This document calculates the thermal resistance (R-value) and thermal transmittance (U-value) of insulated GRC wall panels for a project expanding Dubai Mall's Fashion Avenue. It determines U-values for different wall configurations and building areas, finding values between 0.143 to 0.242 W/m2K. Taking the average of area calculations and the upper and lower thermal resistances, the overall U-value is determined to be 0.180 W/m2K, within specification requirements.

Uploaded by

Kilaru Hareesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views9 pages

Thermal Conductivity

This document calculates the thermal resistance (R-value) and thermal transmittance (U-value) of insulated GRC wall panels for a project expanding Dubai Mall's Fashion Avenue. It determines U-values for different wall configurations and building areas, finding values between 0.143 to 0.242 W/m2K. Taking the average of area calculations and the upper and lower thermal resistances, the overall U-value is determined to be 0.180 W/m2K, within specification requirements.

Uploaded by

Kilaru Hareesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 9

TERRAZZO DUBAI CO. L.L.C.

AL QUOZ, DUBAI, LLC

Sheet No.:

Project Name :

DUBAI MALL - Fashion Avenue Expansion


DUBAI

Customer :

C1

Cal.:

DUTCO BALFOUR BEATTY LLC


Prepared by:

Consultant:

WSP

Rev.:

Date

11/1/2015

Hareesh

Checked by:

Date

Calculation of the Thermal Resistance (R-value) and Thermal Transmittance U-value


for Insulated GRC Wall Panel
Item
No.

Elements

Thickness
(mm)

K-Value R - Value
( mK/W )
(W/mK)

External GRC Panel

15

0.034

0.441

Rockwool

225

0.037

6.08

Block wall

150

0.311

0.483

Total R-Value

REMARKS

7.01

RT = RGRC + RROCKWOOL+ RBLOCKWALL


RT = 0.441 +5.41+ 0.483
= 7.01 mK/W
Therefore :
U value = 1

RT

1
7.01 mK/W

.. OK Safe ( lesser U - value is better )

U value =

0.143

W/mK < 0.2W/mK

(Specification
Value = 0.2)

(As per
DM AR No.66
Requirement)

Weighted Average With Above thickness


0.180 W/M2K
Thermal transmittance 'U' value calculated is as per the requirement in the specification.

Existing
Rock
wool(150)
Added 50
Total:200

TERRAZZO DUBAI CO. L.L.C.


AL QUOZ, DUBAI, LLC

Project Name :

C1

Cal.:

DUTCO BALFOUR BEATTY LLC


Prepared by:

Consultant:

Rev.:

Date

11/1/2015

DUBAI MALL - Fashion Avenue Expansion


DUBAI

Customer :

Sheet No.:

WSP

Hareesh

Checked by:

Date

Calculation of the Thermal Resistance (R-value) and Thermal Transmittance U-value


for Insulated GRC Wall Panel
Item
No.

Elements

Thickness
(mm)

K-Value R - Value
( mK/W )
(W/mK)

External GRC Panel

15

0.034

0.441

Rockwool

125

0.037

3.4

Concrete

400

1.300

0.31

Total R-Value

Remarks

Existing
Rock
wool(50)
Added 50
Total:100

4.1

RT = RGRC + RROCKWOOL+ RBLOCKWALL


RT = 0.441 +2.7 + 0.31
= 4.1 mK/W
Therefore :
U value = 1

RT

1
4.1 mK/W

U value =

W/mK0.2W/mK
<
(As per
DM AR No.66
Requirement)

.. OK Safe ( lesser U - value is better )


Weighted Average With Above thickness

0.242

0.180 W/M2K

TERRAZZO DUBAI CO. L.L.C.


3

Sheet No.:

Project Name :

DUBAI MALL - Fashion Avenue Expansion


DUBAI
Cal.:

Customer :

DUTCO BALFOUR BEATTY LLC

C1

Rev.:
Date

11/1/2015

Prepared by: Hareesh


WSP
Checked by:
Date
Calculation of the Thermal Transmittance U-value for Insulated GRC Wall Panel
Consultant:

Thermal Resistance considering different areas in the building (Typcial)

AREA 1

Assume the highlighted column and beam concrete structure


AREA 1
(Elev 3-Typ
Floors)

Item No.

GRC cladded Sections

U Value
Calculated

Area %

U value average

Block Wall (9565 x 5000 - 7826000)


= 39999000 mm2

0.143

50.66

0.072

Concrete Beam (9565 x 1000 x 2)


= 19130000 mm2

0.242

24.23

0.059

Concrete Column (6000 x 1000 x 2)


= 12000000 mm2

0.242

15.20

0.037

Concrete column stiff (9565 x 400 + 400 x 5000 x 2)


= 7826000 mm2

0.242

9.91

0.024

TOTAL AREA = 30608000 + 19130000 + 12000000


+ 17217000 = 78,955,000 mm2
Average U Value for Area 1

0.192

AREA 2
(Elev 3Level 3 &
Level4 )

Assume the highlighted column and beam concrete structure

AREA 2
(Elev 3 Level 3 &
Level4 )

Item No.

GRC cladded Sections

U Value
Calculated

Area %

U value average

Block Wall ( 12483 x 10300) - 8080000 =


120494900mm2

0.143

39.32

0.056

Concrete Beam (10083 x 1000 x 2) + ((6236 + 1370


+ 2947) x 900) = 29663700mm2

0.242

9.68

0.023

Concrete Column (13000 x 1000) + (13000 x 1400) =


148208000 mm2

0.242

48.36

0.117

Concrete column stiff (( 5550 + 5100 +5000 + 4550)


x 400) = 8080000 mm2

0.242

2.64

0.006

TOTAL AREA = 120494900 + 29663700 +


148208000 + 8080000 = 306,446,600 mm2
Average U Value for Area 2

0.203

Assume the highlighted column and beam concrete structure

AREA 3
(Elev 3 - GF)

Item No.

U Value
Calculated

GRC cladded Sections

Area %

U value average

Block Wall (9565 x 6000 - 8626000)


= 48764000 mm2

0.143

55.09

0.079

Concrete Beam (9565 x 1000 x 2)


= 19130000 mm2

0.242

21.61

0.052

Concrete Column (6000 x 1000 x 2)


= 12000000 mm2

0.242

13.56

0.033

Concrete column stiff (9565 x 400 + 400 x 6000 x


2)= 8626000 mm2

0.242

9.74

0.024

TOTAL AREA = 48764000 + 19130000 + 12000000


+ 8626000 = 88,520,000 mm2
Average U Value for Area 3

0.187

Summary based on values obtained at different areas


Considering the average values of Area 1 , Area 2 & Area 3
Average Thermal transmittance U = 0.192+0.203+0.187
3
U value =

0.194

0.194

W/mK < 0.2W/mK


(As per
DM AR No.66
Requirement)

TERRAZZO DUBAI CO. L.L.C.


AL QUOZ, DUBAI, LLC

Sheet No.:

Project Name :

DUBAI MALL - Fashion Avenue Expansion


DUBAI

Customer :

C1

Cal.:

Rev.:
Date

DUTCO BALFOUR BEATTY LLC

2
11/1/2015

Prepared by:
Consultant:

WSP

Checked by:

Date

Calculation of the Thermal Transmittance U-value for Insulated GRC Wall Panel
Total Thermal Resistance considering different areas and combining in parallel the total resistance
of all possible heat flow paths through the building element.
Summary
1 Upper resistance limit (Rupper)

7.01

W/mK

2 Lower resistance limit (Rlower)

4.1

W/mK

RT =

7.01 + 4.1
2

3 Thermal Resistance (RT) from


RT = R upper + R lower
2

5.555

Therefore :
U value = 1

RT

1
5.555

U value =

0.180

W/mK < 0.2W/mK

mK/W
(As per
DM AR No.66
Requirement)

.. OK Safe ( lesser U - value is better )