General Description
Application Information
Multiple Ratings
DO-III Expulsion Fuses are manufactured in Current
Sensing, Dual Sensing, and Dual Element types of fuses per
Table1. Current Sensing Fuse Links sense secondary faults,
extreme overload currents and transformer faults, while the
Dual Sensing and Dual Element Fuse Links additionally detect excessive transformer fluid temperature to keep damage caused by extreme temperature environments and longterm overloads from occurring.
The first method is to use the time versus current characteristics curves (TCC Curves) of the DO-III Expulsion Fuse Link
and the TCC Curves of related system devices and confirm
that the DO-III Expulsion Fuse Link curve lies between its
nearest upstream and downstream device curves.
Table 1
Current Sensing
Dual Sensing
Dual Element
Fuse Style
Fuse Style
1B11143G04
1B11144G03
3 1B11145G03
1B11143G06 10 1B11144G05
8 1B11145G04
Fuse Style
10
15
25
37.5
50
75
100
167
250
333
500
2.4
06b
08b
10b
10
12
14b
14
17b
-
4.16
04b
06b
08b
08
10
12b
12
14b
16
17b
-
4.8
04b
06b
06
08
10b
10
12
14b
16b
17b
-
Primary Voltage in kV
7.2 7.62 8.32 12.0 12.47 13.2 13.8
04b 04b 04b 04b 04b 04b 04b
04b 04b 04b 04b 04b 04b 04b
06b 04b 04b 04b 04b 04b 04b
06 06 06 06b 06b 04b 04b
08b 08b 08b 06b 06b 06b 06b
10b 08b 08b 08b 08b 08b 06
10 10 10 08 08
08 08
12 12 12 10 10
10 10
14b 14b 14b 12 12
12 12b
16b 14 14b 14b 12
12 12
17b 17b 16 14 14b 14b 14b
14.4
04b
04b
04b
04b
06b
06
08b
10
12b
12
14b
1B11145G11 40
1B11143G17 140
1B11145G12 50
Table 3
kVA
5
10
15
25
37.5
50
75
100
167
250
333
500
Primary Voltage in kV
2.4 4.16 4.8 7.2 7.62 8.32 12.0 12.47 13.2
03 03 03 03 03 03 03 03 03
05 05 03 03 03 03 03 03 03
08 05 05 03 03 03 03 03 03
10 08 08 05 05 05 03 03 03
12 10 08 08 08 08 05 05 05
12 10 10 08 08 08 05 05 05
14 12 12 10 10 10 08 08 08
14 12 12 10 10 10 08 08 08
14 14 12 12 12 10 10 10
14 14 14 12 12 12
- 14d 14 14 12 12 12
14 14 14
13.8
03
03
03
03
05
05
08
08
10
12
12
14
14.4
03
03
03
03
05
05
08
08
10
12
12
14
ABB
Table 4
Table 6
Primary Voltage in kV
2.4 4.16 4.8 7.2 7.62 8.32 12.0 12.47 13.2
5 03 03 03 03 03 03 03 03 03
10 05 04 04 03 03 03 03 03 03
15 07 05 05 03 03 03 03 03 03
25 09 06 06 04 04 04 03 03 03
37.5 11 09 08 06 06 06 05 05 04
50 12 09 09 07 07 07 06 06 05
75 - 12 11 09 09 09 07 06 06
100 - 12 12 09 09 09 09 09 07
167 - 12 12 12 11 11 09
250 - 12 12 11
333 - 12 12 12
kVA
13.8
03
03
03
03
04
05
06
07
09
11
12
kVA
14.4
03
03
03
03
04
05
06
07
09
11
12
45
75
112.5
150
225
300
500
750
1000
1500
Table 7
08
10
12
12
14
14
-
08
10
10
12
14
14
-
b.
c.
d.
e.
kVA
45
75
112.5
150
225
300
500
750
1000
a.
c.
kVA
45
75
112.5
150
225
300
500
750
1000
1500
2000
2500
ABB
08b 06
10b 08
10 10
12 12b
14b 12
14 14b
17b 16
17
-
Primary Voltage in kV
12.0,
13.8,
8.32
13.2
20.8c,d
12.47
14.4
06b 04b 04 b 04b 04b
06 06b 06 b 06b 04b
08 06 06 06 06b
10b 08b 08 b 08b 06b
10 10b 10 b 08 08b
12 10 10 10
08
14b 12 12 12
10
16b 14b 14 b 14b 12
17b 16b 14 14 14b
14
17b 17 b 16
17 17 16b
17b
d.
e.
f.
22.9c,d 24.94c
04b
04b
04b
06b
08b
08
10
12
12
14b
16b
17b
07
09
11
12
-
07
09
09
12
-
Primary Voltage in kV
12.0,
13.8,
8.32
13.2
20.8 c,d 22.9 c,d 24.94 d
12.47
14.4
04 03 03 03
03
03
03
06 04 04 04
03
03
03
07 06 06 06
05
04
04
09 07 07 07
06
05
05
11 09 09 09
07
06
06
12 09 09 09
09
07
07
12 12 12
11
09
09
12
11
11
12
12
b.
Table 5
Primary Voltage in kV
12.0,
13.8,
8.32
13.2
20.8c,d 22.9 c,d 24.94 d
12.47
14.4
05 03 03 03 03
03
03
08 05 05 05 03
03
03
08 08 08 08 05
05
05
10 08 08 08 05
05
05
12 10 10 10 08
08
08
12 10 10 10 08
08
08
14 12 12 12 10
10
10
12
12
14 14 14 12e
- 14e 14e 14e 12e
12
12
14
14
14
04b
04
04
06
06
08
10
12
12
14b
16b
16
ABB, Inc.
1128 S. Cavalier Drive
Alamo, TN 38001, USA
Telephone: 731-696-5561
Fax: 731-696-5269
www.abb.com
4.
Figure 3
5.
Use a 3/4 inch and 1/2 inch wrench to remove the end plug
from the fuse cartridge. (See Figure 4)
Figure 1
3.
Figure 4
6.
7.
Use a 3/4 inch wrench to remove the fuse cartridge from the
puller assembly and remove and discard the damaged fuse.
(See Figure 5)
Figure 2
Figure 5
NOTE: FOLLOW ALL FEDERAL, STATE AND LOCAL LAWS AND REGULATIONS WITH REGARD TO DISPOSING OF ALL MATERIAL
INCLUDING FUSES.
9.
Thread the end plug against the fuses castle end of the
fuseholder and tighten to 50-70 inch pounds.
(See Figure 6)
Remove the end plug and ensure that the catle ends have
flared evenly.
Replace the end plug and retighten to 50-70 inch pounds.
8.
Figure 7
ABB
ABB Inc.
1128 S. Cavalier Drive
Alamo, TN 38001, USA
Telephone: 731-696-5561
Fax: 731-696-5362
www.abb.com
Figure 6
Push down and rotate the locking handle, hooking it over the
shoulder of the housing.