Programming For PowerFlex 7 Class
Programming For PowerFlex 7 Class
Direction
Drive Status
Alarm
Auto/Man
ESC
Sel
Key Descriptions
Escape
Pressing the Escape Key once takes you back one level.
Select
When at the parameter level pressing select will move the cursor to the line of the
Display where the parameter value is. Then you are able to change its value. If the value
of the parameter is at a Bit level then repeatedly pressing the Select key will move the
cursor from one bit to the next (going from right to left).
Up and Down Arrows
Allows you to move between the different levels in the menu. When changing the
parameter value these will increase or decrease the value. The longer you hold down the
key the faster it changes the value.
Enter (This is the Universal key/Symbol used for Enter)
Pressing this key will select the Item Highlighted in the menu and take you to the
next level. Pressing this key when the value of a parameter has been changed will
then write the changed value to the drive.
1
Key Descriptions
Jog
Start
Pressing Start will cause the Drive Output/Power IGBTs to start modulating or put the
drive in a run condition. If no start inhibit is present, Mask, fault or alarm. If a digital input
is programmed for 2 wire control. The Start Button is disabled unless P192 Bit 1 = 1.
Once started the STS LED should be solid Green.
Jog
From a stopped state press and HOLD Jog this causes the Drive Output /Power
IGBTS to start modulating and follow the speed reference of P100 Jog1. If no start inhibit
is present, Mask, fault or alarm. When the Jog Key is released - Then the Drive Output/
Power IGBTs will stop modulating and the Drive will be in a stopped condition.
Backspace
Pressing Backspace will delete / remove the text immediately to the left of the cursor.
Stop
Pressing stop will do one of the following based on P155 or P156 setting: Coast, Ramp,
Ramp to Hold, DC Brake or Fast Brake. If a fault is displayed and is resetable pressing
and releasing the stop key will clear the fault when P241 is enabled.
2
Key Descriptions
Change Direction
Pressing the change direction key will cause the Drive/Motor to go in the opposite
Direction. Unless a mask is set to lock out this function. Or reverse disable P190
Digital Pot Up and Down Arrows
When the HIM is used as the speed reference. Either Press and hold or press and
Release repeatedly the Up/Down arrows. Will Increase/Decrease the speed.
7
4
1
8
5
2
0
9
6
3
.
+/-
Key Descriptions
ALT (using the ALT Key)
The ALT key is Color coded Yellow for 2nd function. This means whenever the ALT Key is
Pressed and Released the Keys that are labeled in Yellow text that is their 2nd function
And are now available to be selected within a 3 sec time frame. (See below for details).
Note: For the list below typically you will be at the User Display window.
(If after pressing ALT and the 2nd Function Key - nothing happens then Press the ESC Key once.)
ALT
S.M.A.R.T
ESC
View
Sel
View
Sel
Lang
2nd Function Auto / Man (Providing or Removing Manual control with the HIM)
Auto / Man Pressing and Releasing the ALT key and then within Approximately 3 sec Press and
Release the Blue Down Arrow key Attempts to provide or remove Manual control
Remove
Alternate (ALT)
Key is Active
Then
Press and Release
SMART List:
Digital IN2 Sel
Stop/Brk Mode A
Minimum Speed
S.M.A.R.T
ESC
Displays the S.M.A.R.T Start-up menu.
(Starting At the User Display window)
0.00
Then
Press and Release
View
Sel
Amps
Then
Press and Release
English?
Franais?
Espaol?
Italiano?
Lang
Then
Press and Release
Auto Manual
Go to HIM Manual
Speed Control?
Press Enter ()
Auto / Man
(To toggle between HIM and Auto control of the Drive when using the HIM)
Then
Press and Release
Remove HIM
Do you wish to?
To Continue
Press Enter ()
Remove
Allows HIM removal without causing a fault if the HIM is not actively controlling the drive/motor
with logic commands (the only one Selected in the Logic mask) or providing a speed reference
Param #:
Then
Output Freq
+/-
0.0 HZ
Param #
Allows entry of a parameter number for viewing/editing
6
Then
Press and Release
View
Sel
Provides the selection of how parameters will be viewed and continued to be viewed this way
even when AC power has been cycled.
Programming Instructions shown using a 20-HIM-A3
Programming/Changing Parameters
ESC
ESC
Sel
Sel
Escape
Select
UP
Down
Enter
0.00
HZ
Main Menu:
Diagnostics
Parameter
Device Select
Diagnostics
Parameter
Device Select
Memory Storage
Start-Up
Preferences
These Selections will be explained in
greater detail in the following pages /
Menu Structure
Programming/Changing Parameters
ESC
ESC
Sel
Sel
Escape
Select
UP
Down
Enter
Note: Changing Parameter 196 to a value of 1 Advanced allows access to all Parameters.
Press and Release
ALT
Then
Press and Release
View
Sel
Then
Then
Key in any parameter number you want to go to - then Press and Release the Enter key. This will
take you to that parameter. Then you can Press and Release the Sel Key Now you are able to
change the value of the parameter -with the Up/ Down Keys or the Numerical Keys once the value
is changed -then you must Press and Release the Enter Key to write the change into the drive. Then
you can key in the next parameter or Press and Release the Esc Key to go back to any previous
Menu/Display.
Note: Changing Parameter 196 to a value of 1 Advanced allows access to all Parameters.
8