
50V ~ 300V
Auto, No,
Manual
80V
1-PH, 3-PH
3-PH
AC In
AC PH
No
3.7.4 DC Settings
At the Settings page, press or to select DC Settings menu. Then press ENT to enter the DC Settings page, as
shown in Figure 3-32.
User Manual
Chapter 3
Over Volt 2:
Low Volt 1:
Low Volt 1:
Low Volt 2:
58.5V
58.0V
45.0V
45.0V
21
L-Shunt En: N
Shunt Coeff:
-Current: 500A
-Volt:
75mV
Figure 3-32
DC Settings page
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 3-13.
Table 3-13
Parameter
Range
Factory setting
Over Volt
Low Volt 1
58.5V
40V ~ 60V
Low Volt 2
L-Shunt
Shunt Coeff
Current
Shunt Coeff
Volt
45.0V
1A ~ 5000A
500A
1mV ~ 500mV
75mV
Value description
The DC Over Voltage alarm will be raised when the system
DC output voltage is higher than the value of Over Volt
The DC low voltage alarm will be raised when the system
DC output voltage is lower than the value of Low Volt 1
The DC under voltage alarm will be raised when the system
DC output voltage is lower than the value of Low Volt 2
45.0V
Y, N
Walk-in On:
Walk-in:
8s
Interval T:
0s
AC OverV On: N
Figure 3-33
ACCurrLim: 30A
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 3-14.
Table 3-14
Parameter
Range
Factory setting
Position En
Y, N
R-Posi
1 ~ 30
HVSD
56V ~ 59V
59V
Default V
48V ~ 58V
53.5V
Walk-in On
Walk-in
Y, N
8s ~ 128s
N
8s
The output soft start function means the rectifier voltage will rise from 0V to
the Default Volt after the Walk-in time
Interval T
0s ~ 10s
0s
The monitoring module can set the DCDC Interval Start of the modules.
Start time = module address * interval time
User Manual
22
Chapter 3
Parameter
Range
AC OverV On
Y, N
ACCurrLim
1A ~ 50A
Factory setting
Value description
The monitoring module can set the rectifier to OverVolt Enable, meanwhile,
the rectifier can start forcibly. The monitoring module will set automatically the
rectifier with least address to have this function. If the rectifier always exceeds
the normal voltage for 60s, the function will be canceled automatically
The monitoring module limits the input current of the rectifier in the AC current
limiting.
30A
Lang: Chinese
Tzone GMT+08: 00
Date: 2000-01-15
System Type:
48V/set
ComDownLoad: N
Reset PWD: N
Figure 3-34
Reset Para: N
Op1 PWD: ******
Op2 PWD: ******
Adm PWD: ******
If the Rest Para is set to Y, press ENT and prompt a page shown in Figure 3-35.
Notice:
ENT Continue
ESC Quit
Figure 3-35
Press ESC to cancel the resetting, or ENT to confirm. All the parameters will resume the default value. It is
recommended to power off or reset to perform system resetting when the monitoring module cannot work normally.
Press or to select the parameter, and or to select the parameter value. Then press ENT to confirm.
The value description of the parameters is listed in Table 3-15.
Table 3-15
Parameter
Lang
Tzone
Range
Chinese, English
-
Factory setting
Chinese
-
Date
2000 ~ 2099
ComDownLoad
Reset PWD
Reset Para
Op1 PWD
Op2 PWD
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
Y, N
Y, N
-
Adm PWD
System Type
48V/500
N
N
-
Value description
Set according to your need
Set according to actual instance
Set the time according to the current actual time, regardless of
whether it is a leap year or not
The system type of the monitoring module has been set
according to the actual instance before the monitoring module is
delivered with power supply system. You need not to change the
value except that the monitoring module is replaced with a new
one.
After changing the type, the monitoring module will restart and
the other parameters will resume the default. You need to reset
and change some parameters according to the battery and
equipment configured with system
Whether resetting the password to the default
Whether resetting the parameters to the defaults
The password can be 6 digits long at most. If it is shorter than 6
digits, end it with a #. Use or to change the number, and
or to move the cursor left or right. Press ENT to confirm. You
should input the same number twice to complete the setting
User Manual
Chapter 3
23
Address: 1
Comm Mode: RS232
BaudRate: 9600
IP/Subnet/Gate:
Figure 3-36
192.168.1.2
255.255.255.0
192.168.1.1
CallbackTime: 3
Phone Number:
......
......
......
When the Comm Mode is MODEM, the CallbackTime and Phone Number should be set. Use or to change the
Phone Number or move the cursor left or right. And then press ENT to confirm. The communication parameter
settings list is given in Table 3-16.
Table 3-16
Parameter
Range
Factory setting
Address
1 ~ 254
Comm Mode
MODEM
RS232
BaudRate
IP/Subnet/Gate
CallbackTime
Phone Number
Value description
The addresses of power systems that are at the same monitored
office should be different
The system only supports RS232 mode communication
Make sure the baud rates of both the sending and receiving
parties are the same
Set according to actual instance
Figure 3-37
If you want the system operating under energy saving mode, set Save Enable to Y, otherwise, set it to N. Set Cyc
Period according to actual instance. The saving operating theory of the system is described as follows:
1. Operating theory
Under energy saving mode, the monitoring module will switch off some rectifiers, the power-on rectifiers will be
charged with all loads. Each power-on rectifier works on the best efficiency to improve utilization ratio of the rectifier
and save energy consumption. After certain time (that is Cyc Period in Figure 3-37), the power-off rectifiers will work,
meanwhile the power-on rectifiers will stop work. Two states circulate, so as to make sure that the working hours of
the rectifiers in the system approach. If the battery current and load current change, the monitoring module will switch
off some power-on rectifiers or switch on some power-off rectifiers. In any case, the system guarantees at least one
rectifier to work.
2. Prerequisite
If the battery is configured and load current without instantly shocks, the system will operate under energy saving
mode, that is, Save Enable is set to Y.
3. Advantage
Working on the best efficiency to save energy.
Balancing working hours of the rectifiers to prolong the lifetime of the rectifier.
In shutdown state, preventing rectifiers from damaged about AC inrush to reduce lightning fault.
M520S Monitoring Module
User Manual
24
Chapter 3
Range
Factory setting
Value description
It can be set to Y when the battery is configured and load current without
Y, N
N
instantly shocks
Time of rectifier under power-on state and power-off state, it can be set
Cyc
1h ~ 8760h
48h
according to actual requirement
Period*
Output capacity percentage. More rectifiers will startup to work when larger than
Rect Work
30% ~ 90%
80%
this setting percentage
Minimum number of the rectifier
Rect Limit
1 ~ 30
1
Note*: Cyc Period, Rect Work and Rect Limit are available when Save Enable is set to Y
Figure 3-38
At the Fast Settings page, you can set the system type and battery capacity, as listed in Table 3-18.
Table 3-18
Parameter
System
Type
Capacity
Range
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
50Ah ~ 5000Ah
Factory setting
Value description
48V/500
The system type of the monitoring module has been set according to the
actual instance before the monitoring module is delivered with power supply
system. You need not to change the value except that the monitoring module
is replaced with a new one.
After changing the type, the monitoring module will restart and the other
parameters will resume the default. You need to reset and change some
parameters according to the battery and equipment configured with system
600Ah
The capacity of the total battery strings. You should set this parameter
according to the actual battery configuration
User Manual
Chapter 3
25
Note
This procedure needs to be performed only when the Controller is connected to an Intranet and the User has set that the access to
the intranet needs to be made through proxy. If the Controller is connected Internet and the user computer is connected to the
intranet, the user cannot disable the proxy, and otherwise he will have no access to the Controller.
1. Launch Internet Explorer.
2. Select Internet Options from the Tools menu. The Internet Options window opens. In the Internet Options
window, select the Connections tab.
Figure 3-39
3. Click on the LAN Settings... button. The following window opens. In the LAN Settings window, uncheck the proxy
box and click OK.
Figure 3-40
User Manual
26
Chapter 3
Figure 3-41
Access to Controller
Figure 3-42
Homepage Window
System information
At the top of homepage, System Information is displayed, such as system voltage, system load, number of major
alarms and critical alarms, number of observation alarms, battery charging mode, site name, hardware version, and
software version.
Parameter and control function
You can set the following parameters and control functions:
M520S Monitoring Module
User Manual
Chapter 3
27
Battery Temp Comp: To disable or enable the battery temperature compensation function.
Battery Test: To disable or enable the periodical battery test function. This setting has no effect on the short
test.
Current Limitation: To disable or enable the battery charging current limitation function.
Boost Charge: To disable or enable the periodical battery boost charging function. This setting has no effect on
auto boost charging.
LVD1 Level, LVD2 Level: To set the low voltage disconnection point.
Under Voltage Level 1, Under Voltage Level 2: To set the under voltage point.
System Volt: To set the system voltage.
Boost Volt: To set the battery boost charging voltage.
NMS1 IP, NMS2 IP: To set the IP address of SNMP
Remote1 IP, Remote2 IP: To set the IP address of EEM protocol.
TCP IP address: To set the IP address of TCP IP protocol.
Upload/download files
1. Procedure
1) To upload a configuration file, click the Upload button. The following window opens. Click the Save button.
Figure 3-43
2) The following window opens. Navigate to where you want the file to be saved. Click the Save button.
Figure 3-44
Save As window
User Manual
28
Chapter 3
After the upload is completed, the system will pop up a window to prompt the user that the upload is successful:
Figure 3-45
Upload successful
Figure 3-46
User Manual
Chapter 3
Figure 3-47
Then click Download button, the system will pop up a window requiring you to confirm:
Figure 3-48
Confirmation window
Click OK, the system will prompt you that the download is successful:
User Manual
29
30
Chapter 3
Figure 3-49
Download Successful
In the above screen, you can click Back to the Homepage to return to the Homepage.
Administrator can click Go to Firmware Download Mode to enter Bootloader download interface.
Figure 3-50
WEB webpage
User Manual
Chapter 3
31
Figure 3-51
Figure 3-52
User Manual
32
Chapter 3
Figure 3-53
Here we can see there are 5 options, choose 1 to updata the application program, choose 2 to updata the
bootloader program ,choose 3 to updata the configuration, choose 4 to upload the data configuration file, choose 5
to execute the application program.
1. Method of updataing the application program:
a. Press 1 on the keyboard, enter the surface of download;
b. Choose Transfer->Send File, select the .bin file you want to download;
Figure 3-54
User Manual
Chapter 3
Figure 3-55
33
Figure 3-56
d. After the file downloading is completed successfully, the following interface pops up:
Figure 3-57
2. Method of updating the bootloader program and the configuration File: Similar to the update of application program,
will not be introduced here;
3. Method of uploading the data configuration file:
a. Press 4 on the keyboard, enter the interface of uploading files:
Figure 3-58
User Manual
34
Chapter 3
b. Choose Transfer->Receive File to select the position in which you save the file
Figure 3-59
Figure 3-60
Figure 3-61
d. After the file downloading is completed successfully, the following interface pops up.
Figure 3-62
User Manual
Chapter 4
Troubleshooting
35
Chapter 4 Troubleshooting
This chapter introduces the fault estimation and troubleshooting of the monitoring module.
Fixing screw
PCB board
Front panel
Figure 4-1
2. Estimate fault causes according to the indicator status of the PCB board, as listed in Table 4-1.
Table 4-1
Phenomenon
Handling method
Check if J421 terminal is connected reliably. If the connection is
reliable and the terminal voltage is normal (approximately the
busbar voltage of the system), the PCB board is faulty and needs
replacement
Software is updating
about firmware
User Manual
36
Chapter 4
Troubleshooting
The indicators and terminals of the PCB board are shown in Figure 4-2.
B
J424
J411
J408
J412
J409
J407
J416
J427
J426
D2
D1
J419 J422
J420
2
1
32
31
Power indicator
J421
5
J421 terminal
Watchdog indicator
Figure 4-2
4.2 Replacement
Note
Care should be taken when replacing components of the monitoring module. Unplugging terminals optionally may result in
system shut down. Carry out the replacement sequentially according to the following procedures.
1. Replace the PCB board
The procedures of replacing PCB board are described as follows:
1) Unplug J426 and J427 terminals to prevent shutting down of the system.
2) Unplug the J421 power supply terminal to power off the PCB board.
3) Unplug other terminals and DI/DO cables.
4) Wrap the DI/DO cable terminals with insulating tape. (Keep the unconnected terminals and cables should be
insulated from components of the system and the PCB board to prevent short circuit.)
5) Remove the fixing screws of the PCB board and replace the PCB board. (Note that the screwdriver should be
prevented from touching the bare parts of the signal cables to prevent short circuit.)
6) Connect the signal cables in reverse sequence, that is, reconnect signal cables other than J421, J426, J427
terminal cables and DI/DO cables.
7) Check the cable connections. If the connections are correct, reconnect J421 terminal. If the watchdog indicator
flashes and power indicator is on, the PCB board works normally.
8) Check the voltages of J426 and J427 terminals with a multimeter. Make sure that they output low voltage. Connect
J426 and J427 terminals.
9) Set the parameters of the monitoring module according to 3.7
User Manual
Appendix 1
37
Alarm
Basic
Parameter
Factory
setting
Range
DI No.
1~8
DI Name
Alarm Mode
High, Low
SPD
High
Sys Mode
Auto, Manual
Auto
Bat. Fuse
0~4
Capacity
Bat. Shunt1
Bat. Shunt2
Shunt Coeff
Current
Shunt Coeff Volt
LVD1 Enable
LVD2 Enable
LVD
Y, N
Y
N
1A ~ 5000A
500A
1mV ~ 500mV
75mV
Y
Y, N
LVD1 Volt
Y
44.0V
40V ~ 60V
LVD2 Volt
43.2V
Float
53.5V
42V ~ 58V
Boost
Battery
Limit (current
limit point)
Over (over
current point)
0.1C10 ~
0.25C10
0.1C10
0.3C10 ~ 1.0C10
0.300C10
Automatic Boost Y, N
Automatic Boost
Current
Automatic Boost
Cap
Const Boost
Charge
Current
management
Const Boost
Time
56.4V
Value description
0.050C10 ~
0.080C10
0.06C10
10% ~ 99%
80%
0.002C10 ~
0.02C10
30min ~
1440min
0.01C10
180min
Cyclic Boost
Y, N
Cyclic Boost
Period
48h ~ 8760h
2400h
Cyclic Boost
Time
30min ~
2880min
720min
Boost Limit
Time
60min ~
2880min
1080min
User Manual
38
Appendix 1
Item
Parameter
Range
43.1V ~ 57.9V
5min ~
1440min
0.01C10 ~
0.95C10
Battery test
Battery
Coeff
Temperature Temp1
coefficient
Temp2
AC
0.7C10
Y
Month, day,
time
01-01-00:00
04-01-00:00
07-01-00:00
10-01-00:00
Y, N
1A ~ 100A
10A
24h ~ 8760h
720h
5min
Y, N
0 ~ 9999A
9999A
25C
10C ~ 40C
0 ~ 500mV/C
72mV/C/str
(48V system)
36mV/C/str
(24V system)
Batt T H2
Batt T H1
-40C ~ 100C
50C
Batt T L1
-40C ~ 100C
0C
Over Volt
50V ~ 300V
280V
Low Volt
50V ~ 300V
170V
Under Volt
50V ~ 300V
80V
AC In
Auto, No,
Manual
None
AC PH
1-PH, 3-PH
3-PH
Over Volt
DC
300min
Ambient Temp,
None, Battery
Temp
-40C ~ 100C
Low Volt 1
Value description
Y, N
Factory
setting
45.2V
None
50C
58.5V
40V ~ 60V
45.0V
Low Volt 2
45.0V
L-Shunt
Y, N
Shunt Coeff
1A ~ 5000A
Current
Shunt Coeff Volt 1mV ~ 500mV
N
500A
75mV
User Manual
Appendix 1
Item
Rectifier
Parameter
System
Y, N
R-Posi
1 ~ 30
HVSD
56V ~ 59V
59V
Default V
48V ~ 58V
53.5V
Walk-in On
Walk-in
Y, N
8s ~ 128s
N
8s
Interval T
0 ~ 10s
0s
AC OverV On
Y, N
ACCurrLim
1A ~ 50A
30A
Tzone
Chinese,
English
-
Date
2000 ~ 2099
Address
MODEM
1200bps ~
BaudRate
9600bps
IP/Subnet/Gate CallbackTime
Phone Number -
N
N
N
-
1 ~ 254
48V/500
39
Value description
Chinese
24V/100
24V/300
24V/500
24V/1000
24V/SET
System Type
48V/100
48V/300
48V/500
48V/1000
48V/SET
ComDownLoad Y, N
Reset PWD
Y, N
Reset Para
Y, N
Op1 PWD
Op2 PWD
Adm PWD
-
Comm Mode
Communication
Factory
setting
Range
Position En
Lang
RS232
9600bps
-
User Manual
40
Appendix 1
Item
Energy saving
Factory
setting
Range
Save Enable
Y, N
Cyc Period*
1h ~ 8760h
48h
Rect Work
30% ~ 90%
80%
Rect Limit
1 ~ 30
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
System Type
Fast settings
48V/500
Value description
It can be set to Y when the battery is configured and load
current without instantly shocks
Time of rectifier under power-on state and power-off state,
it can be set according to actual requirement
Output capacity percentage. More rectifiers will startup to
work when larger than this setting percentage
Minimum number of the rectifier
The system type of the monitoring module has been set
according to the actual instance before the monitoring
module is delivered with power supply system. You need
not to change the value except that the monitoring module
is replaced with a new one.
After changing the type, the monitoring module will restart
and the other parameters will resume the default. You
need to reset and change some parameters according to
the battery and equipment configured with system
User Manual
Appendix 2
Status
Maintenance
DC Voltage
DC Current
Rectifiers
FC
BC
Start
Curr Limit
Test
AC Voltage
AC on/off
Reconnect
DC on/off
AC Derated
Temp Derated
Alarm serial No.
Active
Alarm
Settings
Alarm level
Alarm name
Battery
Disconnect
Alarm
Settings
Rectifier
AC ON
AC OFF
AC
Settings
Reset
Start time
End time
DC
Settings
Note:
1.
2.
3.
DI No.
Mode
Set DI Name
--See Figure 2
DC ON
DC OFF
Alarm name
Voice Sign
Alarm
Control
Rect Trim
Rect Limit
Alarm Type
Level
Relate Relay
Reconnect
Disconnect
Load
Alarm time
Alarm
History
Alarm
Type
Rectifier
Settings
OverVolt
LowVolt
280V
180V
UnderVolt
80V
AC Input
AC PH
No
3-PH
Over Volt
58.5V
Low Volt
45.0V
Under Volt
Load Shunt
45.0V
N
500A
75mV
Position En
R-Posi
HVSD
Y
59V
Default V
Walk-in On
53.5V
N
Walk-in
Interval T
AC OverV On
ACCurrLim
8s
Lang
Chinese
0s
N
30A
Tzone
Date
System
Settings
System Type
ComDownLoad
48V/500
N
Reset PWD
Reset Para
N
N
Change Password
Communication
Settings
Address
Comm Mode
RS232
BaudRate
9600bps
IP/Subnet/Gate
CallbackTime
Phone Number
Energy Saving
Save Enable
Cyc Period
48h
Rect Work
80%
Rect Limit
System Type
48V/500
Capacity
600Ah
Fast Settings
Figure 1
User Manual
41
42
Appendix 2
Battery Settings
System information
Sys Mode
Basic
LVD
Bat. Fuse
Auto
2
Capacity
600Ah
Bat. Shunt1
Bat. Shunt2
500A
75mV
LVD1 Enable
DC voltage
DC current
System
operation
state
Normal
Alarm
Battery
management
mode
Power
management
mode
LVD2 Enable
LVD1 Volt
44.0V
LVD2 Volt
43.2V
Float
Boost
53.5V
56.4V
limit
Over
0.1C 10
0.3C 10
0.06C 10
80%
0.01C 10
Bat. Temp
180min
2400h
Amb. Temp
Energy Saving
Auto
Manual
FC
BC
Temperature compensation
Battery
state
Cyclic Boost
Test
Short Test
Charge
Bat. Test
Temp
Comp
Cyc Test
Battery1 current
Battery1 remaining capacity
Battery2 current
Battery2 remaining capacity
AC voltage
System Power
Cyc BC After
720min
Boost Limit
1080min
Note:
45.2V
300min
0.7C 10
Cyc Test En
00:00, Jan.1
00:00, April1
st
00:00, July1
00:00, Oct.1
st
10A
720h
5min
N
9999A
Center Temp
Coeff
25
72mv/
Temp1
None
Temp2
None
50
Batt T H1
50
Batt T L1
Figure 2
3.
st
st
Batt T H2
2.
User Manual