Product data sheet

Characteristics

LV516303

Easypact CVS - CVS160B TM160D circuit


breaker - 3P/3d

Commercial Status

Commercialised

Range of product

Easypact CVS100...250

Product or component
type

Circuit breaker

Device short name

CVS160B

Circuit breaker application

Distribution

Poles description

3P

Protected poles description

3d

Earth-leakage protection

Without

[In] rated current

160 A ( 40 C )

Breaking capacity code

Network type

AC

[Ue] rated operational


voltage

440 V conforming to EN/IEC 60947-2 AC 50/60 Hz

Breaking capacity

25 kA Icu conforming to IEC 60947-2 at 380/415 V


AC 50/60 Hz
20 kA Icu conforming to IEC 60947-2 at 440 V AC
50/60 Hz
40 kA Icu conforming to IEC 60947-2 at 220/240 V
AC 50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

Utilisation category

Category A

Trip unit name

TM-D

Trip unit technology

Thermal-magnetic

Trip unit rating

160 A ( 40 C )

Protection type

Overload protection (thermal)


Short-circuit protection (magnetic)

Complementary
Network frequency

50/60 Hz

Control type

Toggle

Mounting mode

Fixed

Mounting support

Backplate

Upside connection

Front

[Ui] rated insulation voltage

690 V conforming to EN/IEC 60947-2

Downside connection

Front

[Uimp] rated impulse withstand voltage

8 kV conforming to EN/IEC 60947-2

[Ics] rated service breaking capacity

Ics 40 kA conforming to IEC 60947-2 220/240 V AC 50/60 Hz


Ics 25 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz
Ics 15 kA conforming to IEC 60947-2 440 V AC 50/60 Hz

Mechanical durability

25000 cycles

Electrical durability

12000 cycles conforming to IEC 60947-2 415 V In

Connection pitch

35 mm

Contact position indicator

Yes

Long time pick-up adjstment type Ir

Adjustable

Long time pick-up adjustment range

0.7...1 x In

Apr 6, 2014

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Main

Long time delay adjustment type

Fixed

Short-time delay adjustment type

Fixed

Instantaneous pick-up adjustment type Ii

Fixed

Instantaneous pick-up adjustment range

1250 A

Height

161 mm

Width

105 mm

Depth

86 mm

Environment
Electrical shock protection class

Class II

Standards

EN 60947-2
IEC 60947-2

Product certifications

GOST
IEC

Pollution degree

3 conforming to IEC 60947-1

Ambient air temperature for operation

-25...70 C

Ambient air temperature for storage

-50...85 C

Offer Sustainability
Sustainable offer status
RoHS

Green Premium product


Compliant - since 1041 -

Schneider Electric declaration of conformity

REACh

Reference not containing SVHC above the threshold

Product environmental profile

Available

Product end of life instructions

Need no specific recycling operations

Contractual warranty
Period

18 months