Cooling Classes of Transformers
Cooling Classes of Transformers
Cooling Classes of Transformers
ONAN
How the oil is internally circulated
First Letter
Internal Cooling Medium in Contact with the Windings
K
L
Second Letter
Circulation Mechanism for
Internal Cooling Medium
Letter
O
by Ron Widup
Shermco Industries
Definition
Mineral oil or synthetic insulating liquid with fire point
300C
Insulating liquid with fire point > 300C
Insulating liquid with no measurable fire point
Letter
Definition
N Natural convection flow
through cooling equipment
and in windings
F
Forced circulation through
cooling equipment (i.e.,
coolant pumps) and natural convection flow in
windings (also called nondirected flow)
D Forced circulation through
cooling equipment, directed
from the cooling equipment
into at least the main windings
Third Letter
External Cooling Medium
Letter
A
W
Spring 2003
Definition
Air
Water
1
Fourth Letter
Circulation Mechanism for External Cooling Medium
Letter
N
F
Definition
Natural convection
Forced circulation [fans (air cooling) or
pumps (water cooling)]
Comparison of past transformer cooling designations versus present-day transformer cooling designations is detailed in the following table:
Present Designations
ONAN
ONAF
ONAN/ONAF/ONAF
ONAN/ONAF/OFAF
ONAN/ODAF
ONAN/ODAF/ODAF
OFAF
OFWF
ODAF
ODWF
Previous Designations
OA
FA
OA/FA/FA
OA/FA/FOA
OA/FOA
OA/FOA/FOA
FOA
FOW
FOA
FOW
NETA WORLD