Dwyer Ms2 w101 102 LCD Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Bulletin P-MS2

Series MS2 Magnesense IIDifferential Pressure Transmitter


Specifications - Installation and Operating Instructions
21/32
[16.67]

3-7/16
[87.31]

2-41/64
[67.07]
1/2 NPT

21/32
29/32
[16.67] [23.02]
2-11/64
1/2 [55.17]
[12.70]
2-9/16
[65.09]

57/64
[22.62]
Wall Mount Bracket

(3) 3/16 [4.76] HOLES


EQUALLY SPACED ON A
4.115 [104.52] BC
3/8
[9.53]

3-7/16
[87.31]

7-3/4
[196.77]
Duct Mount Bracket
21/32
21/32
2-11/64
[16.67]
[16.67]
29/32
[55.17]
[23.02] 1/2
2-41/64
[12.70]
[67.24]
1/2 NPT

1-41/64
[41.71]

The Series MS2 Magnesense II Differential Pressure Transmitter combines


the proven stable Hall Effect sensing technology of our original Series MS with
additional features to reduce installation time and simplify ordering. In this second
generation transmitter, we have added additional field selectable pressure ranges
so that each model can have four selectable ranges along with four additional
bidirectional ranges. When using the pluggable integral display or the portable
remote display tool, both Metric and English engineering units can be selected via
on board dip switches. Dual current and voltage outputs allow users to
simultaneously take either a current or voltage output to their building controller
and have a local test circuit for verification of the output reading. The voltage output
can be selected to be either 0 to 5 VDC or 0 to 10 VDC, while the current is always
4 to 20 mA. Both the current and voltage output can also be inverted. Alternatively,
the MS2 can be ordered with either a BACnet or MODBUS Communications
protocol that will allow the transmitters to be daisy-chained together.
Like the original Series MS, the second generation transmitter can be used as a
linear pressure output or a linear velocity output with the square root extraction
done in the transmitter. Additional parameters have been included to expand the
square root capability to include flow measurements.
BACnet and Modbus Communications protocol recommend limiting the number
of nodes in any segment to 32. Therefore, the transceiver may be rated at one unit
load. Fractional loads are also acceptable. The MS2 accounts as an eighth of a
load on the MSTPnetwork.

INSTaLLaTION
Surface Mount:
The transmitter should be mounted on a vertical surface with the connections
directed down to prevent moisture from entering either the pressure ports or the
electrical cable entry. The diaphragm must be vertical to minimize gravity effects on
the diaphragm. Attach the mounting flange to a flat surface using three #8 x 1/2
pan head sheet metal screws. Do not over tighten.
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling
coils and other equipment that will effect the measurement of the pressure.
1. To mount the transmitter, drill a .562 (12.70 mm) diameter hold into the duct.
2. Insert transmitter probe into the duct.
3. Mark location of three mounting holes on duct using mounting flange as
template. Drill holes.
4. Attach mounting flange to duct with three #8 x 1/2 pan head sheet metal
screws. Do not over tighten screws.

25/64
[9.96]

57/64
[22.62]

DIN Mount Bracket

3-11/32
[84.84]
3-1/2
[88.90]

SPECIfICaTIONS
Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200.
Data Size: 8.
Parity: None.
Stop Bits: 1.
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
accuracy: 1% FS for 0.25 (50 Pa), 0.5 (100 Pa), 2 (500 Pa), 5 (1250 Pa),
10 (2 kPa), 15 (3 kPa), 25 (5 kPa); 2% FS for 0.1 (25 Pa), 1 (250 Pa), 0.1
(25 Pa) and 1 (250 Pa).
Stability: 1% / year FSO.
Temperature Limits: 0 to 150F (-18 to 66C).
Pressure Limits: 1 psi max., operation; 10 psi burst.
Power Requirements: 10 to 35 VDC (2 wire), 17 to 36 VDC or isolated 21.6 to
33 VAC (3 wire).
Output Signals: 4 to 20 mA (2-wire), 0 to 5 VDC, 0 to 10 VDC (3-wire).
Response Time: Averaging 0 to 240 sec, 2.5 Hz sample rate, 1.5 to 228 sec for
95% step change.
Zero & Span adjustments: Digital push buttons.
Loop Resistance:
Current Output: 0 to 1250 max;
Voltage Output: Min. load resistance 1k.
Current Consumption: 40 mA max.
Display (optional): 5-digit LCD.
Electrical Connections: 3-wire removable European style terminal block for 16
to 26 AWG.
Electrical Entry: 1/2 NPS thread;
Accessory (A-151): Cable gland for 5 to 10 mm diameter cable.
Process Connection: 3/16 ID tubing (5 mm ID); Max. OD 9 mm.
Enclosure Rating: IP66.
Mounting Orientation: Diaphragm in vertical position.
Weight: 8.0 oz (230 g).
agency approvals: CE.
Electrical Connection:
The Series MS2 simultaneously transmits a 2-wire 4 to 20 mA current output and
a 3-wire 0 to 5 V / 0 to 10 V voltage output via a removable European-style three
conductor terminal block. The transmitter can be wired in one of the following three
ways to utilize the current and / or voltage output. The range of the voltage output
can be selected using the on board dip switches as described in the Dip Switch
Settings section of this manual.

Modbus is a registered trademark of Schneider Automation, Inc.

DWYER INSTRUMENTS, INC.


P.O. BOX 373 MICHIGaN CITY, INDIaNa 46360, U.S.a.

Phone: 219/879-8000
fax: 219/872-9057

www.dwyer-inst.com
e-mail: [email protected]

Power Supply
Refer to the below table for the required supply rating.

The range of appropriate receiver load resistances (RL) for the power supply voltage
available is given by the formula listed below. Shielded 2-wire cable is recommended
for control loop wiring. Ground the shield at the power supply end only.

Power Supply Rating


10 to 40 VDC (40 mA min)
17 to 40 VDC or 21.6 to 33
VAC (40 mA min)
Simultaneous Current 17 to 40 VDC (40 mA min)
and Voltage
Output Type
2-Wire Current
3-Wire Voltage

Choose a power supply with a voltage and current rating sufficient to meet the power
specifications under all operating conditions. If the supply is unregulated, make sure
that the output voltage remains within the required voltage range under all power line
conditions. Ripple on the supply should not exceed 100 mV.
aC/DC Jumper Selection
NOTICE

The jumper is factory set to AC. If DC power is applied while the


jumper is set to AC, no damage will occur. However, the
accuracy of the unit may temporarily be affected.
CaUTION

Powering the unit with AC power while the jumper is set to DC


may permanently damage the transmitter.

Refer to Figure 1 for the location of the AC / DC jumper. Place the shorting jumper
across either the two pins marked AC or the two pins marked DC.

AC/DC JUMPER

SPAN

The receiver may be connected to either the negative or


positive side of the loop, whichever is most convenient. Should
polarity of the transmitter or receiver be inadvertently reversed, the loop will not
function properly but no damage will be done to the transmitter.
R L=

Vps - 10.0
20 mA DC

The maximum length of connecting wire between the transmitter and the receiver is
a function of wire size and receiver resistance. That portion of the total current loop
resistance represented by the resistance of the connecting wires themselves should
not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 feet),
it is desirable to select receivers with lower resistances in order to keep the size and
cost of the connecting leads as low as possible. In installations where the connecting
run is no more than 100 feet, connecting lead wire as small as No. 22 ga. can be
used.
3-Wire 0 to 10 V and 0 to 5V Voltage Operation
CaUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.


PERMANENT DAMAGE NOT COVERED BY WARRANTY

WILL RESULT.
The connection to the transmitter are made to Terminals 1, 2, and 3 on the terminal
block as shown in Figure 3. The terminal block is removable and each of the terminals
are labeled underneath the terminal block on the circuit board. Polarity is indicated by
PWR, COM, and +VOUT. When connecting using a DC power source, make sure the
AC/DC selection jumper is set for DC. If the polarity of the transmitter is inadvertently
reversed, the unit will not function properly, but no damage will be done to the
transmitter. When connecting to an AC power source, make sure the AC/DC selection
jumper is set for AC. Either lead of the supply power may be connected to PWR and
COM without affecting the operation of the transmitter or damage to the transmitter.

ZERO

SPAN

DC

4 5

4 5

ZERO

NOTICE

AC

figure 1

RECEIVER

2-Wire 4 to 20 ma Current Operation

POWER

CaUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.


PERMANENT DAMAGE NOT COVERED BY WARRANTY
WILL RESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC
VOLTAGE OPERATION.

figure 3
The minimum receiver load is 1K . The resistance due to the wire should be low
compared to the receiver load resistance. While the voltage at the terminal block
remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause
errors in the voltage delivered to the receiver. For a 1% accurate gauge, the
resistance of the wires should be less than 0.1% of the value of the receiver load
resistance. This will keep the error caused by the current flow below 0.1%.

ZERO

SPAN

4 5

The connections to the transmitter are made through terminals 2 and 3 on the terminal
block as shown in Figure 2. The terminal block is removable and each of the terminals
are labeled underneath the terminal block on the circuit board. Polarity is indicated by
+IOUT and -IOUT. The AC/DC selection jumper should be set for DC operation.

VOLTAGE OUTPUT WIRING

RECEIVER

POWER

CURRENT OUTPUT WIRING


figure 2

The output across +VOUT and COM will be either 0 to 5 V, 0 to 10 V, or the inverse
depending on the dip switch setting. See Dip Switch Setting Section for more
information.

CaUTION

DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS.


PERMANENT DAMAGE NOT COVERED BY WARRANTY
WILL RESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC
VOLTAGE OPERATION.

DIP SWITCH SETTINGS


DIP Switches can be located next to the terminal block as shown in Figure 5. A
small screw driver or pen can be used to change the position of the switches.
WaRNING

All power should be turned off to the transmitter before adjusting


the dip switch settings to avoid electrical shock.

DIP SWITCH SETTINGS

SPAN

SPAN

UNIDIRECTIONAL
RANGE

6
4 5
3

UNITS

BIDIRECTIONAL

CURRENT
RECEIVER

REV
5V

DIR
10V

+
VOLTAGE
RECEIVER _

POWER

ZERO

4 5

ZERO

NOTE - POWER
AND VOLTAGE
RECEIVER "-" MUST
BE SEPERATE WIRES
AND BOTH WIRED TO

The connection to the transmitter are made to Terminals 1, 2, and 3 on the terminal
block as shown in Figure 4. The terminal block is removable and each of the
terminals are labeled underneath the terminal block on the circuit board. Polarity
is indicated by PWR, COM, and +VOUT. The AC/DC selection jumper should be set
for DC operation. The voltage output and the power supply must have separate
wire leads that are only joined at terminal 2 of the transmitter. Additional error may
occur for the voltage output if a single wire is used or if the wires are joined at the
power supply or receiver.

4 5

Simultaneous Current and Voltage Operation

ON

figure 5

SIMULTANEOUS CURRENT AND


VOLTAGE OUTPUT WIRING
figure 4
For the current output, the maximum allowable loop resistance (wiring + receiver
resistance) is dependent on the power supply. The maximum loop voltage drop
must not reduce the transmitter voltage below 17 V. The maximum loop resistance
can be calculated using the following equation:
RMAX = (VPS 17.0) / 0.02 Where VPS is the power supply voltage
The equation uses 17.0 instead of 10.0 used in current only equation. This
represents the minimum voltage supply which is higher on the simultaneous output
configuration due to the requirements of the voltage outputs.
Shielded 4-wire cable is recommended for control loop wiring. Ground the shield at
the power supply end only. Should the polarity of the transmitter or receiver be
inadvertently reversed, the unit will not function properly, but no damage will be
done to the transmitter.
For voltage outputs, the minimum receiver load is 1K . The resistance due to the
wire should be low compared to the receiver load resistance. While the voltage at
the terminal block remains unchanged with a 10 mA current flow, resistive losses in
the wiring do cause errors in the voltage delivered to the receiver. For a 1%
accurate gauge, the resistance of the wires should be less than 0.1% of the value
of the receiver load resistance. This will keep the error caused by the current flow
below 0.1%.
The output across +VOUT and COM will be either 0 to 5 V, 0 to 10 V, or the inverse
depending on the dip switch setting. See Dip Switch Setting Section for more
information.

factory Settings
Mode = Unidirectional
Range = Highest Range Setting (0.5, 5, or 28 in w.c.)
Units = Inches W.C.
Voltage Output Range = 10 V
Direct / Reverse Output Action = Direct
Setting the Pressure Range
Ranges are selected by adjusting DIP Switch Positions 1 and 2 according to the
below tables. The range also depends on the units selected (Refer to Setting the
Engineering Units Section) and if the input is set for unidirectional or bidirectional
(Refer to the Setting for Unidirectional or Bidirectional Section). The tables below
show the maximum full scale value for the selected range and selected units. If the
unit is set to unidirectional, the ranges are all zero based. If the unit is set for
bidirectional, the ranges will be the maximum full scale value shown in the tables
below.
DIP Switch
2
1
OFF
OFF
ON
OFF
OFF
ON
ON
ON

full Scale Range for MS2-X101


kPa
mm w.c.
Pa
in w.c.
0.025
2.5
25
0.1
0.040
4
40
0.15
0.050
6
50
0.25
0.125
10
125
0.5

DIP Switch
2
1
OFF
OFF
ON
OFF
OFF
ON
ON
ON

full Scale Range for MS2-X102


kPa
mm w.c.
Pa
in w.c.
0.250
25
250
1
0.500
50
500
2
0.750
75
750
3
1.25
125
1250
5

DIP Switch
2
1
OFF
OFF
ON
OFF
OFF
ON
ON
ON

full Scale Range for MS2-X103


kPa
mm w.c.
Pa
in w.c.
2.50
250
2500
10
3.50
350
3500
15
5.00
500
5000
25
6.98
700
6975
28

Setting for Unidirectional or Bidirectional


The Models MS2-X101 and MS2-X103 can be set to measure pressure in one
direction or two directions based on the setting of DIP Switch 3. The Model MS2X102 can only be set to unidirectional.
When the switch is in the ON direction, the transmitter will be set for Unidirectional
and will be 0 based (i.e. 0 to 5 in w.c.).
When the switch is in the OFF position, the transmitter will be set for Bidirectional
and will be the maximum of the selected range (i.e. 5 in w.c.).
For unidirectional units only, switch has no effect and unit will remain in
unidirectional mode.

Setting the Engineering Units


Magnesense II comes with the selection of four engineering units (in w.c., Pa, mm
w.c., or kPa). The engineering units are selected using DIP Switch 4 and 5. The
units will be displayed on the optional LCD display.
DIP Switch
5
4
OFF
OFF
ON
OFF
OFF
ON
ON
ON

Another option for models that do not have a display would be to use a Model A435-A remote display tool which can plug into the connector shown in Figure 7. The
remote display tool has two buttons that function identically to the buttons on the
PCB.

Units
Pressure Velocity Air Flow
m3/h
m/s
kPa
m/s
mm w.c.
m3/h
m/s
Pa
m3/h
FPM
in w.c.
cfm

Setting the Output Voltage Range


Voltage output can be either 0 to 10 V or 0 to 5 V depending on the position of DIP
Switch 6.
When the switch is in the ON position, the output will be 0 to 10 V
When the switch is in the OFF position, the output will be 0 to 5 V

Setting the Input / Output action


The output will either directly or indirectly follow the input based on the position of
DIP Switch 7.
When the switch is in the ON position, the output directly follows the input (i.e
output increases as the input increases)
When the switch is in the OFF position, the output acts in reverse of the input (i.e.
output decreases as the input increases)
CaLIBRaTION
NOTICE

There is a 5 second delay from the time the zero or span


calibration buttons is released until the time that the change in
calibration takes place. This delay is used to prevent stress related offsets on the
lower ranges.
NOTICE

The security level that is set in the Programming Menu Section


of the manual will determine which calibrations, if any, may be
adjusted by the user.
Zero Calibration
The zero calibration can be set by applying zero pressure to both the pressure ports
and pressing the zero button for 3 seconds. If either the remote or local LCD is
present, the display will read ZEroand then sequence back to the home display.

figure 7
Display Error Messages
ovEr= The applied pressure is greater than the maximum span value causing an
Over Range Error.
UndEr = The applied pressure is less than the minimum span value causing an
Under Range Error.
FAiL= When the span or zero buttons are pressed, the pressure value is out of the
range to allow a correct setting. This may be due to a sensor failure or incorrect
pressure being applied.
Err1= The sensor is damaged.
PROGRaMMING MENUS

SPaN Calibration
The span calibration can be adjusted only after setting the zero adjustment. It must
be completed within 5 minutes of the last zero calibration. The span calibration
button will be ignored until the zero calibration is completed. Apply pressure to the
ports of the transmitter that is associated with the maximum output of the
transmitter (20 mA, 5 V, or 10 V depending on output being used). Press and hold
the span button for 3 seconds. If either the remote or local LCD is present, the
display will read SPAn and then sequence back to the home display. If the span
calibration is attempted before adjusting the zero calibration, the FAIL error
message will flash on the display. On bi-directional models, separate spans can be
performed on the positive and negative sides of the range.
LCD DISPLaY
The Magnesense II can be ordered with an optional, integral LCD. If the display is
not needed for normal operation, the transmitter can be ordered without the LCD.
An A-MS2-LCD field upgradeable display is available. It comes with a housing
cover with the overlay cut out for the display. The display will plug into the pins as
shown in Figure 6.

Home Menu
During normal operation, the display will be in the Home Menu and will display the
current measured pressure and the engineering units.
Menu access Security
While in the Home Menu, press and hold the Zero and Span buttons
simultaneously until SECUr appears on the display in order to access the other
programming menus. Upon releasing the buttons, the display will indicate the
current security level.
If the current security level is the security level desired (i.e. Security Level 0), press
and hold the span button for three seconds to enter the Pressure, Velocity, or Air
Flow Menu.
If the security level is not the desired level, the security level can be changed
temporarily to a lower security level or permanently to a higher level of security by
pressing the zero button. A security code will be shown on the display and it can be
changed to one of the codes listed in the below table. The span button chooses
which digit and the zero button increments the value of that digit. Pressing and
holding the span button will store the value.
View
Security
Level Setting Menu
Yes
000
0
Yes
111
1
No
222
2
No
333
3

access
Edit
Span
Menu
Yes
Yes
No
No
No
No
No
No

Zero
Yes
Yes
Yes
No

The level of access to the programming menus and the calibration is limited based
on the security level. The above table details the level of access for each security
level.
figure 6

Mode Selection / Digital Dampening Menu


From the home display, pressing the span and zero button simultaneously for 3
seconds will access the Menu Security Level. If the level is set to 0 or 1, pressing
and holding the span button for 3 seconds a second time will access the Mode
Selection Menu. The display will default to Pressure when first powered up.
Pressing the zero button will cycle to Velocity and Flow.
Once the desired Mode is displayed, pressing and holding the span button for three
seconds will save the selected mode and display the digital dampening or
averaging parameter. This parameter stabilizes the output and the display by
averaging the readings. There are 2.5 readings taken each second and the user
can select the number of seconds that they would like to average up to 240
seconds. The display and the output will continue to update at a rate of 2.5 updates
per second, but the moving average is used for these updates.
PRESSURE MODE
Maximum Output adjustment
If the Pressure Mode was selected, pressing and holding the span after adjusting
the digital dampening will enter the Pressure Mode. In this menu, the maximum
output pressure (POH ) can be adjusted to any pressure between the lowest dip
switch range to the highest dip switch range. If the dip switch settings are preferred
over manually setting the range, the POH parameter can be set to off.
VELOCITYMODE
K-factor adjustment
If the Velocity Mode was selected, pressing and holding the span after adjusting the
digital dampening will enter the Velocity Mode and the transmitter will display the
engineering unit that has been selected by the dip switch. Pressing and holding the
span button for three seconds will enter the K Factor adjustment. The K Factor
can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing
the span button to select the digit and pressing the zero button to increment the
value of the digit. Pressing and holding the span button for three seconds will enter
the Maximum Output Adjustment parameter.
Maximum Output adjustment
The maximum output can be equivalent to a velocity or a pressure. After adjusting
the K-Factor, the display will indicate if the adjustment is set for pressure or velocity.
Pressing the zero button will toggle between the selections. Pressing and holding
the span button for three seconds will enter the maximum output adjustment. The
maximum output can be adjusted by pressing the span button to select the digit and
pressing the zero button to increment the value of the digit. Pressing and holding
the span button for three seconds will save this value and go to the Security Update
Menu.
fLOWMODE
K-factor adjustment
If the Flow Mode was selected, pressing and holding the span after adjusting the
digital dampening will enter the Flow Mode and the transmitter will display the
engineering unit that has been selected by the dip switch. Pressing and holding the
span button for three seconds will enter the K Factor adjustment. The K Factor
can be adjusted between 0.001 to 9.999. The K-Factor can be adjusted by pressing
the span button to select the digit and pressing the zero button to increment the
value of the digit. Pressing and holding the span button for three seconds will enter
the Area Adjustment parameter.
area adjustment
For Flow applications, the area is multiplied by the velocity to determine the
volumetric air flow. The area will be listed in either feet or meters depending on the
dip switch settings. The units will be indicated on the display at the time of
adjustment.The area can be adjusted by pressing the span button to select the digit
and pressing the zero button to increment the value of the digit. Pressing and
holding the span button for three seconds will enter the Maximum Output
Adjustment parameter.
Maximum Output adjustment
The maximum output can be equivalent to a flow or a pressure. After adjusting the
Area parameter, the display will indicate if the adjustment is set for pressure or flow.
Pressing the zero button will toggle between the selections. Pressing and holding
the span button for three seconds will enter the maximum output adjustment. The
maximum output can be adjusted by pressing the span button to select the digit and
pressing the zero button to increment the value of the digit. Pressing and holding
the span button for three seconds will save this value and go to the Security Update
Menu.
Security Update / Save Changes Menu
The Security Update Menu allows the security level to be set either higher or lower
than the current security level setting. This security level will be displayed the next
time the Menus are accessed from the home screen. Pressing the zero button
cycles through the security levels. Pressing and holding the span button for three
seconds accepts the new security level and gives the option to save all the menu

changes. Pressing the zero button will toggle between yes and no. Yes will save the
changes made to all menu items and no will discard all the changes made to all
menu items. If the display is set to yes, pressing and holding the span will save the
menu items and return the display to the Home Position.
faCTORY DEfaULT PROCEDURE
In order to reset all of the menu settings back to their factory programmed values,
press and hold both the span and zero buttons simultaneously for 10 seconds until
FACt is displayed on the LCD. Upon releasing the buttons, the unit will be factory
defaulted. Since resetting the transmitter will wipe out all changes, it is necessary
to zero (and possibly span) the transmitter before taking measurements.
MaINTENaNCE/REPaIR
Upon final installation of the Series MS2 MagnesenseII Differential Pressure
Transmitter, no routine maintenance is required besides zeroing the transmitter
occasionally. Besides routine calibration and installation of the LCD, the Series
MS2 is not field serviceable and it is not possible to repair the unit. Field repair
should not be attempted and may void warranty.
WaRRaNTY/RETURN
Refer to Terms and Conditions of Sales in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping
the product back for repair. Be sure to include a brief description of the problem
plus any additional application notes.
aPPENDIX I
air Velocity / air flow Calculations
Velocity is calculated using the below equation:
Velocity(fpm) = K-Factor x 4004.4 x (Diff. Press. (in of w.c.)
Velocity in m/s is then calculated from the equation:
Velocity(m/s) = Velocity(fpm) x 0.00508
Flow is calculated using the below equation:
Flow(cfm) = Area(Ft2) x K-Factor x 4004.4 x (Diff. Press. (in of w.c.)
Flow (m3/h) = Flow (cfm) x 1.6992

aPPENDIX II
Maximumflow
Range
in w.c.
0.5
5
28

Max Displayed flow Max (K factor x area)


M3/H
CfM Mode M3/H Mode
CfM
2037.2
5885000 9999000
154.5
644.2
5885000 9999000
59.9
272.2
5885000 9999000
25.3

aPPENDIX III
Quick Start Guide
MENU fLOW CHaRT
BUTTON PRESS LEGEND
ZERO

= PRESS ZERO BUTTON

SPAN

= PRESS SPAN BUTTON

ZERO

= PRESS AND HOLD ZERO BUTTON

SPAN

= PRESS AND HOLD SPAN BUTTON

ZERO
SPAN

= PRESS AND HOLD ZERO AND SPAN BUTTONS

MENU CONVENTIONS
IN HOME POSITION:
ZERO

CALIBRATE UNIT TO ZERO PRESSURE.

SPAN

CALIBRATE UNIT TO SPAN PRESSURE.

ZERO
SPAN

DISPLAY IS NOT NECESSARY

ENTER MENU DISPLAY

IN MENU DISPLAY:
SPAN

SEQUENCES TO NEXT MAIN MENU ITEM, AND IF A MENU ITEM IS CHANGED TEMPORARILY SAVES THE SELECTION

ZERO

SEQUENCES THROUGH SUB MENU SELECTIONS OR INCREMENTS DIGITS

SPAN

SEQUENCE TO NEXT DIGIT. ACTIVE DIGIT WILL BLINK.

0.0
in

HOME POSITION

WC

ZERO

SECUr
SEC

ZERO

ZERO

TO CHANGE
SECURITY LEVEL

IF SECURITY IS SET TO
0,1, OR 2

345

PrES

ZERO

uEL

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

SECURITY LEVEL SETTING


000
0
111
1
2
222
3
333

SPAN

IF SECURITY IS SET TO 3

LoCK
MODE SELECTION
PRESSURE, VELOCITY,
OR FLOW

FACt

SPAN

WHEN BUTTONS ARE


RELEASED DISPLAYS CURRENT
SECURITY LEVEL

0
SPAN

FACTORY SETTINGS
RESTORED, THEN RETURNS
HOLD 7
TO HOME POSITION
SECONDS

WHILE BUTTONS ARE


PRESSED

SPAN

SECURITY LEVEL
SELECTION

3 = BLINKING DIGIT

HOME POSITION

0.0

PRESS ANY KEY


OR WAIT 5 SECONDS

ZERO

in

WC

FLo
ZERO

SPAN

SPAN

ADJUST AVERAGING
A

VG

000

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

SPAN

TO " PRESSURE, VELOCITY, OR FLOW " MENUS

SPAN

SPAN

TO SELECT MODE

PRESSURE MODE MENU


FROM AVERAGING MENU

PoH
FROM

"

AdJ P " MENUS

ADJUST PRESSURE
OUTPUT HIGH

SPAN

PoH = DIP SWITCH FULL SCALE SETTING

UPON RELEASE

SET PoH TO DESIRED VALUE

PoH

ZERO

PoH

SPAN

ZERO

SPAN

288

THIS MENU DEPENDS ON


DIP SWITCH SETTING

in

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

WC

UNITS SET BY DIP SWITCH


WILL BLINK

SPAN

TO

" UPDATE SECURITY


AND SAVE " MENU

VELOCITY MODE MENU


FROM AVERAGING MENU

SELECTED UNITS
DISPLAYED

Unit

Unit

OR

FP M

UNITS SELECTED
BY DIP SWITCH
SETTING

SPAN

ADJUST DISPLAY
K FACTOR

diSP

SPAN

UPON RELEASE

d1000

SPAN

SELECT MAXIMUM OUTPUT


SET BY PRESSURE OR
VELOCITY

AdJ

SPAN

UPON RELEASE

AdJ

ZERO

AdJ

ZERO

SPAN

SPAN

TO PoH , PRESSURE
MODE MENU
ADJUST VELOCITY
OUTPUT HIGH

uoH

SPAN

UPON RELEASE

0233
FP M

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

FPM OR M/S BASED


ON DIP SWITCH SETTING

0233
SPAN

TO " UPDATE SECURITY


AND SAVE " MENU

K
M

FLOW MODE MENU


FROM AVERAGING

SELECTED UNITS
DISPLAYED

Unit

MENU

UNITS SELECTED
BY DIP SWITCH
SETTING

Unit

OR

M3 H

C FM

SPAN

ADJUST DISPLAY
K FACTOR

diSP

d1000

UPON RELEASE

SPAN

SPAN

ArEA

SPAN

UPON RELEASE
ARE A

1000

SQ. FEET OR SQ. METERS


ON DIP SWITCH SETTING

ARE A

1000

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

BASED

SPAN

SELECT MAXIMUM OUTPUT


SET BY PRESSURE
OR
FLOW

AdJ

AdJ

UPON RELEASE

SPAN

AdJ

ZERO

EZ RO

SPAN

SPAN

TO PoH , PRESSURE
MODE MENU
ADJUST FLOW
OUTPUT HIGH

FoH

SPAN

0233

UPON RELEASE

C FM

EZ RO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

ZERO

INCREMENT
DIGIT

SPAN

SELECT
DIGIT

FPM OR M/S BASED


ON DIP SWITCH SETTING

0233
M3

SPAN

TO " UPDATE SECURITY


AND SAVE " MENU
FROM " UPDATE SECURITY
AND SAVE " MENU

UPDATE SECURITY
LEVEL

SEC

ZERO

SEC

SEC

ZERO

ZERO

SEC

ZERO

SPAN

SAVE CHANGES

SPAN

SPAN

SAuE

SPAN

UPON RELEASE

no

SPAN

YES

ZERO

ZERO

SPAN

0.0

SPAN

HOME POSITION

in W C

Copyright 2014Dwyer Instruments, Inc.

Printed in U.S.A. 6/14

DWYER INSTRUMENTS, INC.


P.O. BOX 373 MICHIGaN CITY, INDIaNa 46360, U.S.a.

Phone: 219/879-8000
fax: 219/872-9057

FR# 01-444021-00 Rev. 3

www.dwyer-inst.com
e-mail: [email protected]

You might also like