Enertork TQ020
Enertork TQ020
Enertork TQ020
for TQ Actuators
Contents (1/2)
1. Cautious Notes
2. Usage
3. Storage
4. Configuration of TQ Series
5. Installation
5.2 Installations
6. Operation
10
12
17
17
18
18
19
19
Contents (2/2)
6.11 Customizing the actuator in LCD
20
26
27
7. Trouble Shooting
30
7.1 Jamming
30
31
33
8. Maintenance
36
8.1 Lubrication
36
36
36
9. Auxiliaries
37
37
39
40
43
44
46
47
1. CAUTIOUS NOTES
Please carefully read this manual before installing and operating TQ Actuator.
A full understanding of this manual will assist in installing the actuator in the most
effective manner.
Check name plate and confirm the actuator have been provided as described in the
specifications.
Before all wiring works including main power, absolutely disconnect all incoming
power and avoid outdoor wiring works in the rain.
Do electric wiring in accordance with wiring diagram. Incorrect wiring may cause
damages to actuator and/or valve.
Connect main power cables correctly to the motor terminals in matching phase.
Connect external earth located in the middle of cable entry boss in addition to the
ground connection inside the terminal compartment.
Connect power to space heaters if actuators are to be stored in a damp place for
long period prior to installation.
During final installation, ensure that all cable entries are correctly sealed to
prevent water or moisture from infiltrating.
Tightly close switch cover and terminal cover after wiring, adjusting and setting.
Loose fastening of the cover bolts may cause rain water infiltration.
Check and clean the mating faces and V-packings before closing the covers.
Do not manually operate actuator with devices other than installed handwheel.
Using additive force devices (bars, wrenches or the like) on the handwheel or
change lever may cause personal injury and/or damage to the actuator or valve.
Do setting and trial operation after bringing the actuator manually to the
intermediate position.
Do not have an unqualified person adjust the pre-set value or parameter without
any consultation or permission.
If the amplitude of vibration is over 0.5G in the site to install the actuator,
contact us for consulting appropriate solutions.
In case that any function is different to as described in this instruction,
please contact our technical engineer.
For performance improvement, the specifications of the actuator are subject to
change without any notice in advance.
- Intended blank -
2. USAGE
Our TQ series, driven by electric power, are quarter turn actuator, which
are available to 90 degree valves such as ball, butterfly and plug, and dampers.
TQ is the result of our accumulated technology over 20 years of experience
in valve actuation, offering customers the reliable and economical product
quality.
3. STORAGE
Storing actuators indoors is preferable.
If outdoor storage is unavoidable for long time, store actuators on a raised
platform under proper shelter or cover and connect wiring to space heaters
to avoid condensation in switch case.
A dry agent pack is put inside switch unit and take it out before trial
operation.
- Intended blank -
4.
4.
5. INSTALLATION
5.1 Orientation of installation of actuator
1)
2)
It
is
recommended
entries
face
handwheel
if
3)
the
faces
to
install
ground
front
actuator
orientation
for
easy
in
the
position
which
for
watertight
function
manual
operation
without
cable
and
interruption,
possible
010
020
040
060
080
120
200
300
105
115
130
145
145
145
145
145
5.2 Installations
1)
Check the dimension of actuator base and drive bushing with the dimension of
valve or damper bracket.
2)
Fit actuator to valve(or damper), under the conditions that actuator and valve
are at fully closed positions.
3)
After applying grease to damper stem and drive bushing properly, assemble
valve or damper with spring washers and bolts.
*CAUTION : KEEP PROCEDURE ABOVE & KEEP ALL THE PARTS CLEAN.
FOREIGN OBJECTS INSIDE MAY CAUSE DAMAGE TO BUSHING, O-RING &
OTHER PARTS.
- Intended blank -
6. OPERATION
6.1 Electrical connections and conduit
Before wiring, check one more time that the supply voltage details on the
nameplate are correct for this installation.
1)
Check
if
electrical
specification
like
as
power,
wiring
&
etc
are
correct or not.
2)
Do
the
control
3)
wiring
power,
Make
sure
actuator
4)
Make
6)
Plug
at
use
and
given
supply
electric
and
or
more
are
relay
and
diagram,
such
as
power,
ground.
power
operates
actuators
machined
delivery.
wiring
to
heater
for
keeping
inside
of
dry.
one
entries
the
wiring
that
two
Cable
per
internal
to
clean
sure
operate
5)
as
Please
one
actuator
only.
Can
not
simultaneously.
with
remain
two
the
PF
1"
taps
plug
as
it
and
is
if
sealed
user
with
doesn't
After the completion of wiring, clean the mating faces, put on the covers and
fasten the cover bolts tightly.
7)
When
user
certified
use
connection
actuator. This
suitable
ex-proof
actuator
is
ex-proof,
component
not
component,
as
which
our scope
factory
of
won't
is
please
at
make
least
supply, but
guaranty
the
sure
same
if
to
use
grade
with
user don't
performance
the
use
of
actuator.
Check the direction of rotation by pressing the open button. If the direction is
opposite, change 2 wires each other out of 3 power wires.
2)
After
rewiring
of
power
wires,
if
actuator
is
successful.
open
signal,
the
countermeasure
Then
check
the
rotating
direction
again
in
moves
to
order to
open
confirm
as
per
it again.
2)
10
In LCD screen
In status of lamps
11
Function of buttons
Place the selector switch in "OFF" position and press the "RESET" button
for over 2 seconds to enter setting mode.
2)
Place the arrow () in front of VIEW character in pushing "A" green button
and press "RESET" blue button.
Then, you can view the setting parameter by pushing "A" or "C" button.
Please refer to Fig. 2 in front page about button identification.
"Enter" in the flow schematics means "RESET" button on the operating panel.
- Intended blank -
12
You can check the rotating direction of motor in this mode, which is right or
left.
4) Check of stop condition in full close position
In this mode, you can check the method for stopping in the full close position,
which is limit or torque.
13
5)
6)
In this mode, you can check the method for stopping in the full close position,
which is limit or torque.
Check of the wiring error for power supply
"Auto Phase = Yes" means that the auto phase discriminator is effective,
and "Auto Phase = No" means that auto phase discriminator is not effective.
7)
You can check the current setting condition for Emergency Shut Down signal.
In "Close", the actuator moves to full close position for ESD signal.
In "Open", the actuator moves to full open position for ESD signal.
In "Stop", the actuator keeps as-is position for ESD signal.
In "Do not use", ESD signal will be neglected by actuator.
8) Check of maximum output mA value
14
You can check the type of line redundancy, which is single or dual type.
14) Check of the total running time of Motor
You can check the total cycle which was operated so far.
Total memory capacity is 100 million cycle.
You can check the total number which the limit switch in full open position
was touched so far.
The data will be restored only if stop condition is "Limit seating" in full open
position.
Total memory capacity is 100 million times.
You can check the total number which the limit switch in full close position
was touched so far.
The data will be restored only if stop condition is Limit seating in full close
position.
Total memory capacity is 100 million times.
You can check the total number which the torque switch in full open position
was touched so far.
The data will be restored only if stop condition is "Torque seating" in full
open position.
Total memory capacity is 100 million times.
15
You can check the total number which the torque switch in full close position
was touched so far.
The data will be restored only if stop condition is "Torque seating" in full
close position.
Total memory capacity is 100 million times.
You can check the total number which open torque fault occurred so far.
The data will be restored only if stop condition is "Limit seating" in full open
position.
Total memory capacity is 100 million times.
21) Check of the total number of torque fault in close position.
You can check the total number which close torque fault occurred so far.
The data will be restored only if stop condition is "Limit seating" in full close
position.
Total memory capacity is 100 million times.
You can check the total number which motor protection fault occurred so far.
Motor protection fault means that thermal, high temperature stopped motor.
Total memory capacity is 100 million times.
* Default Configuration Set
>
>
>
>
>
>
>
16
Upper two limit switches(RLS) are used for close and lower two limit
switches(LLS) are used for open.
RLS1 and LLS1 are used for limiting position and RLS2 and LLS2 are used for
control lamp in advance.
If push the limit switch, it sounds 'click' twice.
procedure
of
close
position
- Intended blank
Fig. 3 Schematic of switch cluster
2)
Connect circuit tester (DC, mA) to, referring wiring diagram attached inside,
signal output terminal (+, -) and ;
> in case tester reads the value between 3.4 and 4.6mA, set zero point of
transmitter or,
> in case tester reads the value outside 3.4 - 4.6mA, turn potentiometer shaft
with screwdriver until tester reads value between 3.4 - 4.6mA.
17
DIVISION
BOLT SIZE
TQ-010
TQ-020
M6 1P M8 1.25P
TQ-060
M12
1.75P
TQ-120
M14 2P
Max. allow.
range (mm)
18
28
35
43
"A"
18
Local control
19
2)
Remote control
2-1) Place the selector switch in REMOTE mode to permit command control
by a remote device.
Local open or close command will be non-effective in this mode.
2-2) After checking once more the cable connection compared to wiring diagram,
send required signals from a remote device for opening and closing of valve.
3-3) When you want to stop the actuator in the middle of operation, send stop
signal from a remote device.
Rotating the selector switch to the "OFF" position will automatically stop the
actuator regardless of the remote control signal.
3-4) Carefully check on/off of lamp during operation.
* You can choose View or Edit Mode by pushing Button "A"or "C"
* In Edit Mode, you can change and save each of parameters.
* In View Mode, you can only look into each of parameters.
* Start to input password from first digit and press button D to move
into next digit.
* Arabic number can be up and down by Button A and C.
* If Good P/W message is displayed in screen, you can enter to next mode
by button "D", and if Wrong P/W , you have to retry password input after
pressing button "D"
* The original set password would be 0000 when shipped
"Enter" in the flow schematics means "RESET" button on the operating panel.
20
21
4)
You can choose seating method, limit or torque, in full close position.
* The original set condition would be "Limit" seating when shipped.
5)
You can choose seating method, limit or torque, in full open position.
* The original set condition would be "Limit" seating when shipped.
6)
22
7)
* You can automatically save the potentiometer value when the open and
close position are detected in this mode.
After switching the selector switch to "LOC", move the actuator to full
close position.
When the actuator arrive in full close position, it starts for full open
position automatically.
Thus, during moving on, do not try to do any operation.
Through these procedures, the actuator will memorize the current
potentiometer value in full close position as the start point of Zero.
Also, in full open position as the start point of Span.
- Intended blank -
23
9)
Dead Time means that implementation of any signal is delayed when any
input signal is above dead band.
* It can be used in proportional operation or automatic positioning in profibus.
* The value is adjustable between 0.0 sec and 10.0 sec in 0.5 sec increment.
* Recommended value is above 1.0 sec.
* The original set value is 2.0 sec when shipped.
* You are sure to check the value before use.
11) Decision of Profibus accessibility
* In this mode, it can be decided whether you use Profibus remote control or
not.
* The original set condition would be "Disable" when shipped.
- Intended blank -
24
When using Profibus line redundancy, you can choose the type of control,
which is Single or Dual
* For adapting Line Redundancy in your control, the specification of Master and
configuration of system have to satisfy the requirement.
13) Password
Set -up
25
- Intended blank -
26
- Intended blank -
27
MASTER
TERMINATION
TERMINATION
28
29
7.
TROUBLE SHOOTING
7.1 Jamming
1) What's jamming
In case that actuator moves wrong direction due to negative phase
and moves over the travel limit, internal worm gear contacts the
stopper bolt and engaged each other. This is we call, jamming and
can not move actuator at all.
2)
How to solve
2-1)
2-2)
2-3)
Turn the
wheel.
2-4)
2-5)
2-6)
2-7)
change
lever
to
manual
position
until
bolt
and
50%
at
operate
open
by
hand
with
position.
original position.
- Intended blank -
30
Switching to manual
is not possible
Abnormal signal
indicator
Remote operation is
not possible
Cause
How to solve
Power on.
Check power.
Do wiring again.
Wiring is loosen.
Do wiring tightly.
Capacitor is damaged.
Jamming happens.
Actuator is undersized.
Do wiring again.
31
2)
Proportional
Control Unit
doesn't work
Output signal is
not detected
3)
Cause
How to solve
Cause
How to solve
4)
Others
Trouble
Cause
How to solve
Occasionally fail
32
In LED type
- Intended blank -
33
2) In LCD type
- Intended blank -
34
- Intended blank -
35
8. MAINTENANCE
After trial operation, check damages on paint and touch-up, if necessary.
Before fastening, check V-rings at the covers of switch unit and terminal unit
are rightly placed.
Use suitable cable gland and fasten tightly to secure IP68 class watertightness
and/or flame proofness.
8.1 Lubrication
Lubrication(EP R0 grade grease) is already done by factory and
generally no need to refill it again.
If required refill of grease, please fill the grease through the space of output
base after disassembling the output base.
and
it
is
36
9.
AUXILIARIES
This chapter shows the general electrical specification and the schematics for
sub assembly of electrical parts to help user do maintenance the actuator.
In LCD type
37
- Intended blank -
38
2)
39
40
41
42
2)
43
- Intended blank -
44
2)
- Intended blank -
45
Externals
Fig. 21 External View for TQ-010, 020, 040, 060, 080, 120
2) Internals
for TQ-010
for TQ-020/040/060/080/120
Fig. 22 Internal View
46
47
48