Ideal Transformer:: S P S P
Ideal Transformer:: S P S P
Ideal Transformer:
If the secondary coil is attached to a load that allows current to flow, electrical power is
transmitted from the primary circuit to the secondary circuit. Ideally, the transformer is
perfectly efficient; all the incoming energy is transformed from the primary circuit to the
magnetic field and into the secondary circuit. If this condition is met, the incoming
electric power must equal the outgoing power.
Practical Transformer
An ideal transformer is useful in understanding the working of a
transformer. But it cannot be used for the computation of the
performance of a practical transformer due to the non-ideal nature of
the practical transformer. In a working transformer the performance
aspects like magnetizing current, losses, voltage regulation, efficiency
etc are important. Hence the effects of the non-idealization like finite
Losses
An ideal transformer would have no losses, and would therefore be 100% efficient. In
practice energy is dissipated due both to the resistance of the windings (known as copper
loss), and to magnetic effects primarily attributable to the core (known as iron loss).
Transformers are in general highly efficient, and large power transformers (around 100
MVA and larger) may attain an efficiency as high as 99.75%. Small transformers such as
a plug-in "power brick" used to power small consumer electronics may be less than 85%
efficient.
Winding resistance
Current flowing through the windings causes resistive heating of the conductors.
Eddy currents
Induced currents circulate in the core and cause its resistive heating.
Stray losses
Not all the magnetic field produced by the primary is intercepted by the
secondary. A portion of the leakage flux may induce eddy currents within nearby
conductive objects such as the transformer's support structure, and be converted to
heat. The familiar hum or buzzing noise heard near transformers is a result of
stray fields causing components of the tank to vibrate, and is also from
magnetostriction vibration of the core.
Hysteresis losses
Each time the magnetic field is reversed, a small amount of energy is lost to
hysteresis in the magnetic core. The level of hysteresis is affected by the core
material.
Mechanical losses
The alternating magnetic field causes fluctuating electromagnetic forces between
the coils of wire, the core and any nearby metalwork, causing vibrations and noise
which consume power.
Magnetostriction
The flux in the core causes it to physically expand and contract slightly with the
alternating magnetic field, an effect known as magnetostriction. This in turn
causes losses due to frictional heating in susceptible ferromagnetic cores.
Cooling system
Large power transformers may be equipped with cooling fans, oil pumps or watercooled heat exchangers designed to remove the heat caused by copper and iron
losses. The power used to operate the cooling system is typically considered part
of the losses of the transformer.
Copper Losses The power lost in the form of heat in the armature winding of a generator
is known as COPPER LOSS. Heat is generated any time current flows in a conductor.
Copper loss is an I2R loss, which increases as current increases. The amount of heat
generated is also proportional to the resistance of the conductor. The resistance of the
conductor varies directly with its length and inversely with its cross- sectional area.
Copper loss is minimized in armature windings by using large diameter wire.
lower) voltage is produced across another portion of the same winding. For voltage ratios
not exceeding about 3:1, an autotransformer is less costly, lighter, smaller and more
efficient than a two-winding transformer of a similar rating.
By exposing part of the winding coils and making the secondary connection through a
sliding brush, an autotransformer with a near-continuously variable turns ratio can be
obtained, allowing for very small increments of voltage.
Instrument transformers
Current transformers
Current transformers used as part of metering equipment for three-phase 400 ampere
electricity supply
A current transformer is designed to provide a current in its secondary which is
accurately proportional to the current flowing in its primary.
Current transformers are commonly used in electricity meters to facilitate the
measurement of large currents which would be difficult to measure more directly.
Care must be taken that the secondary of a current transformer is not disconnected from
its load while current is flowing in the primary as in this circumstance a very high voltage
would be produced across the secondary.
Current transformers are often constructed with a single primary turn either as an
insulated cable passing through a toroidal core, or else as a bar to which circuit
conductors are connected.
Voltage transformers
Voltage transformers (also known as potential transformers) are used in the electricity
supply industry to measure accurately the voltage being supplied. They are designed to
present negligible load to the voltage being measured.
Impulse test;
Ratio test;
Insulation test;
Mega test;
No load loss test;
Full load loss test;
Open circuit test;
Short circuit test;
Double frequency test;
Etc.
.
some of these test are briefly explain below:
Impulse Test
This test is made to prove that the transformer insulation will
withstand voltage surges which may be caused by lightning
or switching; this includes insulation to ground, insulation
between turns and windings, and the flashover value of the
associated bushings. A high-voltage wave of standard values,
and approximating a lightning surge, is imposed on the unit
Through the open and short circuit test we can get the value of parameter of a
transformer. The parallel parameter values are found with no load connected to the
secondary (open circuit) and the series parameter values are found with the secondary
terminals shorted (short circuit). It is possible, for convenience in the lab, to make the
tests on either the primary or the secondary. Figure 2 shows the equivalents circuits for
the two tests. For the open circuit test, the series parameters are neglected for
convenience. This is reasonable since the voltage drops are across Req and Xeq are
normally small.
Figure . Equivalent circuits for tests. (a) Open circuit. (b) Short circuit.
Expressions for the non-ideal transformer parameters are derived from the equivalent
circuits shown in Figure 2. The results are Equations (1), (2), (3), and (4). All parameters
are expressed in terms of quantities measured in the open circuit and short circuit tests.
Figure . Connection for open circuit test and short circuit test
Insulation-Resistance Test
This is the often mentioned Megger test. It is meant to give some indication of the
condition of the insulation, and is often used in maintenance procedures. The connections
are the same as for the high-voltage test. The insulation resistance of a transformer
depends largely on the temperature and cleanliness and dryness of the windings.
Insulation resistance should be at least 1 megohm (I million ohms) for each 1000 volts of
test voltage. If it falls below this figure, presence of dirt or moisture may be indicated.
C. Leakage Current
This is the current we are really concerned about. It is a steady current leakage through or
over the insulation due to moisture, dirt, or other reasons. This test must be continued for
one minute or until the reading holds steady for 15 seconds. This assures us that the
capacitative and absorption currents have reached a static point. This will vary with the
equipment under test. Motors and transformers will take longer than average conductors.
Company Profile
Basic Information
Company Name:
Business Type:
Product/Service
(We Sell):
Number of Employees:
Main Markets:
North America
South America
Western Europe
Eastern Europe
Eastern Asia
Southeast Asia
Mid East
Africa
Oceania
US$1 Million - US$2.5 Million