Specification Sheet

Pulse Input Source and Isolated Modules


The Pulse Input Source and Pulse Input Isolated
Modules plug into a ROC300-Series Remote
Operations Controller or FloBoss 407 Flow Manager
and are used for monitoring the pulses from pulsegenerating devices. Each module can accommodate
one pulse input (PI).

The source module provides a source voltage for dry


relay contacts or for an open-collector solid-state
switch. The isolated module accepts an external
voltage from a powered device while maintaining
electrical isolation from the ROC or FloBoss power
circuits.

Both types of modules provide an LED to show when


the input is active and use a scaling resistor for scaling
the input range. Input pulses are counted by a 16-bit
counter.

Field wiring connections are made through a separate


terminal block, which plugs in next to the module. This
design facilitates replacement of the module without
disconnecting field wiring.

Source Module Specifications


FIELD WIRING TERMINALS

INPUT (continued)

A: Not used
B: Pulse input/source voltage
C: Common

Source Current: Determined by source voltage (Vs),


loop resistance (Rl) and scaling resistor (Rs):
I = (Vs - 1)/(2.2K + Rl + Rs)

INPUT

POWER REQUIREMENTS

Type: Contact sense.


Input Signal
Low-speed: 10 Hz.
High-speed: 12 kHz
Source Voltage: 11 to 30 V dc.
Range: Inactive, 0 to 0.5 mA. Active, 3 to 12 mA.

Source Input: 11 to 30 V dc, 6 mA maximum from ROC


power suppler I/O converter card.
Module: 4.9 to 5.1 V dc, 1 mA maximum (supplied by
ROC or FloBoss).
INPUT ISOLATION
Not isolated. Terminal C tied to power supply common.
Rs=10
PI SRC
A

N/C

Vs

2.2K

Rs=10
PI ISO
N/C
A

SENSITIVE

2.2K

+
-

C
DOC0034C

Simplified Schematics
Typical Pulse Input Module

Remote Automation Solutions


Website: www.EmersonProcess.com/flow

D301011X012
D301216X012

STATIC

2:PI
Page 2

Specification Sheet

Isolated Module Specifications


FIELD WIRING TERMINALS

POWER REQUIREMENTS

A: Not used
B: Positive pulse input
C: Negative pulse input

4.9 to 5.1 V dc, 2 mA maximum (supplied by ROC or


FloBoss).
INPUT ISOLATION

INPUT
Type: Two-state, current-pulse sense.
Range: Inactive; 0 to 0.5 mA. Active; 3 to 12 mA.
Input Current: Determined by input voltage (Vi), loop
resistance (Rl) and scaling resistor (Rs):
I = (Vi - 1)/(2.2K + Rl + Rs)

Insulation: 100 M minimum, input to output, and


input or output to case.
Voltage: 4,000 V ac (RMS) minimum, input to
output.
Capacitance: 6 pF typical, input to output.

Common Specifications
INPUT

CASE

Scaling Resistor (Rs): 10 supplied (see Input


Current equation to compute other value).
Frequency Response: 0 to 12 KHz maximum, 50%
duty cycle.
Input Filter: Single-pole low-pass, 10 microsecond
time constant.

Solvent-resistant thermoplastic polyester, meets


UL94V-0.

VIBRATION
20 Gs peak or 0.06 in. double amplitude, 10 to 2,000
Hz, per MIL-STD-202, method 204, condition F.
MECHANICAL SHOCK
1500 Gs 0.5 millisecond half sine per MIL-STD-202,
method 213, condition F.
WEIGHT

Dimensions are 15 mm D by 32 mm H by 43 mm W
(0.60 in. D by 1.27 in. H by 1.69 in. W), not including
pins.
ENVIRONMENTAL
Meets the environmental specifications of the ROC
or FloBoss unit in which the module is installed,
including temperature, humidity, and transient
protection.
APPROVALS
Approved by CSA for hazardous locations Class I,
Division 2, Groups A, B, C, and D.

37 grams (1.3 oz.).

FloBoss is a mark of one of the Emerson Process Management companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other
marks are the property of their respective owners.
While this information is presented in good faith and believed to be accurate, Emerson Process Management does not guarantee satisfactory results from
reliance upon such information. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding the performance,
merchantability, fitness or any other matter with respect to the products, nor as a recommendation to use any product or process in conflict with any patent.
Emerson Process Management reserves the right, without notice, to alter or improve the designs or specifications of the products described herein.

Emerson Process Management


Remote Automation Solutions
Marshalltown, IA 50158 U.S.A.
Houston, TX 77041 U.S.A.
Pickering, North Yorkshire UK Y018 7JA
1991-2007 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.

You might also like