Csepro F Catalogue
Csepro F Catalogue
Csepro F Catalogue
CSEPRO-F
CSEPRO
Series
Catalogue
INDEX
S.No.
Description
1.
Introduction
2.
Application
3.
Hardware
4.
Protection Features
5.
Supervision Functions
6.
Functional Diagram
7.
Protection Functions
8.
9.
Fault Record
10.
Event Record
11.
Output Contacts
12.
13.
Communication
14.
Setting Ranges
15.
Technical Data
16.
Standards
16.1 High Voltage Tests
16.2 EMC Immunity Tests
16.3 Environmental Tests
16.4 Mechanical Tests
02
17.
Connection Diagram
18.
Dimension Details
19.
20.
Ordering Information
1.0 Introduction
3.0 Hardware
?
Current Analog input
?
Voltage analog input
?
Max. 6 digital inputs
?
Max. 6 digital outputs
?
LAN-RJ45/RS485/USB ports for Communication
?
8 LEDs at Pkup & Trip on fault + 3 LEDs with special
function of 3 control keys
?
16x4 Alpha numeric LCD
?
8 Push button on the front for MMI
(Figure-1)
2.0 Application
The CSEPRO-F relay has been designed for controlling,
protecting and monitoring industrial, utility distribution networks
and substations. They can also be used as part of a protection
scheme for feeders, transformers and generators.
CSEPROF Model
?
Ground instantaneous over current (50 N)
?
Current unbalance (46)
?
Broken conductor detection (46 BC)
?
Auto recloser
?
Fuse failure
?
Cold load pickup
?
Thermal overload (49)
?
Under / over voltage (27)
?
Residual voltage / voltage unbalance
?
Trip circuit supervision function
?
Circuit brekaer failure protection
03
Front port
AUXILIARY FUNCTIONS
Rear port
CB local remote
CB monitoring
Cold load pickup
VTS & logic applications
Trip circuit supervision
Blocking logic
Remote ctrl on output relays
RJ45/RS485 port
to SCADA system
MEASUREMENTS
Phase current
Residual current
Residual voltage
Line & phase voltage
Auto reclose counters
CB operation counter
-ve/+ve/Zero phase sequence
RECORDING
FEATURES
Fault recording
10
Event recording
100
Dist recording
1200 cycle
27
59
59N
79
86
67
67N
50/51
P
50N
51N
37
46
46BC
49
50BF
04
05
79 AR Close CB
79 Lockout
AR-Blocked: Unit changes immediately to "AR-blocked" status when an external AR Blocking DI is applied or internal EXIT is chosen for
AR cycle in MMI. No Auto reclosing is possible in "AR-blocked" status.
Activating of AR: Prior to every AR it is possible to select which kind of tripping (I> or I>>, Ie> etc.) will lead to automatic reclosing. This
can be separately fixed for each protection.
Dead time (td): Starts with the off signal of the circuit breaker. No closing command to the circuit breaker is given till expiry of the set
dead time.
User programmable dead times are available for each protection trip operation.
The dead time is initiated when the trip output contact resets, the pickup is reset and the CB is open.
The CB close output relay is energized after the dead time has elapsed If CB ready input is present.
The dead time (dead time td1, dead time td2 dead time td3 dead time td4) starts when the feedback on 'CB CLOSE DI' is not available.
Trip Circuit Supervision (74TC)
This feature detects any anomalies in the circuit with the switch open or close. It detects trip circuit supply failure of circuit breaker,
tripping mechanism failure like circuit breaker contact degeneration in wires, contacts and coils.
Automation
Lockout Relay (86)
Relays programmed with this function will act when the differential unit acts (instantaneous or percentage type) so that they can be used
as a locking device for breaker close circuits.
Protection Function Locking
Each protection function can be locked via a digital input as selected and assigned in HMI.
* Note: These are the model dependent and are available in auxiliary models only.
06
If the circuit breaker dose not trip again, the auto reclose cycle resets
to original STATE-1 at the end of the reclaim time.
1) Lockout occurs when all auto reclosure attempts are over and
protection operates during the final Reclaim Time.
l
either advances to the next AR cycle that is expected in next auto
reclose state or
l
if all the programmed recloser attempts have been accomplished,
it locks out.
Pickup
Trip Command
Starting of reclaim time
CB Close Status
Dead Time
Reclaim Time
Reclaim Time
CB Ready
AR Cycle
AR Cycle
Reclose Command
First Fault: AR State:1 : Successful
07
Voltage Protevtion
The relay is equipped with an independent, 2-step over-(U>, U>>) and under voltage supervision (U<, U<<)simultaneously with
separately adjustable tripping values and delay times. Voltage measuring is 3-phase. In this process there is a continuous comparison
of the line conductor voltages in case of a delta connection and of the phase voltages in case of a star connection with the preset limit
values.
4.2 Zero-sequence
Over voltage CSEPRO-F relays will operate from the zero sequence voltage, which is calculated internally, or from the residual voltage,
which is measured directly or internally
U0=1/3| (U1+U2+U3)|
Disturbance Record
The CSEPROF relay has an oscillograph data recorder with the following characteristics:
?
Oscilloscopic recording can trigger on Pickup or on trip or via DI i.e. change from pre-fault to post-fault stage. It is
programmable.
?
Each record comprises the samples from 7 analog signals and the status of 6 digital inputs and 6 digital outputs. There will be
30 samples per cycle.
?
Relay saves maximum 1200 cycles, and the number of cycles per record is programmable (for example: if 40 cycles are
selected, then there will be maximum 30 records of 40 cycles each).
?
The pre-fault and post-fault cycles are programmable.
?
Records are in the non volatile memory.
?
The records are transferred to PC using USB interface. The data is graphically displayed and can be taken on printer.
?
Record 1 is always latest record. 2nd record is older than 1st...... and so on.
08
Fault Format
IL1
00.00A
Iref
00.00A
IL2
00.00A
Ie
00.00A
IL3
00.00A
I2
00.00A
VL1
00.00V
HR MIN
HH:MIN
VL2
00.00V
SEC Ms
Sec: mSec
VL3
00.00V
DATE
DD:MM:YR
Ve
00.00V
F-TYPE
Type of fault
09
EVENT NUMBER
HOUR
HH.MM
SEC mSEC
SEC: mSEC
DATE
DD/MM/YY
The user can view event records via the front USB interface software
10
Type of outputs
Relay
Yes
Programmable (Auto/Manual)
No of digital inputs
Type of inputs
AC/DC Voltage
Yes
Inputs
11
CSEPROF
FE
PR
E D E R
L 1L 2
L3
O T E C T I O N
E
RE
PICKUP
F1
C
O
N
T
R
O
L
TRIP
L A Y
BLOCK
I
R
OPEN
CLOSE
(Figure-8) HMI
Keys
I
Manual Key
is used as intelligent key to see the details of the last fault.
is used as a ENTER key.
F1
OPEN
CLOSE
12
Parameters
Display
Setting Range
Max
Min
I>
0.2xIp
Phase characteristics
CURVE
ti
0.01
t>
4xIp
Step
Size
Default
Setting
0.05
Disable
DEFT,EINV,VINV, LINV,
NINV1.3, NINV3.0 (1)
DEFT
1.5
0.005
0.010
0.1 Sec
150 Sec
0.01
0.10 Sec
I>>
0.5xIp
40xIp
0.5
Disable
t>>
0.02 Sec
20 Sec
0.01
0.02 Sec
(Table-1)
Earth Protection *
Parameters
Display
Ie>
Earth characteristics
CURVE
Setting Range
Min
Min
0.05xIn
2.5xIn
Step
Size
0.05
Default
Setting
Disable
DEFT,EINV,VINV,LINV
NINV1.3, NINV3.0(1)
DEFT
tie
0.01
1.5
0.005
0.010
te>
0.03 Sec
150 Sec
0.01
0.03 Sec
Ie>>
0.5xIn
8xIn
0.05
Disable
te>>
0.02 Sec
20 Sec
0.01
0.02 Sec
(Table-2)
(1) Refer following formula for EINV, VINV, LINV, NINV1.3, NINV3.0 characteristics:
13.5
Very Inverse
t=
ti [s]
(I / IS) 1
80
Extremely Inverse
t=
ti [s]
2
(I / IS) - 1
120
Long time Inverse
t=
ti [s]
(I / IS) 1
0.14/0.061
t=
ti [s]
(I / IS) 0.02 1
Where
t =Tripping time
ti =Time multiplier
I =Fault current
13
Parameters
Display
TCS
td
Setting Range
Max
Min
Step
Size
Default
Setting
0.03 Sec
0.01
Disable
Setting Range
Max
Min
Step
Size
Default
Setting
0.03 Sec
2 Sec
0.01
Disable
Setting Range
Max
Min
Step
Size
Default
Setting
2 Sec
(Table-3)
Circuit Breaker Failure Protection
Parameters
Display
CBFP
td
(Table-4)
Negative Phase Sequence Setting
Parameters
Display
Ib
0.50xIp
2.5xIp
0.1xIp
Disable
NPS characteristic
CHAR
DEFT
NPS-INV(2)
----
DEFT
Time multiple
K1
5 Sec
60 Sec
0.1 Sec
5.0 Sec
Time constant
K2
0.02
0.4
0.01
0.02
Definite time
td
0.02 Sec
0.4 Sec
0.01 Sec
0.02 Sec
(Table-5)
K1
=
(I2 / Ib)2 (K2)2
Parameter
Display
Setting Range
Min.
Max.
Default
Size
Setting
Enable
Yes
No
Dead Time 1
D1
0.20 Sec.
300 Sec.
0.01 Sec.
0.20 Sec.
Dead Time 2
D2
0.20 Sec.
300 Sec.
0.01 Sec.
0.20 Sec.
Dead Time 3
D3
0.20 Sec.
300 Sec.
0.01 Sec.
0.20 Sec.
Dead Time 4
D4
0.20 Sec.
300 Sec.
0.01 Sec.
0.20 Sec.
Reclaim Time
tR
0.20 Sec.
300 Sec.
0.01 Sec.
0.20 Sec.
Phase Overload
l>cycle
l>>cycle
le>cycle
le>> cycle
le>>cycle
tspr
0.05 Sec.
2 Sec.
0.01 Sec.
max AR cylcle
8
Earth overload
le> cycle
10
11
Yes
13
2
Earth
E
h overload
l d
(Table-6)
14
Step
2
0.05 Sec.
Parameter
Display
Setting Range
Step
Default
Min.
Max.
Size
Setting
Enable
NO
YES
-----
NO
l2/l1
l2/l1
0.10
0.50
0.01
0.01
tcon
0.05 Sec.
20 Sec.
0.01 Sec.
0.05 Sec.
Step
Size
Default
Setting
(Table-7)
Harmonic Restrain
Parameters
Display
Setting Range
Max
Min
2nd H
20% If
50% If
5% If
25% If
5th H
20% If
50% If
5% If
25% If
3rd H
20% If
50% If
5% If
25% If
Protection blocked,
if harmonic in all 3 Ph/1Ph
Phase
1 Phase
3 Phase
1 Phase
DIFF BLK
Disable
Enable
Enable
OL_BLK
Disable
Enable
Disable
SC-BLK
Disable
Enable
Disable
NPS_BLK
Disable
Enable
Disable
EL BLK
Disable
Enable
Disable
EH BLK
Disable
Enable
Disable
REF BLK
Disable
Enable
Disable
(Table-8)
Parameters
Display
Setting Range
Max
Min
Step
Size
Default
Setting
(Iref)
0.2xIn
30xIn
0.01
0.2xIn
(tref)
0.0Sec
10Sec
0.01
0.0Sec
(Table-9)
15
General Setting
These are the settings common for all the protections:
Parameters
Display
Common Setting
-----
Ip
In
Phase CT ratio
Ph CTRatio
Earth CT ratio
E CT Ratio
Nominal frequency
Nom.FREQ
Setting Range
Max
Min
Default
Setting
Step Size
-----
1.00 Amp
5.00 Amp
-----
1.0 Amp
1.00 Amp
5.00 Amp
-----
1.0 Amp
999
999
50 Hz
60 Hz
-----
50 Hz
Step Size
Default
Setting
(Table-10)
Oscilloscope (Disturbance) Record Setting
These are the settings for Oscilloscope recording:
Parameters
Display
Setting Range
Max
Min
RECORD
NO
YES
-----
NO
Pre-fault cycle
PRE CYCLE
298
2 Cycle
Post-fault cycle
POST CYCLE
298
2 Cycle
Triggering mode
TRIG. MODE
PK-UP/TRIP/DI
PK-UP
(Table-11)
Default
Setting
RS-485 Communication
Protocol
MODBUS
19200 bps
None
Stop Bit
1 Bit
1 Bit
Data Bit
8 Bit data
8 Bit data
(1 to 32)
------
(Table-12)
USB Communication
Protocol
Baud rate
19200 bps
16
(Table-14)
Measurement Accuracy
Range
Parameters
Accuracy
Frequency Range
(Table-15)
Parameters
Accuracy
(Table-16)
Auxiliary Supply
Parameters
Frequency Range
Accuracy
Universal
Normal Voltage UN
Power consumption
Quiescent approx. 3W
(Table-17)
Common Data
Dropout ratio
> 96%
30 ms
30 ms
Transient overreach at
instantaneous operation
5 %
(Table-18)
17
16.0 Standards
Design Standards
IEC 60255-22-[1-6]
IEC 60255-5
16.1 HIGH VOLTAGE TESTS:
High Frequency Interference Test
IEC 60255-22-1
Class 3
:
:
Auxiliary Supply
2.5 kV/2 s
Circuit to Earth
2.5 kV/2 s
+2 kV, 5 kHz
Circuit to Earth
Air discharge
8 kV
Contact Discharge
6 kV
IEC 61000-4-4
Class 4
Surge Immunity Test
IEC 61000-4-5
Class 4
Electrical Discharge Immunity Test
IEC 60255-22-2
IEC 61000-4-2
Class 3
Radiated Immunity Test
EN 61000-4-3 / IEC60255-22-3 :
18
Storage 25 C to +85 C
IEC 60068-2-2
Operation: 25 C to + 70 C
Temperature
55C
Relative humidity
<50%
Test duration
72 h
Temperature
70C
Relative humidity
<50%
Test duration
2h
Temperature
55C
Relative humidity
95%
(10Hz 59 Hz)
0.035 mm
IEC 60255-21-1
Class 1
displacement
:
(59Hz-150Hz)
0.5 gn
Acceleration
:
1.0 gn
20
Acceleration
each direction
each direction
Class 1
19
Front View
CSEPROF
PR
E D E R
L 1L 2
L3
O T E C T I O N
E
PICKUP
F1
C
O
N
T
R
O
L
OPEN
RE
L A Y
TRIP
BLOCK
Panel cutout
dimension
145.0
156.0
FE
112.0
I
R
CLOSE
(Figure-10)
249.0
Side View
(Figure-11)
21
ANSI
CT Inputs
F120
F200
F220
F240
F260
F300
F400
F500
VT inputs
Function Keys/Hotkeys
lll l l ll l
Programming Logic
ll l
Protection
3 Phase overcurrent
50/51P
Ground fault
50/51N
ll ll l
ll ll l
Phase directional
67P
67N
Sensitive Earthfault
50/51SN
Restricted earthfault
64
51V
ll
ll ll
l
l
46
Thermal overload
49
l
ll ll l
Undercurrent
37
Over/Under voltage
27/59
59N
l
l
47
l
---
l
l
l
l
l
l
l
l ll
-
---
---
l ll
l ll
ll
ll
Over/Under frequency
81O/U
87R
50BF
Autoreclose
79
Broken conductor
46BC
l
-ll
-ll l ll
l lll ll
ll ll l
l
Inrush blocking
74TC
--
ll ll l
ll ll l
l
l
l ll ll l ll
Communication
Front (USB)
llll ll l l
Rs485 Modbus
llll ll l l
l ll l ll l l
l ll l ll l l
l ll l ll l l
RJ45 IEC60870-5-101
l ll l ll l l
RS485 IEC60870-5-103
l ll l ll l l
RJ45-IEC61850
l ll l ll l l
SNTP-Time Synch-RJ45
l ll l ll l l
Webserver on Rj45
l ll l ll l l
l
Optional-Based on Ordering Information
(Table-19)
22
CSEPRO-F
MODEL NO.
120
200
220
240
260
300
400
500
09
COMMUNICATION PROTOCOL
MODBUS on RS-485
MT
MF
IEC60870-5-103 on RS-485
I103
CSE-Protocol on RS-485
CSP
I650
F650
IEC60870-5-101 on RJ-45
I101
WT
23 11
CSEPRO-F
Branch office
Branch
Phone
Fax
Ahmedabad:
Bangalore:
Bhubaneswar:
Chennai:
Cochin:
Delhi:
Hyderabad:
Kolkata:
Mumbai:
Pune:
+91 79 30074534/35/36
+91 80 3057 0372/73, 3057 0347
+91 674 2507265
+91 44 3918 0531-35
+91 0484 3071717
+91 11 30838822-25
+91 40 3918 2496/97
+91 33 22275850/51
+91 22 30487146/47/48
+91 20 30283244/45
+91 79 30074519
+91 2558 4839
+91 674 2507265
+91 44 39180514
+91 0484 3071716
+91 11 30838826
+91 40 3910 3631
+91 33 2227 5849
+91 22 2412 6631
+91 20 30283244
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
Rev.No.: 00, Rev. Date: 05.08.10, Issue Date: 05.08.10