06 - P746 - en - Ap - F21
06 - P746 - en - Ap - F21
06 - P746 - en - Ap - F21
P746/EN AP/F21
MiCOM P746
AP
APPLICATION NOTES
Date:
2010
Hardware Suffix:
Software Version:
02
Connection Diagrams:
10P746xx
P746/EN AP/F21
Application Notes
MiCOM P746
Application Notes
MiCOM P746
P746/EN AP/F21
(AP) 6-1
CONTENTS
1.
INTRODUCTION
1.1
2.
2.1
2.1.1
CT Ratios
2.1.2
VT Ratios
2.2
Busbar settings
2.2.1
Setting guidelines
2.3
14
2.3.1
14
2.3.2
14
3.
CURRENT TRANSFORMERS
16
4.
17
4.1
17
4.1.1
17
4.1.2
17
4.1.3
17
4.1.4
18
4.1.5
18
4.1.6
18
4.2
18
4.3
19
4.3.1
TCS scheme 1
19
4.3.2
Scheme 1 PSL
20
4.3.3
TCS scheme 2
21
4.3.4
Scheme 2 PSL
21
4.3.5
TCS scheme 3
22
4.3.6
Scheme 3 PSL
22
5.
23
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-2
AP
6.
TOPOLOGY
24
6.1
Topology Configuration
24
6.2
25
6.3
Topology processing
26
6.3.1
26
6.3.2
27
6.3.3
28
6.3.4
30
6.3.5
31
6.3.6
CTs on one side of bus coupler, CB closed and fault evolves between CT and CB (even for
switch onto fault).
32
6.3.7
CTs on both sides of coupler, CB closed and fault evolves between CT and CB.
33
7.
34
7.1
34
7.2
Application solutions
36
7.2.1
1 box mode:
36
7.2.2
3 boxes mode:
36
7.2.3
Voltage information
37
7.2.4
41
7.2.5
2 out of 2 solution:
41
7.3
Check list
42
7.4
43
7.5
43
7.6
Switchgear
43
7.7
Substation Architecture
43
8.
STANDARD CONFIGURATIONS
44
9.
49
9.1
Function keys
49
10.
CT REQUIREMENTS
50
10.1
Notation
50
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-3
10.2
50
10.2.1
50
10.2.2
51
10.3
52
11.
53
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-4
AP
BLANK PAGE
Application Notes
MiCOM P746
1.
P746/EN AP/F21
(AP) 6-5
INTRODUCTION
Before carrying out any work on the equipment, the user should be familiar with the contents
of the safety section/safety guide SFTY/4LM/C11 or later issue, the technical data section
and the ratings on the equipment rating label.
1.1
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-6
2.
AP
2.1
Provides the main protection element for the scheme. This protection provides highspeed discriminative protection for all fault types
Circuit breaker failure protection two stage breaker fail logic that can be initiated
internally or externally.
Non-directional phase fault over current protection provides two stage protection.
Low Burden Allows the protection to be installed in series with other equipment on a
common CT secondary.
2.1.1
CT Ratios
Only 3 values have to be known and entered:
1.
2.
3.
2.1.2
1.
2.
VT Ratios
Only 2 values have to be known and entered:
1.
Phase VT Primary voltage (from 100 to 100 kV) given by the manufacturer.
2.
Application Notes
MiCOM P746
2.2
P746/EN AP/F21
(AP) 6-7
Busbar settings
Busbar Biased Current Differential Protection
2.2.1
Setting guidelines
2.2.1.1
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-8
2.2.1.1.1 Sub-station features
Only 8 values have to be known:
1.
2.
3.
4.
5.
6.
7.
8.
AP
2.
3.
ID>2 (from 50 A to 30000 A (primary value)) as low as possible*, whilst ensuring the
single CT failure will not cause tripping under maximum load conditions with no VT.
4.
5.
6.
7.
ID>1 Alarm Timer (from 0 to 100 s) shall be greater than the longest protection time
(such as line, overcurrent, etc.)
8.
below twice the maximum load for the phase comparison algorithm to pickup the
load and if possible below 50% of the minimum fault to be sub-cycle (80%
otherwise)
and if no voltage criteria is used above 100% (and when possible 120% to allow
20% margin) of the biggest load to not maloperate in case of CT short-circuited or
open circuit
Note: voltage criteria can be used for single busbar only in one box mode.
and less than 80% of the minimum fault current to operate sub-cycle for the
minimum fault (and 50% when possible to be sure to always operate in 13ms)
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-9
4. Slope k2 (ID>2)
a.
Recommendation is 60%
To be always stable in the worth CT ratio conditions (between the biggest CT and
the smallest CT).
b.
Recommendation is 30%
The requirement is to be able to trip for a fault that is counted twice by the Check
Zone (for example one and half circuit breaker substation) and depends on the
number of bars:
AP
Q
Q
CB
CB
CB
CB
CB
CB
CT
CT
CT
CT
CT
CT
Feeder
Feeder
Feeder
Feeder
Feeder
Feeder
P3945ENa
IF
CB
CT
CB
CB
CB
CB
CB
CT
CT
CT
CT
CT
Feeder
Feeder
Feeder
Feeder
Feeder
P3946ENa
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-10
During the internal fault:
the bias current is: Icc min (1 bar) + (n-1) x IloadMax (1 bar)
Thus the biggest slope for the Check Zone to detect the fault is:
________________Icc min (1 bar)________________________
((Independent bars - 1) x IloadMax (1 bar)) + Icc min (1 bar)
If for example:
There are 3 buses and Icc min = IloadMax, the slope must be below 33%
For a one and half breaker scheme there are:
Feeder
Feeder
Feeder
Feeder
Feeder
AP
lload
lload
lload
lload
Feeder
P0582ENa
when the busbar is split in 2 and goes as well through the opposite bar
Thus the biggest slope for the Check Zone to detect the fault is:
___________Icc min (1 bar)___________
(4 x IloadMax (1 bar)) + 2 x Icc min (1 bar)
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-11
If for example:
Icc min = IloadMax, the slope must be below 17%
b.
7. ID>1 Alarm Timer to not operate for an external fault shall be greater than the longest
protection time (such as line, overcurrent, etc.)
8. Phase comparison
Phase comparison is used to define the minimum current to be included in the phase
comparison algorithm; it is recommended to be 80% of (ID>2 / In of Infeed CTs).
The requirement is to be able to detect a through fault that is fed by the infeeds; it does not
depend on the number of bars but depends on:
AP
CB
CB
CB
CB
CB
CB
CT
CT
CT
CT
CT
CT
Feeder
Feeder
Feeder
Feeder
Feeder
Feeder
P3945ENa
The worst scenario is when the CT is fully saturated and the differential algorithm picks up
on the ID>2 threshold. The phase comparison must block the trip by detecting the incoming
currents:
We assume the infeeds will contribute to the ID>2 fault in proportion to their CT primary
nominal current (worst situation).
Then we need for each infeed, phase comparison threshold to be lower than:
So, for any infeed, phase comparison max = ID>2 / (In CTs infeeds))
We take 80% of this value so that to keep sufficient margin. Recommended setting is then:
PC max = 0.8 ID>2 / (In CTs infeeds)
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-12
Example:
Infeed
CT
Contribution*
PC%
Infeed 1
2500 / 5
2500 / 11300
Infeed 2
2000 / 1
2000 / 11300
ID>2
11300
Infeed 3
2000 / 1
2000 / 11300
ID>2
11300
Infeed 4
1200 / 1
1200 / 11300
ID>2
11300
Infeed 5
1200 / 1
1200 / 11300
ID>2
11300
Infeed 6
1200 / 1
1200 / 11300
ID>2
11300
Infeed 7
1200 / 1
1200 / 11300
ID>2
11300
ID>2
11300
AP
2.2.1.2
2.
3.
Maximum single phase steady state faulty current (Ph-N Max.) in a bus
4.
5.
2.
3.
ID>1 Alarm Timer (from 0 to 600 s) shall be greater than the longest Busbar protection
time
4.
5.
ID>2 (from 50 A to .30 kA (primary value)), recommendation is: Lower than 0.8 (PhPh min) and higher than 1.2 Iload Max and if possible, equal to 6 (ID>1).
6.
7.
Application Notes
MiCOM P746
P746/EN AP/F21
(AP) 6-13
ID>1 shall be higher than 120% of the highest phase to neutral fault to not operate in
case of phase to neutral fault.
2.
3.
ID>1 Alarm Timer to not operate for an external fault shall be greater than the longest
protection time (such as line, overcurrent, etc)
4.
To be always stable in the worth CT ratio conditions (between the biggest CT and the
smallest CT). 60% is OK as long as the CT ratio is less than 5.
1.
ID>2 shall be lower than 80% of the minimum phase to phase fault current to operate
sub-cycle for the minimum fault and higher than 120% Iload Max (120% to allow 20%
margin) and if possible equal to 6 (ID>1) to be insensitive to the worth CT saturation.
2.
3.
The requirement is to be able to trip for a fault that is counted twice by the Check Zone (for
example one and half circuit breaker substation).
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-14
2.3
2.3.1
2.3.1.1
Setting guidelines
For each CT connected to a Feeder Circuit Breaker (not on bus couplers or bus sections)
For the phase:
I>DZ must be below 80% of the minimum Dead Zone fault level (and if possible bigger
than the maximum load).
I>DZ Time delay must be at least 50ms if the CB status positions are used (any value
otherwise)
IMPORTANT NOTE:
When a dead zone fault occurs and the bias current flowing through the bus is small,
there could be a maloperation of the 87BB.
To prevent that, it is recommended to enable an additional criterion such as voltage
(voltage criteria can be used for single busbar only in one box mode).
AP
2.3.2
2.3.2.1
Setting guidelines
Typical timer settings to use are as follows:
CB fail reset mechanism
CB open
CB auxiliary contacts
opening/ closing time (max.) +
error in tBF timer + safety margin
50 + 10 + 50 = 110 ms
Undercurrent elements
CB interrupting time +
undercurrent element (max.) +
safety margin operating time
50 + 15 + 20 = 85 ms
The examples above consider direct tripping of a 2-cycle circuit breaker. Note that where
auxiliary tripping relays are used, an additional 10-15ms must be added to allow for trip relay
operation.
The phase undercurrent settings (<) must be set less than load current, to ensure that <
operation indicates that the circuit breaker pole is open. A typical setting for overhead line or
cable circuits is 20% n, with 5% n common for generator circuit breaker CBF.
Application Notes
P746/EN AP/F21
MiCOM P746
2.3.2.2
(AP) 6-15
AP
P746/EN AP/F21
MiCOM P746
(AP) 6-16
3.
Application Notes
CURRENT TRANSFORMERS
A P746 can accommodate different CT ratios throughout the protected zone, the maximum
difference being 40. In other words, the maximum ratio between the smallest primary CT
winding and the biggest primary CT winding is 40. This mix must, therefore, be accounted for
by the scheme and this is achieved by using the primary currents sent by the P746 to the
P746 that undertakes scheme calculations.
In the P746, a settable common virtual current transformer of is used to convert to secondary
values and more important is used as a setting for the phase comparison algorithm.
3.1.1.1
Setting guidelines
From 1 to 30000 by default 2000/1.
See the busbar protection setting guideline.
AP
Application Notes
MiCOM P746
4.
4.1
P746/EN AP/F21
(AP) 6-17
The P746 protections require a reliable indication of the state of the isolators to decide which
breaker to trip in case of fault. The relay can incorporate isolator state monitoring, giving an
indication of the position of the isolator, or, if the state is unknown, an alarm can be raised
using the following PSL:
4.1.1
In that case, in the P746 topology, the position will be forced as closed as soon as the
isolator will leave the open position.
4.1.2
In that case, in the P746 topology, the position will be forced as open as soon as the isolator
will leave the closed position.
This is not recommended as the P746 may trip in 2 steps instead of 1 in case of a fault
appearing during the closing period of the isolator.
4.1.3
In that case, in the P746 topology, the position will be forced as closed as soon as the
isolator will leave the open position.
AP
P746/EN AP/F21
MiCOM P746
(AP) 6-18
4.1.4
Application Notes
In that case, in the P746 topology, the position will be seen closed only when the isolator will
arrive at the closed position.
This is not recommended as the P746 may trip in 2 steps instead of 1 in case of a fault
appearing during the closing period of the isolator.
4.1.5
AP
In that case, in the P746 topology, the position will be seen closed only when the isolator will
arrive at the closed position and seen open only when the isolator will arrive at the open
position.
This is not recommended as the P746 may trip in 2 steps instead of 1 in case of a fault
appearing during the closing period of the isolator.
4.1.6
4.2
Application Notes
P746/EN AP/F21
MiCOM P746
4.3
(AP) 6-19
4.3.1
TCS scheme 1
4.3.1.1
Scheme description
AP
Optional
P2228ENa
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-20
This TCS scheme will function correctly even without resistor R1, since the opto input
automatically limits the supervision current to less that 10mA. However, if the opto is
accidentally shorted the circuit breaker may trip.
Auxiliary Voltage (Vx)
Resistor R1 (ohms)
24/27
30/34
48/54
1.2k
24/27
110/250
2.5k
48/54
220/250
5.0k
110/125
Note:
When R1 is not fitted the opto voltage setting must be set equal to
supply voltage of the supervision circuit.
AP
Scheme 1 PSL
Figure 2 shows the scheme logic diagram for the TCS scheme 1. Any of the available opto
inputs can be used to indicate whether or not the trip circuit is healthy. The delay on drop off
timer operates as soon as the opto is energized, but will take 400ms to drop off/reset in the
event of a trip circuit failure. The 400ms delay prevents a false alarm due to voltage dips
caused by faults in other circuits or during normal tripping operation when the opto input is
shorted by a self-reset trip contact. When the timer is operated the NC (normally closed)
output relay opens and the LED and user alarms are reset.
The 50ms delay on pick-up timer prevents false LED and user alarm indications during the
relay power up time, following an auxiliary supply interruption.
0
Opto Input
Drop-Off
Straight
400
&
Latching
50
Pick-up
NC Output Relay
LED
User Alarm
P2229ENa
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-21
4.3.3
TCS scheme 2
4.3.3.1
Scheme description
Optional
Optional
P2230ENa
Scheme 2 PSL
The PSL for this scheme (Figure 4) is practically the same as that of scheme 1. The main
difference being that both opto inputs must be off before a trip circuit fail alarm is given.
CB Aux 3ph (52a)
Opto Input A
1
Opto Input B
0
Drop-Off
400
0
Straight
0
Output Relay
Latching
LED
&
0
Pick-Up
50
User Alarm
P2187ENb
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-22
4.3.5
TCS scheme 3
4.3.5.1
Scheme description
P2231ENa
AP
As with schemes 1 and 2, resistors R1 and R2 are used to prevent false tripping, if the
opto-input is accidentally shorted. However, unlike the other two schemes, this scheme is
dependent upon the position and value of these resistors. Removing them would result in
incomplete trip circuit monitoring. The table below shows the resistor values and voltage
settings required for satisfactory operation.
Auxiliary Voltage
(Vx)
Resistor R1 & R2
(ohms)
Resistor R3 (ohms)
Opto Voltage
Setting
24/27
30/34
48/54
1.2k
0.6k
24/27
110/250
2.5k
1.2k
48/54
220/250
5.0k
2.5k
110/125
Note:
Scheme 3 PSL
The PSL for scheme 3 is identical to that of scheme 1 (see Figure 2).
Application Notes
MiCOM P746
5.
P746/EN AP/F21
(AP) 6-23
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-24
6.
TOPOLOGY
The topological analysis of the state of the substation in real time is one of the primary
factors of the reliability of numerical differential busbar protection. Thus in the case of a
power system fault, this analysis determines the sections of the substation concerned with
the fault and only takes those sections out of service. The algorithms available for topological
analysis make this level of discrimination possible and it is these algorithms that are utilized
in the P746 scheme.
6.1
Topology Configuration
The P746 topology is determined by replication of the circuit, i.e. the connections between
the various pieces of plant on the system. This topological replication is carried out from the
setting information in SYSTEM CONFIG:
Note the connection n1 is on the right and increasing to the left up to 6 for one box mode
and up to 18 for three boxes mode.
AP
Z1 Terminals
Z2 Terminals
Xfer Terminals
ChZONE Terminal
If there is no bus coupling or it is an isolator all the following settings shall be none.
For Bus coupling by Breaker with 1 CT
Z1 Bus CT
Z1 Bus CT Pol
Z2 Bus CT
Z2 Bus CT Pol
Z1 Bus CT Pol
Z2 Bus CT
Z2 Bus CT Pol
Note:
Application Notes
P746/EN AP/F21
MiCOM P746
6.2
(AP) 6-25
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-26
6.3
Topology processing
The following scenarios demonstrate how the dynamic topology processing works and
accommodates anomalies and discrepancies in the scheme.
6.3.1
Isolator Closed
CB Closed
AP
P0583ENa
Isolator Closed
CB Closed
Isolator Closed
CB Closed
Application Notes
P746/EN AP/F21
MiCOM P746
6.3.2
(AP) 6-27
Coupling Closed
Zone 1 = CT1 + CT3
Zone 2 = CT2 + CT3
Zone 1 = BB1
Zone 2 = BB2
Isolator Closed
CB Closed
Isolator Closed
CB Closed
Zone 1 = CT1
Zone 2 = CT2
Zone 1 = BB1
Zone 2 = BB2
Coupling Open
Isolator Closed
CB Closed
Isolator Closed
CB Closed
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-28
6.3.3
CT 4
BB 2
BB 1
Coupling Closed
Isolator Closed
Isolator Closed
CB Closed
CB Closed
CT 2
CT 1
AP
Zone 1 = CT1
Zone 2 = CT2
Zone 1 = BB1
Zone 2 = BB2
Coupling Open
Isolator Closed
CB Closed
Isolator Closed
CB Closed
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-29
CT 4
VZ 3
CT 3
BB 2
BB 1
Coupling Closed
Zone 1 =
Zone 2 =
Zone 1 =
Zone 2 =
CT1
CT2
BB1
BB2
Isolator Closed
Isolator Closed
CB Closed
CT 1
CB Closed
CT 2
Check Zone = CT1 + CT2
P0590ENa
Extended
Zone
Zone 1 = CT1
Zone 2 = CT2
Zone 1 = BB1
Zone 2 = BB2
Coupling Open
Isolator Closed
Isolator Closed
CB Closed
CB Closed
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-30
6.3.4
CT CLOSED
but auxiliary
contact OPEN
P0842ENa
AP
Treating this as an open bus coupler circuit breaker the topology algorithm will have
extended Zone 1(with the area located between the CT and the circuit breaker). This then
fully replicates the scheme up to the open bus coupler CB on both sides.
If the circuit breaker was open no load current would flow through the circuit breaker. The
differential current in the two main zones would equal zero, as the current flowing into the
zones would still equal the current flowing out.
However, if the circuit breaker is actually closed, the external fault current will flow through
the circuit breaker. The differential current in main zone 1 and in main zone 2 will be equal in
magnitude but opposite in sign. (fault)
When the check zone element is calculated, the differential currents seen in zone 1 and 2,
which result from the discrepancy in the plant status, can be seen to be cancelled out.
Zone 1 Idiff = I1+ I2= idiffZ1 = -ifault > (ID>2 and k2 x IBias)
Zone 2 Idiff = I5+ I6=idiffZ2 = +ifault > (ID>2 and k2 x IBias)
Check zone Idiff = I1+ I2+ I5+ I6=(-ifault) + (+ifault) = 0
Again the system retains its stability for discrepancies in plant status (even for switch onto
fault).
Application Notes
P746/EN AP/F21
MiCOM P746
6.3.5
(AP) 6-31
CT CLOSED
but auxiliary
contact OPEN
P0843ENa
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-32
6.3.6
CTs on one side of bus coupler, CB closed and fault evolves between CT and CB (even for
switch onto fault).
P0844ENa
AP
Under normal operating conditions when the circuit breaker is closed load current would flow
through the circuit breaker and differential current in the two main zones would equal zero,
as the current flowing into the zones would still equal the current flowing out.
However, if a fault occurs between the CT and the circuit breaker, the current will flow from
zone 1 into zone 2 which feeds the fault. The differential current in main zone 1 will still equal
zero, as the current flowing into the zone 1 will still equal the current flowing out, but the
differential current measured in zone 2 will be equal to that of the fault current.
In this case zone 2 would operate as will the check zone element.
Zone 1 Idiff = I1+ I2+ I3= idiffZ1 = 0
Zone 2 Idiff = I3+ I5+ I6=idiffZ2 = ifault > (ID>2 and k2 x IBias)
Check zone Idiff = I1+ I2+ I5+ I6= idiffZ2 = ifault > (IDCZ>2 and kCZ x IBias)
However, when zone 2 trips the fault will still be present. The topology then analyses the
remainder of the system as follows.
1 CT coupler with CB closed - Fault clearance - Stage 2
(zone 2 tripped but fault still present)
Dead
Zone 11
CT removed
from Zone 1
Dead
Zone 10
P0845ENa
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-33
Treating this as an open bus coupler circuit breaker as before the topology algorithm will
have extended zone 1 with the area located between the CT and the circuit breaker. This
then fully replicates the scheme up to the open bus coupler CB. Remember that in this
example zone 2s limit extended up to the circuit breaker but this zone has been tripped
already.
The circuit breaker is now open and the fault current would flow to feed the fault. The
differential current in the main zone 2 would equal zero, as the current is flowing into zone 1
whereas the current measured will be equal to the fault current ifault.
Zone 2 Idiff = I5+ I6= idiffZ2 = 0
Zone 1 Idiff = I1+ I2=idiffZ1 = ifault > (ID>2 and k2 x IBias)
Check zone Idiff = I1+ I2+ I5+ I6=idiffZ1 = ifault > (IDCZ>2 and kCZ x IBias)
Hence, the system reacts to the continuing presence of the fault and trips the zone 1 as the
check zone Idiff > (IDCZ>2 and kCZ x IBias) and the zone Idiff > (ID>2 and k2 x IBias).
In this example it can be seen that the opposite zone is tripped first but the dynamic topology
reacts to the changed scheme and subsequently trips the adjacent main zone.
6.3.7
CTs on both sides of coupler, CB closed and fault evolves between CT and CB.
2 CT Coupler with the CB closed and Fault between a CT and the CB
AP
P0846ENa
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-34
7.
7.1
Up to 6
Up to 18
Set of VTs
0 or 1
0 or 1
Mode
3 boxes mode
AP
Set of CTs
Up to 6
Up to 12
Up to 18
Up to 36
Set of VTs
0 or 1
0 to 2
0 or 2
0 to 2
Mode
One box
mode
3 boxes mode
3 boxes
mode
Note
2 sets of
2 sets of
Up to 6
Up to 6
Up to 18
Up to 18
Set of VTs
0 or 1
0 to 2
0 or 1
0 or 2
Mode
3 boxes
mode
3 boxes mode
3 boxes
mode
Up to 6
Up to 6
Up to 12
Up to 18
Up to 18
Up to 36
Set of VTs
0 or 1
0 to 1
0 or 1
0 or 2
0 to 2
Mode
One box
mode
3 boxes mode
3 boxes
mode
3 boxes
mode
1 sets of
2 sets of
Note
2 sets of
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-35
4 buses example:
Feeder 1
Feeder 14
Feeder 15
Feeder 28
P0854ENa
AP
The trip information must be shared among the 2 sets of 3 P746 with high speed contact to
the filtered or via goose messages with IEC 61850-8.1.
Note:
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-36
7.2
Application solutions
7.2.1
1 box mode:
All analogue inputs, all digital inputs and all relay outputs are connected to one p746:
3 Phase
P0848ENa
7.2.2
AP
3 boxes mode:
Each phase inputs, all digital inputs and all relay outputs are connected to one p746:
Ph A
Ph B
Ph C
P0849ENa
Application Notes
P746/EN AP/F21
MiCOM P746
7.2.3
(AP) 6-37
Voltage information
When the 3 boxes mode is set, voltage information (based on set criteria) must be shared
among the 3 P746.
AP
P0850ENa
The information to be shared is the voltage algorithm output that allows the trip.
There are two ddbs outputs:
P746/EN AP/F21
MiCOM P746
(AP) 6-38
AP
Application Notes
To do so, the blocking information has to be sent from the connected P746 to
the two other ones with the following methods:
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-39
AP
Note:
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-40
AP
Note:
Application Notes
P746/EN AP/F21
MiCOM P746
7.2.4
(AP) 6-41
Ph A
Ph B
AP
Ph C
Neutral
P0851ENa
7.2.5
2 out of 2 solution:
Using the same principle, to have the 2 out of 2 solution, the following cabling can be done:
Ph C
Ph B
Ph A
Ph A
+ Vcc
Trip PhA
Ph B
Trip PhB
Trip PhC
Trip PhN
A&B
A&C
Ph C
A&N
B&C
Neutral
B&N
C&N
3 Phase Trip
P0852ENa
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-42
7.3
Check list
The following steps shall be performed:
Engineering phase:
1.
AP
2.
3.
4.
5.
6.
7.
Draw the topology line diagram (optional but to use the P746 remote HMI)
(using P746 Remote HMI Tips)
8.
9.
Testing phase:
1.
2.
3.
4.
5.
Commissioning phase:
1.
2.
Check CT connections
3.
Application Notes
P746/EN AP/F21
MiCOM P746
7.4
(AP) 6-43
7.5
Planned future extensions with circuit breaker, isolator and current transformer (CT)
Solid:
- Minimum two phase busbar fault current
- Minimum load current on the smallest feeder
- Maximum load current on the biggest feeder or coupler
- Optional: Maximum three phase busbar fault current
With impedance:
- Minimum two phase busbar fault current
- Minimum single phase to earth busbar fault current
- Minimum load current on the smallest feeder
- Maximum load current on the biggest feeder
- Optional: Maximum three phase busbar fault current
Switchgear
7.7
Nominal CT ratio
Substation Architecture
Due to the flexibility of the differential busbar protection there is a number of busbar
configurations that can be accommodated via the topology. Each may have very different
architecture and, therefore, vary in complexity.
You will find in the following pages topology examples of layouts most frequently
encountered. For each example, the number of P746 necessary to protect the busbars is
specified.
Generally, the elements of the protection architecture will be identified in a similar manner to
the principal parts of the substation e.g. by the letters A and B.
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-44
8.
STANDARD CONFIGURATIONS
The following information relates only to the more common standard schemes. For further
information on the accommodation of other busbar configurations consult your AREVA
representative.
Here after is summarised the solution identification:
P746 mode selection
Single bus or radial bus with no CT coupling (1 zone)
Set of CTs
Up to 6
Up to 18
Set of VTs
0 or 1
0 or 1
Mode
3 boxes mode
Up to 6
Up to 12
Up to 18
Up to 36
Set of VTs
0 or 1
0 to 2
0 or 2
0 to 2
Mode
One box
mode
3 boxes mode
3 boxes
mode
Note
AP
2 sets of
2 sets of
Up to 6
Up to 6
Up to 18
Up to 18
Set of VTs
0 or 1
0 to 2
0 or 1
0 or 2
Mode
3 boxes
mode
3 boxes mode
3 boxes
mode
Up to 18
Up to 18
Up to 6
Up to 6
Up to 12
Set of VTs
Mode
0 or 1
0 to 1
3 boxes
mode
One
mode
Note
box
2 sets of
Up to 36
0 or 1
0 or 2
0 to 2
3 boxes mode
3 boxes
mode
3 boxes
mode
1 sets of
2 sets of
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-45
AP
FIGURE 22: SINGLE BUSBAR APPLICATION WITH BUS SECTION ISOLATOR
The above example shows a single busbar with a bus section isolator. It is split into two
zones.
There are up to 6 feeders connected to the busbar. This configuration requires 1 P746.
If it was up to 18 feeders connected to the busbar. This configuration would require 3 P746.
There is no solution for more feeders.
The type of P746 used will depend on the i/o requirements of the scheme in question.
FIGURE 23: SINGLE BUSBAR APPLICATION WITH BUS SECTION CIRCUIT BREAKER
The above example shows a single busbar with a bus section circuit breaker. It is split into
two zones.
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-46
There are 4 feeders connected to the busbar. The bus section circuit breaker has CTs on
either side. This configuration requires 1 P746.
If it was up to 10 feeders connected to the busbar. This configuration would require 2 sets of
1 P746 or 3 P746.
AP
If it was up to 14 feeders connected to the busbar. This configuration would require 3 P746.
BB1
BB2
If it was up to 34 feeders connected to the busbar. This configuration would require 2 sets of
3 P746.
The type of P746 used will depend on the i/o requirements of the scheme in question.
It is recommended that the CTs for feeder protection are sited such as to overlap with the
CTs defining the limits of each busbar protection zone.
Application Notes
P746/EN AP/F21
MiCOM P746
(AP) 6-47
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-48
The additional P746 being for the bus section isolators is optional.
The number of additional P746 being dependant on the number of bus section/bus coupler
CTs. The type of P746 used for each bay will depend on the i/o requirements of the bay in
question.
P3792ENa
AP
FIGURE 26: DOUBLE BUS BAR WITH TWO CIRCUIT BREAKERS PER FEEDER
Application Notes
P746/EN AP/F21
MiCOM P746
9.
(AP) 6-49
9.1
Scheme is centralised.
Local, zone and scheme measurements various measurements are available locally
via the relay LCD or remotely via the serial communication link.
Event, fault and disturbance recording Comprehensive post fault analysis available via
event lists, disturbance records and fault records which can be accessed locally via the
relay LCD or remotely via the serial communication link.
Real time clock/time synchronisation Time synchronisation available via IRIG-B input.
Four settings groups Independent remotely selectable setting groups to allow for
customer specific applications.
CB and isolator state monitoring indication of the circuit breaker/isolator position via
the auxiliary contacts, scheme acts accordingly should discrepancy conditions be
detected.
Graphical programmable scheme logic allowing user defined protection and control
logic to be tailored to the specific application.
Function keys
The following default PSL logic illustrates the programming of function keys to enable/disable
the commissioning mode functionality.
Function Key 2 is set to Toggle mode and on activation of the key, the commissioning mode
will be in service as long as the function has been enabled in the Configuration menu. The
associated LED will indicate the state of the protection function in service as GREEN and
RED for the Overhaul mode.
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-50
10.
CT REQUIREMENTS
10.1
Notation
IF max fault
IF max
cont
int
Inp
In
RCT
RB
Vk
SVA
Nominal output in VA
KSSC
General recommendations for the specification of protection CTs use common rules of
engineering which are not directly related to a particular protection.
AP
10.2
10.2.1
e.g. A power line likely to import electricity at 20 kA gives rated primary current Inp as
1000 A.
In any case the maximum peak current shall be less than 90 In (90A for 1A input and 450A
for 5A Input) i.e. 32 In RMS fully offset.
This recommendation is used for the majority of line or transformer protection applications.
The CT must be sized so as not to saturate during internal faults:
For each CT, IFeederMax = maximum contribution of the feeder to an internal fault (could be
different for each feeder):
Vk > IFeederMax * (RCT + RB)
Note:
Application Notes
P746/EN AP/F21
MiCOM P746
10.2.2
(AP) 6-51
Class X according to British Standard: Minimum knee point voltage for saturation
Vk min = secondary IF max x (RCT + RB)
With secondary IF max not less than 20 (if IF max < 20 In then IF max = 20)
Note:
Class 5P to IEC 185. Conversion of class X (BS) with the 5P equivalent (IEC)
3.
Class TPX and TPY according to IEC 44-6. IEC defines a composite error as a
percentage of a multiple of the rated current (IN) on a definite load SVA.
e.g.
This definition indicates that the composite error must be lower than 5%, for a primary
current of 20Inp when the external load is equal to 2 ohms (50VA to In). If secondary
resistance, RCT, is known it is easy to calculate the magnetising EMF developed with the
fault current (20In). Actually if the error is 5% (= 5A) with this EMF, the point of operation is
beyond the knee point voltage for saturation. By convention one admits that the knee point
voltage, Vk, is 80% of this value. For a conversion between a class 5P (IEC) and a class X
(BS) CT one uses the relation:
Vk=0.8 X [(SVA x Kssc)/In + (RCT x Kssc x In) ]
SVA = (In x Vk/0.8 Kssc) RCT x In2
In particular cases, calculation could reveal values too low to correspond to industrial
standards. In this case the minima will be: SVA min = 10 VA 5P 20 which correspond to a
knee point voltage of approximately Vkmin = 70 V at 5A or 350V at 1A. Class TPY would
permit lower values of power, (demagnetisation air-gap). Taking into account the weak
requirements of class X or TPX one can keep specifications common.
For accuracy, class X or class 5P current transformers (CTs) are strongly recommended.
The knee point voltage of the CTs should comply with the minimum requirements of the
formulae shown below.
Vk
k (RCT + RB)
Where:
Vk
Dimensioning factor
RCT
CT secondary resistance
RL
RB
Burden resistance
X/R
Primary system X/R ratio (for the P746 system, X/R up to 120)
>
With RB = 2 RL
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-52
10.3
AP
C50
C100
C200
C400
C800
Vk
Vk
Vk
Vk
Vk
0.04
56.5
109
214
424
844
200/5
0.8
60.5
113
218
428
848
400/5
0.16
68.5
121
226
436
856
800/5
0.32
84.5
137
242
452
872
1000/5
0.4
92.5
145
250
460
880
1500/5
0.6
112.5
165
270
480
900
2000/5
0.8
132.5
185
290
500
920
3000/5
1.2
172.5
225
330
540
960
CT Ratio
RCT (ohm)
100/5
For 5A CTs, the typical resistance is 0.0004 ohm secondary per primary turn (for 1A
CTs, the typical resistance is 0.0025 ohm secondary per primary turn).
2.
Given:
1.
2.
3.
Where:
Vk
= C Rating
In
= 5A
RCT
Kssc = 20 times
Application Notes
P746/EN AP/F21
MiCOM P746
11.
(AP) 6-53
6A
10A Fuse
15 or 16A Fuse
24 to 54V
Not permitted
60 to 125V
12
Not permitted
138 to 250V
10
16
Not permitted
Alternatively, miniature circuit breakers (MCB) may be used to protect the auxiliary supply
circuits.
AP
P746/EN AP/F21
Application Notes
MiCOM P746
(AP) 6-54
AP
BLANK PAGE