When To Us A Line or Load Reactor
When To Us A Line or Load Reactor
Input and output reactors serve very different purposes. Simply put, an input reactor protects the drive and an output reactor protects the motor. However, there are a few more details to determine the correct application.
Input (Line) Reactors
An input or line reactor helps protect a variable frequency drive (VFD) from input power line disturbances that could
cause nuisance tripping or damage to the drive. An input (line) reactor also reduces the harmonics that the VFD
generates back onto the line. Line reactors are sized based on the HP and voltage ratings of the drive in use. LenzeAC Tech uses 3% or 5% reactors. Input (line) reactors should be used in these circumstances:
. The input line power is prone to have disturbances such as surges, spikes, transients, etc.
2. The supply line power is very stiff (greater than 10 times the kVA rating of the connected VFD).
3. Where harmonic distortion is a concern. (IEEE-519 Harmonic Control in Electrical Power Systems)
Line reactors are connected in series between the input source and the VFD Controller. Refer to Figure 1 for proper
wiring installation. The reactor should be mounted as close to the drive as possible.
Input Line Reactor
Input Fuse
A1
A2
Input Fuse
B1
B2
Input Fuse
C1
C2
Controller
Motor
AN 0032/A1
www.lenze-actech.com
For general information only. Content subject to change without notice.
July 2008
1-508-278-9100
Application Note
5% Impedance Line Reactors
5% impedance line reactors have the same benefits as the 3% reactors plus they provide maximum harmonic mitigation without added capacitance. These harmonic signals produce distortion levels that may not be acceptable for
certain high frequency or noise sensitive equipment. Use of them will help to comply with the IEEE 519 Standard
and reduce motor operating temperature and motor noise.
Multiple Input (Line) Reactors
In applications involving multiple drives in parallel, having more than one VFD connected to a common power line
requires one line reactor per drive. Individual reactors will provide proper filtering and optimum surge protection for
each VFD and reduce crosstalk between each unit. A single reactor connected to multiple VFDs does not provide
adequate protection, filtering or reduce harmonic distortion when the system is partially loaded.
Each line reactor is connected in series between the input source and the VFD Controller. Refer to Figure 2 for
proper wiring installation. Each set of input lines to the drive should be in its own separate steel conduit. The reactor
should be mounted as close to the drive as possible.
Input Line Reactors
Input Fuse
A1
A2
Input Fuse
B1
B2
Input Fuse
C1
C2
Input Fuse
A1
A2
Input Fuse
B1
B2
Input Fuse
C1
C2
Controller
Motor
Controller
Motor
Copyright 2008 by AC Technology
AN 0032/A1
www.lenze-actech.com
For general information only. Content subject to change without notice.
July 2008
1-508-278-9100
Application Note
If the distance is between 500 and 1000 ft, you would use a special type of filter called a dV/dT filter, as they
provide better protection at these extreme distances. This also varies depending on output cable specs, shielding,
power conditions, and noise suppression as well as isolation techniques.
Load reactors are connected in series between the VFD Controller and the motor. Refer to Figure 3 for proper wiring
installation. The reactor should be mounted as close to the drive as possible.
Output Load Reactor
Input Fuse
Input Fuse
Controller
Input Fuse
A1
A2
B1
B2
C1
C2
Motor
Controller
A1
A2
B1
B2
C1
C2
Motor
Motor
Copyright 2008 by AC Technology
AN 0032/A1
www.lenze-actech.com
For general information only. Content subject to change without notice.
July 2008
1-508-278-9100