Fire-Lite ACC-2550ZST Data Sheet
Fire-Lite ACC-2550ZST Data Sheet
Fire-Lite ACC-2550ZST Data Sheet
ACC-25/50ZST
Zoned System Voice with Telephone
Evacuation Control Panel
Emergency Voice Evacuation
General
Theaters
Auditoriums
Restaurants
Dormitories
Lodging
Places of Worship
Features
Listed to UL Standard 864, 9th edition.
25 watts of audio power can be divided into eight Style Y
(Class B) or four Style Z (Class A) speaker circuits (zones),
utilizing the zone splitter module (ACC-ZSM).
Full manual control of all audio zones provided by zone
page module with keypad (ACC-ZPMK).
ACC-FFT Fire Fighter Telephone module for control and
annunciation of up to 24 remote telephone jacks
acc25-50_datasheet.tif
ACC-25/50ZST
Activation by the FACP using the ACS serial link and/or the
five Command (CMD) inputs.
ACS serial link compatible with all FireLite FACPs,
depending on function. FACP automatically directs the
voice message to each or all audio zones.
Paging by zone or All-Call.
Full status indication (normal, active, fault) of each speaker
circuit.
Fault indication via ACS serial link and/or the two Form-C
trouble relays (System and AC Power Loss).
Integral 25 watt, 25 VRMS audio amplifier with single Style
Z (Class A) or Style Y (Class B) speaker circuit (expandable
to 50 watts using the ACC-AAM25).
Modular design for maximum system flexibility and ease of
service.
Two command input circuits can be independently field-programmed for activation by a Notification Appliance Circuit
(NAC) or contact closure.
Three command input circuits activate on contact closure.
ACS link or Command Input (CMD) control of:
One 60-second message.
Two 30-second messages.
Three 20-second messages.
Four 15-second messages.
Five 12-second messages.
Microphone time-out feature.
Nineteen different system and diagnostic LEDs.
Optional equipment: second amplifier; local playback
speaker; remote microphone; paging equipment interface
and remote phone jacks.
Integral digital message generator with standard, factory
prerecorded emergency evacuation message.
Standard Modules
ACC-AAM25: 25 watt, 25 VRMS Audio Amplifier Module with
single Class A or Class B speaker circuit.
ACC-ZPMK: Zone Page Module with keypad
ACC-ZSM: Zone Splitter Module. These modules provide up
to eight speaker circuits that may be manually or automatically
activated.
ACC-FFT: Fire Fighter Telephone Module with keypad which
provides indications of phone activation, remote page activation, remote microphone activation and corresponding trouble
conditions.
Optional Modules
ACC-AAM25
25 watt, 25 VRMS audio amplifier module.
Field-programmable for system expansion to 50 watts or as
a backup to the primary 25 watt amplifier where required.
Provides single Class A or Class B speaker circuit.
ACC-25/50DAZS
ACC-25/50ZST
Audio Riser
Speaker Circuit #1
Audio Riser
Speaker Circuit #8
Speaker
Circuit #9
Speaker
Circuit #16
Automatic Control
via the ACS Link or
CMD Input
RPJ-F
up to 24
remote
FireFighter
Telephones
FPJ-F
ACC Control Serial Link (RS-485)
1. The FACP controls the audio system via the ACS Link or CMD
inputs on the ACC-25/50ZST
2. The Audio Riser connects the audio output of the ACC-25/
50ZST to each of the ACC-25/50DAZS(s) to distribute alarm or
paging audio.
3. The ACC-25/50ZST uses the Control Serial Link to control the
routing of the alarm or paging audio.
4. Riser conductors must be installed in accordance with the survivability from attack by fire requirements in National Fire Alarm
Code, NFPA 72.
ACC-25/50DAZS
ACCDADISTSYS3.CDR
Speaker
Circuit #17
Speaker
Circuit #24
Power On (green).
System Trouble (yellow).
Message Generator Trouble (yellow).
Tone Generator Trouble (yellow).
Microphone Trouble (yellow).
Record/Playback (green).
All-Call (green = Active).
Audio ON/OFF (green = Active, yellow = Manual Deactivation).
9. Status of each speaker zone (green = Active, yellow = Manual Deactivation or Fault).
10.Remote Handset Page (green LED) - turns on steady to
indicate that a remote phone has been connected to the
telephone loop and the Remote Phone Jack Keyswitch has
been activated for remote paging by phone.
11.Remote Microphone Page (green LED) -turns on steady to
indicate active paging from Remote Microphone.
12.Remote Handset Trouble (yellow LED) - turns on steady to
indicate that a fault exists on the telephone loop connected
to TB1 of the ACC-FFT
13.Local Handset Trouble (yellow LED) - turns on steady to
indicate that the local handset has a connection fault
14.Remote Key Trouble (yellow LED) - turns on steady to indicate a remote keyswitch wiring fault (TB2)
15.Remote Microphone Trouble (yellow LED) - turns on steady
to indicate a fault on the Remote Microphone wiring or electronics (TB3)
16.FFT 1 through FFT 24 (green LEDs) - LED for each of 24
possible remote phone circuits will turn on if an addressable
monitor module has been connected and programmed for
activation when a remote phone is plugged into the corresponding Remote Phone Jack.
Wiring Requirements
Connecting external system accessories to the ACC-25/50ZST
main circuits must be carefully considered to ensure proper
operation. It is important to use the correct type of wire, wire
gauge and wire run length per each circuit. Refer to the following table to specify wire requirements and limitations.
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Wire Type &
Limitations
Circuit Type
Circuit Function
AC Power
TB3 (nonpower-limited)
See Note 1
Notification Appliance
Circuit
See Note 2
Untwisted,
unshielded or
twisted, shielded
Audio Output
ACC-AAM25 Module
TB1 and
ACC-ZSM Module
(power-limited)
ACC-ZPMK Module
ACC-FFT TB1
ACC-FFT TB2
ACC-FFT TB3
ACC-EPM Module
CMD1 and CMD2 Main
Board TB2 and TB5
1.
2.
3.
4.
See Note 2
Untwisted
unshielded or
twisted, shielded
Untwisted
unshielded
See Note 4
Recommended Maximum
Distance (Feet)
Power Supplied must be:
120 VAC, 60 Hz, 1.5 amps or
240 VAC, 50/60 Hz, 0.75 amps
(see Note 1)
Wire Gauge
Terminals Support
12-18 AWG
(see Note 1)
See Note 3
12 - 18 AWG
4,000 feet
12 - 18 AWG
54 maximum impedance
12 - 18 AWG
54 maximum impedance
12 - 18 AWG
See Note 4
See Note 4
12 - 18 AWG
Triggers ACC-25/50ZST
See Note 1
Untwisted,
unshielded or
twisted, shielded
Triggers ACC-25/50ZST
See Note 1
Untwisted,
unshielded or
twisted, shielded
12 - 18 AWG
Untwisted,
unshielded
12 - 18 AWG
Trouble Output
Maximum
Current 2 amps
12 - 18 AWG
AC Loss Output
Maximum
Current 2 amps
12 - 18 AWG
Circuit
9 - 32 VDC, 1.6 mA for polarity
reversal relay must be rated at 0.5
amp, 24 VDC
12 - 18 AWG
SYSTEM SPECIFICATIONS
System Capacity
Shipping Specifications
Weight: 38.5 lbs. (17.46 kg.)
Electrical Specifications
Cabinet Specifications
Door: 26.174" (66.482 cm) high x 15.780" (40.081 cm) wide x
1.125" (2.858 cm) deep.
Backbox: 26.0" (66.040 cm) high x 15.5" (39.370 cm) wide x
4.75" (12.065 cm) deep, depth includes door.
For more information, contact FireLite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
www.firelite.com
Page 6 of 6 DF-60319:A 2/09/09