Cla-Val, Relief Vana
Cla-Val, Relief Vana
Cla-Val, Relief Vana
U.L. Listed
U.L. Listed
F.M. Approved
2050B-4KG1 (Angle)
Typical Application
Operation Sequence:
At pump start, CLA-VAL Relief Valve modulates to
relieve excess pump capacity, maintaining positive
system pressure at the pump discharge.
When fire demand slows or ceases, CLA-VAL Model
50B-4KG1 opens, diverting entire pump output to
discharge, allowing fire pump to be stopped without
causing surging in the lines.
Fire Pump
Valve Capacity
Valve size (mm)
NFPA 20 Pump Rating
(GPM)
` CLA-VAL Europe
50
65
80
100
150
200
250
300
250
300
500
1000
2500
5000
11000
16000
www.cla-val.ch
Copyright CLA-VAL Europe - Specifications subject to change without notice - no contractual illustrations.
1 - 050100DE
C 02/10
Dimensions
50
65
80
100
150
200
250
Threaded Ends
238
279
318
300
-
A 150 Flanged
238
279
305
381
508
645
756
864
A 300 Flanged
254
295
337
397
533
670
790
902
300 x 150
327
389
522
657
773
883
84
102
116
146
200
254
300
356
305
311
318
330
363
414
457
522
38
43
65
81
109
135
235
273
Threaded Ends
121
140
159
E 150 Flanged
121
140
152
191
254
324
378
432
E 300 Flanged
127
149
162
200
267
337
395
451
Threaded Ends
83
102
114
F 150 Flanged
83
102
102
127
152
203
219
349
F 300 Flanged
89
109
111
135
165
216
236
368
G&H
152
170
197
200
216
248
337
362
Specifications
Size:
Globe 2" - 12" flanged
Angle 2" - 12" flanged
End Details:
Flanged: 150 and 300 ANSI B16.5
Flanged: ISO PN10, 16, 25
Other end details available
Pressure Ratings:
Class - 175 psi max.
Class - 300 psi max.
Pressure Adjustment Range:
Available in the following relief pressure ranges:
20-200 psi (150 Class)
100-300 psi (300 Class)
Temperature Range:
Water Max. 180F / 82C
Materials
Purchase Specifications
The Fire Pump Pressure Relief Valve shall modulate to relieve excess pressure in a fire protection system. It shall maintain
constant pressure in the system regardless of demand changes. It shall be pilot controlled and back pressure shall not affect
its set point. It shall be actuated by line pressure through a pilot control system and open fast in order to maintain steady
system pressure as system demand decreases. It shall close gradually to control surges and shall re-seat drip-tight within
5% of its pressure setting. The main valve shall be of the hydraulically-operated, pilot-controlled, diaphragm-type, globe or
angle valve. It shall have a single, removable, Teflon-coated seat, a grooved stem guided at both ends, and a resilient disc
with a rectangular cross section, being contained on 3 1/2 sides. No external packing glands shall be permitted and the
diaphragm shall not be used as a seating surface. The pilot control shall be a direct-acting, adjustable, spring-loaded,
diaphragm-type valve designed for modulating service to permit flow when controlling pressure exceeds spring setting. This
valve shall be UL Listed and Factory Mutual approved. It shall be the Model 50B-4KG1 (globe) or Model 2050B-4KG1
(angle) Pressure Relief Valve as manufactured by CLA-VAL Europe.
Special Note: The Model 50B-4KG1 Pressure Relief Valve is available with 300# ANSI inlet flange and 150# ANSI outlet
flange. This valve is used on higher pressure systems where 300# flange connections are required, and allows for adapting
of a discharge cone (generally supplied with 150# flange) to accommodate "atmospheric break" at relief valve discharge.
This relief valve, with 300# / 150# flanges is available on special order, and is UNDERWRITERS LABORATORIES LISTED
AND FACTORY MUTUAL APPROVED.
` CLA-VAL Europe
www.cla-val.ch
Copyright CLA-VAL Europe - Specifications subject to change without notice - no contractual illustrations.
2 - 050100DE
C 02/10