NT00337-EN-01 - Flair 23DM Modbus Protocol PDF
NT00337-EN-01 - Flair 23DM Modbus Protocol PDF
NT00337-EN-01 - Flair 23DM Modbus Protocol PDF
Easergy range
Flair 23DM
Communicating fault passage indicators
For all neutral arrangement system
Voltage detection relay
Modbus communication
Appendix to the user's manual
Flair 23DM
Summary
PRESENTATION ................................................................................................................................
................................
......................................... 3
NT00337-EN-01
Presentation
Flair 23DM
1 Presentation
The Flair 23DM has a communication
on port.
Modbus communication allows Flair 23DM relays to be connected to a supervisor or any other device with a master
Modbus communication port.
Flair 23DM is always the slave.
Accessible data:
Modbus communication can be used
sed to perform functions remotely such as:
Reading of measurements, counters and diagnosis
Reading of status conditions and remote indications
Transfer of time-tagged events
Reading of Flair 23DM identification
Time-setting and synchronization
Reading of settings
Remote settings when these have been enabled
Transmission of remote controls
Function
Code
1 byte
Refer to the
next section
Control Word
W
2 bytes
CRC 16 (for
( detection
of transm
mission
errors)
NT00337-EN-01
Presentation
Flair 23DM
Broadcast commands are necessarily write commands. No reply is transmitted by the slaves.
slaves
Exception Function
tion
Code
1 byte
Request function code
co
+128 (80h)
Exception Code
Contr
trol Word
1 byte
Possible codes
1: unknown function code
2: incorrect address
3: incorrect data
2 bytes
CRC 16 (for detection
of transmission
nsmission errors)
Turnaround time
The response time Tr is the time between the end of receipt of a request and sending the
response:
Note: Tr includes the silence between 2 frames and is usually expressed for a format of 8 bits,
odd parity, 1 stop bit, at 9,600 Bauds.
The Flair 23DM response time is less than 10 ms (for
for all the speeds supported).
supported
Synchronizing Exchanges
Any character received
ceived after a silence lasting more than 3.5 characters is deemed to be
the start of a fram
me.
A minimum silence
lence with more than 3.5 characters must always
lways be kept
between 2 frames.
At 38400 bauds, this silence time is equal to 1,75 ms.
A slave ignores any
a frame:
received with a physical error on one or more characters (format, parity error, etc.)
with an invalid
d CRC 16
which is nott addressed
a
to it
NT00337-EN-01
Flair 23DM
Addr
Modbus address
Modbus
bAUd
Baud rate
Authorized values
Display
on HMI
0 (the
the Modbus address is configurable manually
manually) nonE
129 (the Modbus address is proposed
automatically depending to the cubicle number
129
defined)
Default
value
0
1247
247
Auto-mode
Prty
Parity (hidden
parameter if Auto-mode activated
Auto
1.2
2.4
4.8
9.6
19.2
38.4
None
EUEn
Odd
rCnF
Remote
control
OFF
On
ON
SbO
Selection before
execution
OFF
On
OFF
Even
NT00337-EN-01
Auto-adaptation
adaptation of the configuration
Flair 23DM
NT00337-EN-01
Access to data
Flair 23DM
Addressing a bit
Some data can also
a
be accessed in the form of a bit. The bit address
ddress is then
t
deducted from
the word address
dress by:
Bit address = (word address x 16) + bit number (0...15).
Example:
Address word 3072 (0C00h)
(
bit 0 address = C000h
bit 14 address = C00Eh
Undefined Addresses
d
in this document should be used. If other addresses
ad
are used, the
Only addresses defined
Flair 23DM can either respond with an exception message, or provide
rovide non-significant data.
Access mode
ect-access: they are permanently identified
entified by their Modbus
Mod
address.
The data are dire
These can
n be reached
reach in a single read or write operation, applying
ying to all or part of the
relevant zone.
In Flair 23DM, all zones are accessed directly, however for some zones,
z
such as those for
time-tagged even
nts, a particular protocol can be used to optimize exchanges
exchan
with the
supervisor. This protocol
p
is specified in the relevant zones.
NT00337-EN-01
Flair 23DM
Word Address
Range
(Hexadecimal)
0002h to 0005h
0002h to 0005h
0006h to 003Fh
0006h to 003Fh
00F0h to 00F5h
00F0h to 00F3h
0100h to 0103h
0100h to 0103h
0400h to 040Dh
0400h to 040Dh
0500h to 050Dh
0500h to 050Dh
0A20h to 0A2Fh
0A20h to 0A2Fh
1E00h to 1E2Fh
1E00h to 1E12h
1E20h to 1E27h
1E28h to 1E2Fh
E000h to E4B1h
E000h to E4B1h
Word Address
Range
(Decimal)
2 to 5
2 to 5
6 to 63
6 to 63
240 to 245
240 to 245
256 to 259
256 to 259
1024 to 1037
1024 to 1037
1280 to 1293
1280 to 1293
2592 to 2606
2592 to 2606
7680 to 7727
7680 to 7698
7712 to 7719
7720 to 7727
57344 to 58545
57344 to 58545
Length
(word16)
4
4
58
58
6
4
2
2
14
14
14
14
16
16
34
18
8
8
1202
1202
Access
Mode
Access
Type
Direct
Word
Direct
Word
Direct
Word / Bit
Direct
Word / Bit
Direct
Word
Direct
Word
Direct
Direct
Direct
Word
Word
Word
indirect
Word
Note : the address zones not mentioned in this table are reserved addresses.
NT00337-EN-01
Data coding
Flair 23DM
IEC Format
The date and time are coded on 4 words, in IEC 60870-5-4 format (bits
its at 0 in the table are not
used: they are always
ways read
r
at 0 and ignored in write mode):
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word Reserved (0 in read mode, variable in write mode) 0
Year (0...99
9)
1
Word 0
0
0
0
Month (1...12)
0
0
0
Day (1...31)
2
Word 0
0
0
Hour (0...23)
0
0
Minute
es (0...59)
3
Word Milliseconds
onds (0...59,999)
4
Year - 1 byte for years: varies from 0 to 127 years. (1/1/2000 to 31/12/2127).
Month - (4 bits) for months: varies from 1 to 12.
Day Day of Month, (5 bits): varies from 1 to 31.
Hour - 1 byte for hours: varies from 0 to 23.
Minute - 1 byte for minutes: varies from 0 to 59.
Millisecond - 2 bytes for milliseconds: varies from 0 to 59999.
NT00337-EN-01
Flair 23DM
Synchronization zone
The synchronizati
nization zone contains the 4 words used to code the ab
bsolute time required for
time-tagging even
nts:
Description
Binary time (year)
Binary time (month + day)
Binary time (hours + minutes)
Binary time (milliseconds)
Address
2 (0002h)
3 (0003h)
4 (0004h)
5 (0005h)
Read
3
3
3
3
Write
16
16
16
16
Format
IEC
Note: The write operation should be performed on the whole zone and uses start
address 0002 with a length of 4 words.
words
Year (0 to 99)
b15
b8
0
b15
b0
Month (1 to 12)
b15
0
b8
b7
b7
Hour (0 to 23)
b0
0
b8
Day (1 to 31)
minute (0 to 59)
b7
b0
Milliseconds (0 to 59999)
b15
10
b8
b7
b0
NT00337-EN-01
Flair 23DM
Identification zone
The identification
on label
la
contains:
10 words, used to code the serial number on a Flair 23DM unitit
1 word for the cubicle
cu
number
1 word for the product type
48 to encode
e the basic identification of Flair 23DM.
Description
Serial Number
Adress
Read
25982607
3
(0A26h...0A2Fh)
Write
Format
rmat Value
ASCII
(see after)
Cubicle_Number
14 (000Eh)
16S
Device_Type
Device Identification
15 (000Fh)
1663
(0010h...003Fh)
3
3
16S
ASCII
1 to 29
0 means not used
1 = Fault detector
Basic identification
Serial number :
The Flair 23DM provides a specific product coding (serial number) on 17 characters, within a 10
registers area:
1216066406
0664060010001
OOOOOO : Order
number
Bit
15
Word
2598
0A26h
2599
2600
14
13
12
11
10
0A27h
0A28h
2601
0A29h
2602
0A2Ah
2603
0A2Bh
2604
0A2Ch
2605
0A2Dh
2606
0A2Eh
Reserved (NULL=0)
2607
0A2Fh
Reserved (NULL=0)
dentification:
Product identification:
(see
see the corresponding chapter)
chapter
NT00337-EN-01
11
Flair 23DM
Nb Object
0h VendorName
1h
2h
2A
Regular
3h
4h
5h
Value
Schneider Electric
Lenght
enght
Adress
Read
18 (12h) 1624
3
(0010h..0018h)
ProductCode
(EAN13)3 60648 05158 42 20 (14h)
(reference coded in EAN13 format)
MajorMinorRevision
xxx.yyy
7
(application version number)
numbe
(i.e.: 001.004)
VendorURL
ProductName
ModelName (short iden
dentification
code)
25...34
(0019h..0022h)
3538
(0023h..0026h)
www.schneider-electric.com 26 (1Ah)
FLAIR Serie 20
14
FLAIR23DM
8
6h UserApplicationName
Exploitation
3
80h FirmwareSubRevision number (last zzz
Extended
(i.e.: 000)
field of the application version
number)
3
3
3
3
12 (0Ch)
3
3940
(0027h..0028h)
3
3
xxx.yyy
(i.e.: 000.002)
25922595
3
(0A20h..0A23h)
zzz
(i.e.: 000)
25962597
3
(0A24h..0A25h)
17 (11h)
(1
25982607
3
(0A26h..0A2Fh)
ProductCode
The EAN13 code id
dentifies the reference for a Flair 23DM universally
lly in 13 digits:
d
Standards Organizati
nization Manufacturer Reference Checksum
3
12
60648
05158
42
NT00337-EN-01
Flair 23DM
Request frame
The read identification request frame consists of the following fields:
fields:
Field
Slave number
Function code
MEI type (sub-function
function code)
Read type
Not used
CRC16
Size (Bytes)
1
1
1
1
1
2
Value
1...247
43 (2Bh)
14 (0Eh)
01 or 02 or 03 or 04
00
Calculated
Response frame
The response frame consists of the following fields:
fields
Field
Slave number
Function code
MEI type (sub-function
function code)
Read type
Conformity level
Not used
Not used
Number of objects
First object number
First object length
First object ASCII string
...
nth object number
nth object length
nth object ASCII string
CRC16
Size (Bytes)
1
1
1
1
1
1
1
1
1
1
lg1
...
1
1
lgn
2
Value
1...247
43 (2Bh)
14 (0Eh)
01 or 02 or 03 or 04
131 (83h)
00
00
n = 3, 7 or 11, according to the Read type field
obj1
lg1
txt1
...
objn
lgn
txtn
Calculated
Exception frame
If an errorr occurs while
wh processing the request, the Flair 23DM sends
nds an exception
exce
frame,
consisting off the following fields:
NT00337-EN-01
Field
Slave number
Function code increased by 80h
MEI type (sub-function
function code)
Size (Bytes)
1
1
1
Value
1...247
171 (ABh)
14 (0Eh) or other if MEI type received is
incorrect.
Exception code
CRC16
Flair 23DM
Writte
Fo
ormat Unit
Range
Phase current I1
Phase current I2
Phase current I3
Residual current Io
Maximeter phase current IM1
Maximeter phase current IM2
Maximeter phase current IM3
% nominal voltage phase V1
% nominal voltage phase V2
% nominal voltage phase V3
% nominal voltage residual V0
% nominal voltage phase U12
% nominal voltage phase U13
% nominal voltage phase U23
Note: all the TM are read only.
only
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
16S
16S
16S
16S
16S
16S
16S
16S
16S
16S
16S
16S
16S
16S
0-800 A
0-800 A
0-800 A
0-800 A
0-800 A
0-800 A
0-800 A
0-1000%
0-1000%
0-1000%
0-1000%
0-1000%
0-1000%
0-1000%
0400h
0401h
0402h
0403h
0404h
0405h
0406h
0407h
0408h
0409h
040Ah
040Bh
040Ch
040Dh
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
3, 4
1A
1A
1A
1A
1A
1A
1A
1%
1%
1%
1%
1%
1%
1%
Counters zone
Description
Address
Hexadecimal
0500h to 0501h
Read
Writte
Format
Address
Decimal
1280 to 1281
R/P
32S
1282 to 1283
0502h to 0503h
R/P
32S
1284 to 1285
0504h to 0505h
R/P
32S
0506h to 0507h
R/P
32S
1288 to 1289
0508h to 0509h
R/P
32S
1290 to 1291
050Ah to 050Bh
R/P
32S
Confirmed fault
passages
Confirmed fault
passages
Confirmed fault
passages
Unconfirmed fault
passages
Unconfirmed fault
passages
Relay1
1292 to 1293
050Ch to 050Dh
R/P
32S
Relay1. Duration
shorter than
minimal duration
(T12)
14
NT00337-EN-01
Flair 23DM
Counters for Modbus diagnosis
Frame Sent
01 08 0000 1234 ED7C
Address
62464 (F400h)
62465 (F401h)
62466 (F402h)
62467 (F403h)
62468 (F404h)
62469 (F405h)
62470 (F406h)
Read
3
3
3
3
3
3
Write
6, 16
Format
1 = reset
If no
activity >
80ms
May be displayed
ayed also locally on the product by the following operation:
- 5s press on ESC button => the Flair 23DM displays "Fact",
", blinking
- press left button ""
"
within 3s (if not will the product will be reseted)
reseted
- navigate to reach "CPT" menu
- use the " " button to freeze/unfreeze circular display of counter values
- use Test/Reset button during counter display to reset them (other
(
Reset can be done via
communication or general reset of product
Resetting counters
The counters are reset to 0 in the following cases:
when they reach the maximum value 65535 (FFFFh)
when they are reset by a Modbus command (function 8, subcode 000Ah)
000Ah
during a power failure of Flair 23DM.
NT00337-EN-01
15
Flair 23DM
Writte
Format
5, 6, 15, 16 B
Rserve
e for TCS
241-242
(00F1h-00F2h)
243
(00F3h)
5, 6, 15, 16 B
244-245
(00F4h-00F5h)
1, 2, 3, 4
TCS15
TCS14
TCS13
TCS12
TCS11
TCS10
TCS9
b08
TCS8
b07
TCS7
TCS6
TCS5
TCS4
TCS3
TCS2
TCS1
b00
Bit
3841
(0F01h)
3889
(0F31h)
02...14 38423854
(0F02h...0F0Eh)
38903902
(0F32h...0F3Eh)
Reserved
15
3903
(0F3Fh)
240
00
(00F0h)
01
3855
(0F0Fh)
(*): This command activates a rapid flash on the LED of fault detection on Flair 23DM for 30
seconds and permit so to check the communication between the master and the Flair 23DM.
The selection word is only used for the "confirmed SBO" mode.
Note: a single
le remote control order
or
changing to zero does not gen
nerate time-tagged events
16
NT00337-EN-01
Flair 23DM
NT00337-EN-01
17
Flair 23DM
Word address
Bit address
Control word
256 (0100h)
1000h...100Fh
Fh 1, 2, 3, 4
Status word
257 (0101h)
1010h...101Fh
Fh 1, 2, 3, 4
258 (0102h)
1020h...102Fh
Fh 1, 2, 3, 4
259 (0103h)
1030h...103Fh
Fh
Reserved
260263
(0104h0108h)
1040h...108Fh
Read
Writte Format
Bit Address
Status
4096..4099
Reserved
(1000h...1003h)
04
05
4100 (1004h)
4101 (1005h)
06
07...15
4102 (1006h)
Flair 23DM initialization in progress
4103..4111
Reserved
(1007h...100Fh)
18
NT00337-EN-01
Flair 23DM
Bit Address
41124124
(1010h101Ch)
4125 (101Dh)
41264127
(101Eh101Fh)
Status
Reserved
Setting change of Flair 23DM
Reserved
Bit Address
4128 (1020h)
4129 (1021h)
4130 (1022h)
4131 (1023h)
4132 (1024h)
4133 (1025h)
4134 (1026h)
4135 (1027h)
4136 (1028h)
4137 (1029h)
4138 (102Ah)
4139 (102Bh)
41404143
(102Ch...102Fh)
Remote indication
Voltage presence (on all phases)
Voltage presence V1 or U12
Voltage presence V2 or U13
Voltage presence V3 or U23
Residual voltage presence (summation of the three
phases) voltage presence loss (generate an event)
Transient
Reserved
Reserved
Voltage absence (sur toutes les phases)
phases
Voltage absence V1 or U12
Voltage absence V2 or U13
Voltage absence V3 or U23
Reserved
Note: voltage
oltage presence/absence per phase is valid if corresponding phase voltage
measurement is configured as "active". It relates
lates to simple or composed voltages depending
on "Voltage Measure Type" parameter.
Remote indication No. 2 (Address 0103h)
The remote indication No. 2 signals the status related to the current fault detection:
detection
Word
Bit
259
00
(0103h) 01
02
03
04
05
06
07
08
09...15
...15
NT00337-EN-01
Bit Adress
4144 (1030h)
4145 (1031h)
4146 (1032h)
4147 (1033h)
4148 (1034h)
4149 (1035h)
4150 (1036h)
4151 (1037h)
4152 (1038h)
41534159
(1039h...103Fh)
Remote indication
Phase fault
Earth fault
Earth fault on phase 1
Earth fault on phase 2
Earth fault on phase 3
Transient phase fault
Transient earth fault
Fault by test action
Phase or earth fault
Reserved
19
Time-tagged events
Flair 23DM
20
Word
Inform
mation
Coding
1
2...5
Event number
Date an
nd time of the
event
6 (MSB) Number
er of associated
events
6 (LSB)
7
8...11
Type of data
Event identifier
Associated data
12
Primary or secondary
event identifier
Boolean (04h)
Address of the associated databit
data
Direction of the event:
0: deactivation/disappearance
pearance
1: activation/appearance
Between 1 and 65533. Used to identify the event.
NT00337-EN-01
Time-tagged events
Flair 23DM
Nota:
Event numbering
ering starts at no. 1 and ends with no. 65535. When event
e
no. 65535 is
detected, the next event
ev
numbering restarts at no. 1.
The most significant
ificant byte of word no. 6 corresponds to the type of event (primary or
secondary). On Flair 23DM,
23DM events are always primary type (no associated
assoc
secondary events).
The event identifier always corresponds to a Modbus data adress defined on the Flair
23DM.
For Boolean
n type,
typ words 8, 9 and 10 are set to 0.
Word
rd 12 is incremented
increme
2 at a time on each event.
Event tables
man
an internal storage table with a capacity
city
The Flair 23DM manages
of 100 events. Up
pstream of the table, 2 words contain:
the current number
numb of events present in the queue (between
en 0 and 100)
the number of
o the last detected event
Both these words and
a the number of the first event in the table form
rm a header that will be
used by the supe
ervisor to detect presence of new events.
The table can be
e seen
s
as a FIFO (First In/First Out) type stack.
Header
Table of
100
events
Addresses
57344 (E000h)
57345 (E001h)
Description
Number of events in table
Number of last event in table
Read
3
3
Write
57346 (E002h)
5734757357
Index 0 event (rest of data)
ata)
(E003hE00Dh)
5735857369
Index 1 event
(E00EhE019h)
...
...
5853358545
Index 99 event
(E4A5hE4B1h)
3
3
NT00337-EN-01
21
Flair 23DM
Time-tagged events
Read sequence
The consultation protocol for time-tagged events includes a standard
ndard sequence that can be
executed by a supervisor
superv
to detect and retrieve new events present
resent on the
t Flair 23DM.
This sequence is divided into two parts:
detection off new events on the Flair 23DM
reading of new events
eve
on the Flair 23DM
Detection of new
w events on the Flair 23DM: new events are detect
tected by periodic reading
of the header in the time-tagged
t
events zone (addresses E000h
0h to E002h).
If the number of last event in table changes between two headerr readings, one or more
events have been
n added
add to the table. The supervisor can then
n read the new events.
Read Previous Header
Head (n-1)
Address
Value
57344 (E000h)
X
57345 (E001h)
Y
57346 (E002h)
Z
Loss of Events
If the number of new events
eve
exceeds the table capacity, only the 100 most recent events
will stillll be accessible.
accessi
The oldest events will be lost forever.
The supervisor
pervisor is responsible
respo
for retrieving events from the Flair 23DM.
23DM It is up to him to adapt
his consultation
n strategy
str
to avoid the loss of events.
22
NT00337-EN-01
Time-tagged events
Flair 23DM
NT00337-EN-01
Description
Flair 23DM with time incorrect
Flair 23DM not synchronized
Flair 23DM under initialisation
Setting change on Flair 23DM
Voltage presence (on all the phases)
Voltage presence (V1 or U12)
Voltage presence (V2 or U13)
Voltage presence (V3 or U23)
Residual voltage presence (summation of the three phases)
Transient Voltage presence Loss (generate
enerate an event)
event
Voltage absence (on all the phases)
Voltage absence (V1 or U12)
Voltage absence (V2 or U13)
Voltage absence (V3 or U23)
Phase fault
Earth fault
Earth fault on phase 1
Earth fault on phase 2
Earth fault on phase 3
Transient phase fault
Transient earth fault
Fault by test action
Phase or earth fault
Reset Maximum of current
Reset current fault
Module check
0 -> 1
1 -> 0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
23
Access
ess to remote settings
Flair 23DM
Settings zones
Description
Date of last setting
Write
76847698
(1E04h1E12h)
3, 4
6,16
77127719
(1E20h1E27h)
3, 4
6,16
77207727
(1E28h1E2Fh)
3, 4
6,16
24
NT00337-EN-01
Flair 23DM
Address
Dec.
Address
Hexa.
Format
Unit
7680 to
7683
7684
1E00h
to
1E03h
1E04h
ms
IEC
Datetime
16S
7685
1E05h
16S
7686
7687
7688
7689
1E06h
1E07h
1E08h
1E09h
16S
16S
16S
16S
7690
1E0Ah
7691
1E0Bh
Fault duration
Fault validation time
Inrush filtering time
Automatic fault indication
reset on voltage return
Maximum delay before to
reset the fault indication
Phase Voltage presence
threshold
Residual Voltage presence
threshold
Delay for R1 relay activation
on voltage return (T11)
Description
Range
Default
value
Access
Reading only
ms
s
s
s
Automode
Automode
60ms
70 s
3s
70 s
R/W
R/W
R/W
R/W
16S
2, 4, 8, 12,16 or 24h
24
4h
R/W
16S
R/W
R/W
40 to 90 %
80
(10% step)
step
7692
1E0Ch
16S
%
30 to 60 %
30
(10% step)
step
7693
1E0Dh
16S
ms
0 to 1s (0,1s step)
0,1s
1 to 21s (2s step)
1 to 10 mn (1 mn
step) + 15 mn
7694
1E0Eh
Delay for R1 relay release on
16S
ms
0 to 1s (0,1s step)
step
0,1s
voltage loss (T12)
1 to 3s (0,5s step)
step
7695
1E0Fh
Voltage absence threshold
16S
%
10 to 30 %
20
(10% step)
step
7696
1E10h
Delay for R2 relay activation
16S
ms
0 to 1s (0,1s step)
0,1s
on voltage loss (T21)
1 to 21s (2s
2s step)
1 to 10 mn (1 mn
step) + 15 mn
7697
1E11h
Delay for R2 relay release on
16S
ms
0 to 1s (0,1s step)
step
0,1s
voltage return (T22)
1 to 3s (0,5s step)
step
7698
1E12h
16S
0 = inactive
Inactive
Auto calibration (2)
Boolean
1 = active
(1) : 3 phases CTs mounting: 20 to 200A. 2 phases CTs + zero sequence CT mounting:: 5 to 200A.
(2) : If active, the Auto calibration is performed at each return of LV supply.
NT00337-EN-01
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
25
Access
ess to remote settings
Flair 23DM
Address
Dec.
Address
Hexa.
Description
Format
Unit
7712
1E20h
Auto-mode
Boolean
7713
1E21h
Baud rate
16S
7714
1E22h
Parity
16S
7715
1E23h
16S
7716
7717
1E24h
1E25h
Modbus address
Cubicle number
16S
16S
7718
1E26h
16S
7719
1E27h
Boolean
Range
0= inactive
1= active
1= 4800 baud
2= 9600 baud
3= 19200 baud
4= 38400 baud
1 = None
2 = Even
3 = Odd
1= 1 stop bit
2= 2 stop bits
1 to 247
0 = Nott significant
Else: 1 to 29
1= direct mode
2= SBO active
(confirmed mode)
By default
value
Access
active
Auto-mode
(1)
Even
247
0
R
R
Direct
R/W
Authorized
R
0 = Not authorized
horized
1 = Authorized
(1): Speed is predefined at factory at 38400 bauds. If restarted, the Auto-mode restarts from 19200 bauds and
then upwards until it detects the real speed.
Rules of configuration:
The number of stop bit is automatically derived from parity defined (2 bits if parity = None).
None
The modification of the communication parameters (speed,
(speed parity, stop bits) is only possible if the Auto-Mode is not
activated.
Modifying
odifying the cubicle number causes the automatic assignment of the Modbus address:
address
(@ = 33 + 5*(CubicleNb-1))
Assigning a new Modbus Slave Address automatically resets Cubicle number to 0.
Remote settings zone no. 3: other parameters related to the current fault detection and voltage
presence/absence.
Address
Dec.
Address
Hexa.
Description
Format
Unit
7720
1E28h
CT mounting
16S
7721
1E29h
CT type
16S
7722
1E2Ah
7723
1E2Bh
7724
1E2Ch
Voltage detection
output relays logic
Voltage phase 1
7725
1E2Dh
Voltage phase 2
7726
1E2Eh
Voltage phase 3
7727
1E2Fh
Residual voltage
16S
(Boolean)
16S
(Boolean)
16S
(Boolean)
16S
(Boolean)
16S
(Boolean)
16S
(Boolean)
26
Range
1 = Type A (ooo)
2 = Type B (0oo)
3 = Type C (0)
1 = CT1
2 = CT2
0 = Simple
1 = Composed
0 = Direct
1 = Inverted
0 = Not measured
1 = Measured
0 = Not measured
1 = Measured
0 = Not measured
1 = Measured
0 = Not measured
1 = Measured
By default
value
Access
Type A
CT1
Simple
(dip switch)
Direct
(dip switch)
Measured
(dip switch)
Measured
(dip switch)
Measured
(dip switch)
Not
measured
(dip switch)
NT00337-EN-01
R
R
R
R
R
Flair 23DM
Synchronization cycle
Each synchronization cycle is executed as follows:
Phase
1
NT00337-EN-01
Description
tion
The superrvisor writes its date and time value in the synchronization
ronization zone or by
function 43-16
43
The Flair 23DM changes to non-synchronous state (bit 05 of the control word at 1)
and resets
sets its clock.
If the reset
set amplitude is less than 100 ms, the Flair 23DM changes back to
synchronous state.
27
Flair 23DM
Events generated
At each power-up,
up, Flair23DM generates
rates successively the following events:
Appearance of the incorrect time event
Appearance of the Not synchronous event
At the first broadcast of synchronization message by master (with date & time), slave
generates successively
ccessively the following events:
events
Disappearance of the incorrect time event
Disappearance of the Not synchronous event
After loss of synchronization, slave generates the following event:
Appearance of the Not synchronous event
After return of synchronization, slave
slav generates the following event:
Disappearance of the Not synchronous event
Clock accuracy
ccuracy is linked to the master and its control of the time frame transmission
tra
The clock accuracy
delay on the
e communication
communic
network. Before sending a time frame, the supervisor must
ensure that all the read
re requests sent have received a response.
onse. Synchronization
Sy
of the Flair
23DM is performed
rmed immediately after the frame is received.
For optimum
m synchronization,
synchr
the supervisor must compensate for the
t frame transmission
time. The frame transmission
transmissi time is compensated by the Flair 23DM.
23DM
If the frames pass
ss through
throu a gateway (multi-master operation), make sure that this does not
slow down the frames.
fram
28
NT00337-EN-01
Managing
ging the date and time using
function 43
Flair 23DM
Function 43-15
15 is a read
r
Flair 23DM date and current time function. It is an alternative to
Function 43-15
reading the Modbus
bus registers
re
at addresses 0002h to 0005h inclusive.
usive.
The IEC 60870-5-4
4 format is used for data returned by function 43-15
5 (common to reading via
the Modbus
bus registers).
registe
Request frame stru
ucture:
Slave Number
Function
1 byte
1 byte
Request destination:
stination: 43
1247 (unique) (decimal)
MEI Type
Reserved
(Sub-Function Code)
1 byte
1 byte
15 (decimal)
0
Function
2 bytes
CRC 16
NT00337-EN-01
MEI Type
Reserved Data
(Sub-Function Code)
1 byte
1 byte
43 (decimal) 15 (decimal)
1 byte
0
8 bytes
Date and
time in IEC
60
60870-5-4
format
Control
Word
2 bytes
CRC 16
29
Managing
ging the date and time using
function 43
Flair 23DM
Function 43-16
Function 43-16
16 is a write Flair 23DM date and current time function. It is an alternative to
writing the Modbus
us registers
re
at addresses 0002h to 0005h inclusive.
usive.
The IEC 60870-5-4
4 format is used for data supplied to function 43-16 (common to reading via
the Modbus registers).
registe
Correct request fra
ame structure:
Slave Number
Function
MEI Type
Reserve Data
(Sub-Function Code) d
Control
Word
1 byte
Request
destination:
0: broadcast
1247
(unique)
1 byte
43
(decimal)
1 byte
16 (decimal)
2 bytes
CRC 16
1 byte
0
8 bytes
D
Date
and
time in IEC
60870
60870-5-4
f
format
Response
onse frame structure: No response if it is sent in broadcast mo
ode. Otherwise the
response
onse is as follows:
30
Slave Number
Function
MEI Type
Reserve Data
(Sub-Function Code) d
Control
Word
1 byte
Request
destination
:
1247
(unique)
1 byte
43
(decimal)
1 byte
16 (decimal)
2 bytes
CRC 16
1 byte
0
8 bytes
Flair 23DM
date and
current time
in IEC
60870
60870-5-4
format after
updating
NT00337-EN-01
Flair 23DM
NT00337-EN-01
Personal notes
31
http://www.schneider-electric.com
E-mail : [email protected]
NT00337-EN-01
07/2013