0% found this document useful (0 votes)
34 views8 pages

Inputs For Coordination Calculation

This document provides an example calculation for coordinating cascaded circuit breakers in an electrical distribution system. It involves selecting circuit breakers and cable sizes, calculating fault currents at different points, and checking that the circuit breakers will operate in a coordinated manner. The example calculates ratings for an incoming circuit breaker, incoming cable size, load cable size, and verifies coordination between the circuit breakers. A coordination curve is plotted to show the circuit breakers will operate as required.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views8 pages

Inputs For Coordination Calculation

This document provides an example calculation for coordinating cascaded circuit breakers in an electrical distribution system. It involves selecting circuit breakers and cable sizes, calculating fault currents at different points, and checking that the circuit breakers will operate in a coordinated manner. The example calculates ratings for an incoming circuit breaker, incoming cable size, load cable size, and verifies coordination between the circuit breakers. A coordination curve is plotted to show the circuit breakers will operate as required.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

PrintFriendly.

com: Print web pages, create PDFs

Pgina 1 de 8

Inputs for Coordination Calculation


electrical-engineering-portal.com/example-for-coordination-of-cascaded-circuit-breakers
Edvard

Example for Coordination of Cascaded Circuit Breakers (on photo: Low voltage SIEMENS SIKUS 1600 power distribution board; credit: DirectIndustry.com)

A 440 V 60 Hz switchboard feeds a 4-wire distribution board for small loads such as socket outlets. The
switchboard has a fault making capacity of 100kA rms. After applying diversity factors to the loads the total load
current is 90 A. Moulded case circuit breakers (MCCBs) rated at 16 A and 32 A are to be used for the loads.
The installation will use cables having copper conductors and XLPE insulation. The cable from the switchboard to the
distribution board is 20 metres in length.
A typical load cable is 15 metres in length and will carry a current of 29 A at a power factor of 0.85 lagging.
Ignore the presence of induction motors at the switchboard and find the following:
1. Rating of the incoming circuit breaker.
2. Size of the incoming cable.
3. Size of the load cable.
4. Check that the MCCB coordination is complete.

The following sequence will be used to calculate the results:

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 2 de 8

1. Choose the upstream MCCB at the switchboard and its settings


2. Choose the incoming feeder cable
3. Choose the downstream load MCCB and its settings
4. Find the upstream fault source impedance
5. Find the cut-off, or let-through, current from the switchboard
6. Find the impedance of the incoming cable
7. Find the impedance of the load cable
8. Find the fault current at the distribution board, point B
9. Find the fault current at the beginning of the load cable, point C
10. Find the fault current at the end of the load cable, point D
11. Check the peak making capacity and peak let-through capacity of the MCCBs chosen above
12. Find the highestI-squared-t value for the upstream MCCB
13. Calculate a suitable size for the load cable to satisfy the I2t duty
14. Calculate the volt-drop in the load cable
15. Select the largest conductor size from the above calculations
16. Plot the results (coordination curve)

Lets dive into solution!


1. Choose the upstream MCCB at the switchboard and its settings
From a manufacturers data sheet a 125 A MCCB with an adjustable 100 A thermal release is chosen. The thermal
release is set to 90 A to match the total load.

2. Choose the incoming feeder cable


From a manufacturers data sheet several cables can be compared for the same ambient conditions and laying
arrangements. Their details are:
50 mm2 cable, maximum current 124 A, R = 0.492, X = 0.110 ohms/km.
70 mm2 cable, maximum current 159 A, R = 0.340, X = 0.106 ohms/km.
95 mm2 cable, maximum current 193 A, R = 0.247, X = 0.093 ohms/km.
The 70 mm2 cable is chosen since the rating of the 50 mm2 cable is just too low.
Go back to Index

3. Choose the downstream load MCCB and its settings


From a manufacturers data sheet a 32 A MCCB with an adjustable 32 A thermal release is chosen. The thermal
release is set to 29 A to match its load.

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 3 de 8

4. Find the upstream fault source impedance


For a prospective symmetrical fault current of 100 kA rms the upstream fault source impedance Zup is:

Go back to Index

5. Find the cut-off, or let-through, current from the switchboard


From a manufacturers data sheet a 125 A MCCB has a let-through current Ip of 25 kA peak for a prospective
fault current Is of 100 kArms.

6. Find the impedance of the incoming cable


The impedance Zc1 of the incoming cable is:

Go back to Index

7. Find the impedance of the load cable


The impedance Zc2 of the incoming cable is:
From a manufacturers data sheet several cables can be compared for the same ambient conditions and laying
arrangements. Their details are:
6 mm2 cable, maximum current 33.8 A, R = 3.91, X = 0.130 ohms/km.
10 mm2 cable, maximum current 46.7 A, R = 2.31, X = 0.126 ohms/km.
The 6 mm2 cable is chosen provisionally, since its rating is above the 32 A rating of the MCCB that feeds it.
The impedance Zc2 of the load cable is:

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 4 de 8

Go back to Index

8. Find the fault current at the distribution board, point B


From a manufacturers data sheet the contact impedance data for low voltage MCCBs are:
MCCB
(Rating in Amps)

Resistance Reactanse
(in Ohms)
(in Ohms at 60Hz)

16

0.01

neglect

20

0.008

neglect

25

0.0065

neglect

32

0.005

0.000009

50

0.0027

0.000016

63

0.002

0.000025

80

0.0014

0.000042

100

0.0011

0.00007

125

0.0008

0.0001

160

0.00055

0.00015

200

0.0004

0.0002

250

0.00029

0.00027

320

0.0002

0.0004

Hence the upstream MCCB impedance Zm1 is 0.0008 + j 0.0001 ohms. Therefore the fault impedance Zfb is:
The fault making current Ifb is:

Where Vp is the line-to-neutral voltage. Locate the point R for 26,195 A on the prospective curve in Figure 1.
Go back to Index

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 5 de 8

9. Find the fault current at the beginning of the load cable, point C
Hence the downstream MCCB impedance Zm2 is 0.005+j0.000009 ohms. Add this to Zfb to give the fault impedance
Zfc as:

The fault making current Ifc is:

Locate the point S for 17,443 A on the prospective curve in Figure 1.


Go back to Index

10. Find the fault current at the end of the load cable, point D

Add Zc2 to Zfc to give the fault impedance Zfd


as:

Figure 1 Coordination of MCCBs at a distribution board

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 6 de 8

The fault making current Ifd is:

Locate the point U for 3473 A on the prospective curve in Figure 1.


Go back to Index

11. Check the peak making capacity and peak let-through capacity of the MCCBs chosen
above
The following manufacturers data are typical for 125 A and 32 A MCCBs:
MCCB Rating Making capacity

Let-through capacity
kApeak (cut-off)

kArms

kApeak

32 A

95

209 ***

6.0

125 A

132

290 ***

25.0

*** Approximate values of the doubling factor taken to be 2.2


Hence the peak making capacity of the 32 A MCCB is well in excess of the let-through peak current of the 125 A
MCCB.
Go back to Index

12. Find the highest I2t value for the upstream MCCB
Locate two points P and Q on the curve of the upstream MCCB as follows,
Point

Current in p.u. Current in Amps

Time in seconds I2t

14

406

989016.0

602

17,450

0.0016

487204.0

Hence I2t at P exceeds that at Q.

13. Calculate a suitable size for the load cable to satisfy the I2t duty
For XLPE cables the k factor for the I2t is 143. The cross-sectional area A is:

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 7 de 8

The next standard cross-sectional area is 10 mm2.


Go back to Index

14. Calculate the volt-drop in the load cable


The usual limit to volt-drop in three-phase cables feeding static loads is 2.5% at full load.
Where, Iflc = 29 A, L = 15 m and = 54.5495
degrees. For a 6 mm2 cable the volt-drop is found to be:

which is well within the limit of 2.5%.


Go back to Index

15. Select the largest conductor size from the above calculations
Comparing the conductor sizes found in 13. and 14. gives the larger as 10 mm2, and this size should be used.
Revise the calculation of the fault current Ifd. The impedance Zc2 of the load cable is:

Add Zc2 to Zfc to give the fault impedance Zfd as:

The fault making current Ifd is:

Go back to Index

16. Plot the results

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

PrintFriendly.com: Print web pages, create PDFs

Pgina 8 de 8

The results are plotted in Figure 1.

Refrence // Switchgear and Motor Control


Centres Handbook of Electrical Engineering:
For Practitioners in the Oil, Gas and
Petrochemical Industry by Alan L. Sheldrake
(Download here)

Figure 1 Coordination of MCCBs at a distribution board

http://www.printfriendly.com/print/?source=cs&url=https%3A%2F%2Ffanyv88.com%3A443%2Fhttp%2Felectrical-engi... 22/10/2015

You might also like