Zig-Zag Grounding Transformer W/Resistor Installation and Maintenance Instructions
Zig-Zag Grounding Transformer W/Resistor Installation and Maintenance Instructions
Zig-Zag Grounding Transformer W/Resistor Installation and Maintenance Instructions
Table of Contents
SECTION 1
1.1
1.2
Unpacking .............................. 3
Shipping ................................. 3
Receiving ............................... 3
SECTION 2
Installation .............................. 3
SECTION 3
Inspection ............................... 4
SECTION 4
4.1
4.2
Connection ............................. 4
Neutral Lead........................... 5
Ground Lead .......................... 6
SECTION 5
Maintenance/Inspection ......... 7
Section 1 Unpacking
1.1 Shipping
Post Glover neutral grounding assemblies are placed in their normal mounting position onto a wooden skid and
securely fastened to the skid with lag bolts. The units are then covered with plastic to protect the finish and to
prevent dirt or moisture buildup that can occur during shipping or storage.
Wooden supports are used inside the enclosure to support the resistor banks and/or transformer. Finally, the
units are skid-mounted.
All units are loaded by forklift into the enclosed van of a common carrier. At that point, it is the responsibility of
the carrier to provide proper care in shipping and handling.
1.2 Receiving
Once received, the skid-mounted unit should be unloaded and moved by forklift. At this point, a preliminary
inspection of the unit should be made to ensure proper handling was practiced during shipment. It is
recommended that the unit remain on the skid until it reaches the job site to prevent possible damage during
transfer.
All skid-mounted neutral grounding assemblies are suitable for prolonged storage. If the unit is to be stored, it
should sit horizontally (as shipped). Never store the unit on the sides or top as this could result in damage to the
bushings or insulators. Do not stack.
Section 2 Installation
When the unit arrives at the job site, remove the lag bolts which fasten the resistor unit to the skid.
NOTE: It is recommended that all packing material within the enclosure remain intact until the unit is installed.
Top-mounted eye-bolts are provided for easy hoisting and placement by crane.
Post Glover neutral grounding assemblies can be mounted on a concrete pad or support stand near the
transformer if the units size and weight permit. It is important that the enclosure be mounted horizontally (as
shipped). This keeps the unit drip-proof, allows for adequate cooling, and prevents unnecessary strain on the
support insulators.
The unit should be bolted to the mounting surface using the holes provided at the bottom of each enclosure leg.
Expansion-type anchors are recommended for concrete pad mounting.
NOTE: The enclosure should always be securely grounded to prevent a shock hazard to personnel or wildlife.
Section 4 Connection
CONDUIT
2. The connection is made directly to a top or side-mounted exit bushing. The bushing has a NEMA twohole pad type connector. The bushing will be factory wired to the transformer terminal. (See Figure 4.)
In both cases, the ground terminal is tagged for easy identification and the proper connection is shown
schematically on the drawing. CHECK TO SEE THAT ALL CONNECTIONS ARE FIRMLY TIGHTENED.
CONDUIT