This document contains a list of access control, infrastructure, cabling, climate control, compliance, communication, electric, and fire protection requirements for a datacenter. Some key requirements include installing CCTV cameras inside and outside to monitor access points, using synchronized doors and identification badges to control entrance, separating different cable types and removing unused cables, ensuring independent and redundant climate control and power systems, periodically checking configurations for compliance, protecting communication lines from tapping, installing generators and circuit breakers for continuous power, and conducting fire drills. The document outlines many physical and technical security controls for restricting access and protecting the datacenter environment.

Uploaded by

Sergio Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
827 views6 pages

CheckList Datacenter

This document contains a list of access control, infrastructure, cabling, climate control, compliance, communication, electric, and fire protection requirements for a datacenter. Some key requirements include installing CCTV cameras inside and outside to monitor access points, using synchronized doors and identification badges to control entrance, separating different cable types and removing unused cables, ensuring independent and redundant climate control and power systems, periodically checking configurations for compliance, protecting communication lines from tapping, installing generators and circuit breakers for continuous power, and conducting fire drills. The document outlines many physical and technical security controls for restricting access and protecting the datacenter environment.

Uploaded by

Sergio Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 6

Group : Access control

Exists

Control
13602 - Closed-circuit TV cameras (CCTV) should be installed both inside and
outside the areas providing access to the roof terrace.
2771 - A pair of synchronized doors should be used at the entrance of the
datacenter.
2773 - Guests and service providers' employees should be allowed to go in only
after being properly authorized.
2774 - The ways of access to critical areas of the facility should be monitored by
closed circuit TV.
2775 - Access to the datacenter should be determined by security perimeters.
2776 - An automatic closing device should be installed on doors providing
access to the datacenter.
2777 - Only people wearing their identification badges in a way that makes them
clearly visible should be allowed in the data center.
2779 - Authorized personnel should always accompany visitors and service
providers.
2780 - Devices should be installed to block entry into the datacenter through
areas which are not frequently used.
2781 - Datacenter's doors should be equipped with alarms programmed to go on
whenever they are opened.
2782 - The key cabinet must be placed somewhere protected against
unauthorized access.
2783 - Fireproof doors and windows should periodically be checked to see
whether they are properly closed.
2784 - Reinforced bars should be installed on easily accessible windows to
outside areas and on skylights.
2785 - The door installed on the terrace roof should provide only outward
access.
2786 - Opening of emergency exit doors should only be allowed from the inside
of the data center.
2787 - Entrance through parking areas or car entrances exclusive to the
datacenter building should be allowed only to previously authorized persons.
2788 - All vehicles going in or out of the data center building's parking garage
should be carefully checked.
2789 - The comings and goings of assets, and all sorts of materials, in the facility
should be controlled.
2790 - The way of access for vehicles, especially when inside the building main
structure, should be protected.
2791 - TV cameras should be used to monitor the building's parking lot and
garage.
2792 - Redundancy should be provided to the electrical power infrastructure that
supplies electricity to the access control systems.
2793 - A mechanism restricting access to authorized persons should be installed
on emergency, equipment and maintenance entrances.

2794 - An access control mechanism should be installed on the datacenter to


restrict access after work hours.
2795 - The Closed Circuit TV should be connected to an alarm system.
2826 - Security rounds should happen as often as possible, 7 x 24.
28262 - Access to the switchboards of the datacenter's telecommunication
facilities should be restricted to authorized users.
2864 - The maintenance and cleaning personnel should be rigorously monitored.
2865 - Cleaning and maintenance personnel should be treated as visitors when
in areas of maximum security.
2940 - Access authorization should be required for entry into the datacenter.
Group : Building infrastructure
17188 - The doors providing access to the data center should look like common
doors.
2827 - A reception area should be set as a clear zone in order to isolate the data
center from other facilities.
2828 - Materials which are resistant to break-in attempts, as well as to fire and
water should be installed on the doors, windows and walls of the datacenter.
2829 - The datacenter should be located away from risk areas.
2830 - The data center should be located in a building used exclusively by the
organization to which it belongs or by organizations belonging to the same
business group.
2831 - Data center windows should face areas of the building's interior.
2832 - The elevated floor should be laid at an adequate height from the
building's floor concrete structure.
2833 - Mechanisms for permanent lighting should be installed in the datacenter.
2834 - The data center should have the necessary number of ways of access.
2835 - Signs showing the location of the datacenter should be removed.
2837 - The empty space underneath the elevated floor should be walled to
prevent invaders from using it to break in, especially at the data center's outer
perimeter.
2839 - The data center should be situated above the ground level.
2841 - Physical barriers should be built along the external walls of the data
center, effectively leaving no gaps between the building's floors concrete
structures.
2842 - The data center environment should be situated where rescue and
emergency teams and equipment would be able to easily access it.
Group : Cabling

2737 - Switchboards and connection boxes used for communication cables


should be kept locked.
2738 - Cabling should be laid out in a way that prevents electromagnetic
interferences.
2739 - All cables existing in the environment should be marked and labeled.
2741 - Compliance of the voice and data cabling system with structured cable
standards and regulations should be checked.
2743 - Each type of network (such as the power distribution, telephone,
automation control, data, sound and signal networks), with its corresponding
wiring or cabling, should be installed separately.
2744 - Cables that are not being used should be removed from the data center.
28263 - Cables belonging to the datacenter telecommunication infrastructure
should be installed directly (end-to-end) without any seams and/or extensions.
Group : Climate control
2737 - Switchboards and connection boxes used for communication cables
should be kept locked.
2738 - Cabling should be laid out in a way that prevents electromagnetic
interferences.
2739 - All cables existing in the environment should be marked and labeled.
2741 - Compliance of the voice and data cabling system with structured cable
standards and regulations should be checked.
2743 - Each type of network (such as the power distribution, telephone,
automation control, data, sound and signal networks), with its corresponding
wiring or cabling, should be installed separately.
2744 - Cables that are not being used should be removed from the data center.
28263 - Cables belonging to the datacenter telecommunication infrastructure
should be installed directly (end-to-end) without any seams and/or extensions.
2753 - An extra air conditioning system for using during contingencies should be
specified and installed.
2754 - The datacenter's air conditioning system should be independent from the
other systems in the building, responding exclusively to the datacenter's
demand.
2755 - Protection mesh should be installed to guard external cooling equipment.
2756 - The cooling systems supplying the datacenter should be provided with
mechanisms for maintaining continuous power.
2757 - Preventive maintenance services performed on the air-conditioning
system should be recorded.
2758 - Air-conditioning systems should be installed in locked, covered
compartments.
2759 - The cold water circuit for the fan coils should be coated with heat
insulating material.
2760 - The water ducts of the air-conditioning system should be protected
against corrosion.

Group : Compliance
6524 - Corporate servers should be periodically checked to see whether their
configuration is in compliance with the established security standards and
requirements.
Group : Data/voice communication
2768 - Telephone lines should be protected against tapping.
2769 - The telephone lines should be frequently checked for tapping and
listening devices.
2770 - The telephone lines installed on the data center should not be allowed to
accept or make external calls.
Group : Electric circuits and power
17189 - The data center's power circuits should be divided according to the load
distribution.
2799 - Lightning rods should be installed to protect equipment and buildings.
2800 - Insulating material should be applied to the exposed areas of the data
center's electric installations.
2801 - Conductive installations and all types of conductive equipment that are
submitted to significant power levels should be electrically connected to the
ground.
2802 - Mechanisms to block access to electrical switchboards and control panels
should be installed in the datacenter.
2803 - Only the energy grid and control circuits belonging to the data center
should be located inside its facilities.
2805 - The circuits used for the datacenter should have a sufficient amount of
electric outlets.
2806 - Power outlets located on the floor should have a protective cover.
2808 - Emergency lights should be installed in the correct places inside the data
center facilities.
2809 - A redundant electric grid for the equipments should be in place and ready
for use.
2810 - The voltage at the entry point of the electrical distribution panels should
be monitored by a voltmeter that is capable of logging the readouts.
2811 - The amperage at the entry point of the electrical distribution panels should
be monitored by an ammeter that is capable of logging the readouts.
2813 - Up-to-date electric grid plans should be kept by the maintenance
personnel of the building's security team.
2814 - The IT hardware's supply electric power should be stabilized and fed by
exclusive non-shared wirings.
2815 - Electric generators and no-breaks should be installed in order to ensure
the continuous supply of power for the critical equipments.
2816 - Transformers, capacitors, stabilizers, central power generators and other
critical electric equipment should be well sheltered and protected.

2818 - Circuit breakers should be installed on the datacenter's electrical circuits.


3375 - The circuit breakers of the power distribution panels should be properly
labeled.
Group : Fire protection and treatment
2735 - Flammable material should be stored in well-ventilated environments.
2804 - Automatic fire extinguishing systems should be installed in the datacenter.
2846 - Emergency exits should be located so as to facilitate evacuation of the
environment.
2847 - Fire drills should be performed periodically involving the people that work
in the environment.
2848 - Portable fire extinguishers, compatible with the classes of fire to be
fought, should be installed in the environment.
2849 - The fire extinguishers should be placed in accessible locations.
2850 - An identification tag should be attached to all fire extinguishers.
2853 - A sufficiently large number of fire alarms should be installed on every floor
of the building.
2854 - The fire alarm sound should use distinct tone and pitch from the other
sound-generating devices present in the environment.
2855 - Smoke detectors should be installed in the facility as a way of detecting
fire.
2856 - A fire suppression system based on pressurized gas should be installed in
the environment.
2857 - Smoke detectors should be periodically tested.
2858 - The fire alarms should be tested periodically.
2859 - Fire and smoke detectors should be located under the raised floor.
2860 - Fire and smoke detectors should be located above the lowered ceiling.
2861 - Smoke detectors should be installed in the ventilating ducts of the air
conditioning system.
2862 - Fire extinguishers inspections should be recorded.
2863 - Inflammable material should be removed from the faciltiy or replaced with
fireproof equivalents.
Group : Hydraulics
2819 - Pipes with pressurized liquids should be repositioned outside the
datacenter.
2820 - Sewage drainage pipes that pass through the datacenter should be
removed.

2821 - Rainwater drainage pipes that pass through the datacenter should be
removed.
2822 - Pressurized gas pipes should be repositioned outside the datacenter
(except those used for firefighting purposes).
2836 - The rain drainage pipes should be cleaned regularly.
2838 - The terrace floor and building roof should be periodically waterproofed.
2840 - Water drainage gutters should be installed outside the building.
2851 - A gas suppression system should be used to fight fire in the datacenter.
Group : Identification and authentication
2772 - Employees and workers should always wear identification badges.
2778 - Badges with different colors and visual signs should be used to identify
individuals allowed in the environment.
Group : Information disposal
2796 - Trash pickups should be performed periodically.
2797 - Any material with sensitive information should be protected against nonauthorized access when being disposed of.
2798 - Specific-destined shredders should be used for disposing sensitive
information.
Group : Security incidents
2823 - Records of physical security incidents should be kept.
2824 - All images captured by the organizations' TV cameras should be recorded
and kept.
2825 - The images captured by the Closed Circuit TV should be often reviewed
and stored for any future need.
Group : Work environment
2844 - Any material that does not pertain to the data center operation should be
removed from its interior.
2845 - Warnings about the handling and storage of dangerous materials should
be affixed to places where they can be easily seen.
6120 - A list with the authorized types of dangerous material, accompanied by
their respective security procedures for storage, usage and transport, should be
released.