AUTO MODE
Closing conditions-B/C
When fault (U/V) on bus side-A Than it checks,
Selector switch is on Auto Mode.
Incomer-1 off & no fault trip.
Incomer-2 On & in service.
Bus PT-1 unhealthy.
Bus PT-2 healthy.
This conditions are satisfy than contactor will be pick up & close
the breaker.
When fault (U/V) on bus side-B Than it checks,
Selector switch is on Auto Mode.
Incomer-2 off & no fault trip.
Incomer-1 On & in service.
Bus PT-2 unhealthy.
Bus PT-1 healthy.
This conditions are satisfy than contactor will be pick up & close
the breaker.
Closing For B/C-Manual mode
MANUAL MODE
TRIPPING CONDITIONS
Posted on March 26, 2013 under Auto changeover scheme
Manual Mode Tripping conditions-I/C-2
Trip selector switch on I/C-2
Incomer-1 On & in Service
Bus coupler On & in Service
After some time delay, I/C-2 will be trip.
Go to Next page
Go Back
Leave a comment
MANUAL MODE
Manual Mode
Closing conditions-I/C-2
Mode selector switch in Manual mode
Supply is Synchronize
Incomer-1 On & in Service
Bus coupler On & in Service
Trip selector switch on B/C
Trip selector switch on I/C-1
Go to Next page
Go Back
Leave a comment
GENERAL REQUIREMENT,
Posted on March 26, 2013 under Auto changeover scheme
General Requirement
Bus Pt for measuring Bus voltage & checking bus is healthy or
unhealthy.
Line Pt for measuring Line voltage & Synchronizing between two
sources.
Numerical relays with maximum BI-BO & breaker with maximum aux.
contacts.
Independent Mode
Closing conditions-I/C-1
Mode selector switch in independent mode
Bus PT-1 Unhealthy
Incomer-2 Off & no fault trip
Bus coupler Off & no fault trip
Independent Mode
Mode selector switch in independent mode
Bus PT-2 Unhealthy
Incomer-1 Off & no fault trip
Bus coupler Off & no fault trip
Closing For incomer-2-Ind. mode
Independent Mode
Closing conditions-B/C
Mode selector switch in independent mode
Bus PT-1 Unhealthy
Bus PT-2 Unhealthy
Incomer-1 Off & no fault trip
Incomer-2 Off & no fault trip
For Bus Coupler-Ind. mode
Go to Next page
Go Back
Leave a comment
INDEPENDENT MODE,MANUAL
MODE,AUTO
MODE,FEEDER REQUIRED
Posted on March 26, 2013 under Auto changeover scheme
INCOMER-1
ON
INCOMER-2
ON
BUSCOUPLER
OFF
INCOMER-1
ON
INCOMER-2
OFF
BUSCOUPLER
ON
INCOMER-1
OFF
INCOMER-2
ON
BUSCOUPLER
ON
Manual Mode
In this mode, When supply is Synchronize, Then Three Breakers
can close at the same time. But after some time delay, one
breaker will be Trip by using Trip Selector Switch.
For e.g.:I/C-1 & B/C are ON & if I/C-2 ON than I/C-1 will be trip after some time
delay. (if Trip selector switch is on I/C-1)
Auto Mode
This mode is only for Bus coupler.
If two incomer is On & Bus coupler is Off. If one incomer trip due
to under voltage. At that time B/C is On automatically.
Feeder Required
Incomer-1 with Line Pt-1
Incomer-2 with Line Pt-2
Bus Coupler
Bus Pt-1
Bus Pt-2
Outgoing Feeders