MX Detection Panel FMZ5000 PDF
MX Detection Panel FMZ5000 PDF
MX Detection Panel FMZ5000 PDF
Modular principle
One panel for all eventualities
Few different types of modules
Easy to operate
Low replacement part requirement
Can easily be expanded
Redundant safety technology
Fire detection and extinguishing
System-specific data
mod 4
mod 12
Operating voltage
24 Vdc
24 Vdc
Power packs
24 V 1.5 A/2.7 A
2 x 12 V, 12 Ah internal, up to 24 Ah external
Protection class
IP 54
IP 54
5 C to +40 C
5 C to +40 C
<93 %
<93 %
Model-specific data
mod 4
mod 12
up to 8
up to 24
Serial ports
Total weight
19 kg
48 kg
Dimensions
U4
VdS
Certified according to
ISO 9001
P50Fe_01/0704/5/01.05/EIN
No. S 89201
FMZ 5000
Fire detection and extinguishing
control panel
U1
Minimax has been designing and build ing fire alarm panels for over 30 years.
The heart of the newest generation the FMZ 5000 is the redundant central card as an intelligent control system for maximum
safety. It goes without saying that the new technology with freely
programmable controls and few different operating modules
fulfils the requirements of DIN EN 54 Parts 2 and 4 as well as
DIN EN 12094 Part 1. Flexibility and easy adaptation to increasingly frequent changes in operational requirements are important
factors. The FMZ 5000 can easily be adapted to a wide range of
requirements. Of course, this process is not yet fully automatic
but it is very fast and easy. Users of a building need this kind
One
MODU L AR
KI T
Functions
There are lines for detectors which signal an alarm by
increasing the current (conventional detectors). All
conventional Minimax detectors can be connected. These
include smoke and heat detectors for normal conditions
and all industrial fire detectors. The latter include heat,
flame and CO conflagration gas detectors, in addition
to manual alarms with many individual housings and
designs for various uses.
S N A P
4
Two standard sizes are available, the small mod 4 and the
mid-sized mod 12. The front panels of the mod 12 enable
even large expansions in 19" housings. Only the outer
shell size is permanent, while the interior workings
remain fully flexible. The basic hardware is strikingly well
designed, with high functionality. The housing of the
mod 4 is also suitable for installation in a console or wall
mounting.
FMZ 5000
A N D
5
G O !
SIMPLY
Configuration
Customer advantages
The clear structure of the new technology facilitates planning and set-up of the project configuration. Instead of having to choose from many
options, specific project tasks can be solved with
only one fire alarm panel and
the combination of just a few
modules.
Future
TECHNICAL DATA
SHEETS MISSING?
PLEASE CALL
Phone: +49 (0)4531 803 0
Fax:
+49 (0)4531 803 248
INGENIOUS
Minimax
is a full service provider for
extinguishing technology
and fire detection technology
from one source.
ADVANTAGES
Modular principle
One panel for all eventualities
Few different types of modules
Easy to operate
Low replacement part requirement
Can easily be expanded
Redundant safety technology
Fire detection and extinguishing
System-specific data
mod 4
mod 12
Operating voltage
24 Vdc
24 Vdc
Power packs
24 V 1.5 A/2.7 A
2 x 12 V, 12 Ah internal, up to 24 Ah external
Protection class
IP 54
IP 54
5 C to +40 C
5 C to +40 C
<93 %
<93 %
Model-specific data
mod 4
mod 12
up to 8
up to 24
Serial ports
Total weight
19 kg
48 kg
Dimensions
U4
VdS
Certified according to
ISO 9001
P50Fe_01/0704/5/01.05/EIN
No. S 89201
FMZ 5000
Fire detection and extinguishing
control panel
U1
FMZ 5000
Conventional detector module
Product
Application
Safe
e for certain.
cer ain.
+ Benefits
All Minimax industrial detectors for
increased environmental conditions
and all Minimax standard fire
detectors for smoke and heat can be
connected to each line in any combination. All requirements of every
type of safety concept imaginable
can easily be implemented.
The alarm can be freely selected
for each group. This makes it
possible to use the module for
various functions, e. g. fire alarms,
function monitoring of system
elements, and for manual controls,
e. g. extinguishant shut-off or
additional discharge.
Function
Configuration data
Manual alarms
Flame detectors
Heat detectors
IR
Smoke detectors
Multi-sensor detectors
Monitoring of
extinguishing systems
and the data bus are established automatically by contacts on the bottom of the housing. No wiring is required
within the fire alarm panel for the conventional module.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download.
Operating voltage
Current consumption
Number of lines/detectors
Line voltage
15 mA
Operating temperature
5 C to +40 C
Relative humidity
Dimensions
99 x 17.5 x 114.5 mm (L x W x H)
Article number
901773
PB50Fe_01/0704/5/01.05/EIN
Technical data
FMZ 5000
Loop module
Product
Application
Safe
e for certain.
cer ain.
+ Benefits
In each loop, any combination of
Minimax detectors of the DIS and 95
series for smoke and heat can be
used, and by means of loop couplers
it is also possible to use all industrial
detectors for increased environmental requirements and different line
voltages.
Each individual detector can be adapted to changing operating requirements in 8 time zones for each day.
Function
Loop module
Fire detection
Manual alarms
Standard
fire detectors
Alarm
Alarm
Stub lines
Industrial
detectors
Activate
extinguishing system
Manual activation
Additional
discharge
Stub lines
Hazard barriers
Monitor/control
extinguishing areas
Acoustic signal
transmitter
Visual signal
transmitter
Actuators
Hazardous areas
Loop coupler
Operating voltage
Current consumption
35 mA (without detectors)
Number of loops/detectors
2 loops, each with 126 addressable points (detectors, horns, input/output modules)
Loop installation
200 mA
Operating temperature
5 C to +40 C
Relative humidity
Dimensions
99 x 35 x 114.5 mm (L x W x H)
Article number
902748
PB51Fe_01/0704/5/01.05/EIN
Technical data
FMZ 5000
Relay module
Product
Application
Safe
e for certain.
cer ain.
+ Benefits
Function
Operating voltage
Current consumption
Number of relays
Contact capacity
Operating temperature
5 C to +40 C
Relative humidity
Dimensions
99 x 17.5 x 114.5 mm (L x W x H)
Article number
901595
PB52Fe_01/0704/5/01.05/EIN
Technical data
FMZ 5000
Control group module
Product
Application
Safe
e for certain.
cer ain.
+ Benefits
Each control group can be used for
individual properties corresponding
to the respective safety concept.
Function
24 Vdc (19 V to 29 V)
Current consumption
Line monitoring
monitoring for wire breakage and short circuits incl. the connected device
Operating temperature
5 C to +40 C
Relative humidity
Dimensions
99 x 17.5 x 114.5 mm (L x W x H)
Article number
901673
PB53Fe_01/0704/5/01.05/EIN
Technical data
FMZ 5000
Remote transmission unit
Product
Application
Safe
e for certain.
cer ain.
+ Benefits
For each alarm group, it is determined whether the remote transmission should be activated
permanently, based on time periods
or with an additional delay (explore)
in the case of a fire alarm.
organisation and optimum adaptation to your operational requirements, up to 8 freely definable time
periods are available for each day
of the week.
can therefore be fully adapted to
your operational requirements.
Adaptations to shift operations in
various production areas are easy
to implement.
Function
24 Vdc (19 V to 29 V)
Current consumption
Outputs
Line monitoring
monitoring for wire breakage and short circuits incl. the connected device
Operating temperature
5 C to +40 C
Relative humidity
Dimensions
99 x 45 x 114.5 mm (L x W x H)
Article number
901969
PB54Fe_01/0704/5/01.05/EIN
Technical data
FMZ 5000
Reflex module
Product
Application
11549-8_PB_57Fe_FMZ5000 1
+ Benefits
The reflex module is essential
where pneumatic conveyors are
involved and in areas subject to
the risk of rapidly spreading fires.
Pneumatic material conveyors are
at risk from flying sparks or glowing embers. Spark detectors in
various models can reliably spot
sparks and sources of fires the
extinguishing process is triggered
almost immediately.
Alternatively or in addition to the
extinguishing process, combustible
material can be ejected from the
transport system without delay.
In ESTA paint shops flames caused
by high voltage flashovers are
extinguished immediately by cutting off the supply of paint and
applying extinguishing agents
through the paint spray nozzles.
Flame detectors in machine tools
cabinets monitor the material
processing and the cooling agent.
Function
instantaneous
relays
Fault and
performance
monitoring
valve group 1
Valve group 1
Detector group 1
Fault and performance
monitoring external
controls
Valve group 2
instantaneous
relays
Technical data
24 Vdc (19 V to 29 V)
2 detector groups, 2 control groups, 4 monitoring groups, 2 instantaneous relays
Line monitoring
Detectors and valves monitored for connection and function, overall monitoring
of an extinguishing unit with ball valve on a common line
8 spark-/4 flame detectors per detector group, 3 valves per control group
Operating temperature
5 C to +40 C
Relative humidity
95 %, without dew
Dimensions
99 x 52.5 x 114.5 mm (L x W x H)
Article number
906262
11549-8_PB_57Fe_FMZ5000 2
No. S 89201
Certified according to
ISO 9001
Operating/load voltage
FMZ 5000
Spark test module
Product
Application
+ Benefits
Foodstuffs/automotive industry
11549-9_PB58Fe_FMZ5000_Funkentes1 1
Timber industry
Textile industry
Chemical/synthetics processing
industry
+
+
Function
Technical data
24 Vdc nominal voltage (19 V to 29 V)
Power input
Line/function monitoring
3A
Operating temperature
5 C to 40 C
Relative humidity
95 %, without dew
Dimensions
99 x 35 x 114,5 mm (L x W x H)
Article number
906980
11549-9_PB58Fe_FMZ5000_Funkentes2 2
No. S 89201
Certified according to
ISO 9001
Operating/load voltage