Control and Relay Panel
Control and Relay Panel
PANEL
March 2015
Engineering Department
WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
Page 1 of 104
1.00
SCOPE:
1.01
The specification covers design, engineering, manufacture, testing & supply delivery at site
of Control and relay Board and protection relay panels inclusive of internal wiring and
with arrangement for external connection to various Switchyard equipments and Control
room building equipments as necessary. The Contractor has to design the Schematics for
protection and Control of all equipments including monitoring indications, visual and audible
alarm, interlocking schemes between different equipment.
Any other requirement which
are not specifically covered here but which are necessary for successful commissioning
of the Sub-station are also within the scope of the Contract. The same shall be indicated
by the bidder with their price for WBSETCL's consideration.
1.02
The equipment manufactured should conform to the relevant standards and of highest quality
of engineering design and workmanship. The equipment manufactured
shall
ensure
satisfactory and reliable performance throughout the service life.
2.00
STANDARDS:
2.01
Unless otherwise specified all equipment and material shall conform to the latest IS applicable
standards. Equipment complying with other internationally recognised standards will also be
considered if it ensures performance equivalent or superior to Indian standards. In the event
of supply of equipment conforming to any international\ internationally recognised standards
other than the standard listed below, the salient features of comparison shall be brought
out and furnished along with the bid. One copy of such standard specification in English
language shall be enclosed with the tender.
2.02
The equipment provided shall also comply with the latest revisions of Indian Electricity act
and Indian Electricity rules and any other applicable Statutory provisions, rules and
regulations.
2.03
All equipment provided under the specification shall generally conform to the latest issue of
the following:
IEC/Indian Standard No.
Title
Indicating Instrument
Page 2 of 104
3.00
IS 6236
Recorders
IS 722
IEC 679
Static TVM
IS 2705
Current Transformers
IS 3156
Voltage Transformer
IS 4237
General requirement for Switch gear and Control gear for voltage
not exceeding 1 KV.
IS 375
IS 8686
REQUIRED QUANTITIES:
Quantity of C & R panels are to be assessed by the bidders from the Schedule enclosed
with this specification. However, if any corridor in the switchyard layout is left for future use
in between two proposed bays included in the project, blank panels without any equipment,
relays etc but only with matching mimic are to be supplied.
4.00
Technical particulars to be considered for Design of Control and relay board, and
protection panels:
4.01
SYSTEM DETAILS :
a) Nominal System
Voltage
b) Highest System
Voltage
c) Number of Phases
400KV
------400KV
220KV
----220KV
132KV
----132KV
33KV
----33KV
420KV
245KV
145KV
36KV
d) Frequency
e) Grounding
f) Maxm. fault
Current
50KA
(rms)
Page 3 of 104
40KA
(rms)
31.5KA
(rms)
through E.Tr.
4.02
AUXILIARY SUPPLY :
D.C.Supply voltage shall be normally fed from Battery charger and battery connected in
parallel which is 220V +/- 10%. In case of failure of the AC supply to battery charger, DC
Supply voltage will be available automatically from lead acid Battery. The D.C Supply voltage
may vary from -10% to + 10%. The D.C. system shall be 2 wire with necessary positive earth
fault and negative earth fault annunciation scheme. The ripple content in the D.C. supply
from charger will be less than 2%.
AC Auxiliary supply voltage for the C&R panel shall be 230V, 1-phase, 50Hz grounded with
+/- 10% voltage variation.
Page 4 of 104
5.00
5.01
Sl.
No.
Description
1. a)
b)
i
ii
c)
No
of
Core
Core
No.
Application
Current
Ratio
Output
Burden
(VA) at
Lower
Ratio
20
20
ISF
(Max)
Accuracy
class as
per IS
2705
Min Knee
point
Voltage (V)
Max CT Secy
Winding
Resistance
(W)
PS Class
2000/1000
10/5
30/60
PS Class
2000/1000
10/5
30/60
PS Class
2000/1000
10/5
30/60
PS Class
2000/1000
10/5
30/60
PS Class
3000/2000
15/10
30/45
PS Class
3000/2000
15/10
30/45
PS Class
1000V
2.5
30 at Vk/2
Max
excitation
current (mA)
at Knee point
Voltage
0.2
0.2
Bushing CT (Transformer)
400KV side,
220kV side &
Neutral of 315
MVA,
400/220/33KV
Transformer
Protection
1000/1A
Page 5 of 104
Sl.
No.
d)
ii
2. a)
ii
Description
No
of
Core
Core
No.
Application
Current
Ratio
Output
Burden
(VA) at
Lower
Ratio
ISF
(Max)
Accuracy
class as
per IS
2705
Min Knee
point
Voltage (V)
Max CT Secy
Winding
Resistance
(W)
Max
excitation
current (mA)
at Knee point
Voltage
Neutral side of
80MVAR Bus
Reactor
Protection
200/1A
PS Class
200V
40 at Vk/4
Protection
200/1A
PS Class
200V
40 at Vk/4
Protection
200/1A
PS Class
200V
40 at Vk/4
Metering
Protection
PS Class
2000/1000V
10/5
30/60
Protection
PS Class
2000/1000V
10/5
30/60
Protection
200/1A
20001000/1A
20001000/1A
200/1A
PS Class
200V
40 at Vk/4
WTI
Metering
Protection
5/4/2
30/37.5/75
Protection
Protection
Protection
Metering
Protection
Protection
10
10
220 KV CT (Bay)
Feeder,
Transformer &
Bus Transfer Bay
Bus Coupler
1000-800400/1A
1000-800400/1A
1000-800400/1A
1000-800400/1A
1000-800400/1A
20001600/1A
20001600/1A
20001600/1A
20
0.2
PS Class
PS Class
PS Class
PS Class
20
Page 6 of 104
1500/1200/
600V
1500/1200/
600V
1500/1200/
600V
1500/1200/
600V
5/4/2
5/4/2
5/4/2
30/37.5/75
30/37.5/75
30/37.5/75
0.2
PS Class
2000/1600V
10/8
30/37.5
PS Class
2000/1600V
10/8
30/37.5
Control & Relay Panel
Sl.
No.
b)
ii
c)
3. a)
Description
No
of
Core
Core
No.
Application
Current
Ratio
Output
Burden
(VA) at
Lower
Ratio
ISF
(Max)
Accuracy
class as
per IS
2705
Min Knee
point
Voltage (V)
Max CT Secy
Winding
Resistance
(W)
Max
excitation
current (mA)
at Knee point
Voltage
Bushing CT (Transformer)
220KV side,
132KV side &
Neutral of
160MVA
Transformer
220KV side &
Neutral of 50MVA
Transformer
Protection
800/1A
PS Class
1000V
2.5
30 at Vk/2
Protection
400/1A
PS Class
800V
1.5
30 at Vk/2
Metering
200-100/1A
Protection
200-100/1A
PS Class
1200/600V
4/2
30
Protection
200-100/1A
PS Class
1200/600V
4/2
30
Metering
Protection
1000-800400/1A
1000-800400/1A
1500/1200/
600V
5/4/2
30/37.5/75
Protection
5/4/2
30/37.5/75
Protection
1000-800400/1A
PS Class
1500/1200/
600V
5/4/2
30/37.5/75
Protection
1000-800400/1A
PS Class
1500/1200/
600V
5/4/2
30/37.5/75
20
0.2
132KV CT (Bay)
Feeder,
Transformer &
Bus Transfer Bay
20
0.2
PS Class
PS Class
1000-800400/1A
Page 7 of 104
1500/1200/
600V
Sl.
No.
Description
No
of
Core
Core
No.
Application
Metering
20001600/1A
Protection
20001600/1A
PS Class
2000/1600V
Protection
20001600/1A
PS Class
2000/1600V
Protection
400-300/1A
PS Class
ii
Bus Coupler Bay
b)
i
Bushing CT (Transformer)
132KV side &
1
1
Neutral of 50MVA
Transformer
Current
Ratio
Output
Burden
(VA) at
Lower
Ratio
ISF
(Max)
Accuracy
class as
per IS
2705
20
0.2
Min Knee
point
Voltage (V)
Max CT Secy
Winding
Resistance
(W)
Max
excitation
current (mA)
at Knee point
Voltage
8/6.4
30/37.5
8/6.4
30/37.5
800-600V
1.5
30 at Vk/2
ii
33KV side of
50MVA
Transformer
Protection
1000/1A
PS Class
500
2.5
30 at Vk/2
iii
Protection
150/1A
PS Class
600
1.5
30 at Vk/2
Protection
800/1A
PS Class
400
2.5
30 at Vk/2
Metering
Protection
30/37.5/75
Protection
1000/800/40
0
1000/800/40
0
4/3.2/1.6
1000-800400/1A
1000-800400/1A
1000-800400/1A
4/3.2/1.6
30/37.5/75
iv
4. a)
33KV CT (Bay)
i
Feeder,
Transformer,
Capacitor Bank &
Bus Transfer Bay
WBSETCL / TECH SPEC / Rev.-1
20
0.2
PS Class
PS Class
Page 8 of 104
Sl.
No.
b)
i
Description
No
of
Core
ii
Bus Coupler Bay
5.02
Core
No.
Application
Metering
Protection
Protection
Metering
Protection
(O/C & E/F)
Current
Ratio
1000-800400/1A
1000-800400/1A
1000-800400/1A
1000-800/1A
Output
Burden
(VA) at
Lower
Ratio
ISF
(Max)
Accuracy
class as
per IS
2705
20
0.2
30
1000-800/1A
Min Knee
point
Voltage (V)
Max CT Secy
Winding
Resistance
(W)
PS Class
250/200/100
4/3.2/1.6
30/37.5/75
PS Class
1000/800/40
0
4/3.2/1.6
30/37.5/75
250/200
4/3.2
30 at Vk
Max
excitation
current (mA)
at Knee point
Voltage
0.2
PS
CORE DETAILS OF VT
Sl. No.
Description of Core
Number of
Core
100 VA , 3P
2 a)
50/200 VA , 3P
b)
3 a)
b)
3
3
2
50/100 VA, 3P
50/200 VA , 3P
50/100 VA, 3P
4 a)
100 VA, 3P
b)
50 VA, 0.2
50 VA, 3P
Page 9 of 104
5.03
Indicating instruments (Ammeter, Voltmeter, MW meter, MVAR meter) shall be set as per the
CT ratio mentioned in the following table:
Ammeter Range: 400kV AIS
400kV (GIS)
220kV (AIS & GIS)
Feeder
2000A
Line side
3000A
Feeder
800A
315MVA
1000A
160MVA Transformer,
800A
Transformer,
220kV side
400kV side
Reactor
200A
50MVA Transformer,
300A
220kV side
Bus Transfer
2000A
--Bus Transfer (for AIS
800A
only)
Bus Coupler
2000A
Bus Coupler
1600A
132kV AIS
Feeder
600A
160MVA
800A
Transformer,
132kV side
50MVA
300A
Transformer,
132kV side
Bus Transfer
800A
132kV GIS
Feeder
800A
160MVA
800A
Transformer,
132kV side
50MVA
300A
Transformer,
132kV side
Bus Coupler
1600A
1000A
0-500kV
0-250kV
0-150kV
0 40kV
400kV
Feeder
Bus Tr
Bus Coupler
315MVA Trafo
Reactor
220kV
Feeder
160MVA Trafo
315MVA Trafo
Bus Trf
Bus Coupler
One & Half Breaker System
Feeder
160MVA Trafo
MW
MVAR
0 to 1400
0 to 1400
0 to 800
---
0 to 800
0 to 100
0 to 300
0 to 300
0 to 400
0 to 400
0 to 600
0 to 600
0 to 600
0 to 600
132kV
WBSETCL / TECH SPEC / Rev.-1
Page 10 of 104
Feeder
160MVA Trafo
Bus Trf
Bus Coupler
50MVA Trafo
33kV
Feeder
0 to 100
0 to 100
0 to 200
0 to 70
0 to 200
0 to 70
0 to 25
0 to 25
6.00
6.01
GENERAL REQUIREMENT:
a)
The control and relay board panels for 400KV system shall be duplex/simplex type (as
applicable as per Bus configuration) so as to accommodate all the control equipment,
breaker relays, meters etc. excepting the protective relays and its aux. relays/accessories as
necessary for completeness of the protection/control scheme without overcrowding and
cramping. Separate protection panels of simplex type (minimum 2 nos) shall be provided for
accommodating the protective relays and its aux. relays/accessories as required to fulfill the
scheme requirement.
b)
The control and relay board panel for 220KV system and 132KV system shall also be duplex
type for accommodating all relays and aux. relays for protection of respective circuit along
with control equipment, meters etc. as necessary for
completeness
of
the
protection/control scheme without overcrowding and cramping. However, the 33KV C&R
board panels shall be simplex type for accommodating all the control, protection and
metering equipment properly.
c)
Type
Duplex
Depth (mm)
1982
Width (mm)
as necessary but limited
to 1000 mm
Height (mm)
2312 including channel base.
Simplex
610
-do-
There shall be a corridor of 762 mm wide and access doors of 1900 mm height with latch at
two ends of duplex panel board for inspection. The door with door frame shall be detachable
type so that the same can be fitted to newly erected panel of similar design if any new C&R
panel is added. The access door for the simplex type panel shall be at the back side and of
1900 mm height.
d)
The front and rear parts of duplex type C&R panel shall be detachable and all inter
connection between front and rear panels shall be through terminal connector and preferably
underneath the top cover. The interconnection between the simplex type control and relay
panel and duplex type respective C&R panels where applicable will be made through cables to
be laid in the cable trenches under those panels.
e)
The complete panel shall incorporate all necessary instruments, meters, relays, auxiliary
relays, control switches, indicating lamps, mimic, annunciators, audible alarms, horizontal
and vertical wiring trough, wiring supports, interior lighting system, terminal blocks fuses
and links etc.
Page 11 of 104
6.02
CONSTRUCTIONAL FEATURES:
a)
The control & relay board shall comprise of cubicle type panels placed in juxta position to
form a continuous board for each system voltage. If the panels are required to be aligned in
right angular formation, the tenderer shall be required to arrange dummy/covering plates for
the uniform formulation without any extra price.
b)
c)
Panels shall be completely metal enclosed and shall be dust, moisture and vermin proof.
The enclosure shall provide a degree of protection not less that IP-31 in accordance with IS2147.
d)
Panels shall be free standing, floor mounting type and shall comprise structural frames
enclosed completely with specially selected smooth finished, cold rolled sheet steel of
thickness not less than 3 mm for weight bearing members of panels such as base frame,
front sheets and door frames and not less than 2mm for sides, door, top & bottom
portions. There shall be sufficient reinforcement to provide level surfaces, resistance to
vibration and rigidity during transportation and installation.
e)
All doors, removable covers and panels shall be of gasketed all around with neoprene
gaskets. Ventilating covers, if provided shall have screens and filters. The screens shall be
made of either brass or GI wire mesh.
f)
Design, material selection and workmanship shall be such as to result in neat appearance,
inside and outside with no welds, rivets or bolt head apparent front outside, with all exterior
surfaces tune and smooth.
g)
Metal seals in the form of metal channels properly drilled shall be furnished by the Contractor
along with anchor bolts and necessary hardware for mounting the panels. Panels shall be
mounted on the other end of the channel.
h)
Cable entries to the panel shall be from the bottom. The bottom plates of the panel shall be
fitted with removable gland plates and fixed with cable glands. Necessary number of cable
glands of sizes to suit external cables to the panels shall be supplied by the bidder. Cable
glands shall be screwed type made of brass and shall be suitable for PVC armoured cable.
6.03
that the
equipment
specified
and
such unspecified
required for completeness of protection/control scheme be
the panels without congestion and if necessary to provide
price increase at a later date on this account shall be allowed.
MOUNTING:
a)
All equipment on and inside the panels shall be mounted and completely wired to the
terminal blocks ready for external connection. The equipment of panel shall be mounted
flush.
b)
Page 12 of 104
c)
The contractor shall carry out cut out, mounting and wiring of the bought out items which are
to be mounted in the panel in accordance with the corresponding equipment manufacturer's
drawings.
d)
The centre line of switches, push buttons and indicating lamps shall be not less than
750 mm from the bottom of the panel. The centre line of relays and meters and recorders
shall be not less than 450 mm from the bottom of the panel.
e)
The centre lines of switches, push buttons and indicating lamps shall be matched to give a
neat and uniform appearance. Likewise the top of all meters, relays and recorders etc. shall
be in one line.
f)
The control switches for circuit breakers and isolators shall be located on the mimic diagram
corresponding to their exact position of the controlled equipment in the single line drawing.
The location of the switches shall be within working height from the floor level for easy and
comfortable operation.
g)
h)
All the panels in the control room shall be matched with the other panels of the same C&R
board in respect of dimension, colour and appearance. Control equipment on front side of the
panel shall be similarly placed.
i)
All the equipment connections and cabling shall be designed and arranged to minimise the
risk of fire and damage.
6.04
a)
b)
Sl. No.
1
PAINTING:
All unfinished surface of the steel panels and frame work shall be sand blasted to remove
rust, scale, foreign adhering material or grease.
A suitable rust resisting primer shall be applied on the interior and exterior surfaces of the
steel, which shall be followed by of an under coat suitable to serve as base and binder for the
finishing coat. The finishing coat on the exterior of the panel & on the interior faces shall be
as per following table: Painting
Colour
2
3
4
5
Type of Painting
Thickness of Paint
Phosphating
Special
Instruction
Page 13 of 104
6.05
a)
All wiring shall be carried out with 1100 V grade Single core, standard copper conductor
wires with PVC insulation conforming to IS 694 or equivalent International Standard.
b)
c)
Black
Earthing connection
Green
Black
Grey
d)
All internal wiring shall be securely supported, neatly arranged, readily accessible and
connected to equipment terminals and terminal blocks. Wiring gutters & trough shall be used
for this purpose.
e)
All wiring interconnecting the front cubicles with the near cubicles of duplex type panel
over the access corridor shall be wired in gutters held against the ceiling of the corridor by
means of screws and the interconnection shall be made through suitable terminal
connectors securely fixed on the panel.
f)
Longitudinal troughs extending throughout the full length of the panel shall be used for inter
panel wiring. Inter connections to adjacent panels shall be brought out to a separate set of
terminal blocks located near the slot of holes meant for taking the interconnecting
wires. All bus wiring for interpanel connection shall be provided near the top of the panels
running throughout the entire length of the panels.
g)
Wiring connected to the space heaters in the cubicles shall have porcelain beaded
insulation over a safe length from the heater terminals.
h)
Wire termination shall be made with solder less crimping type and tinned copper lugs which
firmly grip the conductor and insulation. Insulated sleeves shall be provided at all the wire
terminations. Engraved core identification plastic ferrules marked to correspond with panel
wiring diagram shall be fitted at both ends of each wire. Ferrules shall fit tightly on the wire
and shall not fall off when the wire is disconnected for any purpose. Termination shall be
such that no strand of a conductor shall left loose or overhanging. Conductor termination
shall be secured to the holding nuts/screws, terminal blocks etc. with washers interposed
Page 14 of 104
between the terminals/holding nuts/screw heads. The terminals shall be so connected that no
conductor ferrule code gets masked due to overlay of conductors.
i)
6.06
TERMINAL BLOCKS:
a)
All internal wiring to be connected to the external equipment shall terminate an terminal
blocks, preferably vertically mounted on the side of each panel. Terminal blocks shall be
1100 V grade and have 10Amp continuous rating, moulded piece, complete with insulated
barriers, stud type terminals, washers, nuts and lock nuts, inserts. The stud, washers, nuts,
locknuts, inserts shall be tin plated Brass/Brass. Terminal block design shall include markings
of terminals and the terminals shall be provided with transparent plastic, slip on/clip
on terminal covers. Markings on the terminal strip shall correspond to wire number and
terminal numbers on the wiring diagram.
b)
Terminal blocks for current transformer and voltage transformer secondary leads shall be
provided with test links and isolating facilities. Also current transformer secondary leads shall
be provided with short circuiting and earthing facilities of adequate rating.
c)
Each terminal block shall be provided with at least 20% spare terminals on each panel and
these spare terminals shall be uniformly distributed on all terminal block.
d)
In case of duplex panels, separate set of terminal blocks shall be provided with separate
internal cable entries for the front (control) and rear (relay) sections.
e)
Terminal blocks shall be suitable for connecting the following conductors on each side.
i)
All C.T. circuits.
: Two of 4.0 sq.mm. copper.
ii)
All P.T. circuits.
: Four of 2.5 sq.mm. copper.
iii)
AC/DC Power Supply Circuit
: Four of 2.5 sq.mm. copper.
iv)
All other circuits.
: Four of 1.5 sq.mm. copper.
f)
There shall be a minimum clearance of 250 mm between the first row of terminal blocks
and the associated cable gland plate. Also the clearance between two rows of terminal
blocks shall be minimum of 150mm.
g)
The number & sizes of the multicore incoming cable will be as per approved scheme. All
necessary cable terminating accessories such as gland plates packing glands, crimp type
tinned copper lugs, supporting clamps and brackets, wiring troughs and gutters etc. for cable
shall be included in contractor's scope of supply.
h)
All studs, nuts, screw etc. shall be threaded according to IS:7684 or equivalent International
Standards.
6.07
MIMIC DIAGRAM:
a)
Coloured mimic diagram and symbols showing the exact representation of the system shall be
provided in the front of control panels.
b)
Mimic diagram shall be made preferably of anodised aluminium or plastic of approved fast
colour material which shall be screwed on to the panel and can be easily cleaned. The mimic
Page 15 of 104
bus shall be 2mm thick. The width of the mimic bus shall be 10mm for bus bars and 7mm for
other connections. Indicating lamp, one for each phase for each bus shall be provided on the
mimic of Bus coupler panel of three Bus system or at Transfer bus panel of two bus system to
indicate bus charged condition.
c)
d)
6.08
LED Position Indicators, Round type, for all earth switches & isolators control switches and
discrepancy type control switch with flash type built-in indicating lamp, for circuit breakers
shall be mounted along the mimic diagram at appropriate location in 400KV, 220 KV and 132
KV duplex type C&R panels.
In 33 KV simplex type C&R panels, LED Position Indicators for the position indication of
isolators, earth switches and ON/OFF indication for such breaker shall be mounted along
the mimic diagram at appropriate location.
a)
All instruments, relays and such other similar electrical devices mounted on the control and
relay panel shall be provided with name plates bearing the manufacturer's name, serial
identifying number and the Electrical rating data.
b)
25mm wide plastic plates bearing suitable identification marks shall be fixed under the
terminal wiring at the test blocks, at the fuse blocks and at the cable terminals. Similar plates
shall be fixed on the exterior of the switch board in appropriate places to indicate function of
control switches, push button etc. such as isolator control switch, breaker control switch, DC
fail test, accept reset etc. Suitable identification marks shall be provided for individual casing
part of the relays and other equipment.
c)
50mm wide plastic plate bearing suitable circuit description (which will be furnished after
order is placed) etched in 30 mm size letters shall be provided for each panel and mounted
on the top of both outer and inner sides of the front and rear panels. These plates shall be
removable type.
d)
Each unit of control and relay panel shall be provided with a label located at the bottom on
the front and shall contain the following details:
i)
Manufacturer's name
ii)
P.O.no. and date
iii)
Drg. ref. no. that pertains to the panel.
Page 16 of 104
6.09
a)
Each unit of cubicle interior (both control and relay panel) shall be illuminated by CFL
connected to 230V single phase AC through individual switch for duplex type panel and
through Door switch for Simplex type panel. The illumination of the interior shall be free from
hand shadows and shall be planned to avoid any strain or fatigue to the wireman likely to be
caused due to subnormal or non uniform illumination. One emergency D.C. light (CFL) shall
also be provided for each relay panel with individual switch with proper identification mark.
b)
Corridor of the duplex type control and relay board formation should be illuminated with
adequate no. of Compact fluorescent lamps, AC operated, through door operated push button
switch provided at both sides.
c)
One 15 amps. 3 pin power socket outlets together with plug pins shall be provided at
convenient points in each panel with marking at the bottom for obtaining AC supply wherever
required.
d)
The above AC auxiliary supply and DC emergency lamp ckt. in each panel shall be HRC fuse
and link protected.
6.10
SPACE HEATERS:
Tubular space heater suitable for connection to the single phase AC supply in each panel
(both control and relay panel in case of duplex type) complete with switches and
thermostat located at convenient position shall be provided at the bottom side of the
cubicle to prevent condensation of moisture. The watt loss per unit surface temperature
of the heater shall be low enough to keep surface temperature well below allowable
heat.
The wattage of the heater shall be such as to keep 10 C above average ambient
temperature in the rainy season but the temperature shall not under any circumstances
damage the insulation of the wiring of the panel.
6.11
SAFETY EARTHING:
a)
All panels shall be provided with an earth bus securely fixed along with the inside base of
the panel extended throughout the length of the C&R board formation. The material and
size of the earth bus bar shall be 25mm x 6mm size copper. Provision shall be made for
extending the earth bus bars at a future date into new adjacent panels to be installed if any.
Provision shall be made at the end panels for connecting the same to the system earth grid
mat.
b)
Earthing of current free metallic parts or metallic bodies of the equipment provided in the
switchboard shall be done with soft drawn conductor of size not less than 2.5 sq.mm.
c)
The neutral point of star connected LV winding of instrument transformers and one corner of
the open delta connected LV side of instrument transformers shall be similarly earthed with
the main earth bar of the switchboard earthing system.
Page 17 of 104
6.12
7.00
INDICATING LAMPS:
a)
These lamps shall be of LED type and suitable for being operated on S/S D.C. voltage or AC
voltage or P.T. secondary supply as and where applicable. All Lamps shall be interchangeable,
panel mounting type with rear terminal connection and shall afford easy replacement from
the front of the panel. Lamps shall have translucent lamp covers to diffuse lights and
coloured Red, green, Amber, clear white or blue as specified. The lamp cover shall be of
screwed type, unbreakable and mounded from heat resisting material. The indicating lamps
with resistors shall withstand 120% of rated voltage on a continuous basis.
b)
c)
8.00
Function
---------C.B. spring charged/compressor
healthy indication
Colour lens
----------Blue
White
Amber
Red/Yellow/Blue
Red/Green
CONTROL SWITCHES:
a)
All control switches shall be of the rotary type provided with escutcheon plates clearly marked
to indicate status of the switch. They shall be semi flush mounted with only the switch front
plate and operating handle projected out. All such control switches shall be provided for
remote operation of isolators and circuit breakers.
b)
All Control switches shall be wire connected at the back. The contact mechanism shall be cam
operated. The contacts shall be silver faced and designed for liberal rating of the duty
involved. The contacts shall be provided with dust and vermin proof removable protection
cover. The protection cover shall preferably be of transparent, inflammable material made of
moulded dielectric material. Springs to be provided in the switch shall not be used as current
Page 18 of 104
carrying parts. The contacts provided in the switch shall be suitable for easy
assembly/disassembly during replacement of the contacts. The control switch springs shall be
strong to prevent any inadvertent operation due to a light touch on the handle.
c)
Control switches for 400KV, 220KV & 132KV circuit breakers shall be of discrepancy type with
built in pilot lamps and having two maintained contact positions for "ON" and "OFF" positions
and two momentary contact positions for "ON" and "OFF" impulse. The built-in pilot lamp
shall give a steady light when the position of the control switch corresponds to the position of
the associated circuit breaker. A flickering light shall be given by the same lamp when due to
hand operation or due to automatic tripping of the circuit breaker the position of the control
switch does not coincide with that of the corresponding circuit breaker. The arrangement to
provide the flickering voltage for the above purpose shall be made by the contractor. In order
to avoid continuous burning of the aforesaid built-in lamps associated with the control
switches, the said lamp shall be connected through a switch. The circuit should be such that
irrespective of the position of the aforesaid switch winking of the lamp shall not be affected
by change in respective control switch position. The winking of the control switch pilot lamp
shall be followed by an alarm annunciation after a preset time adjustable between 0-10 secs.
Switches complete with accessories for the above function shall be supplied.
d)
Control switches for 33KV circuit breakers, 400KV, 220KV isolators, 132KV isolators shall be
with pistol grip type operating handle having "ON & OFF" monetary operating position and an
automatic return to normal neutral position on release from operated positions.
9.00
a)
Instrument selector switches shall be provided for indicating instruments while change over
switches shall be provided for selective operation of controls such as auto/non auto reclose,
trip circuit transfer from main breaker to transfer breaker. Protection selector switches to be
provided in the Bus transfer bay shall be used for adopting the bus transfer bay
protection during Bay transfer. Condition when line side C.T. operated protection of any
bay develops any defect. All these switches shall be stay put type.
b)
Voltmeter selector switch shall be suitable for reading all line to line and line to neutral
voltage for effectively earthed system. This selector switch shall be of the rotary oval head or
knob type.
c)
Trip circuit transfer switch shall be of 3-position Normal-Inter-Transfer. Operating handle shall
be pistol grip, lockable at Normal position and key trapped at transfer position having one
common key for all 400KV, 220KV, 132KV and 33KV panels respectively for a particular Substation.
d)
Protection selector in Bus Transfer bay shall be lockable type, two/three position depending
upon scheme requirement.
e)
One four position selector switch for setting group selection in respect of distance relay in Bus
Transfer panel shall be provided.
f)
One three position selector switch for setting group selection in respect of numerical over
current & earth fault relay in Bus Transfer panel shall be provided.
g)
One five position Selector Switch for Earthing Transformer selection in each 33KV side
transformer C&R panel shall be provided.
Page 19 of 104
Synchronising switch with lock feature two positions, "ON & OFF" shall be provided on all
control panels except the 132/33KV Transformer panel and 33KV C&R panels. The switch
shall be semi flush mounting type.
b)
The switch shall be wired back connected. It's operation in the "ON position shall connect
the incoming and running bus potentials to the respective synchronising instrument and relay
mounted in a trolley, through a synchronising socket having sufficient nos. of ways. The
wiring between the synchronising switch, socket and the main breaker control switch shall be
such that when the main breaker control switch is operated to close position, the breaker
shall not receive a close command unless the synchronising switch is put to the 'ON' position
and receives a synchronising command. If the synchronising trolley is not within the scope of
supply for a particular sub-station, the terminal of the synchronising socket to be shorted
through a plug to be provided to cover the socket.
Push button switches, provided where required, shall be of the monetary contact type wired
back connected. They shall be semi flush mounted. They shall be provided with integral
inscription plates engraved with their functions.
b)
All push buttons shall be with a set of NO/NC contacts as required to fulfill the scheme
requirement. The contact faces shall be silver plated and shall able to make/break and carry
the rated current appropriate to the duty of the desired function.
Unless otherwise specified, all electrical indicating instruments shall be of digital type suitable
for flush mounting.
Instruments shall have 4-digit display; display height being not less than 25 mm
Instrument shall confirm to relevant IS and shall have an accuracy class of 0.5 or better. Watt
and Var meters shall have an indication of (+) and (-) to indicate EXPORT and IMPORT
Page 20 of 104
d)
e)
respectively.
Digital voltage and frequency meters shall be of class: 0.5 and shall have digital display of 5
and 4 digits respectively, with display size, not less than 25mm (height).
All indicating instruments shall preferably of size 72mm X 144mm.
12.02 TRANSDUCERS:
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
n)
Page 21 of 104
Two sets of batteries (220v), their respective chargers and DC boards shall be used for DC
supply to each 400KV control relay and protection panels as DC supply 1 and DC supply-2.
Necessary arrangement for Supervision of both the incoming DC Supplies shall be made.
b)
In each duplex type 400KV C&R panel, following circuits shall be connected to DC Supply 1
through suitable MCBs/ HRC fuses:
i)
Isolator control circuit
ii)
Synchronising circuit
iii)
Metering circuit
iv)
Indication circuit
v)
Annunciation circuit
vi)
CB Closing circuit
vii)
VT Selection circuit & CB Aux. Relay circuit
In case of failure of DC Supply 1, the above circuits will be fed from DC Supply 2. Changeover
can be Automatic (by using changeover contact of power contactor)/Manual (by using
Selector switch).
c)
DC supply 1&2, drawn to each duplex type 400KV C&R panel, shall be divided into the
following sub circuits. Each sub circuit shall be controlled and monitored with the help of
suitable MCBs/HRC Fuses.
i)
CB Trip coil 1 shall be fed from DC supply 1.
ii)
CB Trip coil 2 shall be fed from DC supply 2.
d)
DC Supply -1&2 shall be fed to Protection panel from C&R panel directly. Necessary
arrangement for Supervision of both the incoming DC Supplies shall be made. DC supply
1&2 shall be divided into the following sub circuits. Each sub circuit shall be controlled and
monitored with the help of suitable HRC Fuses.
i)
Circuitry for Main 1 protection, over voltage protection and reactor gr.-A protection
shall be fed from DC supply 1.
ii)
Circuitry for Main 2 protection and reactor gr. B protection shall be fed from DC
supply 2.
e)
b)
There shall be one DC incomer (220V) for each control and relay panel of 220KV system
voltage, fed from D.C. distribution board through a 32Amp. switch fuse unit provided there.
Necessary arrangement for Supervision of the incoming DC supply for each panel shall be
made. One 16 Amp. rating HRC fuse unit both at +ve and -ve side shall be provided for
the D.C. incomer in each panel of 220 KV system.
DC supply in individual panel shall be distributed within the panel as below :
i)
ii)
C.B. remote closing, local operation circuit including auxiliary relay function, C.B.
remote and protection trip to trip coil 1 with trip circuit supervision relay shall be
through HRC fuse and link.
C.B. remote and protection trip to trip coil 2 with trip circuit supervision relay through
HRC fuse and link.
Page 22 of 104
iii)
iv)
v)
vi)
vii)
Protective relay and P.T. selection circuit with D.C. supervision relay through HRC
fuse both at +ve and -ve side.
Indication circuit through HRC fuse and link.
Isolator control circuit through MCB.
D.C. emergency lamp circuit with HRC fuse and link.
D.C. supply to synchronising socket through links both at +VE & -VE side.
D.C. annunciation bus shall also be teed off from the incomer D.C. bus of 220KV Bus
Coupler/Bus Transfer Panel for 220KV annunciation system through 6A HRC fuse both at +ve
and -ve side and the same shall run continuously through the entire C&R board for facia
annunciation system in respective panels. In addition, Annunciation DC shall be supervised by
the Annunciator through auxiliary AC supply of the Annunciator in each panel.
There shall be only one DC incomer (220V) for the entire control and relay panel of 132KV
and 33KV system voltage fed from D.C. distribution board through a 32Amp. switch fuse unit
provided there. One 16Amp. rating HRC fuse unit both at +ve and -ve side shall be provided
for the D.C. incomer in Bus Transfer (2 bus system)/ Bus Coupler (3 bus system) panel of
132KV and 33KV system. The above D.C. incoming bus of 132KV and 33KV CR Panel only
shall run continuously in the control and relay board of each system voltage. Individual panel
D.C. supply for breaker control, isolator control, supervision and indication of circuit breaker
and other protective equipment etc. shall be teed off in each panel from the above D.C. bus
through a set of links.
D.C. annunciation bus shall also be teed of from the incomer D.C. bus of 132 KV and 33
KV Bus Transfer (2 bus system)/ Bus Coupler (3 bus system) panel for 132 KV and 33 KV
annunciation system through 6A HRC fuse both at +ve and -ve side with necessary D.C.
supervision relays and the same shall run continuously through the entire C&R board of
each system voltage for facia annunciation system in respective panels. In addition,
Annunciation DC shall be supervised by the Annunciator through auxiliary AC supply of the
Annunciator in each panel.
b)
DC supply to individual panel thus teed off through links shall be distributed within the panel
as below:
i)
ii)
iii)
iv)
v)
vi)
vii)
C.B. remote closing, local operation circuit including auxiliary relay function, C.B.
remote and protection trip to trip coil 1 with trip circuit supervision relay shall be
through 10A HRC fuse and link.
C.B. remote and protection trip to trip coil 2 with trip circuit supervision relay through
10A HRC fuse and link.
Protective relay and P.T. selection circuit with D.C. supervision relay through 10A
HRC fuse both at +ve and -ve side.
Indication circuit through 6A HRC fuse and link.
Isolator control circuit through 10A HRC fuse and link.
D.C. emergency lamp circuit with 2A HRC fuse and link.
D.C. supply to synchronising socket through links both at +VE & -VE side.
Page 23 of 104
made. From control panel the DC supply will be teed off from the incomer D.C. bus to LCC
panel. For remote operation of GIS equipment the operational DC will generate from LCC
through LOCAL/REMOTE switch of LCC.
14.05 AC CIRCUIT:
a)
230V, single phase 50Hz AC auxiliary supply to the control, relay and protection panel board
of each system voltage 400KV, 220KV, 132KV and 33KV will be fed from AC distribution board
through separate 32Amp. switch fuse units provided there. The supply shall be provided in
Bus coupler/Bus Transfer panel. A continuous AC bus shall be provided at the control, relay
and protection panel board of each group wherefrom AC supply to each panel shall be teed
off through a set of links. One 16Amp rated HRC fuse units shall be provided for a complete
control, relay and protection panel board of each system voltage for the incoming AC supply.
A set of fuse and link rated for 10Amps. for 3 pin plug circuit, cubicle lamp circuit, space
heater circuit shall also be provided in each control, relay and protection panel.
b)
Door operated corridor illumination lamp ckt. of duplex type panel shall be arranged from the
above incoming AC bus through suitably rated fuse and link.
c)
AC circuit for incoming DC Annunciation DC fail alarm scheme shall be provided in the Bus
coupler panel of 400KV & 220 KV system and in the Bus Transfer (2 bus system)/ Bus
Coupler (3 bus system) panel of 132KV and 33KV system. The above circuit shall be teed off
from the above respective panel AC bus through fuse and link suitably rated.
d)
One supervision relay for incoming AC fail with test P.B. and reverse flag indication shall be
provided for monitoring of AC supply healthiness through D.C. operated facia annunciation of
Bus Coupler panel of 400KV & 220KV system and of the Bus Transfer (2 bus system)/ Bus
Coupler (3 bus system) panel of 132KV and 33KV system.
c)
d)
e)
f)
The bus coupler panel shall receive protection VT secondary volts through fuses and links
provided in the respective VT kiosk. The protection VT supply shall run throughout entire
board for each panel through VT supply selection scheme.
The Bus Coupler panel shall also receive Metering VT Secondary volts by at least 25Sqmm
Copper/ equivalent Aluminum per phase/neutral through fuses and links provided in the
respective VT kiosk. The Metering VT supply shall also run throughout entire board for each
panel through VT supply selection scheme.
For 400KV/220KV system three sets VT selection relays operated from DC supply-1/ change
over DC system If VT selection relay is latched type, change over DC system of the respective
panel can be used to energize all the three VT selection relays.
Selected VT secondary supply to the protective relays of each panel shall be fed through
individual fuses in individual phases and link in neutral in each panel. Necessary arrangement
for supervision of VT secondary supply shall be provided in numeric relay.
Selected VT secondary supply to metering and indicating instruments of each panel shall be
fed through MCB. Proper arrangement of supervision through MCB shall also be provided.
In 132KV C&R panel, where more than one set of 132KV PT is available or not, necessary
132KV PT selection scheme shall be adopted and made ready for future use and where more
than one set of 33KV bus PT is available, necessary 33KV PT selection scheme shall be
adopted through switch at 33KV C&R panel.
Page 24 of 104
b)
c)
132KV and 33KV system shall have a "Incoming DC fail and Annunciation Bus D.C. alarm
scheme", as follows: i)
This will be provided at the Bus Coupler/ TBC panel & will be common to the entire
C&R board of each system voltage.
ii)
The scheme shall be operated from 230V single phase AC auxiliary supply for audible
as well as visual alarm through lamp and bell arrangement. The scheme shall
comprise of D.C. supervision relays with test push buttons for incoming DC supply
and Annunciation bus DC system, one AC operated alarm accept relays, one
indication lamp, one AC operated hooter and one push button for cancellation of
audible alarm.
Facia annunciation system shall be provided in each control panel by means of visual and
audible alarm to draw attention of the operator to the abnormal operation or operation of the
protective devices. The annunciation shall be divided into the following categories:
i)
ii)
Trip annunciation
Non Trip annunciation
The annunciator shall be suitable for operation with the sub-station AC/DC voltage and
potential free initiation contact is to be provided.
Page 25 of 104
b)
The visual facia widow shall be flush mounted at a convenient position near top row of the
control panel and necessary switching relays for the same shall be mounted inside the panel
or at the relay side of the panel.
c)
The annunciator facia shall be provided with translucent glass or plastic cover plates of white
colour with inscription in black colour. The size of facia window shall be 70mm x 35mm in
general and the size of the lettering shall not less than 5 mm. Alarm inscription shall be
engraved not more than three line of in each facia window and the same shall be prominently
visible when facia light is ON. The cover plates of the facia window shall be easily removable
to facilitate replacement of lamp when required.
d)
The transparency of cover and wattage of the lamp provided in the facia window shall be
adequate to ensure clear visibility of the inscription from the location of the operator's table in
the control room having high illumination intensity. Each facia window shall be provided with
two lamps to ensure safety against lamp failure. Long life lamp shall be used having resistor
of adequate rating in series.
e)
Accept, Reset and lamp Test push buttons for acknowledgment of alarm, reset of visual
indication and for checking perfectness of the lamps shall be provided below the facia window
in each panel. These push buttons shall be common for both trip and warning annunciation.
The sequence of operation of the annunciation shall be as follows:
Alarm Condition
--------------i) Normal
ii)Abnormal
Fault
contact
------Open
Close
Visual
Annunciation
-----------OFF
Flashing
Audible
Annunciation
-----------OFF
ON
a) Close
b) Open
Steady ON
Steady ON
OFF
OFF
a) Close
b) Open
ON
OFF
OFF
OFF
Steady ON
OFF
Open
f)
In case static annunciation system is used, care should be taken that no spurious alarm
condition arises due to external influences on the annunciator wiring and switching
disturbances from the
neighboring circuits within the panels. The static relay shall be
suitable for operation within a temperature range from 0C to 55C.
g)
The annunciation scheme should be such that momentary closing of any fault contacts shall
also cause operation of annunciation system as above.
h)
The annunciation scheme wiring should be such that the warning annunciation facia window
can be converted to trip annunciation facia window or vice versa with the change in audible
alarm connection accordingly, at site easily.
Page 26 of 104
16.00 RELAY:
GENERAL REQUIREMENT:
The main numerical protective relays shall be of Panel manufacturers own
make or their principal companys make.
Live demonstration of any offered relay has to be arranged by the Party at the laboratory of
Central Testing Department of WBSETCL, if felt necessary by WBSETCL before finalisation of
bid.
16.01 All shall conform to the requirement of IS: 3231 / IEC 255 and shall be suitable for operation
within a temperature range 0C to 55C and 50% to 95% relative humidity. Relays shall be
suitable for flush/ semi flush mounting on the panel with connections from the rear, protected
with dust tight cases for tropical use and with transparent cover removable from the front.
16.02 All protective relays shall be in draw out case or plug-in/modular cases with proper built in
testing facilities. If testing devices are not incorporated in the relay itself separate test block
and switches shall be provided. The adjusting devices shall be accessible with the relay
mounted on the panel board. Flag type operating indicators and flag indicator reset devices
shall be provided which shall be suitable for operation from the front of the relay case without
opening the cover.
16.03 All A.C. relays shall be suitable for operation at 50Hz.The current coils shall be rated for a
continuous current of 1 amp and the voltage coil for 110V normal. The contacts of the relays
shall be properly designed to prevent or minimise damage due to arcs which have to be
broken successfully against 220 +/- 10% volt DC. When open the contacts shall withstand a
voltage of 115% of the normal circuit voltage. The relays shall be designed for satisfactory
operation between 70% and 110% of rated D.C. voltage of the sub-station. The voltage
operated relays shall have adequate thermal capacity for continuous operation.
16.04 Timers shall be of static type. Pneumatic timers are not acceptable.
16.05 The sub-stations may be required to run without air-conditioning plant. Therefore, the static
relays shall be designed for operating satisfactorily under the climatic conditions of
ambient temperature and relative humidity variation from 0C to 55C and 50% to 95%
respectively. The static relays should be capable to withstand the test voltages as stated in
the relevant Indian standard or equivalent. Stringent measures including shielding of long
internal wiring should be taken to make the relays insensitive to the voltage spikes. Insulation
barriers shall be provided to ensure that transients present in CT & VT connection due to
extraneous sources do not cause damage to static circuits.
Page 27 of 104
16.06 DC/DC converter shall be provided in the solid state protective relays wherever necessary in
order to provide a stable auxiliary supply for relay operation. Provision of D.C. Cells in the
protective relays as reliable standby power supply will however not be acceptable. The DC/DC
converter shall have power supply failure annunciation contact.
16.07
a)
The solid state relays shall be stable and suitably protected against transient/induced over
voltages and noise signals. The bidder shall state clearly in his list of special requirement, if
any, for D.C. input arrangement or cabling considered necessary for satisfactory operation of
solid state relays quoted by him.
b)
i)
All the Numerical Relays should have setting parameter access restriction. All the
numerical relay should have provision for setting all the features available in the
relay and viewing those setting as well as different other parameters through both
built in display unit as well as through PC. The supply of relay should be inclusive of
necessary software and hardware for interfacing with a PC., to be supplied by the
bidder. The bidder/manufacturer has to make arrangement for multiplexing the
quoted relays substation wise through LAN configuration via Ethernet switch and
IEC 61850 rear port for communication with all relays, along with supply of cables,
connectors, communication port, converters etc. as necessary for downloading the
storage data for all microprocessor/ numeric relays, disturbance recorder and fault
locator etc. through a centralized PC. The necessary PC, window based Licensed
software along with operating system software and all the necessary hardware for
establishing the Network in IEC 61850 platform to be considered in the scope of
supply by the bidder.
Bidder shall arrange for such local man to machine communication facility for
all the numerical relays inclusive of all the necessary accessories as mentioned
above complete through Local Area Networking System for each 400KV, 220KV &
132KV substation wherever mentioned in the schedule.
For existing and new substations, provision is to be made for connectivity with the
existing and or future numerical relays through PC by providing external comport
multiplier (e.g. Rocket port/Serial sharer etc.).
ii)
All the protective relays shall be numerical type and communication protocol shall be
IEC 61850 compatible. All the numerical relays shall have one front port for direct
access with proprietary protocol and rear port with IEC 61850 protocol. The main
Numerical Protective Relays shall also have a IRIG-B port in addition to the above
ports to synchronise the internal clock with GPS based time synchronising equipment
directly through its own IRIGB port.
iii)
All numerical relays shall be provided with Relay Failure Annunciation Contact.
c)
List of software for local parameterisation, settings, logic configuration, data retrieval,
disturbance evaluation, downloading of storage data and no. of license (minim. 3 for new
400KV & 220KV S/Stn, & one each for other substations involved) shall be supplied by the
bidder.
d)
e)
Page 28 of 104
f)
Interface architecture involving multiple nos. of numerical relays of respective make, with the
monitoring PC.
g)
Interface architecture of the above network with existing/future network of other make
numerical relays with monitoring PC, wherever applicable.
h)
The bidder has to furnish the certificate for IEC 61850 Compliance from KEMA/CPRI,
type test certificate from any Govt. recognized Test House and performance certificate from
Power Utilities in India.
i)
ii)
iii)
iv)
v)
vi)
PC
The distance protection shall be a microprocessor based high speed non-switched distance
relay suitable for all phase to phase faults and phase to earth faults based on numerical
principles. It shall also have necessary phase selection and direction selection facilities. The
relay shall be field selectable for various permissive over reaching, permissive under reaching
and for blocking/ intertripping through communication schemes.
b)
The relay shall have polygonal/ quadrilateral characteristics with a facility to set resistance
and reactance characteristics independently.
c)
The relay shall have three forward and one reverse zone of protection for each PH-PH & PH-E
fault loop with sufficient impedance or reactance and resistance reach of each zone. It shall
have three zone time stepped characteristics. The second and third zone elements shall
provide backup protection in the event of the carrier protection on the first zone element
failing to clear the fault.
d)
It shall be compatible with the PLCC equipment to be procured separately under separate
contract. The distance protecting scheme shall be suitable for any length (short length also
Page 29 of 104
i.e. Minimum Settable value should be 1 Primary) of transmission line. Any limitation in this
regard shall be clearly specified by the bidder.
e)
The relay shall have numerical filtering and measuring techniques. It shall have individual
measuring element for each phase to phase fault and each phase to earth fault. It should
ensure a maximum operating time from the relay to the trip coil of CB within 40 ms for all
types of faults at 50% of the set zone 1 relay reach with CVT being used on the line for a
System Impedance Ratio (SIR) of 4 and the same shall be 45millisecond for an SIR of 15.
However, a relaxation of 5millisecond is allowed for the relays being used for 132 KV.
f)
It shall be provided with continuous self supervision features along with self diagnostic
feature, having output IRF contact for annunciation purpose.
g)
Shall have memory circuits with defined characteristics in all three phases to ensure correct
operation during close up three phase faults and other adverse conditions and shall operate
instantaneously when circuit breaker is closed to zero volt three phase faults.
h)
It shall be suitable for single and three phase tripping mode to be scheduled by WBSETCL
depending upon their application along with necessary trip relays.
i)
The scheme for 400KV & 220 KV system shall be suitable for single phase or/and three phase
Auto-reclosing. It shall have in built features of weak end in feed, switch on to fault, fuse
failure supervision and instantaneous blocking of protection in the event of fuse failure and
should remain inoperative for system earth fault, Power Swing blocking with zone selection
facility for such blocking, broken conductor detection and different indications for relay
monitoring operations.
j)
The relays shall have the provision for Man to Machine Communication for local and
remote control and monitoring complete with software, ports and other hardware e.g.
i)
Required numbers PC hook up cable for direct communication, one for each type of
relay.
ii)
Graphical configuration tool having all the functions used in the relay and sufficient
numbers different logic gates in the inbuilt library (software)
iii)
Basic application licensed software for setting change, service value monitoring etc.,
one each for every substation where numerical relays shall have to be provided.
iv)
Program for disturbance record collection and evaluation of those records.
v)
Any additional software if required for remote communication and for other facilities
available in the relay.
All the above tools/software should be WINDOWS XP/WINDOWS 7 operating system
compatible.
k)
The relay shall have inbuilt auto reclosure, disturbance recorder, fault locator, event logger
facility and additional features shall also be indicated over and above the features already
specified.
l)
Relay should be blocked in case of momentary dropping off of PT switching Relays to avoid
maloperation, if there be any. The VTF protection should be incorporated.
m)
The numerical distance relay should have in built directional sensitive earth fault element for
high resistance fault.
n)
The relay shall have suitable number of potential free contacts for carrier aided tripping, auto
reclosing, event logger, disturbance recorder and data acquisition system.
o)
The relay shall have a continuous current rating of two times of rated current, the voltage
shall be capable of operation at 1.2 times rated voltage. The relay shall also be capable of
carrying a high short time current without damage for a period of 1sec.
Page 30 of 104
p)
The relay shall have at least 15nos of individually site selectable Binary Inputs and 20nos
Binary Outputs (rating of Binary Input shall be 240V DC but they should not pick up at less
than 150V). Latching option for B/O shall have to be provided. Output contact of the
protective relay should operate single phase trip relay which will have sufficient contact to
give trip command to main breaker & TBC breaker & for LBB protection initiation and other
purpose.
b)
c)
d)
e)
f)
g)
h)
The scheme shall be compatible with the distance relaying scheme. It shall be suitable for
single shot, single and/or three phase auto-reclosing feature. The bidder shall coordinate the
auto-reclose relaying scheme with that of the circuit breaker so as to ensure satisfactory and
reliable operation of the auto reclosing scheme.
The auto reclose relays shall have independently adjustable dead timers for single phase and
three phase reclosures and an adjustable reclaim timer.
It shall also be possible to lock out the auto-reclosing scheme relays when the carrier
protection associated with distance protection scheme is out of service or faulty.
It shall have auto-reclose mode selection facilities as required.
It shall have facilities for selecting check synchronising or dead line charging feature. It shall
be possible at anytime to change the required feature as required.
It shall be built-in with the main distance relay.
The autoreclose relay along with necessary check synchronising or dead line charging
facilities and other associated features shall be in built in the Main-1 & Main-2 protection.
Either one shall be activated during operation and the other shall be kept as stand by. The
two inbuilt autoreclose relays should be well coordinated so that autoreclose command/
definite trip command etc may be initiated from either of the two units at the discretion of
WBSETCL personnel. The autoreclose element of the distance relay shall also be suitable for
triggering from other external protections.
In One and Half breaker system, while reclosing the Main breaker & Tie breaker for the Line
bay, a priority shall be assigned. The Main breaker shall be allowed to reclose first and only
after its successful recloser, the Tie breaker shall be allowed to reclose. If the fault persists
after reclosing of the Main breaker, reclosing of the Tie breaker is blocked.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
The distance to fault locator shall be provided for all 400KV, 220KV and 132KV lines. It shall
be: Microprocessor based type.
be "on-line" type
be suitable for breaker operating time.
have built in display unit.
the display shall be directly in kilometers without requiring any further calculations.
have an accuracy of 3% of the line length for which the fault locator is installed or better
for all type of faults and fault levels.
the above accuracy should not be impaired under the following conditions:
i)
presence of remote end in feed.
ii)
predominant d.c. component in fault current.
iii)
high fault arc resistance.
iv)
severe CVT transients.
have facility for remote data transmission.
shall be built-in distance relay with facility for triggering from
external
protection.
shall have built in mutual compensation facility for using in double circuit lines and this
parallel line compensation shall not be used for protection purpose.
Page 31 of 104
b)
c)
d)
e)
f)
g)
h)
i)
Disturbance Recorder shall be used for 400KV, 220KV and 132KV system to record the
graphic forms of instantaneous/ rms values of voltages and currents, in all phases, open delta
voltage and neutral current, open or closed position of relay/ breaker contacts just prior to,
during and immediately after a system disturbance to provide information necessary to
ascertain the causes of disturbance and performance of relays, breakers etc. The system shall
start only on the occurrence of a system abnormality.
The disturbance recorder shall be inbuilt function of numerical distance/ differential relay. The
channels and trigger sources shall be user configurable. Program for disturbance records and
event logger collection and evaluation of those records shall be provided. Also the software
shall be capable of carrying out Fourier /harmonic analysis of the current and voltage
waveform. Disturbance shall also be available in COMTRADE format.
Number of Channels required for each feeder bay :
i)
Analog channel: 8 nos.
ii)
Digital channel: 24 nos.
The relay shall have the disturbance recording function with at least 8nos analog channels
and 24nos binary channels having total recording memory of at least 15secs divided in to 8
records and recording bandwidth may please be indicated. It should have on line pre and
post fault disturbance recording facility.
The disturbance recorder shall be suitable for working with 220V DC available at the Substation.
Each Relay & Disturbance Recorder shall have the facility to synchronise the internal clock
with GPS based time synchronising equipment directly through its own IRIGB port.
The accuracy of the internal clock shall be indicated by the bidder. The drift is limited to
0.5sec per day, if allowed to run without synchronisation. The recorder shall give
annunciation in case of absence of synchronising pulse within a specified time.
Substation where time synchronisation equipment is not available, time generator of any one
of the disturbance recorder can be taken as master and the time generator of other
disturbance recorder and event logger in the substation shall be synchronized to follow the
master.
The recorder shall have facility for automatic uploading of, remote data transmission. Scan
rate of D R shall be at least 1KHZ per channel or better. Facility for triggering of disturbance
recorder from external protection shall also be provided. Acquisition units shall acquire the
fault data for the prefault and post fault period and can be transferred on demand to
connected PC.
Page 32 of 104
vi)
vii)
viii)
ix)
x)
xi)
xii)
xiii)
xiv)
xv)
b)
c)
d)
e)
f)
g)
The time synchronisation equipment shall receive the coordinated Universal Time (UTC)
transmitted through Geo Positioning Satellite system(GPS) and synchronise equipments to
Indian Standard time in a substation. It will also synchronise the substation PC through
necessary software to be supplied by the bidder.
Time synchronising equipment shall include antenna, all special cable and processing
equipments.
It shall be compatible for synchronisation of event loggers, disturbance recorder and SCADA
at a substation.
Equipment shall operate upto the ambient temperature of 50C and 100% humidity.
Equipment shall meet the requirement of IEC 60255 for storage and operation.
Equipment shall have real time display in hour, minute, sec (24 hr. mode)and have a separate
time display unit to be mounted on the top of the control panels or any suitable location
having display size of approximately 100mm height.
Equipment offered shall have six output ports .Various combinations of output ports shall be
selected by the customers, during detailed engineering from the following:
i)
Voltage signal: Normally 0 5 V with 50ms minimum pulse duration. In case any
other voltage signal required it shall be decided during detailed engineering.
ii)
Potential free contact (minm. pulse duration of 50ms).
iii)
IRIG-B
iv)
RS232C
Page 33 of 104
h)
i)
j)
k)
l)
m)
The synchronisation equipment shall have 2micro second accuracy. Equipment shall give real
time corresponding IST (taking into consideration all factors like voltage and temperature
variation, propagation and processing delays etc.).
The output signal of each port shall be programmable at site for either one hour, half hour,
minute or second pulse, as per our requirement.
The equipment shall have a periodic time correction facility of one second periodicity.
The equipment shall be suitable to operate from 220V DC 10% as available at the
substation.
The system shall be able to track the satellites to ensure no interruption of synchronisation
signal.
Time synchronization equipment consisting of :
i)
GPS antenna,
ii)
GPS receiver with detail of output & ports,
iii)
Requisite quantity of interconnecting cable with matching connector,
iv)
Master clock with display unit, power supply unit,
v)
Battery charger if required, time synchronization panel etc.
vi)
Necessary converter arrangement for deriving Power supply DC voltage from 220V
DC supply from our substation battery.
vii)
Synchronisation panel etc.
viii) Other particulars if any.
g)
h)
i)
j)
k)
l)
The protection shall be provided at the HV side panel of the transformers to be protected. It
shall be numerical type adjustable/variable percentage biased differential relay.
Necessary softwares, cables, connectors and other accessories as required in compatible with
Sub-station PC shall be provided by the Tenderer as described under clause 16.07 above.
The relay shall be very fast in operation with an operating time less than 30millisec at 5 times
setting.
The relays shall be inherently stable for external through fault conditions without affecting
the speed of operation for internal faults.
The relay shall have a built in facility of ratio and phase angle correction.
The relay shall be provided with 2nd harmonic restraint (having site selectable setting
facilities of 10% to 40% of I2/I1) or any other inrush proof feature to prevent operation due
to magnetising in rush current when the transformer is charged either from HV or LV side.
But this shall not affect the speed of operation for internal fault.
It shall be provided with 5th harmonic restraint features (having site selectable setting
facilities of 10% to 40% of I 5th/Ifund) to prevent operation due to possible over excitation of
the transformer. This shall also not affect the speed of operation for internal fault.
It shall have three instantaneous high set over current units for clearing heavy internal faults.
The relay shall have adjustable bias setting range 20% to 50% and adjustable operating
setting range of 10% to 50% at zero bias.
The relay shall be with 3-bias winding for 400/220/33KV and 220/132/33KV transformers and
2-bias winding for 220/33KV, 132/33KV and 10MVA and above 33/11KV transformers.
The relay shall be such that there will not be any necessity of changing the setting of the
relay whenever the transformer taps are changed.
The relay shall be provided with GPS based time synchronized disturbance recorder with date
and time tagged records with the facility of triggering from other external protective relays of
the transformer. The disturbance recorder shall be capable of recording graphic form of
values of currents each phase, differential currents of each phase etc. and store them in the
Page 34 of 104
m)
n)
o)
memory which can be downloaded both from local and remote end PC. Memory size and
number of disturbances stored in the relay shall be clearly indicated in the offer.
The in-built disturbance recorder shall have the facility to record the following external digital
signal apart from the digital signals pertaining to differential relay.
i)
REF protection operated
ii)
Over flux relay operated
iii)
Dir/ Non-Dir O/C relay operated
iv)
HV breaker status(Main & Tie)
v)
LV breaker status
vi)
Buchholz/OLTC Buchholz alarm/trip
vii)
WTI/OTI/PRD alarm/trip of transformer
The relay shall have disturbance recording function with at least 9 nos analog channels and
10nos digital channels having total recording memory of 5 secs divided in to 5 records and
recording bandwidth may please be indicated.
The relay shall have at least 5nos of individually site selectable Binary Inputs and 8nos Binary
Outputs (rating of B/I shall be 240V DC but they should not pick up at less than 150V).
Latching option for B/O shall have to be provided. Output contact of protective relay should
operate trip relay which will have sufficient contact to give trip command to main breaker,
TBC breaker & for LBB protection initiation and other purposes.
Necessary hardware and software for downloading the data captured by disturbance recorder
to the personal computer available in the substation shall be included in the scope.
stand-alone type
single pole type.
current/voltage operated high impedance type with a suitable setting to cover the maximum
portion of transformer winding. Necessary calculation to prove the above winding coverage
shall be furnished along with the tender.
tuned to the system frequency.
have suitable nonlinear resistor to limit the peak voltage without detriment to the scheme.
operating time shall be less than 20 ms.
have suitable stabilizing resistor to prevent maloperation during external faults if necessary.
Page 35 of 104
a)
b)
This relay will be used as back up protection of 400/220/33KV & 220/132/33KV Transformer,
HV side of 220/33KV & 132/33kV Transformer and back up to distance relays for 220KV and
132KV system and shall have follow propertiesMinimum two characteristics, one IDMT of 3sec and the other one of definite time
characteristic with instantaneous high set and the same should be site selectable.
Wide range of time and current setting in very small steps without sacrificing the relay
characteristics.
Page 36 of 104
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
n)
o)
p)
q)
r)
s)
t)
Any of the out puts including trip shall be latched and reset of the outputs shall be possible
from a logic input and the front panel operator interface.
Continuous self supervision along with self diagnostic feature for faults within the relay and
the relay should have potential free change over contact for annunciation in the event of
internal failure.
DC auxiliary voltage 220V20%, 110v. 20%
Rated current 1A.
Frequency 50Hz.
Digital input voltage range shall be identical to the DC voltage range.
Thermal withstand capability 100A for 1Sec/ 4A continuous.
Output contacts having sufficient current rating to directly energize trip coil of circuit breaker.
LED indication facility for visual annunciation of different type of faults including phase
identification. Fault indication should be displayed in the stand-by screen.
Individually site selectable both binary Output & Input and latching option for binary Output.
Relay should show fault current with time stamping.
The relay shall have more than one selectable setting group.
The setting group can be changed by binary inputs.
The relay shall have a non volatile memory for i)
Event recorder - shall have the facility of recording up to 75 events with time
stamping.
ii)
Setting values.
iii)
Disturbance recorder data - Recorded data of 5 last events with time stamp. The
disturbance recording function is triggered either by any of programmed threshold or
by an external input. All logic and analog information can be transferred using
communication port to an external data analyzer. Current waveforms shall be
captured.
Fault records - At least five nos fault records shall be available with the following indications:
i)
Fault indication.
ii)
Current values.
iii)
Tripping time.
Measurement -Instantaneous three phase current values and residual current value. All the
measured and derived values can be displayed on the front panel LCD.
No of output contact required 8 nos
No. of digital input required 6 nos
All numerical relays shall have one front port for direct access with proprietary protocol and
one rear port with IEC 61850 protocol.
The numerical directional shall have built in feature for derivation of zero sequence voltage
internally. If separate IVT is required for derivation of zero sequence voltage for directional
earth fault element, the ratio of IVT will be 110/110V with burden of 5VA and class 3P. The
MTA of numerical directional relay shall be 45lag for earth fault and 45lead for over current.
Any extra feature like time synchronization, LAN compatibility with other numerical relays
shall be mentioned specifically.
FOR
TRANSFORMER
&
REACTOR
INTERNAL
TROUBLE
Page 37 of 104
k)
l)
Trip all the breakers on the particular bus in a One & Half breaker system, when any
bus breaker fails to trip in faulty condition. However, when a Tie Breaker fails to
open, the LBB relay shall trip the adjacent bus breakers as well as both the breakers
at the remote end of the bays.
LBB for Tie breaker shall be standalone type.
Page 38 of 104
bar relay, the tripping logic will be based on available relay. The Central Processing Unit of
bus bar protection & Bay Unit of numerical bus bar protection scheme shall be housed in a
separate set of simplex type panel along with equipment/relays.
One Bus bar protection scheme shall be provided for each main and transfer bus for 220KV
and 132 KV voltage levels but for 132KV substations having 1Main + 1 Transfer bus
arrangement, no bus bar protection scheme is required.
a) Bus Bar protection scheme shall: i)
have maximum operating time up to trip impulse to trip relay for all types of faults of
25 milli seconds at 5 times setting value.
ii)
operate selectively for each bus bar
iii)
give hundred percent security up to 50KA for fault level for 400KV and 220KV and
31.5 KA for 132 KV
iv)
incorporate continuous supervision for CT secondary against any possible open circuit
and if it occurs, shall render the relevant zone of protection inoperative and initiate an
alarm
v)
not give false operation during normal load flow in bus bars.
vi)
incorporate clear zone indication.
vii)
be of phase segregated and triple pole type
viii) provide independent zones of protection (including transfer bus if any). If the bus
section is provided then each side of bus section shall have separate set of bus bar
protection schemes
ix)
include individual high speed hand reset tripping relays for each feeder
x)
be transient free in operation
xi)
include continuous D.C. supplies supervision.
xii)
not cause tripping for the differential current below the load current of
heaviest loaded feeder. Bidder shall submit application check for the same.
xiii) shall include necessary C.T. switching relays wherever C.T. switching is involved and
have 'CT' selection incomplete alarm
xiv) include protection 'IN/OUT' switch for each zone
xv) include trip relays, CT switching relays (if applicable), auxiliary CTs (if applicable) as
well as additional power supply modules, input modules etc. as may be required to
provide a Bus-bar protection scheme for the complete bus arrangement i.e. for all the
bay or breakers under this specification as well as for the future bays as per the
Single line diagram for new substations. However for extension of bus bar protection
scheme (if specified in BPS) in existing substations, scope shall be limited to the bay
or breakers covered under this specification. Suitable panels to mount these are also
included in the scope of the work.
b)
c)
Built-in Local Breaker Backup protection feature as a part of bus bar protection scheme shall
also be acceptable.
At existing substations, Bus-bar protection scheme with independent zones for each bus, will
be available. All necessary co-ordination for 'AC' and 'DC' interconnections between existing
schemes (Panels) and the bays proposed under the scope of this contract shall be fully
covered by the bidder. Any auxiliary relay, trip relay, flag relay and multi tap auxiliary CTs (in
case of biased differential protection) required to facilitate the operation of the bays covered
under this contract shall be fully covered in the scope of the bidder.
Bus bar protection scheme shall be provided for 220KV system where the sub-station layout
arrangement is with 3-bus system (Main 1, Main 2 & Transfer Bus) or two bus system with
Main bus with bus section breaker & Transfer bus. Bus bar protection for two main bus
Page 39 of 104
b)
c)
system shall also be provided wherever applicable. Bus bar protection for two main bus with
one & Half breaker system shall also be provided wherever applicable.
Bus bar protection relaying scheme shall be provided in a separate simplex type panel with all
bus differential relays, CT switching relays and trip relays etc. as required considering future
bays.
Bus bar protection scheme shall be Numerical type and it shall have maximum
operating time for all types of fault at five times set value is 25ms up to trip impulse to trip
relay.
Bus Bar protection scheme shall: i)
operate selectively for each bus bar
ii)
give hundred percent security up to 40 KA fault level for 400KV and 220KV and 31.5
KA for 132 KV
iii)
incorporate continuous supervision for CT secondary against any possible open circuit
and if it occurs, shall render the relevant zone of protection inoperative and initiate an
alarm
iv)
not give false operation during normal load flow in bus bars.
v)
incorporate clear zone indication.
vi)
be of phase segregated and triple pole type
vii)
provide independent zones of protection (including transfer bus if any). If the bus
section is provided then each side of bus section shall have separate set of bus bar
protection schemes
viii) include individual high speed hand reset tripping relays for each feeder
ix)
be transient free in operation
x)
include continuous D.C. supplies supervision.
xi)
not cause tripping for the differential current below the load current of
heaviest loaded feeder. Bidder shall submit application check for the same.
xii)
shall include necessary C.T. switching relays wherever C.T. switching is involved and
have 'CT' selection incomplete alarm
xiii) include protection 'IN/OUT' switch for each zone
xiv) include trip relays, CT switching relays (if applicable), auxiliary CTs (if applicable) as
well as additional power supply modules, input modules etc. as may be required to
provide a Bus-bar protection scheme for the complete bus arrangement i.e. for all the
bay or breakers under this specification as well as for the future bays as per the
Single line diagram for new substations. However for extension of bus bar protection
scheme (if specified in BPS) in existing substations, scope shall be limited to the bay
or breakers covered under this specification. Suitable panels to mount these are also
included in the scope of the work.
d) Built-in Local Breaker Backup protection feature as a part of bus bar protection scheme shall
also be acceptable.
e) At existing substations, Bus-bar protection scheme with independent zones for each bus, will
be available. All necessary co-ordination for 'AC' and 'DC' interconnections between existing
schemes (Panels) and the bays proposed under the scope of this contract shall be fully
covered by the bidder. Any auxiliary relay, trip relay, flag relay and multi tap auxiliary CTs (in
case of biased differential protection) required to facilitate the operation of the bays covered
under this contract shall be fully covered in the scope of the bidder.
Page 40 of 104
Stub protection scheme shall be applicable for one and half breaker system. This
protection shall protect the part of one & half breaker system, not covered by
distance protection.
Stub protection scheme shall be: i)
active only when Line isolator is open & there is no voltage from CVT for
distance protection relay.
ii)
the inbuilt function of the main Numerical Protection relay.
iii) Able to sense the fault through a overcurrent sensing element & trip bus
breaker under fault condition.
PC hook-up cable for direct communication in sufficient quantity for each substation.
Graphical configuration tool having all the functions used in the relay and sufficient nos. of
different logic gates in the in built library (software).
Basic application software for setting change, service value monitoring etc.
Programme for disturbance record collection and evaluation of those records.
Any additional software, if required, for remote communication and for other facilities
available in the relay.
All the above tools/software should be Windows XP/WINDOWS 7 Operating system
compatible.
The following protection scheme has been envisaged: Main 1 distance protection by microprocessor based numerical distance relaying scheme
with carrier aided distance protection scheme.
Main 2 distance protection by microprocessor based numerical distance relaying scheme but
of a different make with carrier aided distance protection scheme.
Auto reclosing, fault locator and disturbance recorder scheme.
Local breaker back up protection scheme.
Page 41 of 104
e)
f)
g)
17.03
a)
b)
c)
d)
e)
17.05
a)
b)
c)
d)
e)
f)
g)
Page 42 of 104
17.06
a)
b)
c)
d)
e)
f)
g)
17.07
a)
b)
c)
For the above, selection of necessary tripping scheme shall be achieved with the help of
Selector Switch, as per scheme requirement. This earth fault relay will trip HV
breaker/breakers after a preset time delay. The switches shall be having sufficient number
of contacts. The trip relays shall have sufficient number of contacts for extending the trip
pulse to other 33KV feeders connected with generating stations.
Flag relays for transformer mounted protections like Buchholz, Winding temperature, Oil
temperature, Pressure relief device etc. shall be provided. Internal trouble protection auxiliary
relays for alarm and trip signal to LV breakers for earthing transformer to trip 33KV breaker
shall have sufficient number of contacts for extending the trip pulse to other 33KV feeders
connected with generating stations and only alarm signal for station service transformers
shall also be provided.
Trip transfer scheme for both HV&LV side shall be provided with two separate trip transfer
switch.
Page 43 of 104
b)
c)
Distance protection scheme for feeder bay protection shall be with protection selector switch.
Numerical relay shall be quoted as per feeder protection. The transfer bus numerical distance
relay should be identical type of those relays used in the feeder protection for easy
replacement of the same in future if required.
Back up protection of feeder with voltage polarised, directional, IDMT, two over current and
one earth fault protection scheme with protection selector switch and VT supply supervision
scheme.
Non-directional, IDMT, three over current and one earth fault protection for 132/33 KV
transformer protection. (The relay plug setting should be judged properly for protecting rated
to 100% loading)
The protection scheme for the transfer bus bay shall be Non-directional, IDMT, three over current protection with high set instantaneous unit with
protection selector switch.
Non-directional, definite time earth fault protection with protection selector switch.
Page 44 of 104
c)
One common under frequency relay of setting range 45 to 55 HZ in adjustable steps and with
timer relay of 0 to 20 second adjustable setting range with sufficient number of contacts shall
be provided from tripping of all 33 KV outgoing breakers.
17.15 BUS CONFIGURATION FOR 400KV, 220KV, 132KV AND 33KV SYSTEM OF
DIFFERENT S/S.:
a)
b)
c)
d)
Bus configuration for various voltage class shall be as follows, unless otherwise mentioned:
400KV switchyard of all the sub-stations shall be of One & a Half Breaker system or two Main
bus and one Transfer Bus system.
220KV switchyard of all the sub-stations shall be with two main Bus and one transfer Bus.
132KV switchyard of all the sub-station shall be either with one Main Bus with/without bus
section breaker and one transfer Bus or two Main bus and one Transfer Bus.
33KV switchyard of all the sub-station shall be with one main Bus and one Transfer. But 33KV
shunt capacitor shall be connected at Main Bus only where applicable.
17.16 Approximate route length of different circuits of 400KV, 220KV and 132KV system controlled
by different feeder bays are as stated in GCC under Scope of work.
18.00 SYNCHRONISATION:
One synchronising panel mounted on a movable trolley shall be provided for use in 400KV
system and another one for both in 220KV & 132KV system, wherever mentioned in the
schedule. For 400KV synchronization shall be achieved by comparing between phase to phase
voltage and for 220KV & 132KV, synchronization shall be achieved by comparing between
phase to neutral voltage.
a)
Page 45 of 104
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
Two frequency meters each having scale range 45 to 55Hz, indicating type.
One suitable synchroscope with cut off switch.
One suitable auxiliary voltage transformer for synchronising condition.
One synchronising bypass switch with necessary under voltage relaying scheme of running
system and incoming system to check inadvertent circuit breaker closing under synchronising
bypass condition.
One check synchronising relay with necessary auxiliary equipment which shall permit the
circuit breaker to close after checking the requirement of synchronising of incoming and
running supply.
One guard relay to prevent the closing attempt by means of synchronising check relay when
control switch is kept in close position long before the two systems are in synchronism.
Two synchronizing lamps of white colour.
One green indicating lamp to indicate check synchronism in limit.
One red indicating lamp to indicate check synchronism by pass.
Any other equipment required to render satisfactory operation of synchronism.
Page 46 of 104
20.01 (A) 220 KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR THREE BUS (TWO
MAIN & ONE TRANSFER) SYSTEM:
Q u a n t I t y
Sl. No.
Particulars
Unit
Feeder
HT side of
220/132kV
& 220/33KV
Transformer
Bus
Coupler
Bus
Transfer
3
2
1
1
3
1
1
A. FRONT PANEL:
1.
Metering Device
a)
b)
c)
d)
Ammeter
Voltmeter
Watt meter with transducer
Varmeter with transducer
Nos
Nos
Nos
Nos
3
1
1
e)
Nos
3
1
1
(not reqd.
for
220/33KV
TR.)
1
Nos
Nos
Nos
1
-
1
-
2
2
Nos
Nos
Nos
4
1
4
-
2
-
3
-
Nos
Nos
1
1
1
1
Set
Nos
Nos
Nos
1
-
Nos
Nos
Nos
1
4
f)
g)
h)
2.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
3.
a)
b)
Page 47 of 104
Q u a n t I t y
Sl. No.
Particulars
c)
d)
e)
f)
g)
h)
i)
j)
k)
4.
a)
b)
c)
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like
Heater
with
Switch,
Thermostat, Cubicle Illumination
Lamps, Power Socket, Switches,
Fuses, Link etc. as described in
the main specification
d)
One
Label
Indicating
Manufacturers
Name,
P.O.
Details, Drg. Ref. Nos. etc.
e)
Annunciation Windows as reqd,
with Lamps, Accept/Reset/Test
Push Button etc. and associated
Relays if the annunciator relay is
attached with the windows
f)
Common Bell, Hooter, Associated
relays etc. for Annunciation
Scheme
B. REAR PANEL:
Feeder
HT side of
220/132kV
& 220/33KV
Transformer
Bus
Coupler
Bus
Transfer
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
1
-
Nos
Set
2
1
2
1
2
1
2
1
Set
Set
nos
24
32
24
24
Set
Unit
Page 48 of 104
Q u a n t I t y
Feeder
HT side of
220/132kV
& 220/33KV
Transformer
Bus
Coupler
Bus
Transfer
Nos
Nos
Set
Set
Set
Set
1
1
1
1
1
1
1
1
Set
Set
1 (3 O/C)
Sl. No.
Particulars
Unit
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Set
Set
As reqd.
Set
Set
Page 49 of 104
Q u a n t I t y
Sl. No.
14. i)
14. ii)
14. iii)
Particulars
14. iv)
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
NB:
Unit
Feeder
HT side of
220/132kV
& 220/33KV
Transformer
Bus
Coupler
Bus
Transfer
Set
Set
As reqd.
1+1(for
Ann. Bus
DC)
1
Nos
Nos
Nos
Nos
1
1
Nos
Nos
As reqd.
As reqd.
1
As reqd.
As reqd.
Nos
Nos
Nos
Set
Nos
Set
1
-
Set
Items in the BOM for 220KV side of 400/220KV transformer & 132KV side of 220/132KV
transformer shall be same as 220/132KV transformer except Neutral displacement relay,
differential relay, transformer trouble relay, REF relay, Over Flux Protection relay mentioned
under sl. no 9, 12, 11, 19, 10.24.
Page 50 of 104
20.01 (B)
220KV SIMPLEX TYPE CONTROL & PROTECTION PANEL FOR ONE & HALF
BREAKER SYSTEM:
Q u a n t I t y
Sl.
No.
Particulars
Unit
Feeder-Tie-Feeder
Transformer-Tie
A. RELAY PANEL
1.
Metering Device
a)
b)
c)
d)
e)
Ammeter
Voltmeter
Watt meter with transducer
Varmeter with transducer
Wiring for intelligent electronic
computer compatible energy
meter (0.2 class)
Test Terminal Block
Voltmeter Selector Switch
Frequency Meter
Control Device
Nos
Nos
Nos
Nos
Nos
6
2
2
2
2
6
2
2
2
2
Nos
Nos
Nos
2
2
2
2
2
2
Nos
Nos
Nos
3
8
2
3
7
-
Nos
Set
Nos
Nos
8
10
7
10
Nos
Nos
f)
g)
h)
2.
a)
b)
c)
d)
e)
f)
3.
a)
b)
c)
d)
e)
f)
g)
Nos
Nos
Nos
Nos
Page 51 of 104
Q u a n t I t y
Sl.
No.
h)
4.
a)
b)
c)
d)
e)
Sl.
No.
Particulars
Push Button for
check, if required
Unit
C.B.
Spring
Other Devices
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like
Heater
with
Switch,
Thermostat, Cubicle Illumination
Lamps, Power Socket, Switches,
Fuses, Link etc. as described in
the main specification
One
Label
Indicating
Manufacturers
Name,
P.O.
Details, Drg. Ref. Nos. etc.
Annunciation Windows as reqd,
with Lamps, Accept/Reset/Test
Push Button etc. and associated
Relays if the annunciator relay is
attached with the windows
Particulars
Feeder-Tie-Feeder
Transformer-Tie
Nos
Nos
Set
2
1
1
2
1
1
48
48
Set
Set
nos
Unit
Quantity
Feeder
Transformer
Tie
B. PROTECTION PANEL
1.
2.
3.
4.
5.
6.
Nos
1
Nos
1
1
1
1
1
Set
Set
Set
1
1
-
Set
Page 52 of 104
Sl.
No.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
Particulars
Back up directional O/C and E/F
IDMTL relaying scheme with high
set unit complete in all respect
with PT fuse failure monitoring
feature as described in the
specification.
Neutral displacement relay for
220/132KV Transformer tertiary
protection
Back up restricted E/F relaying
scheme complete in all respect
as per specification.
Transformer trouble auxiliary
relaying scheme for Buchholz,
winding tem. Etc. as per
specification.
Transformer
differential
protection relaying scheme as
described in the specification,
complete in all respect
Tripping relaying scheme as
described in the specification.
Incoming DC/Ann. Bus DC supply
supervision relays
Test terminal block for protective
relays as required
Circuit label
Internally mounted equipment
like
heater
with
switch,
thermostat cubicle illumination
lamps, power socket, switches,
fuses, links etc. as described in
the main specification
Over Flux Protection relaying
scheme
Unit
Set
Quantity
Feeder
Transformer
1 (3 O/C)
Tie
1
-
Set
Set
As reqd.
Set
Set
Nos
Nos
1
As reqd.
1
As reqd.
Nos
Set
Set
Page 53 of 104
As reqd.
2
1
20.01 (C)
220 KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR TWO BUS (TWO
MAIN) GIS SYSTEM:
Q u a n t I t y
Sl. No.
Particulars
Unit
Feeder
HT side of
220/132kV
& 220/33KV
Transformer
Bus Coupler
A. FRONT PANEL:
1.
Metering Device
a)
b)
c)
d)
Ammeter
Voltmeter
Watt meter with transducer
Varmeter with transducer
Nos
Nos
Nos
Nos
3
1
1
3
1
1
3
2
1
1
e)
Nos
f)
g)
Nos
Nos
1
-
1
-
h)
2.
Frequency Meter
Control Device
Nos
a)
Nos
Nos
Nos
Nos
3
4
1
3
4
-
4
6
-
Nos
Set
Nos
Nos
Nos
1
-
b)
c)
d)
e)
f)
g)
h)
i)
3.
a)
b)
Nos
Nos
Page 54 of 104
Q u a n t I t y
Sl. No.
Particulars
Unit
Feeder
c)
d)
e)
f)
g)
h)
i)
j)
k)
HT side of
220/132kV
& 220/33KV
Transformer
Bus Coupler
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
1
-
Nos
Set
2
1
2
1
2
1
Set
Set
nos
24
32
24
Set
4.
a)
b)
c)
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like
Heater
with
Switch,
Thermostat, Cubicle Illumination
Lamps, Power Socket, Switches,
Fuses, Link etc. as described in
the main specification
d)
One
Label
Indicating
Manufacturers
Name,
P.O.
Details, Drg. Ref. Nos. etc.
e)
Annunciation Windows with DC
fail annunciation as reqd, with
Lamps, Accept/Reset/Test Push
Button etc. and associated Relays
if the annunciator relay is
attached with the windows
f)
Common Bell, Hooter, Associated
relays etc. for Annunciation
Scheme
B. REAR PANEL:
WBSETCL / TECH SPEC / Rev.-1
Page 55 of 104
Q u a n t I t y
Sl. No.
Particulars
Unit
Feeder
1.
2.
3.
4.
5.
6.
6a).
7.
8.
9.
10.
11.
HT side of
220/132kV
& 220/33KV
Transformer
Bus Coupler
Nos
Nos
Set
Set
Set
Set
Set
Set
Set
1 (3 O/C)
As reqd.
Set
Set
Page 56 of 104
Q u a n t I t y
Sl. No.
Particulars
Unit
Feeder
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
Transformer
differential
protection relaying scheme as
described in the specification,
complete in all respect
Tripping relaying scheme as
described in the specification.
Incoming DC/Ann. Bus DC supply
supervision relays
AC supply supervision relay
Flasher relay for CB discrepancy
switch
Timer for control switch & CB
discrepancy condition alarm
Test terminal block for protective
relays as required
Distance relay setting group
selector switch - 4 position
Overcurrent/ Earth fault relay
setting group Selector Switch, 3
position, 132/33KV TR OFF
132 KV Feeder Indication
Circuit label
Internally mounted equipment
like
heater
with
switch,
thermostat cubicle illumination
lamps, power socket, switches,
fuses, links etc. as described in
the main specification
Timer for bay transfer sequence
in complete alarm, if required
Over Flux Protection relaying
scheme
HT side of
220/132kV
& 220/33KV
Transformer
Bus Coupler
Set
Set
Nos
Nos
Nos
1
1
Nos
Nos
As reqd.
As reqd.
As reqd.
Nos
Nos
Nos
Set
Nos
Set
Page 57 of 104
20.02 (A) 132KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR TWO MAIN & ONE
TRANSFER BUS SYSTEM:
A.
Feeder
y
Bus Coupler
Bus Transfer
Unit
Sl.
No.
n t
of
side
HT
132/33KV
Transformer
Particulars
u a
of
side
LT
220/132KV
Transformer
FRONT PANEL:
1. Metering Device
a)
b)
c)
d)
e)
f)
2.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
3.
a)
b)
c)
Ammeter
Wattmeter with transducer
Varmeter with transducer
Voltmeter
Wiring for intelligent electronic
computer compatible energy
meter (0.2 class)
Test Terminal Block
Control Device
Circuit Breaker Control Switch
discrepancy type with built-in
indicating lamp
Isolator Control Switch
Auto-reclose Selector Switch (if
any)
Trip Transfer Switch
Synchronising Selector Switch
Multipin Synchronising Socket
(with dummy plug where
necessary)
Discrepancy Switch Steady Lamp
Cut-off Swtich
Voltmeter Selector Switch
Carrier Selector Switch
Bus Transfer Bay Protn. IN/OUT
Selector Switch. 2 position
Bus VT Selector Switch VT1/VT2
Indication
LED Position Indicator for
position indication of Earth
Switch
LED Position Indicator for
position indication of Isolator
Indicating Lamp for incoming DC
fail/ANN. Bus DC fail
Nos
Nos
Nos
Nos
3
1
1
-
3
1
1
-
3
1
-
3
1
1
-
3
1
1
2
-
Nos
Nos
Nos
Nos
Nos
4
1
4
-
4
-
3
-
2
-
Nos
Nos
Nos
1
1
1
1
1
1
1
-
1
1
1
1
Nos
Nos
Nos
Nos
1
-
2
-
Nos
Nos
Nos
Nos
4
-
4
-
4
-
3
-
Page 58 of 104
2
1
e)
f)
g)
h)
i)
j)
k)
4.
a)
b)
c)
d)
e)
f)
B.
1.
of
side
HT
132/33KV
Transformer
n t
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like
Heater
with
Switch,
Thermostat, Cubicle Illumination
Lamps, Power Socket, Switches,
Fuses, Link etc. as described in
the main specification
One
Label
indicating
Manufacturer's
neme,
P.O.Details, Drg. Ref. Nos. etc.
Annunciation
Windows
with
Lamps, Accept/Reset/Test Puish
Button etc. and associated
relays if the annunciator relay is
attached with the windows
Common bell, hooter, associated
relays etc. for annunciation
scheme
REAR PANEL:
Nos
Set
2
1
2
1
2
1
2
1
2
1
1
Set
Set
Nos
Feeder
Bus Coupler
Unit
Bus Transfer
Particulars
Sl.
No.
d)
u a
of
side
LT
220/132KV
Transformer
1
Set
1
16
Nos
16
16
16
16
Page 59 of 104
2.
3.
5.
6.
7.
i)
7.
ii)
8.
9.
10.
11.
12.
13.
14.
15.
y
Bus Coupler
Feeder
Line
CVT operated
under
Voltage Relay for line side earth
switch interlock
Breaker failure relaying scheme
complete with Aux. relay, timers
etc.
Auxiliary
relays
for
C.B.
Closing/Tripping, if necessary
CB monitoring Aux. relays as
required
Distance Protection Scheme
complete in all respect as per
specification, where the line
length is more than 3km.
Line
Differential
Protection
Scheme complete in all respect
as per specification, where the
line length is less than 3km.
Back up directional O/C and E/F
IDMTL relaying scheme with
high set unit complete in all
respect with PT fuse failure
monitoring feature as described
in the specification.
Transformer
differential
protection relaying schemes
described in the specification
complete in all respect
Back up restricted E/F relaying
scheme complete in all respect
as per specification.
Definite time E/F relay for ET
protection
(For Yd Transformer)
Transformer trouble auxiliary
relaying scheme for Buchholz,
winding temp. etc.
Tripping relaying scheme
Protection DC supply supervision
relay
Incoming DC/Ann. Bus DC
supervision relays
Bus Transfer
Unit
Sl.
No.
n t
of
side
HT
132/33KV
Transformer
Particulars
u a
of
side
LT
220/132KV
Transformer
Nos
Set
Set
Set
1
1
1
1
1
1
1
1
Set
Set
1
1
-
Set
1 (3 O/C)
1 (3 O/C)
Set
Set
Set
Set
As reqd.
Set
Nos
1
1
1
1
1
1
1
1
Nos
1
2
Page 60 of 104
16.
17.
Nos
Nos
18.
19.
20.
21.
22.
23.
24.
25.
Feeder
-
Bus Coupler
Bus Transfer
Unit
n t
of
side
HT
132/33KV
Transformer
Particulars
Sl.
No.
u a
of
side
LT
220/132KV
Transformer
1
1
1
Nos
Nos
Set
nos
As
reqd.
-
As reqd.
As reqd.
As
reqd.
1
As
reqd.
-
Nos
Nos
Set
As req
As reqd.
As reqd.
As
reqd.
As
reqd.
Nos
20.02 (B) 132KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR TWO BUS (MAIN &
TRANSFER) SYSTEM:
A.
FRONT PANEL:
1.
Metering Device
a)
b)
c)
d)
Ammeter
Wattmeter with transducer
Varmeter with transducer
Voltmeter
3
1
1
-
Page 61 of 104
3
1
1
-
3
1
-
Bus Transfer
Unit
Nos
Nos
Nos
Nos
n t
of
side
HT
132/33KV
Transformer
Particulars
Feeder
Sl.
No.
u a
of
side
LT
220/132KV
Transformer
3
1
1
1
Control & Relay Panel
e)
f)
2.
a)
b)
c)
d)
e)
f)
g)
h)
i)
3.
a)
b)
c)
d)
e)
f)
g)
h)
Feeder
Wiring for intelligent electronic
computer compatible energy
meter (0.2 class)
Test Terminal Block
Control Device
Circuit Breaker Control Switch
discrepancy type with built-in
indicating lamp
Isolator Control Switch
Auto-reclose Selector Switch (if
any)
Trip Transfer Switch
Synchronising Selector Switch
Multipin Synchronising Socket
(with dummy plug where
necessary)
Discrepancy Switch Steady Lamp
Cut-off Swtich
Voltmeter Selector Switch
Carrier Selector Switch
Bus Transfer Bay Protn. IN/OUT
Selector Switch. 2 position
Indication
LED Position Indicator for
position indication of Earth
Switch
LED Position Indicator for
position indication of Isolator
Indicating Lamp for incoming DC
fail/ANN. Bus DC fail
Push Button Incoming DC
fail/ANN. Bus DC fail alarm
accept & test
Bus PT supply healthy indicating
lamp
Trip Circuit healthy indicating
lamp
Trip Circuit healthy Check Push
Button
C.B. Spring Charge Indicating
Lamp where necessary
y
Bus Transfer
Unit
Sl.
No.
n t
of
side
HT
132/33KV
Transformer
Particulars
u a
of
side
LT
220/132KV
Transformer
Nos
Nos
Nos
Nos
Nos
3
1
3
-
3
-
5
-
Nos
Nos
Nos
1
1
1
1
1
1
1
-
1
1
Nos
Nos
Nos
1
1
-
Nos
Nos
Nos
3
-
3
-
3
-
5
1
Nos
Nos
Nos
Nos
Nos
Page 62 of 104
j)
k)
4.
a)
b)
c)
d)
e)
f)
B.
1.
2.
3.
5.
6.
y
of
side
HT
132/33KV
Transformer
n t
Unit
Nos
Nos
Nos
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like
Heater
with
Switch,
Thermostat, Cubicle Illumination
Lamps, Power Socket, Switches,
Fuses, Link etc. as described in
the main specification
One
Label
indicating
Manufacturer's
neme,
P.O.Details, Drg. Ref. Nos. etc.
Annunciation
Windows
with
Lamps, Accept/Reset/Test Push
Button etc. and associated
relays if the annunciator relay is
attached with the windows
Common bell, hooter, associated
relays etc. for annunciation
scheme
REAR PANEL:
Nos
Set
2
1
2
1
2
1
2
1
Set
Set
Nos
16
16
Set
Nos
Nos
Set
Set
Set
1
1
1
1
1
1
1
1
Feeder
Page 63 of 104
16
Bus Transfer
Particulars
Sl.
No.
i)
u a
of
side
LT
220/132KV
Transformer
16
7.
i)
7.
ii)
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Feeder
Distance Protection Scheme
complete in all respect as per
specification, where the line
length is more than 3km.
Line
Differential
Protection
Scheme complete in all respect
as per specification, where the
line length is less than 3km.
Back up directional O/C and E/F
IDMTL relaying scheme with
high set unit complete in all
respect with PT fuse failure
monitoring feature as described
in the specification.
Transformer
differential
protection relaying schemes
described in the specification
complete in all respect
Back up restricted E/F relaying
scheme complete in all respect
as per specification.
Definite time E/F relay for ET
protection
(For Yd Transformer)
Transformer trouble auxiliary
relaying scheme for Buchholz,
winding temp. etc.
Tripping relaying scheme
Protection DC supply supervision
relay
Incoming DC/Ann. Bus DC
supervision relays
AC supply supervision relay
Flasher relay for CB discrepancy
switch
Timer for control switch & CB
discrepancy condition alarm
Incoming DC/Ann Bus DC fail
alarm accept relay, AC operated
Test
terminal
block
for
protective relays as required
y
Bus Transfer
Unit
Sl.
No.
n t
of
side
HT
132/33KV
Transformer
Particulars
u a
of
side
LT
220/132KV
Transformer
Set
Set
Set
1 (3 O/C)
1 (3 O/C)
Set
Set
Set
Set
As reqd.
Set
Nos
1
1
1
1
1
1
1
1
Nos
Nos
Nos
2
1
1
Nos
Nos
As req
As reqd.
As reqd.
As
reqd.
Set
Page 64 of 104
22.
23.
24.
25.
y
of
side
HT
132/33KV
Transformer
n t
Unit
nos
Nos
Nos
Set
As req
As reqd.
As reqd.
As
reqd.
Nos
Feeder
Bus Transfer
Particulars
Sl.
No.
21.
u a
of
side
LT
220/132KV
Transformer
20.02 (C)
132 KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR TWO BUS (TWO
MAIN) GIS SYSTEM:
A.
FRONT PANEL:
1.
Metering Device
a)
b)
c)
d)
e)
Ammeter
Wattmeter with transducer
Varmeter with transducer
Voltmeter
Wiring
for
intelligent
electronic
computer
compatible energy meter (0.2
class)
Test Terminal Block
Control Device
f)
2.
Bus Coupler
Feeder
Sl.
No.
side
HT
132/33KV
Transformer
Unit
side
LT
220/132KV
Transformer
Particulars
n t
of
u a
of
Nos
Nos
Nos
Nos
Nos
3
1
1
1
3
1
1
-
3
1
1
3
1
1
2
-
Nos
Page 65 of 104
b)
c)
d)
e)
f)
g)
h)
i)
j)
3.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
Bus Coupler
Nos
Nos
Nos
Nos
3
4
1
3
4
-
3
4
-
4
6
-
Nos
Nos
Nos
Nos
Nos
Nos
1
-
2
-
Nos
4
4
6
6
8
Feeder
LED Position Indicator for
position indicaton of Earth
Switch Isolator
Isolator
Status
Indicating
Lamps Red/Green
Indicating Lamp for incoming
DC fail/ANN. Bus DC fail
Push Button Incoming DC
fail/ANN. Bus DC fail alarm
accept & test
Bus
PT
supply
healthy
indicating lamp
Trip Circuit healthy indicating
lamp
Trip Circuit healthy Check
Push Button
C.B. Spring Charge Indicating
Lamp where necessary
Push Button for C.B. Spring
charge check if required
Test
Push
Button
for
Incoming DC Supervision
side
HT
132/33KV
Transformer
Unit
side
LT
220/132KV
Transformer
Particulars
Sl.
No.
a)
n t
of
u a
of
Nos
4
6
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Page 66 of 104
4.
a)
b)
c)
d)
e)
f)
Bus Coupler
Circuit Label
Section of Mimic Diagram
Internally mounted equipment
like Heater with Switch,
Thermostat,
Cubicle
Illumination Lamps, Power
Socket, Switches, Fuses, Link
etc. as described in the main
specification
One
Label
indicating
Manufacturer's
neme,
P.O.Details, Drg. Ref. Nos.
etc.
Annunciation Windows with
DC fail annunciation as reqd,
with
Lamps,
Accept/Reset/Test
Push
Button etc. and associated
Relays if the annunciator relay
is attached with the windows
Common
bell,
hooter,
associated relays etc. for
annunciation scheme
Nos
Set
2
1
2
1
2
1
2
1
Set
Set
As Req
As Req
As Req
As Req
Set
Nos
Nos
Set
Feeder
1.
side
HT
132/33KV
Transformer
Nos
side
LT
220/132KV
Transformer
REAR PANEL:
3.
Unit
B.
2.
Particulars
Sl.
No.
k)
n t
of
u a
of
Nos
Page 67 of 104
5.
6.
6a).
7.
8.
9.
10.
11.
12.
13.
14.
15.
Bus Coupler
Set
Set
Set
Set
Set
Set
1 (3 O/C)
1 (3 O/C)
1(Non
directional)
Set
Set
Set
Set
As reqd.
Set
Incoming
DC
supply
supervision relay
Ann. Bus DC supervision
relays
Nos
Nos
Feeder
Page 68 of 104
side
HT
132/33KV
Transformer
Unit
side
LT
220/132KV
Transformer
Particulars
Sl.
No.
4.
n t
of
u a
of
18.
Bus Coupler
Nos
Nos
1
1
Nos
Nos
Set
As req
As reqd.
As reqd.
As reqd.
nos
Nos
Nos
Set
As req
As reqd.
As reqd.
As reqd.
Nos
Feeder
side
HT
132/33KV
Transformer
Unit
side
LT
220/132KV
Transformer
Particulars
Sl.
No.
16.
17.
n t
of
u a
of
20.
21.
22.
23.
24.
25.
Page 69 of 104
20.03(A)
TRANSFER)
33KV SIMPLEX TYPE CONTROL AND RELAY PANEL FOR TWO BUS (MAIN &
SYSTEM
Sl.
No.
Particulars
1.
Metering Device
a)
b)
c)
Ammeter
Voltmeter
Wiring
for
intelligent
electronic
computer
compatible energy meter
(0.2 class)
Test Terminal Block
Control Device
Q u a n t I t y
Feeder
LT
side
of
220/33KV
&
132/33KV
Transformer
HT side of
33/11KV
Transformer
Bus
Transfer
Nos
Nos
Nos
3
1
3
-
3
1
3
1
-
Nos
Circuit
Breaker
Control
Switch 3-position, Spring
return
Voltmeter Selector Switch
Trip Transfer Switch
Overcurrent/ Earth fault
relay setting group Selector
Switch,
3
position,
132/33KV TR OFF 132
KV Feeder Indication
Five position selector switch
for Earthing Transformer
selection
U/F selector switch
Nos
Nos
Nos
1
-
Nos
Nos
Nos
e)
Nos
3.
Indication
a)
d)
2.
a)
b)
c)
d)
e)
d)
b)
c)
d)
e)
f)
Unit
Nos
Nos
Nos
Nos
Nos
Nos
Page 70 of 104
Sl.
No.
g)
h)
i)
j)
k)
4.
Particulars
lamp
Trip circuit healthy check
push button
CB spring charge indicating
lamp
Push Button for CB spring
charge check
CB Auto Trip indicator
Test Push Button for panel
protection DC supervision
and AC supervision
RELAYS
Unit
Q u a n t I t y
Feeder
LT
side
of
220/33KV
&
132/33KV
Transformer
HT side of
33/11KV
Transformer
Bus
Transfer
Nos
Nos
Nos
Nos
Nos
1
1
1
1
1
1
1
2
a)
Nos
b)
Auxiliary
relay
for
CB
closing/tripping
If necessary
CB monitoring Aux. relays as
reqd.
Directional O/C and E/F
IDMTL relaying scheme with
high set unit complete in all
respect with PT fuse failure
monitoring
feature
as
described
in
the
specification.
Restricted
E/F
relaying
scheme complete in all
respect as per specification.
Power , Earthing & Station
service Transformer Trouble
auxiliary relaying scheme for
Buchholz,
winding
temperature etc.
Tripping Relaying scheme
including lock out feature
Protection
DC
supply
supervision relays
Incoming DC/Ann. Bus DC
supply supervision relays
AC supply supervision relays
Incoming DC / Ann. Bus DC
fail alarm accept relay, AC
Set
Set
Set
Set
Set
As reqd.
As reqd.
Set
Nos
Nos
Nos
Nos
2
1
1
c)
d)
e)
f)
g)
h)
i)
j)
k)
Page 71 of 104
Sl.
No.
l)
m)
5.
a)
b)
c)
d)
e)
f)
Particulars
Unit
operated
Test block for protective
relays
Under frequency relay along
with contact multiplication
relay
Other Devices :
Circuit Label
Section of Mimic Diagram
Internally
mounted
equipment like Heater with
Switch, Thermostat, Cubicle
Illumination Lamps, power
socket, switches, fuses, link
etc. as described in the main
specification
One
Label
Indicating
Manufacturers Name, P.O.
Details, Drg. Ref. Nos. etc.
Annunciation
Windows,
Lamps,
Accept/Reset/Test
Push Button etc. associated
Relays if the annunciator
relay is attached with the
windows.
Common
bell,
hooter,
associated relays etc. for
annunciation scheme
Q u a n t I t y
Feeder
LT
side
of
220/33KV
&
132/33KV
Transformer
HT side of
33/11KV
Transformer
Bus
Transfer
Nos
As
reqd.
As reqd.
As reqd.
As reqd.
Nos
Nos
Set
1
1
1
1
1
1
1
1
Set
Set
Nos
12
12
12
20
Set
20.03(B) 33 KV SIMPLEX TYPE CONTROL AND RELAY PANEL FOR TWO BUS (With Bus
Section) INDOOR TYPE SWITCHGEAR SYSTEM:
Sl.
Particulars
Unit
No.
Q u a n t I
Feeder
1.
Metering Device
a)
b)
c)
Ammeter
Voltmeter
Wiring
for
electronic
intelligent
computer
Nos
Nos
Nos
3
1
Page 72 of 104
3
-
t y
Bus
Coupler
3
2
-
Sl.
Particulars
Unit
No.
d)
2.
a)
b)
c)
d)
e)
3.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
4.
a)
Q u a n t I
Feeder
compatible energy
(0.2 class)
Test Terminal Block
Control Device
t y
Bus
Coupler
meter
Nos
Circuit
Breaker
Control
Switch 3-position, Spring
return
Voltmeter Selector Switch
Five position selector switch
for Earthing Transformer
selection
U/F selector switch
Selector Sw for trip selection
in power injection mode
Indication
Nos
Nos
Nos
2
-
Nos
Nos
1
1
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
1
1
1
1
1
2
Nos
Page 73 of 104
Sl.
Particulars
Unit
No.
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
5.
a)
b)
c)
Q u a n t I
Feeder
Auxiliary
relay
for
CB
closing/tripping
If necessary
CB monitoring Aux. relays as
reqd.
Directional O/C and E/F
IDMTL relaying scheme with
high set unit complete in all
respect with PT fuse failure
monitoring
feature
as
described
in
the
specification.
Restricted
E/F
relaying
scheme complete in all
respect as per specification.
Power , Earthing & Station
service Transformer Trouble
auxiliary relaying scheme for
Buchholz,
winding
temperature etc.
Tripping Relaying scheme
including lock out feature
Protection
DC
supply
supervision relays
Incoming DC/Ann. Bus DC
supply supervision relays
AC supply supervision relays
Incoming DC / Ann. Bus DC
fail alarm accept relay, AC
operated
Test block for protective
relays
Under frequency relay along
with contact multiplication
relay
Other Devices :
Circuit Label
Section of Mimic Diagram
Internally
mounted
equipment like Heater with
Switch, Thermostat, Cubicle
Illumination Lamps, power
t y
Bus
Coupler
Set
Set
Set
Set
Set
As reqd.
Set
Nos
Nos
Nos
Nos
2
1
1
Nos
As
reqd.
As reqd.
As reqd.
Nos
Nos
Set
1
1
1
1
1
1
Set
Page 74 of 104
Sl.
Particulars
Unit
No.
d)
e)
f)
Q u a n t I
Feeder
t y
Bus
Coupler
Set
Nos
12
12
20
Set
20.03(C) 33 KV SIMPLEX TYPE CONTROL AND RELAY PANEL FOR CAPACITOR BANK:
Sl.
No.
Particulars
1.
Metering Device
a)
b)
c)
d)
2.
Ammeter
Voltmeter
VARmeter with transducers
Test Terminal Block
Control Device
a)
b)
3.
a)
a)
e)
f)
g)
h)
i)
Unit
Quantity
Capacitor Bank Bay
Switch
3-position,
Nos
Nos
Nos
Nos
3
1
1
1
Nos
Nos
Nos
Nos
1
As applicable
Nos
Nos
Nos
Nos
Nos
2
1
1
1
1
Page 75 of 104
Sl.
No.
Particulars
j)
Nos
Nos
Set
Set
Set
Set
Set
Set
Nos
Nos
1
As reqd.
Circuit Label
Section of Mimic Diagram
Internally mounted equipment like Heater with
Switch, Thermostat, Cubicle Illumination
Lamps, power socket, switches, fuses, link etc.
as described in the main specification
One Label Indicating Manufacturers Name,
P.O. Details, Drg. Ref. Nos. etc.
Annunciation
Windows,
Lamps,
Nos
Set
1
1
Set
Set
Nos
12
4.
a)
b)
c)
d)
e)
f)
g)
h)
h)
l)
5.
a)
b)
c)
d)
e)
Unit
Quantity
Capacitor Bank Bay
Page 76 of 104
20.04 (A) 400KV DUPLEX TYPE CONTROL AND RELAY PANEL FOR TWO MAIN AND ONE
TRANSFER BUS AIS SYSTEM:
Unit
Sl.
No.
Quantity
Particulars
Feeder
HT side of
400/220KV
transformer
Bus
reactor
Bus
coupler
Bus transfer
3
2
1
A. FRONT PANEL:
1
Metering Device
a)
b)
c)
Ammeter
Voltmeter
Wattmeter
with
transducers
varmeter
with
transducers
Provision for RWTI
meter
Wiring for TVM for
Export/Import
Nos
Nos
Nos
3
1
1
3
1
Nos
Nos
Nos
Nos
1
1
Circuit
breaker
control
switch
Discrepancy
type
with
builtin
Indicator lamp
Isolator
control
switch
Auto-reclose selector
switch
Trip transfer switch
Line VT/ Bus VT
selector switch, 4
position, Line VTInter1-Inter2-Bus VT
Synchronising
Nos
Nos
Nos
Nos
Nos
1
1
Nos
d)
e)
f)
g)
h)
i)
j)
k)
l)
2
a)
b)
c)
d)
e)
f)
Nos
2
1
Nos
Nos
Nos
Nos
1
-
Page 77 of 104
Unit
Sl.
No.
g)
h)
i)
j)
3
a)
b)
c)
d)
e)
f)
4
a)
b)
c)
Quantity
Particulars
selector switch, 2
position
Multipin
synchronising socket
Discrepancy
switch
steady lamp Cut off
switch, 2- position
DC supply selector
switch, 3 position,
Supply-1/
Independent
/Supply-2
VT selector switch, 2
position, VT 1 / VT
2
Indication
Nos
Feeder
HT side of
400/220KV
transformer
Nos
Nos
Nos
Bus
reactor
Bus
coupler
Bus transfer
Nos
Nos
Nos
Nos
Nos
Nos
Circuit label
Section of mimic
diagram
Internally
mounted
equipment
like
Heater with switch,
Nos
Set
2
1
2
1
2
1
2
1
2
1
Set
Page 78 of 104
Unit
Sl.
No.
d)
e)
f)
B.
1
2
5
7
Quantity
Particulars
thermostat,Cubicle
illumination
lamps,
power
Socket,
switches, fuses, link
etc. As described in
the main specification
One label indicating
manufacturers
Name,
P.O.
details,drg. ref. nos
etc.
Annunciation
windows,
lamps,
Accept/reset/test
push button etc. and
Associated relays if
the
annunciator
Relay is attached
with the windows
Common bell, hooter,
associated
Relays
etc. for annunciation
scheme
REAR PANEL:
Trip
circuit
supervision relay
Line CVT operated
under voltage Relay
for line side earth
switch interlock
Bus
VT
supply
selection
relaying
Scheme for metering
and protection Circuit
complete
in
all
respect
Auxiliary relays for
C.B
closing/
Tripping, if necessary
Circuit label
Internally
mounted
equipment
Like
heater with switch,
thermostat, Cubicle
Feeder
HT side of
400/220KV
transformer
Bus
reactor
Bus
coupler
Bus transfer
Set
Set
Set
Nos
Set
Set
Set
Nos
Set
2
1
2
1
2
1
2
1
2
1
Page 79 of 104
Unit
Sl.
No.
10
11
12
13
14
15
Quantity
Particulars
illumination
lamp,
power
Socket,
switch, fuse, links etc
as Described in main
specs
Timer
for
bus
selection incomplete
Alarm
Timer for discrepancy
alarm
of
Control
switch and CB
Flasher
relay
discrepancy condition
Of CB & its control
switch
Timer
for
bay
transfer
sequence
Incomplete alarm
CB
monitoring
auxiliary relays
Common DC supply
& aux. bus DC 1 & 2
supervision relay
AC operated accept
relay for above
AC supply supervision
relay
Feeder
HT side of
400/220KV
transformer
Bus
reactor
Bus
coupler
Bus transfer
Nos
Nos
Nos
Nos
As
As
As
As
As
Nos
reqd.
-
reqd.
-
reqd.
-
reqd.
4
reqd.
-
Nos
Nos
20.04 (B) 400KV SIMPLEX TYPE PROTECTION PANEL FOR TWO MAIN AND ONE
TRANSFER BUS AIS SYSTEM::
Sl.
Particulars
Unit
No.
Quantity
Feeder
HT
side
of
Bus reactor
Bus transfer
400/220KV
transformer
1
Main-1
numerical
distance protection
scheme
as
per
specification
Main-2
numerical
distance protection
scheme
as per
Set
Set
Page 80 of 104
Sl.
Particulars
Unit
No.
Quantity
Feeder
HT
side
of
Bus reactor
Bus transfer
400/220KV
transformer
2
7
8
10
11
12
specification
LBB Scheme with
carrier
tripping,
busbar
protection
and direct tripping
scheme
etc.from
remote
end.
(Preferably built in
Bus
Differential
relay)
DC
supervision
scheme relays for
M-1/Gr-A and M2/Gr.B protection
Over voltage protn
scheme
as
per
specification.
Transformer
differential
protection scheme
Circulatory current
protection relaying
scheme
REF protection
Backup directional
over current & earth
fault protection
Backup single step
impedance
protection scheme
Transformer/Bus
Reactor
internal
trouble
protection
scheme
Trip
relaying
scheme for M1/M2
of feeder GrA/Gr B
for
transformer/
Reactor etc. and
Trip
Relay
Supervision Relay
Over flux protection
Set
Set
Set
Set
Set
Set
Set
1
-
Set
Set
Set
Set
Page 81 of 104
Sl.
Particulars
Unit
No.
Quantity
Feeder
HT
side
of
Bus reactor
Bus transfer
400/220KV
transformer
13
Carrier
Switch
Selector
Nos
14
Distance
relay
setting
group
selector switch - 4
position
Nos
15
Nos
20.04 (C) 400KV SIMPLEX TYPE CONTROL PANEL FOR ONE AND HALF BREAKER
SYSTEM:
Q u a n t i t y
Sl.
No.
Particulars
A.
CONTROL PANEL
1.
Metering Device
a)
b)
Ammeter
Voltmeter
Nos
Nos
c)
d)
e)
f)
g)
Nos
Nos
Nos
Nos
Nos
h)
i)
j)
Frequency Meter
Nos
k)
Recording
voltmeter
(Digital)
Recording frequency meter
(Digital)
Remote
winding
temperature
Indicator
selector switch
Control Device
Nos
l)
m)
2.
Unit
Nos
Nos
Nos
Nos
Feeder Bay
Transformer Bay
Reactor Bay
Tie Bay
3
1+2(in any one
panel for bus)
1
1
1
3
1
3
1
1
1
1
1
1
1
1
1+2(in any one
panel for bus)
2(in any one
panel for bus)
2(in any one
panel for bus)
2(in any one
panel for bus)
-
1
1
1
1
Page 82 of 104
Sl.
No.
a)
b)
c)
d)
e)
f)
g)
h)
i)
3.
a)
b)
c)
d)
e)
f)
g)
g)
Q u a n t i t y
Particulars
Unit
Nos
Feeder Bay
Transformer Bay
Reactor Bay
Tie Bay
Nos
Nos
Nos
Nos
Set
Nos
1no in any one panel.
Nos
1no for each dia.
Nos
Nos
Nos
As reqd.
As reqd.
Nos
1set for each Bus PT in any one panel
Set
Nos
Nos
Nos
Nos
Page 83 of 104
Q u a n t i t y
Sl.
No.
Particulars
4.
Other Devices
a)
b)
c)
Circuit Label
Section of Mimic Diagram
Internally
mounted
equipment like Heater with
Switch,
Thermostat,
Cubicle Illumination Lamps,
Power Socket, Switches,
Fuses,
Link
etc.
as
described in the main
specification
One
Label
Indicating
Manufacturers Name, P.O.
Details, Drg. Ref. Nos. etc.
Annunciation Windows as
reqd,
with
Lamps,
Accept/Reset/Test
Push
Button etc. and associated
Relays if the annunciator
relay is attached with the
windows
d)
e)
Unit
Feeder Bay
Transformer Bay
Nos
Set
Reactor Bay
Tie Bay
Set
Set
48
32
As reqd.
nos
20.04 (D) 400KV SIMPLEX TYPE RELAY PANEL FOR ONE AND HALF BREAKER SYSTEM:
Q u a n t i t y
Sl.
No.
Particulars
A.
RELAY PANEL:
a)
b)
Auto-reclose
Selector
Switch (if necessary)
CB Trip circuit supervision
relay
Line CVT operated under
voltage Relay for line side
earth switch interlock
LBB Scheme with carrier
tripping, busbar protection
and direct tripping scheme
etc. from remote end.
(Preferably inbuilt in Bus
Differential relay)
c)
d)
e)
Unit
Feeder Bay
Transformer Bay
Reactor Bay
Tie Bay
Nos
Set
Set
Set
Page 84 of 104
Q u a n t i t y
Sl.
No.
f)
g)
h)
i)
j)
k)
l)
m)
n)
o)
p)
q)
Particulars
Unit
Nos
Feeder Bay
Transformer Bay
Reactor Bay
Tie Bay
Set
Set
Set
As reqd.
As reqd.
As reqd.
Nos
Set
2
1
2
1
2
1
2
1
Nos
Nos
1set in any one panel
As Reqd.
As Reqd.
As Reqd.
As Reqd.
As Reqd.
As Reqd.
As Reqd.
As Reqd.
Nos
Set
Page 85 of 104
20.04 (E)
400KV SIMPLEX TYPE PROTECTION PANEL FOR ONE AND HALF BREAKER
SYSTEM:
Q u a n t I t y
Sl.
No.
Particulars
Unit
Feeder
Transformer
Reactor
2
1
Set
Set
Set
A. PROTECTION PANEL
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
Nos
Nos
Set
Set
Set
Set
Set
Set
Set
Set
As reqd.
As reqd.
Page 86 of 104
Q u a n t I t y
Sl.
No.
n)
o)
p)
q)
r)
Particulars
Trip relaying scheme for
M1/M2 of feeder GrA/Gr B for
transformer/ Reactor etc. &
Trip Relay Supervision Relay
Over Flux Protection relaying
scheme
Test terminal block for
protective relays as required
Circuit label
Internally
mounted
equipment like heater with
switch, thermostat cubicle
illumination lamps, power
socket, switches, fuses, links
etc. as described in the main
specification
Unit
Feeder
Transformer
Reactor
Set
Nos
As reqd.
As reqd.
As reqd.
Nos
Set
Set
NB:
Items in case of incomplete diameter (D and I type layouts), control panel shall be equipped
fully as if the diameter is complete, unless otherwise specified. Annunciation relays shall also
be provided for the same and if required, necessary panel shall be supplied to accommodate
the same.
20.05 Bus Zone Protection for 400 & 220kV system:
All Equipment/relays, trip relays with trip coil supervision relay, Local Breaker Back-up
protection relay, CT Switching relay etc for all connected bays and bus extension bays with
the provision of future bays along with CPU & Bay unit for the bus bar protection scheme as
required for busbar protection as per Clause No. 16.21.01 & 16.21.02 shall be provided in one
set of separate simplex type panel.
21.00 DEVIATION:
Normally the offer should be as per technical specification without any deviation. For any
deviation in the tender quoted by the tenderer, the same shall be clearly indicated in the
deviation sheet, clause by clause, indicating reason and advantage for such deviation. Such
deviations may or may not be accepted. Deviation not indicated in the deviation sheet will not
be considered.
Page 87 of 104
23.00 TENDER DRAWING, LITERATURE AND TEST CERTIFICATES BOTH FOR ROUTINE
TEST AND TYPE TEST:
Following drawings, literatures, filled up GTP and test certificates shall be submitted with the
tender for evaluation:
a)
b)
c)
d)
e)
Principal dimensioned details of each unit cubicle and complete assembly of panel board.
Front and rear views of the panel board with instrument and device positions marked.
Details of protection scheme of lines, transformers and other bays including annunciation,
monitoring, supervision etc. offered.
Literature describing the instruments, switches, relays and their characteristics, technical
details, relay setting calculation, operating manual etc.
Routine and type test certificates of all the protective relays carried out as per relevant IEC/
IS from a recognised laboratory shall be furnished. Performance certificate of all protective
relays from Power Utilities in India shall also be furnished.
Detailed dimensional drawings of control and relay panel including foundation drg. with cable
slots showing all equipment mounted on them along with complete panel wise list of
equipment and list of Name Plates. Weight of these panels with all the equipment mounted
on these shall also be furnished in the Drg.
b)
c)
Outlined drawings of internal wiring diagram of the instrument, relays, meters, annunciator
and other equipment showing external terminal connections with the equipment terminal
number.
d)
Complete AC and DC Schematic diagram of all panels of control and relay board to indicate
the followings:
i)
Annunciator circuit
ii)
Protection and control circuit
iii)
Indication and Supervision circuit
iv)
Synchronising circuit
v)
Other circuits as necessary
These drawings shall show AC power connection and Secondary connections for relays,
meters, terminal blocks with their number etc. interconnection diagram between control and
Page 88 of 104
relay board and circuit breaker, Power and Instrument Transformer and other equipment as
necessary.
24.02 After approval of above drawings ten sets of those drawings for each set complete set of C&R
board and wiring schedule including bus wire diagram for each panel are to be supplied by
the contractor.
One set of reproducible of the above drawings for each C&R board formation shall also be
supplied.
24.03 Six copies of the following literatures shall be supplied along with the approved drawings and
one
set of the same (soft copy) shall be supplied along with the drawing in the
first
submission:
a)
Literature describing construction, operation, adjustment and rating specification of all the
protective and auxiliary relays, recording instruments, metering instruments, control and
other switches, annunciators, fault locator, disturbance recorder and other equipments which
are used in the C&R panel.
b)
List of spare parts, identification number of renewable parts of relays, instruments, switches
and other equipments with the help of which the purchaser will be able to procure spare
parts from the contractor at any subsequent line.
c)
Commissioning, operating, maintenance instruction manual for each relay and equipment of
the panel.
b)
Relays and meters may be further tested at our testing laboratory. If any equipment is found
to be not in conformity with the specification by our testing engineers during testing, the
same shall be replaced by you at your cost immediately.
Page 89 of 104
SL
DESCRIPTION
Name Of Manufacturer
Conforming Standard
5.1
Front
5.2
Back
5.3
Sides
Details of Painting
10
11
Details of Tropicalisation
12
12.1
Gross weight
12.2
Overall dimensions
Name Of Manufacturer
Conforming Standard
Operating Voltage
TERMINAL BLOCK
Name Of Manufacturer
Conforming Standard
Rated current
Page 90 of 104
SUBMISSION
SL
DESCRIPTION
Rated voltage
Materials used
7.1
Body
7.2
Terminal studs
7.3
Connecting links
7.4
Support springs
8.1
8.2
CT Circuits
CONTROL SWITCHES
Name Of Manufacturer
Conforming Standard
Type of Handle
5.1
5.2
SUBMISSION
Rating of Contacts :
6.1
Voltage
6.2
6.3
6.4
6.5
Mounting details
Dimensions
10
INDICATING LAMPS
Name Of Manufacturer
Conforming Standard
Ratings :
4.1
Current
4.2
Voltage
4.3
Wattage
Page 91 of 104
SL
DESCRIPTION
SUBMISSION
Colour of lamp
7.1
Ohmic value
7.2
Power loss
PUSH BUTTONS
Name Of Manufacturer
Conforming Standard
Whether integral
plates provided
ANNUNCIATORS
Name OF Manufacturer
Conforming Standard
No. of windows
Power Consumption
10
11
12
13
Particulars of wiring
14
Technical literature
15
16
engraved
inspection
Page 92 of 104
SL
DESCRIPTION
INDICATING METERS (Digital) (To be
furnished separately for each type of
meter)
Name Of Manufacturer
Conforming Standard
Range :
4.1
Effective Range
4.2
Fiducial value
CT Ratio
PT Ratio
Accuracy class
Overall dimensions
10
11
Display dimension
12
Display illumination
13
EMC
14
Measurement principal
15
Whether communicable
16
Response time
Name OF Manufacturer
Input Quantities
4.1
4.2
4.3
Rated DC Voltage
4.4
4.5
SUBMISSION
Burden
5.1
C.T. Circuit
5.2
P.T. Circuit
5.3
D.C. Circuit :
Page 93 of 104
SL
DESCRIPTION
5.3.1
Operating (Maxm.)
5.3.2
Quiescent (Maxm.)
SUBMISSION
6.1
6.2
Characteristic on R - X plane
10
10.1
Zone 1
10.2
Zone 2
10.3
Zone 3
10.4
11
11.1
Zone 2
11.2
Zone 3
11.3
12
13
13.1
Setting ranges
13.2
Whether
provided
13.3
14
14.1
15
15.1
16
independent
zone
selection
16.1
Single phase
16.2
Three phase
16.3
17
18
Page 94 of 104
SL
DESCRIPTION
18.1
18.2
18.3
19
Accuracy :
19.1
Zone 1 reach
19.2
Zone 2 reach
19.3
Zone 3 reach
19.4
19.5
Angular reach
20
SUBMISSION
20.1
SIR = 4
20.2
SIR = 15
21
22
23
23.1
23.2
23.3
Break :
23.3.1
Resistive load
23.3.2
24
25
26
Page 95 of 104
SL
DESCRIPTION
SUBMISSION
Triggering Method
Whether
following
fault
provided in displaying unit
4.1
information
4.1.1
Resistive detection
4.1.2
Reactive detection
4.2
Faulted Phase
4.3
Time of Fault
4.4
Date of Fault
Accuracy
NUMERICAL
TRANSFORMER
DIFFERENTIAL RELAYS
Name of Manufacturer
Current Rating
Display
Page 96 of 104
SL
DESCRIPTION
10
11
12
13
14
Contact rating :
14.1
14.2
14.3
Break :
14.3.1
Resistive load
14.3.2
Inductive
constant
load
with
40
SUBMISSION
millisec
time
15
Name of Manufacturer
Conforming Standard
Rated DC voltage
Number of Contacts
8.1
Normally open
8.2
Normally closed
10
11
12
Contact Ratings :
12.1
12.2
12.3
Break
12.3.1
Resistive Load
12.3.2
13
Setting ranges :
Page 97 of 104
SL
DESCRIPTION
13.1
V/F
13.2
13.3
SUBMISSION
Name of Manufacturer
Rated current
Rated DC voltage
Operating Principle
10
Contacts Latched/Unlatched/Programmable
11
Burden
12
13
Contact Ratings
13.1
13.2
13.3
Break :
13.3.1
Resistive Load
13.3.2
14
Operating characteristics
15
15.1
Inverse time
15.2
16
Page 98 of 104
for
SL
DESCRIPTION
Number of
available
binary
inputs
SUBMISSION
&
outputs
5.1
Analog Channel
5.2
Event Channel
Linearity Error
Memory :
8.1
Pre fault in ms
8.2
Frequency Response
10
11
Resolution :
11.1
Time
11.2
Amplitude
12.1
Page 99 of 104
SL
DESCRIPTION
12.2
13
SUBMISSION
Name of Manufacturer
Conforming Standard
Rated current
Rated DC voltage
Operating principle
10
11
Burden
12
13
Contact Ratings
13.1
13.2
13.3
Break
13.3.1
Resistive Load
13.3.2
14
Setting range
15
Operating Time
16
17
18
Name of Manufacturer
Rated current
Rated DC voltage
SL
DESCRIPTION
Operating
principle
(Distributed
architecture or Central architecture)
Operation
Impedance:
10
% Biasing
11
12
Number of Contacts :
12.1
Normally open
12.2
Normally closed
Low
impedance/High
13
14
Burden
15
16
Contact Ratings :
16.1
16.2
16.3
Break :
16.3.1
Resistive Load
16.3.2
17
Operating time
18
Setting ranges
19
20
21
22
23
Name of Manufacturer
Conforming Standard
Rated current
Rated DC voltage
Operating principle
SUBMISSION
SL
DESCRIPTION
Number of Contacts :
9.1
Normally open
9.2
Normally closed
10
Burden
11
12
Contact Ratings :
12.1
12.2
12.3
Break :
12.3.1
Resistive Load
12.3.2
13
Operating time
14
Resetting time
15
Setting range :
15.1
Current
15.2
Time
Name of Manufacturer
Conforming Standard
Rated DC voltage
Operating principle
Electro mechanical
Number of Contacts :
8.1
Normally open
8.2
Normally closed
10
Burden
11
12
Contact Ratings :
12.1
12.2
12.3
Break :
12.3.1
Resistive Load
12.3.2
SUBMISSION
SL
DESCRIPTION
13
14
Time delay
UNIVERSAL
AND VTs :
Name of Manufacturer
Conforming Standard
Ratio
Rated output VA
Class of accuracy
7.1
Current
7.2
Voltage
TYPE
SUBMISSION
post
AUXILIARY
9.1
KPV
9.2
50 Percent KPV
10
Internal resistance of
10.1
Primary
10.2
Secondary
11
Temperature rise
12
Mounting details
13
Overall dimensions
14
Name of Manufacturer
Conforming Standard
Rated DC voltage
Electro mechanical
Number of Contacts :
8.1
Self Reset
8.2
Hand Reset
Burden
10
closing
CTs
SL
11
DESCRIPTION
Contact Ratings :
11.1
11.2
11.3
Break :
11.3.1
Resistive Load
11.3.2
12
Operating Time
Name of Manufacturer
Conforming Standard
7.1
7.2
Burden
10
11
12
Contact Ratings :
12.1
12.2
12.3
12.3.1
12.3.2
SUBMISSION
Break :
Resistive Load
Inductive Load (with L/R = 40)