- Purpose
Transform the high
primary current to a
lower secondary
current
(metering protection)
used to isolate the
circuit (secondary
winding & primary
winding (cable/busbar)
Current Transformer
- Core Design CT
Common used CT
Bar Primary Type
Wound type
Current Transformer
- Core Design CT
Current Transformer
- Common Ratings
o
Primary rating
Secondary
: 1A or 5A
( 5A for indoor & 1A for outdoor (longer distance)
: 15VA to 20VA
Metering CT
Accuracy Class and application
Class
Application
0.1
0.2
0.5
Protection
CT
Has rating for Accuracy class &
accuracy limit factor (ALF).
Perform correctly for fault currents.
Standard value class 5P, class 10P
& class X
Protection CT
Accuracy class
Current error at
rated primary
current %
Composite error at
rated ALF
Std, accuracy
limit factor
5P
5%
10P
10%
5, 10, 15,
20, 30
Protection CT
Primary Current Ip
300/5
Secondary Current Is
Accuracy class,
5% error at 3000A
5P10
Accuracy limit factor
i.e 10 x Ip = 3000A
15VA
Rated Burden.
In ohms = 0.6
(Z = P/I2) = 15/52
= 0.6)
Protection CT
CT
Protection CT
Example : 1200A/1A CT 15VA 5P 10
This CT can read within the tolerance up to 10
times rated current.
1200A x 10 on primary side and 1A x 10 on
secondary side.
1A (+/- 1%)
[0.99A 1.01A]
-1
+1
Between this range: OK