Instruction Manual

for TQ Actuators

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Contents (1/2)
1. Cautious Notes

2. Usage

3. Storage

4. Configuration of TQ Series

5. Installation

5.1 Orientation of installation of actuator

5.2 Installations

6. Operation

6.1 Electrical connections and conduit

6.2 Check of rotation direction

6.3 Driving the actuator

10

6.4 Viewing the existing in LCD type

12

6.5 Setting of the limit switch

17

6.6 Setting the potentiometer and transmitter

17

6.7 Stopper bolt setting

18

6.8 Setting of the torque switch

18

6.9 Trial operation by handwheel

19

6.10 Trial operation by motor power

19

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Contents (2/2)
6.11 Customizing the actuator in LCD

20

6.12 Customizing the actuator in LED type

26

6.13 Setting Profibus-DP

27

7. Trouble Shooting

30

7.1 Jamming

30

7.2 Diagnosis by operator

31

7.3 Self diagnosis

33

8. Maintenance

36

8.1 Lubrication

36

8.2 Regular operation

36

8.3 Regular check-up

36

9. Auxiliaries

37

9.1 General specification

37

9.2 Integral unit

39

9.3 Printed circuit board

40

9.4 Terminal board

43

9.5 Terminal block

44

9.6 Name of main parts

46

9.7 Drive bushing size

47

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

1. CAUTIOUS NOTES
Please carefully read this manual before installing and operating TQ Actuator.
A full understanding of this manual will assist in installing the actuator in the most
effective manner.
Check name plate and confirm the actuator have been provided as described in the
specifications.
Before all wiring works including main power, absolutely disconnect all incoming
power and avoid outdoor wiring works in the rain.
Do electric wiring in accordance with wiring diagram. Incorrect wiring may cause
damages to actuator and/or valve.
Connect main power cables correctly to the motor terminals in matching phase.
Connect external earth located in the middle of cable entry boss in addition to the
ground connection inside the terminal compartment.
Connect power to space heaters if actuators are to be stored in a damp place for
long period prior to installation.
During final installation, ensure that all cable entries are correctly sealed to
prevent water or moisture from infiltrating.
Tightly close switch cover and terminal cover after wiring, adjusting and setting.
Loose fastening of the cover bolts may cause rain water infiltration.
Check and clean the mating faces and V-packings before closing the covers.
Do not manually operate actuator with devices other than installed handwheel.
Using additive force devices (bars, wrenches or the like) on the handwheel or
change lever may cause personal injury and/or damage to the actuator or valve.
Do setting and trial operation after bringing the actuator manually to the
intermediate position.
Do not have an unqualified person adjust the pre-set value or parameter without
any consultation or permission.
If the amplitude of vibration is over 0.5G in the site to install the actuator,
contact us for consulting appropriate solutions.
In case that any function is different to as described in this instruction,
please contact our technical engineer.
For performance improvement, the specifications of the actuator are subject to
change without any notice in advance.
- Intended blank -

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2. USAGE
Our TQ series, driven by electric power, are quarter turn actuator, which
are available to 90 degree valves such as ball, butterfly and plug, and dampers.
TQ is the result of our accumulated technology over 20 years of experience
in valve actuation, offering customers the reliable and economical product
quality.

3. STORAGE
Storing actuators indoors is preferable.
If outdoor storage is unavoidable for long time, store actuators on a raised
platform under proper shelter or cover and connect wiring to space heaters
to avoid condensation in switch case.
A dry agent pack is put inside switch unit and take it out before trial
operation.
- Intended blank -

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

4.

CONFIGURATION of TQ SERIES (1/2)

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

4.

CONFIGURATION of TQ SERIES (2/2)

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

5. INSTALLATION
5.1 Orientation of installation of actuator
1)

It is convenient for maintenance that switch cover faces toward sky,


if possible.

2)

It

is

recommended

entries

face

handwheel
if
3)

the

faces

to

install

ground
front

actuator

orientation

for

easy

in

the

position

which

for

watertight

function

manual

operation

without

cable

and
interruption,

possible

Reserve the overhaul space for opening switch cover.


MODEL
Overhaul
Space (mm)

010

020

040

060

080

120

200

300

105

115

130

145

145

145

145

145

5.2 Installations
1)

Check the dimension of actuator base and drive bushing with the dimension of
valve or damper bracket.

2)

Fit actuator to valve(or damper), under the conditions that actuator and valve
are at fully closed positions.

3)

After applying grease to damper stem and drive bushing properly, assemble
valve or damper with spring washers and bolts.

*CAUTION : KEEP PROCEDURE ABOVE & KEEP ALL THE PARTS CLEAN.
FOREIGN OBJECTS INSIDE MAY CAUSE DAMAGE TO BUSHING, O-RING &
OTHER PARTS.
- Intended blank -

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6. OPERATION
6.1 Electrical connections and conduit
Before wiring, check one more time that the supply voltage details on the
nameplate are correct for this installation.
1)

Check

if

electrical

specification

like

as

power,

wiring

&

etc

are

correct or not.
2)

Do

the

control
3)

wiring
power,

Make

sure

actuator
4)

Make

6)

Plug

at

use

and

given

supply

electric

and
or

more

are

relay

and

diagram,

such

as

power,

ground.

power

operates

actuators

machined

delivery.

wiring
to

heater

for

keeping

inside

of

dry.

one

entries

the

wiring

that

two

Cable

per

internal

to

clean

sure

operate
5)

as

Please

one

actuator

only.

Can

not

simultaneously.

with

remain

two
the

PF

1"

taps

plug

as

it

and

is

if

sealed
user

with

doesn't

make sure of sealing the cable entries after finishing wiring.

After the completion of wiring, clean the mating faces, put on the covers and
fasten the cover bolts tightly.

7)

When

user

certified

use

connection

actuator. This
suitable
ex-proof

actuator

is

ex-proof,

component
not

component,

as

which

our scope

factory

of

won't

is

please
at

make

least

supply, but

guaranty

the

sure

same
if

to

use

grade

with

user don't

performance

the

use

of

actuator.

6.2 Check of rotating direction


In case of 3 phase actuator, operator should check the rotating
direction of actuator before electrical operation. If operating direction
is wrong, limit switches doesn't function and it results damage from
jamming or motor's overheating.
So, check rotating direction at first operating without fail.
Do checking at the mid-travel of actuator. Otherwise due to negative
connection of supply power, limit switches may not work at the full open
( or close ) position.
1)

Check the direction of rotation by pressing the open button. If the direction is
opposite, change 2 wires each other out of 3 power wires.

2)

After

rewiring

of

power

wires,

if

actuator

is

successful.

open

signal,

the

countermeasure

Then

check

the

rotating

direction

again

in

moves

to

order to

open
confirm

as

per

it again.

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.3 Driving the actuator


Before starting to commission the actuator, check that the actuator is installed
correctly on the valve and main power is on.
1)

Place the selector switch in "LOC" position.

2)

Press the OPEN or CLOSE button in complying with desired position.


Confirm whether the direction is correct or not.

Function of buttons and lamps in LED type

Fig. 1 Operating panel in LED type

10

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Function of buttons and lamps in LCD type

Fig. 2 Operating panel in LCD type


Function of selector swtch (Common in LED and LCD type)

In LCD screen

In status of lamps

11

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Function of buttons

6.4 Viewing the existing setting in LCD type


All the existing setup data can be viewed on the LCD screen by following a
simple step-by-step dialogue.
All other actuator parameters are factory-set either in accordance with
Morgan Korea standard set of default values or the requirements specified with
the purchase order. Reconfirm these preconfigured setting before placing the
actuator into service because the requirements of the application may have
changed after the manufacture of the actuator.
1)

Place the selector switch in "OFF" position and press the "RESET" button
for over 2 seconds to enter setting mode.

2)

Place the arrow () in front of VIEW character in pushing "A" green button
and press "RESET" blue button.

Then, you can view the setting parameter by pushing "A" or "C" button.
Please refer to Fig. 2 in front page about button identification.
"Enter" in the flow schematics means "RESET" button on the operating panel.

- Intended blank -

12

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Fig. 7 Schematics for viewing configuration


3)

Check of motor rotating direction (Option)

You can check the rotating direction of motor in this mode, which is right or
left.
4) Check of stop condition in full close position

In this mode, you can check the method for stopping in the full close position,
which is limit or torque.

13

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

5)

6)

Check of stop condition in full open position

In this mode, you can check the method for stopping in the full close position,
which is limit or torque.
Check of the wiring error for power supply

"Auto Phase = Yes" means that the auto phase discriminator is effective,
and "Auto Phase = No" means that auto phase discriminator is not effective.
7)

Check of behavior for ESD signal

You can check the current setting condition for Emergency Shut Down signal.
In "Close", the actuator moves to full close position for ESD signal.
In "Open", the actuator moves to full open position for ESD signal.
In "Stop", the actuator keeps as-is position for ESD signal.
In "Do not use", ESD signal will be neglected by actuator.
8) Check of maximum output mA value

You can check the maximum output mA value which is set.


9) Check of Minimum output mA value

You can check the minimum output mA value which is set.


10) Check of Dead Band value

You can check the dead band value which is set.


11) Check of Dead Time value

You can check the dead time value which is set.


12) Check of Profibus availability

You can check whether profibus communication can be used or not.

14

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

13) Check of the type of line redundancy in profibus communication

You can check the type of line redundancy, which is single or dual type.
14) Check of the total running time of Motor

You can check the total time which motor ran.


###H##M##S means Hours, Minutes and Seconds.
Total memory capacity is about 876,000 hours, equal to 100 years, in case
the memorized time unit is seconds.
15) Check of the total cycle

You can check the total cycle which was operated so far.
Total memory capacity is 100 million cycle.

16) Check of the total touching number of limit in open position.

You can check the total number which the limit switch in full open position
was touched so far.
The data will be restored only if stop condition is "Limit seating" in full open
position.
Total memory capacity is 100 million times.

17) Check of the total touching number of limit in close position.

You can check the total number which the limit switch in full close position
was touched so far.
The data will be restored only if stop condition is Limit seating in full close
position.
Total memory capacity is 100 million times.

18) Check of the total touching number of torque in open position.

You can check the total number which the torque switch in full open position
was touched so far.
The data will be restored only if stop condition is "Torque seating" in full
open position.
Total memory capacity is 100 million times.

15

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

19) Check of the total touching number of torque in close position.

You can check the total number which the torque switch in full close position
was touched so far.
The data will be restored only if stop condition is "Torque seating" in full
close position.
Total memory capacity is 100 million times.

20) Check of the total number of torque fault in open position.

You can check the total number which open torque fault occurred so far.
The data will be restored only if stop condition is "Limit seating" in full open
position.
Total memory capacity is 100 million times.
21) Check of the total number of torque fault in close position.

You can check the total number which close torque fault occurred so far.
The data will be restored only if stop condition is "Limit seating" in full close
position.
Total memory capacity is 100 million times.

22) Check of Total Number Of Motor Protection Faults.

You can check the total number which motor protection fault occurred so far.
Motor protection fault means that thermal, high temperature stopped motor.
Total memory capacity is 100 million times.
* Default Configuration Set
>
>
>
>
>
>
>

Full Open stopped by "Position limit" : Open limit seating


Full Close stopped by "Position limit" : Close limit seating
Switch activated by "Inching mode"-non maintained control
Clockwise to close (CW)
Phase to "Auto Phase=Yes" : Auto phase discriminator is effective
ESD is "Do not use". That is, ESD signal is neglected.
Password is 0000 (4zero)
- Intended blank -

16

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.5 Setting of the limit switch


1)
2)
3)

Upper two limit switches(RLS) are used for close and lower two limit
switches(LLS) are used for open.
RLS1 and LLS1 are used for limiting position and RLS2 and LLS2 are used for
control lamp in advance.
If push the limit switch, it sounds 'click' twice.

>> Setting procedure of close position


(1) Turn the lever for manual operation and turn hand wheel to move
actuator to full close position.(Refer to STOPPER BOLT SETTING)
(2) Turn the close cam until the micro switch is on, by pushing the
slot of cam by using driver(-)
(3) Turn the indicator
dial plate to 0% or close position and fixing
the bolt.
(4) Confirm the setting by electrical operation of actuator (0100%)
>> Setting procedure of open position
Carry out same manner of setting

procedure

of

close

position

- Intended blank
Fig. 3 Schematic of switch cluster

6.6 Setting the potentiometer and transmitter (R/I converter)


Optional parts
1)

Fully close valve.

2)

Connect circuit tester (DC, mA) to, referring wiring diagram attached inside,
signal output terminal (+, -) and ;
> in case tester reads the value between 3.4 and 4.6mA, set zero point of
transmitter or,
> in case tester reads the value outside 3.4 - 4.6mA, turn potentiometer shaft
with screwdriver until tester reads value between 3.4 - 4.6mA.

* When turing potentiometer shaft with screwdriver, tightly grip gear A


with another hand so that it should not rotate.
3) Set zero point of transmitter, fully open valve and set span.
Repeat this procedure 2 -3 times for precise setting.

17

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.7 Stopper bolt setting


1) For setting position limit switches, loose the nut which are engaged
with stopper bolts and turn stopper bolt to pull out within the
ranges of following.
2) Move actuator full close position by manual. Once cam hit the lever
of limit switch to trip, stop manual operation. Then turn close
stopper bolt to go forward until it don't not go further (End of
stopper bolt contacts the 2nd worm wheel).
After that turn close stopper bolt to come out by 2 threads and
tighten the loosen nut.
3) Do as per same with above for open stopper bolt.
Maximum range of stopper bolt setting

DIVISION

BOLT SIZE

TQ-010

TQ-020

M6 1P M8 1.25P

TQ-060
M12
1.75P

TQ-120

M14 2P

Max. allow.
range (mm)

18

28

35

43

"A"

Fig. 4 Schematic of stopper bolts


CAUTION : Please pay an attention that the worm wheel is net out of range
of matching the worm by setting within above range "A".

6.8 Torque switch setting (Except TQ-010)


1)

Torque Switches are set by factory before delivery, therefore no


need to set the switches again.
2) When trip the torque switch, check the valves or dampers.
3) No guaranty in performance if this switches are set again.
4) If required resetting of the torque switches, please consult with our
design dept.
- Intended blank -

18

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.9 Trial operation by handwheel


1)

Turn the change lever toward manual position until


change lever
stands perpendicularly.
If lever does not stand perpendicularly, pull over it again turning
handwheel slowly. This require about 10 20Kg force.
2) Confirm the direction of manual operation
- Clockwise is close direction and counter clockwise is open
direction.
3) No need to position the change lever to original for electrical
operation by manual. Once electrical power is on, the change lever
automatically return its original position by internal clutch
mechanism.
* CAUTION : USING CHEATER BAR OR THE LIKE ON HANDWHEEL MAY
CAUSE DAMAGE TO THE ACTUATOR AND/OR VALVE

6.10 Trial operation by motor power


Before switching power on to the actuator, check that the supply voltage
details on the nameplate are correct for this installation. An incorrect supply
connected to the actuator terminals could cause severe or permanent damage
to the electrical or electronic components in the actuator.
Apply power to the actuator and carefully check that it has been set up and
configured correctly for its intended application before operating the actuator.
The operation mode is automatically changed from manual to power by just
energizing the motor.
1)

Local control

1-1) Place the selector switch in LOCAL mode.


1-2) In order to open or close the valve, push open "A" or close "C" button on
the operating panel.
Repeat this 3 ~ 4 times to both directions.
1-3) If you want to stop the actuator in the middle of opening or closing, just
push the STOP button or shift the selector switch to OFF.
1-4) Carefully check on/off of lamp during operation.
- Intended blank -

19

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2)

Remote control

2-1) Place the selector switch in REMOTE mode to permit command control
by a remote device.
Local open or close command will be non-effective in this mode.
2-2) After checking once more the cable connection compared to wiring diagram,
send required signals from a remote device for opening and closing of valve.
3-3) When you want to stop the actuator in the middle of operation, send stop
signal from a remote device.
Rotating the selector switch to the "OFF" position will automatically stop the
actuator regardless of the remote control signal.
3-4) Carefully check on/off of lamp during operation.

6.11 Customizing the actuator in LCD type


The actuator setting can be customized. That is, the default setting can be
changed and the purchased options can be re-configured.
1)

Original display for setting mode


When shifting the selector switch to OFF and pressing the RESET button
for 2 seconds, you can enter into setting mode.

* You can choose View or Edit Mode by pushing Button "A"or "C"
* In Edit Mode, you can change and save each of parameters.
* In View Mode, you can only look into each of parameters.

2) Entering into Edit Mode


After choosing EDIT, press button "D" to move into Input P/W screen.

* Start to input password from first digit and press button D to move
into next digit.
* Arabic number can be up and down by Button A and C.
* If Good P/W message is displayed in screen, you can enter to next mode
by button "D", and if Wrong P/W , you have to retry password input after
pressing button "D"
* The original set password would be 0000 when shipped

When password is correct

When password is incorrect

"Enter" in the flow schematics means "RESET" button on the operating panel.

20

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Fig. 5 Schematics for customizing the parameters


3)

Setting of motor rotating direction (Option)

* You can decide the rotating direction of motor in this mode.


* The original set direction would be "Right" when shipped.

21

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

4)

Decision of the seating method in full close position

You can choose seating method, limit or torque, in full close position.
* The original set condition would be "Limit" seating when shipped.
5)

Decision of the seating method in full open position

You can choose seating method, limit or torque, in full open position.
* The original set condition would be "Limit" seating when shipped.
6)

Decision of behavior for Emergency Shutdown signal

When ESD signal detected, the actuator moves on corresponding to pre-set


condition. In "Close", the actuator move to full close position and "Open" to
full open position. In "Stop", the actuator keeps as-is position.
Also in "Do not use", ESD signal will be neglected by the actuator.
* The original set condition would be "Do not use" when shipped.

22

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

7)

Fine adjustment of Output mA in zero and span

* In this mode, you can adjust precisely the Output mA.


Max mA can be adjusted from 254 to zero on the base of 0~23mA and 5V.
Min mA can be adjusted from 254 to zero on the base of 0~23mA and 5V.
However, as the values are optimized by manufacturer, you are strongly
advised not to adjust them, except for inevitability.
8) Automatic memory of potentiometer value

* You can automatically save the potentiometer value when the open and
close position are detected in this mode.
After switching the selector switch to "LOC", move the actuator to full
close position.
When the actuator arrive in full close position, it starts for full open
position automatically.
Thus, during moving on, do not try to do any operation.
Through these procedures, the actuator will memorize the current
potentiometer value in full close position as the start point of Zero.
Also, in full open position as the start point of Span.
- Intended blank -

23

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9)

Adjustment of Dead Band value

Dead Band is an area of a signal range or band where no action occurs.


* It can be used in proportional operation or automatic positioning in profibus.
* The value is adjustable between 0% and 20% in 1% increment.
* Recommended value is above 3%.
* The original set value is 3% when shipped.
* You are sure to check the value before use.
10) Adjustment of Dead Time value

Dead Time means that implementation of any signal is delayed when any
input signal is above dead band.
* It can be used in proportional operation or automatic positioning in profibus.
* The value is adjustable between 0.0 sec and 10.0 sec in 0.5 sec increment.
* Recommended value is above 1.0 sec.
* The original set value is 2.0 sec when shipped.
* You are sure to check the value before use.
11) Decision of Profibus accessibility

* In this mode, it can be decided whether you use Profibus remote control or
not.
* The original set condition would be "Disable" when shipped.
- Intended blank -

24

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

12) Set-up of Profibus line redundancy

When using Profibus line redundancy, you can choose the type of control,
which is Single or Dual
* For adapting Line Redundancy in your control, the specification of Master and
configuration of system have to satisfy the requirement.
13) Password

Set -up

* You can change and save a password in this mode.


* When you press button "D" in last digit, new password will be restored.
- Intended blank -

25

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.12 Customizing the actuator in LED type

- Intended blank -

26

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

6.13 Setting Profibus-DP


Morgan Korea's TM Series offer Profibus-DP of network options.
Profibus is based on RS 485 communication. Particular cares should be taken
when terminating a shielded twisted pair cable for Profibus in a control
network. Avoid any inappropriate finishing such as nicks or cuts in the
insulation of data communication cables, since this may result in inadvertent
ground connection.
1)

General data for Profibus-DP

- Intended blank -

27

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2) Wiring the bus cable

MASTER

TERMINATION

TERMINATION

Fig. 6 Schematic of Profibus Connection

3) Allocating the bus address


You can allocate the bus address to the actuators installed in system by
mixing the numbers of S/W2 and S/W3.

Fig. 7 Profibus Card

28

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

4) Symbol and address

Fig. 8 Table of Symbol and Address in switch


Example :
If you choose "5" of Symbol in S/W 2 and "E" in S/W 3,
the selected addresses are 80 and 14 respectively.
Thus, the allocated bus address will be 94, which equals 80 plus 14.
- Intended blank -

29

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

7.

TROUBLE SHOOTING

7.1 Jamming
1) What's jamming
In case that actuator moves wrong direction due to negative phase
and moves over the travel limit, internal worm gear contacts the
stopper bolt and engaged each other. This is we call, jamming and
can not move actuator at all.
2)

How to solve

2-1)

Off the power.

2-2)

If jamming is happened during close, turn close stopper bolt to


come out by about 2 threads.
(If during open, turn open stopper bolt to come out by about 2
threads.)

2-3)

Turn the
wheel.

2-4)

If jamming is happened during open, procedure is same


close, but turn hand wheel to clockwise by manual.

2-5)

Turn hand wheel to counterclockwise


Check rotating direction again.

2-6)

If everything is O.K, fix the stopper


(Refer to "Stopper bolt setting")

2-7)

Close switch cover with bolts.

change

lever

to

manual

position

until
bolt

and

50%
at

operate

open

by

hand

with

position.

original position.

- Intended blank -

30

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

7.2 Diagnosis by operator


1)

110/220V AC 1 PH , 380/440 AC 3 PH STANDARD SPEC


Trouble

Actuator don't work


at all

Torque switch works


abnormally

Switching to manual
is not possible

Abnormal signal
indicator

Remote operation is
not possible

Cause

How to solve

Check if power is on.

Power on.

Check if voltage is too low.

Check power.

Motor and supplied power is different.

Check motor power and supplied power

Wiring is not correct.

Do wiring again.

Wiring is loosen.

Do wiring tightly.

Coil of motor is damaged.

Change the motor

Thermostat of motor trips.


(High duty cycle)

Lower around temperature and duty cycle.

Capacitor is damaged.

Change the capacitor.

Limit switch works.

Refer to "Limit s/w setting"

Torque switch works.

Check valve and torque value.

Jamming happens.

Check rotating direction per instruction.

Actuator is undersized.

Select again as per real required torque.

Foreign material between valve seat


and disc.

Check and change the valve.

Stopper bolt is set prior to limit switch.

Reset the stopper bolt.

Lever is not fully pulled over.

Fully pull over the lever.

Lever is not pulled over because of


jamming.

Disengage the jamming.

Clutch of lever and handle is engaged


each other.

Turning handle slowly, pull over lever.

Damage of signal indicator(option).

Change the signal LED unit.

Damage of micro switches

Change the micro switches.

Setting of limit switch is wrong.

Do setting switch again.

Stopper bolt is set prior to limit switch.

Do setting stopper bolt again.

Wiring is not correct.

Do wiring again.

Switch is not at remote position.

Put the switch at remote position.

31

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2)

Proportional Control Unit Option


Trouble

Proportional
Control Unit
doesn't work

Output signal is
not detected

3)

Cause

How to solve

Input signal is fault.

Check input signal.

R/I Convertor signal is failed.

Check the resistance of potentiometer and


change it if resistance is not correct.

Proportional Control Unit card


is damaged.

Change the Proportional Control Unit


card.

R/I Convertor signal is failed.

Check the resistance of potentiometer and


change it if resistance is not correct.

Proportional Control Unit card


is damaged.

Change the Proportional Control Unit


card.

R/I converter option


Trouble

Cause

How to solve

R/I converter signal is failed.


Output signal is
not detected
R/I converter is damaged.

4)

Check the resistance of potentiometer and


change it if resistance is not correct.
Change the R/I converter.

Others
Trouble

Cause

How to solve

Remote operation is not


possible

Switch is not at remote position.

Put the switch at remote position.

Occasionally fail

Wring is loosen or switch is not


contacted.

Change the switch and check wiring.

Proportional Control Unit


fails occasionally

Thermostat is on and off due to


motor overheated.

Lower duty cycle.

Proportional Control Unit fail


and return to normal

Defect of wire, high volts & noise

Remove the cause.

Output signal from


Proportional Control Unit is
unstable

Defect of wire, high volts & noise

Remove the cause.

R/I converter signal fails


occasionally

PIU is not contacted tightly

Check the resistance of


potentiometer and change the PIU.

Output signal from R/I


converter is unstable

Defect of wire, high volts & noise

Remove the cause.

Valve torque is sharply


increased

Foreign material in valve.

Check and change the valve.

Resistance of coil is sharply


increased

Humidity or gas invade in heater.

Check and change the heater.

32

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

7.3 Self diagnosis


1)

In LED type

- Intended blank -

33

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2) In LCD type

- Intended blank -

34

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

- Intended blank -

35

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

8. MAINTENANCE
After trial operation, check damages on paint and touch-up, if necessary.
Before fastening, check V-rings at the covers of switch unit and terminal unit
are rightly placed.
Use suitable cable gland and fasten tightly to secure IP68 class watertightness
and/or flame proofness.

8.1 Lubrication
Lubrication(EP R0 grade grease) is already done by factory and
generally no need to refill it again.
If required refill of grease, please fill the grease through the space of output
base after disassembling the output base.

8.2 Regular operation


Electrical power always should be supplied to actuator
recommended to operate actuator once a month.

and

it

is

8.3 Regular check-up


In order to use actuator for long time, regular maintenance once a
year is required. Pleas check operating condition, corrosion, painting
& etc.
- Intended blank -

36

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.

AUXILIARIES
This chapter shows the general electrical specification and the schematics for
sub assembly of electrical parts to help user do maintenance the actuator.

9.1 General specification


In LED type

In LCD type

37

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

1) Control circuit is isolated from the remote signal by the opto-isolater so


that it might not be affected by any disturbance.
2) Two operating modes of INCHING / HOLD. If there is no any requirement
when ordering, the actuator will be shipped as INCHING mode.
If you want HOLD mode, please connect and of terminal by using
jumper line.
3) Transformer

4) Please use Magnetic contactor and Fuse as followings.

- Intended blank -

38

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.2 Integral unit


1)

For LED type

Fig. 9 Integral unit for LED type

2)

For LCD type

Fig. 10 Integral unit for LCD type

39

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.3 Printed circuit board


1)

For LED type

Fig. 11 Control board for LED type

Fig. 12 Power board for LED type

40

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Fig. 13 Terminal board for LED type


2)

For LCD type

Fig. 14 Control board for LCD type


- Intended blank -

41

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

Fig. 15 Logic board for LCD type

Fig. 16 Power board for LCD type


- Intended blank -

42

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.4 Terminal board


1)

For LED type

Fig. 17 Terminal board for LED type

2)

For LCD type

Fig. 18 Terminal board for LCD type


- Intended blank -

43

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.5 Terminal block


1)

For LED type

Fig. 19 Terminal blocks for LED type

- Intended blank -

44

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

2)

For LCD type

Fig. 20 Terminal blocks for LCD type

- Intended blank -

45

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.6 Name of main parts


1)

Externals

Fig. 21 External View for TQ-010, 020, 040, 060, 080, 120
2) Internals

for TQ-010

for TQ-020/040/060/080/120
Fig. 22 Internal View

46

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

9.7 Drive Bushing Size

Fig. 23 Bushing drawing


Caution : Be careful of position of key way during machining.
- Intended blank -

47

TQ ELECTRIC ACTUATOR - INSTRUCTION MANUAL (09/2008 v-1.0)

For further more information about our products or service,


please do not hesitate to contact us.

Head Office & Factory :


#64-6, Ogye-1Ri, Neungseo-Myun, Yeoju-Gun, Gyunggi-Do, Korea
Tel: + 8 2 - 3 1 - 8 8 1 - 5 8 4 0 /5
Fax: + 8 2 - 3 1 - 8 8 1 - 5 8 6 0
Seoul Office :
#301, Sunil Bldg. 696-17, Yeoksam-Dong, Kangnam-Gu, Seou, Korea
Tel: + 8 2 - 0 2 - 5 5 5 - 0 8 8 3
Fax: + 8 2 - 2 - 5 5 6 - 3 0 2 6
Web Site : http://www.enertork.com
E-mail : [email protected]

48

You might also like