ADVANTAGES

FIRE DETECTION SYSTEMS


FMZ 5000

OF OUR FLEXIBLE FMZ 5000

Modular principle
One panel for all eventualities
Few different types of modules
Easy to operate
Low replacement part requirement
Can easily be expanded
Redundant safety technology
Fire detection and extinguishing

control panel in one unit

Technical data for the FMZ 5000

System-specific data

mod 4

mod 12

Operating voltage

24 Vdc

24 Vdc

Power packs

24 V 1.5 A/2.7 A

24 V 2.7 A/5 A/15 A

Emergency power supply

2 x 12 V, 12 Ah internal, up to 24 Ah external

2 x 12 V, 24 Ah internal, up to 130 Ah external

Protection class

IP 54

IP 54

Approved ambient temperature

5 C to +40 C

5 C to +40 C

Approved relative humidity

<93 %

<93 %

Model-specific data

mod 4

mod 12

Max. number of modules*

up to 8

up to 24

Group /area displays

16 LED pairs, red/yellow

max. 192 LED pairs, red/yellow

Serial ports

RS232, RS422, RS485 (number as required)

RS232, RS422, RS485 (number as required)

Total weight

19 kg

48 kg

Dimensions

480 x 310 x 192.5 (W x H x D)

600 x 605 x 232.5 mm (W x H x D)

U4

VdS
Certified according to

ISO 9001

P50Fe_01/0704/5/01.05/EIN

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

No. S 89201

* Depending on the type of module used.

Safe for certain.

FMZ 5000
Fire detection and extinguishing
control panel

U1

FIRE DETECTION SYSTEMS


FMZ 5000

Fire alarm panels are mandatory for many construction projects


like safety belts in your car both protect life and existence.

Seat belts have been compulsory for the past 30 years


and led to many innovations, such as the airbag and
sidebag.
At first, the seat belt was a relatively uncomfortable
safety device. But the development of heightadjustable belts with automatic tighteners resulted in
a very flexible and effective restraint system featuring
high comfort and safety. What began as an obligation
was refined and widely accepted. Ensuring health,
future compliance and comfort comes first. The same
development from simple to complex also applies
to fire detection and alarm systems from Minimax.

Minimax has been designing and build ing fire alarm panels for over 30 years.
The heart of the newest generation the FMZ 5000 is the redundant central card as an intelligent control system for maximum
safety. It goes without saying that the new technology with freely
programmable controls and few different operating modules
fulfils the requirements of DIN EN 54 Parts 2 and 4 as well as

of flexibility in order to create efficient work-flows. Never before


has it been so easy to change complex structures so quickly
via programming alone and with just a few snap-in modules.

DIN EN 12094 Part 1. Flexibility and easy adaptation to increasingly frequent changes in operational requirements are important
factors. The FMZ 5000 can easily be adapted to a wide range of
requirements. Of course, this process is not yet fully automatic
but it is very fast and easy. Users of a building need this kind

One

FIRE DETECTION SYSTEMS

MODU L AR

KI T

for all your needs


Hardware structure of the fire alarm panel

Functions
There are lines for detectors which signal an alarm by
increasing the current (conventional detectors). All
conventional Minimax detectors can be connected. These
include smoke and heat detectors for normal conditions
and all industrial fire detectors. The latter include heat,
flame and CO conflagration gas detectors, in addition
to manual alarms with many individual housings and
designs for various uses.

Loop couplers enable connection to all conventional


detectors, including industrial alarms.

FMZ 5000 one model for all tasks

Due to the configurable line voltage of 9 V to 20 V,


detectors from other manufacturers can also be used.

Equipment monitored directly via the fire alarm panel,


e.g. extinguishing systems or alarm systems, can be
activated.

The user purchases only what he needs since expansion


to any size is possible at any time without additional
wiring. Space should be reserved, however, for modules
to be added at a later time. This saves both money and
space.
In the event of changes in processes or use, or in case
retrofitting becomes necessary, the new function can
be adapted directly on the premises of the FMZ 5000
customer quickly and at low cost.

S N A P
4

The FMZ 5000 fire alarm panel

Two standard sizes are available, the small mod 4 and the
mid-sized mod 12. The front panels of the mod 12 enable
even large expansions in 19" housings. Only the outer
shell size is permanent, while the interior workings
remain fully flexible. The basic hardware is strikingly well
designed, with high functionality. The housing of the
mod 4 is also suitable for installation in a console or wall
mounting.

Identical modules are used for mod 4 and mod 12 to


implement a wide variety of projects. Before the fire
alarm panel can process the special tasks of a particular project, it is configured via the computer with the
necessary information for the project. All fire alarm
panels, small and large, consist of the same modules.
This minimises the storage of spare parts for service and
set-up personnel. Less is more. Our modules are very
efficient, highly flexible and easy to understand. They can
be used to configure straightforward fire detection
systems or combined fire detection and extinguishing
control panels.

The FMZ 5000 mod 12 features high flexibility for total


freedom of expansion in a 19" housing.

FMZ 5000

Up to 126 addressable points can be connected and


operated on the detector loops: fire detectors for smoke,
heat and flames, in addition to manual alarms. But they
can also be input or output modules for monitoring,
controls or horns.
Stub lines for up to 32 detectors can be connected to the
loop.
On each loop, addressable points and devices can be
supplied with a current of up to 200 mA.
The maximum length of the loop is 2,000 m and it can be
installed with a normal J-Y(ST)Y 0.8 mm fire alarm cable.
Horns on the loop are either independent units or they
are located in the base of a detector; they are supplied
by the loop and need no separate power supply.

Input modules on the loop can be used for monitoring,


e.g. extinguishing systems.
Output modules on the loop can be used for controls and
activations (including monitoring the supply line to the
connected device).

Two monitored activations for transmission units are


provided for calling the fire brigade or a service company.
Non-monitored controls can be implemented by means
of relay modules.
Up to 32 fire alarm panels and control units can be
networked in a ring. In this configuration, all fire alarm
panels can be operated from one or more locations and
all messages are displayed either centrally or at multiple
locations.
A standardised interface for danger warning systems
for notification of control centres and for operation from
the control centres to the fire alarm panels is provided.

Horns are addressable on the alarm loop and can be


controlled individually or synchronised as a group for
a uniform alarm tone.

A N D
5

G O !

SIMPLY
Configuration

FIRE DETECTION SYSTEMS


FMZ 5000

Customer advantages

All messages from detectors, groups, etc. can be freely


defined: what should be reported, the message text,
group number, and corresponding single/collective
LEDs. All logical and time-dependent links between
the messages and the related actions can be freely
defined. For functions such as blocking, revision and
shutdown, one can easily connect
key-operated switches or program
buttons on the front panel.

Easy, menu-controlled user interface with soft keys.


Maximum information at a glance due to the large,
clear layout of the full-graphic display.

No matter what the requirements of a


project, the FMZ 5000 can provide the solution.
This is made possible by the high modularity of
the hardware and the flexibility of the software
PLC, together with the graphic configuration.

The same applies to extensions in the customers building.


The fire alarm panel can largely be adapted to the
growing requirements by means of SNAP AND GO
technology.

The clear structure of the new technology facilitates planning and set-up of the project configuration. Instead of having to choose from many
options, specific project tasks can be solved with
only one fire alarm panel and
the combination of just a few
modules.

Low training requirements due to ease of operation.


If rooms or buildings are reallocated for new uses, the
fire alarm panel can easily be adapted without rewiring,
due to the flexibility of the modules. Many of the changes
can be implemented by adapting the configuration.

Since industrial detectors can also be connected to


detector loops via loop couplers, all industrial requirements can be fulfilled.
The FMZ 5000 is a combined fire detection and extinguishing control panel, meaning all fire alarm and
extinguishing tasks can be controlled from a single fire
alarm panel.
All tasks and all requirements can be implemented.

SNAP AND GO! All you have


to do is plug in the modules,
with no wiring in the
alarm panel,
then connect
the external
devices!

Future

TECHNICAL DATA
SHEETS MISSING?
PLEASE CALL
Phone: +49 (0)4531 803 0
Fax:
+49 (0)4531 803 248

The fire alarm panels and modules of the mod 4 and


mod 12 are designed as future-oriented platforms and
can be adapted to new developments and changes in
regulations, in addition to expanded functions.

INGENIOUS

Minimax
is a full service provider for
extinguishing technology
and fire detection technology
from one source.

ADVANTAGES

FIRE DETECTION SYSTEMS


FMZ 5000

OF OUR FLEXIBLE FMZ 5000

Modular principle
One panel for all eventualities
Few different types of modules
Easy to operate
Low replacement part requirement
Can easily be expanded
Redundant safety technology
Fire detection and extinguishing

control panel in one unit

Technical data for the FMZ 5000

System-specific data

mod 4

mod 12

Operating voltage

24 Vdc

24 Vdc

Power packs

24 V 1.5 A/2.7 A

24 V 2.7 A/5 A/15 A

Emergency power supply

2 x 12 V, 12 Ah internal, up to 24 Ah external

2 x 12 V, 24 Ah internal, up to 130 Ah external

Protection class

IP 54

IP 54

Approved ambient temperature

5 C to +40 C

5 C to +40 C

Approved relative humidity

<93 %

<93 %

Model-specific data

mod 4

mod 12

Max. number of modules*

up to 8

up to 24

Group /area displays

16 LED pairs, red/yellow

max. 192 LED pairs, red/yellow

Serial ports

RS232, RS422, RS485 (number as required)

RS232, RS422, RS485 (number as required)

Total weight

19 kg

48 kg

Dimensions

480 x 310 x 192.5 (W x H x D)

600 x 605 x 232.5 mm (W x H x D)

U4

VdS
Certified according to

ISO 9001

P50Fe_01/0704/5/01.05/EIN

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

No. S 89201

* Depending on the type of module used.

Safe for certain.

FMZ 5000
Fire detection and extinguishing
control panel

U1

FIRE DETECTION SYSTEMS


FIRE ALARM PANEL

FMZ 5000
Conventional detector module

 Product

 Application

The conventional detector module


provides 4 lines for connecting
detectors based on the current
increase principle.
4 analysis limits can be freely
configured for each line: 2 alarms,
wire breakage, and short circuit.
Each group can be configured individually, e.g. 2-detector dependency, group number, group text,
alarm type and alarm delays.
With the MxSysCon configuration
software, all alarms of the various
groups can be logically linked with
other groups and detectors, and
connected to controls on loops,
control groups, relays, LEDs, etc.
The module is inserted into the fire
alarm panel without wiring. The
lines can be connected directly to
the module.
Technical measures for preventing
false alarms are integrated
(TM operating mode).

Safe
e for certain.
cer ain.

+ Benefits
All Minimax industrial detectors for
increased environmental conditions
and all Minimax standard fire
detectors for smoke and heat can be
connected to each line in any combination. All requirements of every
type of safety concept imaginable
can easily be implemented.
The alarm can be freely selected
for each group. This makes it
possible to use the module for
various functions, e. g. fire alarms,
function monitoring of system
elements, and for manual controls,
e. g. extinguishant shut-off or
additional discharge.

+ For detectors with different line

voltages, you can configure a


different voltage from 9 to 20
volts for each line of a module.

+ Free configuration of the alarm and

interruption limits, combined with


high maximum currents, enable the
use of detectors from a wide variety
of manufacturers.

+ 2-detector and 2-group dependency


can be programmed simultaneously
for 8 explore time periods per day.

+ Freely definable alarms enable the


use of the lines for any function.

+ SNAP AND GO! All you have to do is


plug in the modules, with no wiring
in the control panel, then connect
the external devices.

Function

Detectors for industrial environments


Standard fire detectors
Special detectors

Configuration data

Manual alarms

Flame detectors
Heat detectors

IR

Fire detection monitoring

Smoke detectors
Multi-sensor detectors

2-detector, multi-group dependency


4 alarm limits can be configured,
line voltage 9 to 20 Vdc

Monitoring of
extinguishing systems

The conventional module has four independent detector


lines. The voltage for each line can be set between 9 V
and 20 V. Up to 32 detectors can be connected on each
line directly via a plug-in terminal on the module housing.
Standard and industrial detectors for each fire indicator
can be connected in any sequence.

and the data bus are established automatically by contacts on the bottom of the housing. No wiring is required
within the fire alarm panel for the conventional module.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download.

The conventional modules can be connected to the FMZ


5000 control panel on a TS35 mounting rail (top hat rail)
in any sequence. The connections to the power supply

Operating voltage

24 Vdc rated voltage (19 V to 29 V)

Current consumption

5 mA, plus approx. 5 mA for each line used

Number of lines/detectors

4/ 32 in accordance with EN54-2

Line voltage

adjustable from 9 V to 20 Vdc

Alarm current (average)

15 mA

Operating temperature

5 C to +40 C

Relative humidity

95%, without dew

Dimensions

99 x 17.5 x 114.5 mm (L x W x H)

Article number

901773

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

PB50Fe_01/0704/5/01.05/EIN

Technical data

FIRE DETECTION SYSTEMS


FIRE ALARM PANEL

FMZ 5000
Loop module

 Product

 Application

The loop module provides the


option of 2 detector loops, 4 stub
lines or 1 detector loop and 2 stub
lines for connecting Minimax ring
bus alarms of the DIS and 95 series.
Up to 126 addressable points
can be operated on each loop.
Addressable points can be detectors, control, input and output
modules or alarm units.
In the event of wire breakage or
a short circuit on the loop, all
addressable points remain fully
operable.
All detectors can be incorporated
into detector groups, regardless of
which loop they are connected to
within the fire alarm panel. With the
MxSysCon configuration software, all
alarms and control commands of the
groups can be linked with each other
in practically any combination.

Safe
e for certain.
cer ain.

+ Benefits
In each loop, any combination of
Minimax detectors of the DIS and 95
series for smoke and heat can be
used, and by means of loop couplers
it is also possible to use all industrial
detectors for increased environmental requirements and different line
voltages.

+ Even the event of a single detector

Each individual detector can be adapted to changing operating requirements in 8 time zones for each day.

+ SNAP AND GO! All you have to do is

If required, detectors can also be


used in hazardous areas by means
of Zener barriers without extra
components.
Any number of stub lines can be set
up in each loop.
The message text can be freely
selected for each group. This makes
it possible to use the module for
various functions, e.g. fire alarms,
function monitoring of system
elements, and for the control of
external units.

within a group can be configured to


initiate various actions.

+ The high maximum current in the

loop enables you to operate


a relatively large number of looppowered devices such as loop
sounders, etc.
plug in the modules, with no wiring
in the fire alarm panel, then connect
the external devices.

Function

Loop module

Fire detection

Manual alarms
Standard
fire detectors

Alarm

Alarm

Stub lines

Industrial
detectors

Activate
extinguishing system

Manual activation
Additional
discharge

Stub lines

Hazard barriers

Monitor/control
extinguishing areas

Acoustic signal
transmitter
Visual signal
transmitter

Loop coupler for


conventional detectors

Actuators
Hazardous areas

Loop coupler

The loop module has two independent detector loops,


each with connections for up to 126 detectors. The loops
are connected directly by means of two plug-in terminals
on the module housing. Detectors of the DIS and 95 series
can be connected in any sequence, industrial detectors
can be connected via loop couplers.
The loop modules can be connected to the FMZ 5000 fire
alarm panel on a TS35 mounting rail (top hat rail) in any
sequence. The connections to the power supply and the
data bus are established automatically by plugging in the

modules. No wiring is required within the fire alarm panel


for the loop module.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download
or on a compact Flash card. This enables operation in the
office independent of the construction progress.

Operating voltage

24 Vdc nominal voltage (19 V to 29 V)

Current consumption

35 mA (without detectors)

Number of loops/detectors

2 loops, each with 126 addressable points (detectors, horns, input/output modules)

Loop installation

2,000 m cable, J-Y(ST)Y 0.8 mm

Current in the loop (max.)

200 mA

Operating temperature

5 C to +40 C

Relative humidity

95%, without dew

Dimensions

99 x 35 x 114.5 mm (L x W x H)

Article number

902748

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

PB51Fe_01/0704/5/01.05/EIN

Technical data

FIRE DETECTION SYSTEMS


FIRE ALARM PANEL

FMZ 5000
Relay module

 Product

 Application

Safe
e for certain.
cer ain.

+ Benefits

The relay module provides 8 relays,


each with one potential-free
changeover contact.

Activation is possible either without


a message or with a freely definable
message on LCD and a single LED.

Each relay can be used with


4 different function modes:
continuous activation
pulsed activation
delayed activation
combinations with delay

A power relay card can easily be


connected via a ribbon cable.

Activation and delay times of up to


18 hours can be configured.

+ This enables fast application and

Defined by the configuration, each


relay can display the activation with
the alarm type, number, alarm text
and LED.
Each relay can be used for controlling fire protection equipment,
shutting down machinery
or activating acoustic signals.
Relays are activated via door
contact and vice versa.

The configuration software MxSysCon


enables the use of the 8 relays with
free logical circuits similar to freely
programmable controls.
configuration changes directly at
the customers facilities.

You can use each relay within the


module freely and independently.
If your project requires the display or
forwarding of the relay activations,
the necessary messages are freely
configurable.

+ The extensive configuration

options of the switching and delay


times and the ability to combine
all times offer maximum flexibility
for use in any project.

+ Use to activate a shutdown in the

case of fire enables deactivation


from the fire brigade control panel.

+ If the relay is intended for horn


control, it is dependent on the
acoustic signals command.

+ SNAP AND GO! All you have to do

is plug in the modules, with no


wiring in the fire alarm panel, then
connect the external devices.

Function

Forwarding switching initiating


Time-controlled activation, pulsed activation, delayed
activation
Activated relays are displayed on the LCD or at the
control centres with the group text and group number

The relay module has eight independent relays. Each relay


has one potential-free changeover contact, which is
connected via a plug-in terminal directly on the module
housing.
The relay modules can be connected to the FMZ 5000 fire
alarm panel on a TS35 mounting rail (top hat rail) in any
sequence. The modules are automatically connected with
the power supply and the data bus by means of contacts

on the bottom of the housing when they are pushed


together. No wiring is required within the fire alarm
panel for the relay module. For larger switching capacities, a power relay card can be connected via a plug
connector.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download.

Operating voltage

24 Vdc nominal voltage (19 V to 29 V)

Current consumption

10 mA, all relays released, plus 10 mA for each activated relay

Number of relays

Number of contacts per relay

1 potential-free changeover contact

Contact capacity

1 A/30 Vdc, 30 W 0.5 A/125 Vac, 60 VA

Operating temperature

5 C to +40 C

Relative humidity

95%, without dew

Dimensions

99 x 17.5 x 114.5 mm (L x W x H)

Article number

901595

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

PB52Fe_01/0704/5/01.05/EIN

Technical data

FIRE DETECTION SYSTEMS


FIRE ALARM PANEL

FMZ 5000
Control group module

 Product

 Application

The control group module provides


4 control groups for triggering
valves and horns and monitoring
the lines for wire breakage and
short circuits.
Each control group can be used
with 4 different function modes:
continuous activation
pulsed activation
delayed activation
combinations with delay
Activation and delay times of up to
18 hours can be configured.
Defined by the configuration, each
control group can display the
activation with the group number,
alarm type, number, alarm text and
single LED.
Each control group can be used for
controlling fire fighting equipment,
for activating acoustic signals,
dependent on door contact or vice
versa.

Safe
e for certain.
cer ain.

+ Benefits
Each control group can be used for
individual properties corresponding
to the respective safety concept.

+ If the control group is intended for

Up to 3 devices can be connected


for each control group. Each device
is included in the wire breakage and
short circuit monitoring.

+ SNAP AND GO! All you have to do

The configuration software


MxSysCon enables free use of the
4 control groups with free logical
circuits similar to freely programmable controls.

The extensive configuration options


of the switching and delay times
and the ability to combine all times
offer maximum flexibility for use in
any project.

horn control, it is dependent on the


silence alarms command.
is plug in the modules, with no
wiring in the fire alarm panel, then
connect the external devices.

Function

Alarm activation monitoring


Time-controlled activation, pulsed activation, delayed
activation
Activated control groups are displayed on the LCD or at the
control centres with the group text and group number
Monitoring of the supply lines and of the connected device
for wire breakage and short circuits

The control group module has four independent control


groups. Each control group monitors the connected device
including the supply line for wire breakage and short
circuits. They are connected directly by means of plug-in
terminals on the module housing.
The control group modules can be connected in the
FMZ 5000 fire alarm panel on a TS35 mounting rail (top
hat rail) in any sequence. The modules are automatically
connected with the power supply and the data bus by

means of contacts on the bottom of the housing when


they are pushed together. No wiring is required within
the fire alarm panel for the control group module.
The nominal switching voltage is 24 Vdc with a maximum
release current of 2 A.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download.

Operating /consumer voltage

24 Vdc (19 V to 29 V)

Current consumption

25 mA, no triggering active

Number of control groups

Line monitoring

monitoring for wire breakage and short circuits incl. the connected device

Load current (max.)

2 A for each control group

Operating temperature

5 C to +40 C

Relative humidity

95%, without dew

Dimensions

99 x 17.5 x 114.5 mm (L x W x H)

Article number

901673

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

PB53Fe_01/0704/5/01.05/EIN

Technical data

FIRE DETECTION SYSTEMS


FIRE ALARM PANEL

FMZ 5000
Remote transmission unit

 Product

 Application

The remote transmission unit


provides 2 outputs for activating
remote transmission for fire and/or
faults or for combinations of the
two.
For each remote transmission, the
configuration determines whether
the activation should be
continuous or
pulsed.
Connections for a fire brigade
control panel in accordance with
DIN 14661 and a fire brigade key
depot in accordance with VdS 2139
are provided. All functions of both
devices are fully supported.

Safe
e for certain.
cer ain.

+ Benefits
For each alarm group, it is determined whether the remote transmission should be activated
permanently, based on time periods
or with an additional delay (explore)
in the case of a fire alarm.

+ For a very finely structured alarm

You can define whether the explore


function is deactivated automatically
after a time or only manually.

+ The configurable alarm organisation

The requirements for the PM operating mode in accordance with DIN


VDE 0833-2 for preventing false
alarms are fully implemented.
The remote transmission for faults
also reports complete power
outages.
A fire brigade control panel in
accordance with DIN 14661 can be
connected via a 20-pin sheathed
ribbon cable.

+ You can specify for each individual


alarm group whether the fire
brigade should be called or not.

organisation and optimum adaptation to your operational requirements, up to 8 freely definable time
periods are available for each day
of the week.
can therefore be fully adapted to
your operational requirements.
Adaptations to shift operations in
various production areas are easy
to implement.

+ SNAP AND GO! All you have to do is


plug in the modules, with no wiring
in the control panel, then connect
the external devices.

Function

Remote transmission for fire


Explore 8 time periods per day, shift operation, holidays

Remote transmission for fault

Activate remote transmission, call fire brigade

Activate remote transmission, notify service points

Fire brigade control panel activation and operation

Fault is reported even in the case of a power outage

Key depot activation/monitoring

The remote transmission unit has two independent


controls for remote transmission (RT). Each output monitors
the connected RT including the supply line for wire
breakage and short circuits. They are connected directly
by means of plug-in terminals on the module housing. A
fire brigade control panel and key depot can easily be
connected via a 20-pin ribbon cable and a plug contact.
An RTU can be connected to the FMZ 5000 control panel
on a TS35 mounting rail (top hat rail) in any module

position. The module is automatically connected with


the power supply and the data bus by means of contacts
on the bottom of the housing when they are pushed
together. No wiring is required within the control panel
for the module. The release voltage for both outputs is
24 Vdc.
The module is configured via a computer with the configuration program MxSysCon. The configuration data is
downloaded to the fire alarm panel via serial download.

Operating /consumer voltage

24 Vdc (19 V to 29 V)

Current consumption

25 mA, no triggering active

Outputs

2 for remote transmission of fire/fault, 1 each for fire brigade control


panel and key depot

Line monitoring

monitoring for wire breakage and short circuits incl. the connected device

Load current (max.)

1 A for each remote transmission

Operating temperature

5 C to +40 C

Relative humidity

95%, without dew

Dimensions

99 x 45 x 114.5 mm (L x W x H)

Article number

901969

Minimax GmbH & Co. KG


Industriestrasse 1012
23840 Bad Oldesloe
Phone: +49 (0) 4531 803 0
Fax:
+49 (0) 4531 803 248
E-mail: [email protected]
www.minimax.de

PB54Fe_01/0704/5/01.05/EIN

Technical data

FIRE DETECTION SYSTEMS


FIRE ALARM PANELS

FMZ 5000
Reflex module

 Product

Application

 The reflex module offers all


functions for 2 extinguishing
zones where very fast fire
detection and instantaneous
extinction are of particular
importance.
 All components are available for
use in each single extinguishing
zone of the reflex module as well
as between modules for the
formation of complex controls.
 2 detector lines for each 8 spark
detectors or 4 flame detectors.
 2 transmission lines for activating
and monitoring a maximum of
3 valves each.
 4 lines to monitor the condition
of each valve unit and the
extinguishing process.
 All detector, control and monitoring lines are monitored for wire
breaks and short circuits. The
detectors also report possible
malfunctions after performing
a self-test.

11549-8_PB_57Fe_FMZ5000 1

+ Benefits
 The reflex module is essential
where pneumatic conveyors are
involved and in areas subject to
the risk of rapidly spreading fires.
 Pneumatic material conveyors are
at risk from flying sparks or glowing embers. Spark detectors in
various models can reliably spot
sparks and sources of fires the
extinguishing process is triggered
almost immediately.
 Alternatively or in addition to the
extinguishing process, combustible
material can be ejected from the
transport system without delay.
 In ESTA paint shops flames caused
by high voltage flashovers are
extinguished immediately by cutting off the supply of paint and
applying extinguishing agents
through the paint spray nozzles.
 Flame detectors in machine tools
cabinets monitor the material
processing and the cooling agent.

Complete protection of your plant


through the safe and most rapid fire
detection, combined with the greatest
possible safety of the extinguishing
triggers.

+ Individual configuration for each

project: detectors, detector groups,


extinguishing valves, extinguishing
controls and extinguishing monitoring
as well responses to flying sparks.

+ Adapted production interventions

by evaluating of flying sparks and


extinguishing: a continuous series of
sparks, exceeding a defined number
of flying sparks or the average value
per unit of time, unacceptably long
extinguishing time.

+ Precise monitoring of the supply lines

and equipment: the smallest possible


deviations are hereby recognised, thus
guaranteeing safe operations at all
times.

+ Displaying and recording the instant

that fire is detected and extinguished


accurate to the millisecond: fire events
can be reproduced precisely and
effective measures carried out.

21.05.2008 10:16:50 Uhr

Function
instantaneous
relays
Fault and
performance
monitoring
valve group 1

Valve group 1
Detector group 1
Fault and performance
monitoring external
controls

Fault and performance


monitoring external
controls
Detector group 2
Fault and
performance
monitoring
valve group 2

Valve group 2

instantaneous
relays

 Components from several Minimax reflex modules


can be combined to create larger extinguishing zones.
Parts of the module, which are not used in extinguishing zones, are available for other fire alarm panel
tasks.

 The module is configured via a computer with the


configuration program MxSysCon. The configuration
data is downloaded to the fire alarm panel via serial
download.

Technical data
24 Vdc (19 V to 29 V)
2 detector groups, 2 control groups, 4 monitoring groups, 2 instantaneous relays

Line monitoring

All lines monitored for line breaks and short circuits

Fault and performance monitoring

Detectors and valves monitored for connection and function, overall monitoring
of an extinguishing unit with ball valve on a common line

Number of detectors/valves (max.)

8 spark-/4 flame detectors per detector group, 3 valves per control group

Operating temperature

5 C to +40 C

Relative humidity

95 %, without dew

Dimensions

99 x 52.5 x 114.5 mm (L x W x H)

Article number

906262

Subject to technical modifications.

11549-8_PB_57Fe_FMZ5000 2

Minimax GmbH & Co. KG


Industriestrasse 10/12
23840 Bad Oldesloe
Germany
Tel.: +49 4531 803-0
Fax: +49 4531 803-248
E-mail: [email protected]
www.minimax.de

No. S 89201

Units per module

Certified according to
ISO 9001

PB57Fe_02/04.08/2/05.08/HA Printed in Germany

Operating/load voltage

21.05.2008 10:16:57 Uhr

FIRE DETECTION SYSTEMS


FIRE ALARM PANELS

FMZ 5000
Spark test module

 Product

Application

+ Benefits

 Materials transported in the duct


system can leave sediments on the
detector optics or cause damage
to them.

Typical areas of application:

 The spark test module in conjunction with the test light


monitors spark detector performance during ongoing operations.

 Foodstuffs/automotive industry

 The test actuator is mounted on


the pipe wall located opposite the
spark detector. The performance
of the optics and the detectors
detection effectivity is verified by
detecting a simulated spark from
the test actuator.

11549-9_PB58Fe_FMZ5000_Funkentes1 1

 Timber industry
 Textile industry
 Chemical/synthetics processing
industry

Constantly monitors the operational


safety of the protection system.

No interruption of plant operations


during the test.

The detector`s optical integrity can


be verified automatically or manually
at any time by the control panel.

+
+

Records test times and results.

SNAP AND GO! Installation of the


modules in the reliable FMZ 5000
system. No further wiring within
the panels is required. The only task
is to connect the external equipment to
the module and programm it.

Triggers a test to repeat if the test


light impulse has not been recognized.

21.05.2008 12:09:28 Uhr

Function

 The test light intensity is automatically determined in a


self adjusting process, based on the duct diameter and
the material transport. However, it can also be to set
manually to a fixed value.

 The module is configured via a computer with the


configuration program MxSysCon. The configuration
data is downloaded to the fire alarm panel via serial
download.

 It is possible to select as many test periods as desired


per day. The tests are then carried out automatically
and recorded.

Technical data
24 Vdc nominal voltage (19 V to 29 V)

Power input

24 mA (at rest, without test power)

Number of test actuator outputs

8 each for one test actuator

Line/function monitoring

Each test actuator prior to and during triggering

Actuator load (max.)

3A

Operating temperature

5 C to 40 C

Relative humidity

95 %, without dew

Dimensions

99 x 35 x 114,5 mm (L x W x H)

Article number

906980

Minimax GmbH & Co. KG


Industriestrasse 10/12
23840 Bad Oldesloe
Germany
Tel.: +49 4531 803-0
Fax: +49 4531 803-248
E-mail: [email protected]
www.minimax.de

11549-9_PB58Fe_FMZ5000_Funkentes2 2

No. S 89201

Subject to technical modifications.

Certified according to
ISO 9001

PB58Fe_01/04.08/2/05.08/HA Printed in Germany

Operating/load voltage