SAIC-M-1003Location, Depth of TrenchBoreholes & Elevation For Types I - V Fences Inspection
SAIC-M-1003Location, Depth of TrenchBoreholes & Elevation For Types I - V Fences Inspection
SAIC-M-1003Location, Depth of TrenchBoreholes & Elevation For Types I - V Fences Inspection
SAIC NUMBER
SAIC-M-1003
WBS / BI / JO NUMBER
EQUIPMENT ID NUMBER(S)
EQUIPMENT DESCRIPTION
REV. NO.
REFERENCE
A1
SAES-A-114
Sec. 7.1
A2
SAES-A-114
Sec. 7.2.1
A3
SAES-A-114
Sec. 7.2.3
A4
A5
A6
Special Gate Posts over 175mm O.D. shall have foundations minimum
300mm diameter and 1320mm deep for fence types I, II, III and V.
A7
A8
Drawing
AC-036680
Sht. NO. 1
A9
Type VI fencing posts shall be painted with adhesive, wrapped with one
wrap of pipe wrapping, and painted with a top coat of adhesive to extend
25mm above top of concrete and 125mm into the concrete.
Drawing
AC-036681
Sht. NO. 1
A10
Type VI, corner and gate posts shall have foundations a minimum of
300mm diameter and 650mm into the ground from grade elevation.
A11
A12
A13
Saudi Aramco Security Fencing only shall have fence anchor blocks
minimum 300mm deep and 150mm wide cast from post froundation to
post foundation with the top surface flush with grade elevation.
Drawing
AC-036680
Sht. NO. 1
A14
One 8mm reinforcing bar shall run the full length of the anchor block at
the block centerline with 75mm's clearance at the ends for concrete.
Drawing
AC-036680
Sht. NO. 1
Page 1 of 3
PLANT NO.
TRAVEL TIME
SYSTEM ID.
QUANTITY INSP.
CIVIL-
CONTRACTOR / SUBCONTRACTOR
ACCEPTANCE CRITERIA
QR NUMBER
18-May-05
EQPT CODE
ITEM
No.
DATE APPROVED
Drawing
AC-036680
Sht. NO. 1
Drawing
AC-036680
Sht. NO. 1
Drawing
AC-036680
Sht. NO. 1
Drawing
AC-036680
Sht. NO. 1
Drawing
AC-036681
Sht. NO. 1
Drawing
AC-036681
Sht. NO. 1
Drawing
AC-036681
Sht. NO. 1
PASS
FAIL
N/A
RE-INSP DATE
ITEM
No.
A15
SAIC NUMBER
SAIC-M-1003
WBS / BI / JO NUMBER
ACCEPTANCE CRITERIA
REFERENCE
One 8mm reinforcing bar shall run the full length of the anchor block
along the block centerline with 75mm's clearance at the ends, 100mm
below the top of concrete elevation with triangular projections for
connecting the chain link fabric 150mm's from the ends and spaced at
600mm on center in between. Turn downs shall exist at the ends,
150mm's long.
Drawing
AC-036680
Sht. NO. 1
B1
The top of the fence shall follow the profile of the ground.
Drawing
AA-036677
Sht. NO. 1
B2
Drawing
AA-036677
Sht. NO. 1
B3
The fences' wire fabric shall extend from 25mm clear of grade elevation
to 2425 mm's up from grade elevation.
Drawing
AA-036677
Sht. NO. 1
B4
Seven (7) bar bands shall be used to connect the fences wire fabric at
corner posts, line posts, end and gate posts. They shall be spaced at
360mm's on center on corner end and gate posts and 350mm on line
posts.
Drawing
AA-036678
Sht. NO. 1
B5
Security Fencing types II and III shall have double corner extension arms
with 6 strands of barbed wire on the tops of all corner posts.
Drawing
AA-036678
Sht. NO. 1
B6
Security Fencing types II and III shall have double extension arms with 6
strands of barbed wire on the tops of all line posts.
Drawing
AA-036678
Sht. NO. 1
B7
Security Fencing types II and III gate posts shall have three (3) type I
bands for connecting the barbed wire at top.
B8
Security Fencing Type II shall have double corner post extensions for
connecting the barbed wire.
B9
Type IV shall have single corner and line post extensions for supporting
3 strands of barbed wire at 450 from horizontal.
B10
B11
B12
Gates shall be provided with at least 2 hinges per leaf, more as required
by IFC Drawings or specifications.
B13
Gate leaves shall be provided with latches, fork catch bars, lock keepers,
strecher bars for wire fabric, plunger rods, hook bolts and diagonal truss
rods.
Drawing
AB-036679
Sht. NO. 1
B14
Walk gates shall have a top rail and any barbed wire shall be continuous
over the top of the walk gate.
Drawing
AB-036679
Sht. NO. 1
Page 2 of 3
Drawing
AA-036678
Sht. NO. 1
Drawing
AA-036678
Sht. NO. 1
Drawing
AA-036678
Sht. NO. 1
Drawing
AA-036678
Sht. NO. 1
Drawing
AA-036678
Sht. NO. 1
Drawing
AB-036679
Sht. NO. 1
DATE APPROVED
QR NUMBER
18-May-05
Civil
CONTRACTOR / SUBCONTRACTOR
PASS
FAIL
N/A
RE-INSP DATE
SAIC NUMBER
DATE APPROVED
SAIC-M-1003
WBS / BI / JO NUMBER
ITEM
No.
ACCEPTANCE CRITERIA
REFERENCE
QR NUMBER
18-May-05
Civil
CONTRACTOR / SUBCONTRACTOR
PASS
FAIL
N/A
RE-INSP DATE
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-A-114 -- Excavation and Backfill, 28 April 2004
2- AC-036681, Sht. 1 -- Perimeter Fencing for Onshore Helipads, Footing Details, Type IV Fence, 1 June 1992
3- AC-036680, Sht. 1 -- Saudi Aramco Security and General Fencing, Footing Details, 3 March 1997
4- AA-036679, Sht. 1 -- Saudi Aramco Security and General Fencing, Gate Details, 4 February 1990
5- AA-036678, Sht. 1 -- Saudi Aramco Security and General Fencing, Post and Fabric Details, 4 January 1990
6- AB-036677, Sht. 1 -- An Overview (Architectural), Saudi Aramco Security and General Purpose Fencing, 2 March 1990
Contractor / Third-Party
Saudi Aramco
Construction Representative*
PMT Representative
T&I Witnessed
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
T&I Witnessed
QC Record Reviewed
Work Verified
QC Inspector
PID Representative
Performed Inspection
QC Supervisor
Name, Organization,
Initials and Date:
Y = YES
Page 3 of 3
N = NO F = FAILED