N6867e PXLP 3000
N6867e PXLP 3000
N6867e PXLP 3000
Fields of application
PXLP 3000 is a static full scheme
distance protection capable of
detecting all types of faults. It is
mainly designed for fast and selective
protection of high and very high
voltage networks interconnected or
not, with solidly earthed neutral or
using impedance earthing (reactive) at
low value. PXLP 3000 is particularly
suitable for networks in which fault
currents may be well below the load
current and for the supervision of long
lines because of its lenticular or
circular characteristic which is
capable of being offcentered.
Main characteristics
Underimpedance starting
Circular or lenticular characteristics
selected by internal switch.
4 forward zones, 1 reverse zone.
4 tripping steps.
Reactance type zone measurement
for eliminating the influence of fault
resistance and load current.
Independent measurement system
for each loop being monitored.
Electronic voltage memory slaved
onto the network frequency permitting
directional operation even in the event
of sub-station close-up three-phase
faults.
Fuse failure detection.
Instantaneous tripping in the event
of closing onto fault.
Locking device in event of power
swing detection.
Programming by switches for the
following signalling schemes :
- step acceleration,
- permissive overreach,
- blocking,
- direct inter-tripping.
Programming of single phase or
three-phase tripping modes for various
steps.
Built-in single phase-three-phase
auto-recloser.
Operation
The three voltages and three currents
from the measurement reducers feed
transformers ensuring galvanic
insulation and reducing levels to
values compatible with the electronics.
In bloc 1, the signal from the
transformer are added to generate
zero sequence quantities of Vo, Io,
Ko.
Bloc 2 includes six underimpedance
relays and their settings. These relays
serve to start the protection.
Bloc 3 includes the voltage memory
circuit.
Bloc 4 ensures band pass filtering of
input quantities, thus eliminating all
signals which are harmful for
measurement : aperiodic component,
line oscillation, CVT transients,
harmonics...
Bloc 5 carries out zone setting.
Bloc 6 makes measurements.
Bloc 7 receives measurement data,
Starting
Direction measurement
without dead zone
Phase-to-phase faults
The voltage representing the direction
of fault current flow is compared with
a stored positive-sequence voltage
(electronic memory voltage). Thus
even in the event of a three-phase
fault witout voltage, correct directional
information is preserved.
Phase-to-earth faults
The zero sequence power flow
direction is measured. To avoid any
incertainties when the fault is far off
and the sources are powerful, the
zero sequence voltage is
compensated for. This is equivalent to
bringing the relay closer to the fault
point.
Distance measurement
A differential voltage is generated for
each of the loops (six per zone). In the
same way as for starting, the phase
shift of this voltage is measured whith
respect to a current image voltage.
The impedance point is within the
zone in question when the phase shift
is greater than 90.
For earth faults, distance measurement
in the first zone is carried out when
the voltage drop in the fault resistance
is zero (zero instantaneous residual
current), rendering this measurement
particularly insensitive to fault
resistance. It is also insensitive to
frequencies, aperiodics and loads.
Alarms
On the front panel of the protection,
there are indicator lamps which
indicate the faulty phase or phases
and the tripping zone. The indication
is stored (bistables) even in the event
of auxiliary supply loss. Many
polarity-free contacts are provided to
permit remote signalling.
Tripping
In its basic version, the protection
includes six tripping contacts (two per
phase) providing direct control of the
circuit-breaker coils. To prevent any
deterioration, the contacts are held as
long as the current conducted through
them is greater than 0.2 A.
Complementary modules
Operation block diagram
9
13
8
CC
7
12
3I
U, I
Logical
11
3U
10
3
VD
memory
CC
Technical characteristics
Input circuits
Rated voltage Un
Constantly permissible voltage
Burden
Frequency
Rated current In
Constant overload current
Overload current for 10 s
Overload current for 1 s
Burden measured across rack terminal
100 to 130 V
(or 200 to 260 V for non-standard model)
2 Un
0.1 VA
50 or 60 Hz
1 or 5 A
4 In
30 In
100 In
0.1 VA (1 A) ; 0.5 VA (5 A)
Auxiliary supply
Inaudible DC/DC converter
Tolerance
Standby state consumption
Fault state consumption
Settings
Forward supervision limit : X4
X
X4
X4 = 10
x Fn ohms/phase
In
N4 + 1
N4 adjustable from 0 to 99 by
thumbwheels switches
Table of X4 limits (in ohms/phase)
In
Fn
1A
5A
X5
50 Hz
60 Hz
5 to 500
1 to 100
6 to 600
1.2 to 120
X1 = a1 x
0.4
x Fn ohms/phase
In
N1 +1
a1 = 1, 5, 10, 50
thumbwheel switches
N1 = 0 to 99
Second zone limit : X2
(same equation as for X2 with index 2)
Table of X1 limits
(in steps equal or less than 5%)
In
Fn
1A
5A
50 Hz
60 Hz
Earth coefficient : Ko = Xo - Xd
Setting from 0 to 1.5 in steps of 0.1
3 Xd
(thumbwheel switch)
Reference impedance characteristic angle F = 50 Hz : 45 to 86 in 16 steps
(line angle) :
F = 60 Hz : 50 to 87 (thumbwheel
switch)
Settings
Time delays : step 1 T1
step 2 T2
X1
R
step 3 T3
step 4 T4
Sensitivity : phase current threshold
Earth current threshold
Directional sensitivity
X2
R
5% of set value
10% of set value
2% of set value
Operating time
Minimum value : 15 ms, typical value : 25 ms
Auto-recloser
Single phase cycle
Fast three phase cycle
Slow three phase cycle
Reclaim time
0 to 495 ms in steps of 5 ms
0 to 990 ms in steps of 10 ms
thumbor 0 to 9.9 s in steps of 0.1 s
wheel
0 to 9.9 s in steps of 0.1 s
switches
0 to 9.9 s in steps of 0.1 s
0.15 In
0.1 to 1.6 In in steps of 0.1 In or
0.2 to 3.2 In in steps of 0.2 In
or percentage relay (thumbwheel switch)
unlimited for all unbalance faults
unlimited for 0.5 s for nearby three-phase
faults (voltage memory)
X4 with X4 : forward zone value
: setting : 0.1 ; 0.2 ; 0.4 ; 1
Tripping circuits
2 tripping contacts per phase, self-held for current greater than 0.2 A
X
X3
Indication :
Max service voltage
Permanent current
Breaking capacity (L/R = 40 ms)
R
X5
Contacts
Tripping :
Max service voltage
Making current (0.5 s)
Permanent current
Breaking capacity (L/R = 40 ms)
250 V
30 A
5A
0.75 A at 48 VDC
0.30 A at 125 VDC
0.15 A at 220-250 VDC
250 V
5A
0.75 A at 48 VDC
0.30 A at 125 VDC
0.15 A at 220-250 VDC
Environment
In operation
Storage
Relative humidity
-10 C to +55 C
-40 C to +70 C
less than 95% without condensation
Insulation
(International standard IEC 255)
Dielectric strength
Impulse wave withstand
High frequency perturbation
2 kV, 50 Hz, 1 mn
5 kV, 1.2/50 s, 0.5 J
2.5 kV, 1 MHz
Presentation
Size : one 19 rack, 8 U
Width
Height
Depth
Weight of complete model
483 mm
354 mm
304 mm
25 kg
Variants
Signalling schemes
Zone 2
independent
Zone 3
independent
P/S
2-pole opening on
3001
3002
3003
3004
3005
3006
3007
3008
3009
3010
3011
3012
3013
3014
3015
3016
Step acceleration
B detects the fault in Zone 1 and
sends a signal to A which switches its
measurement reach in Zone 2 without
waiting for the second step. Thus, a
fault near B, normally eliminated at T2
by A, will be eliminated at T1.
Z2A
Z1A
Z2B
Z1B
Permissive overreach
Z1B or Z2B
Blocking
(2) : B detects the reverse fault and
sends a signal to A, inhibiting it from
tripping.
(1) : A and B both detect the fault in
extended Zone 1 and trip after a
slight waiting delay for a possible
blocking order.
Z4A
Z1A or Z2A
A
Auto-recloser module
Z1B or Z2B
B
(1)
(2)
Z4B
A Single Standardized
Presentation
L3 L2 L1
br
br
Auxiliary supply
Indication card
Presentation
PXLP 3000 is a modular range
protection. It is built in the form of an
8 U 19 standardized rack, whatever
the model. All these models include
the following basic parts :
- transformer unit,
- card for low level testing,
- starting, zone measurement and time
delay modules,
- memory voltage modules,
- indicating and tripping modules,
- input-output modules.
At all stages of manufacture, from
component incoming checking to final
inspection, protection is put through a
severe quality control plan designed to
ensure optimum reliability. To
eliminate faults in the early stage, the
protection undergoes oven debugging
for a period of 168 hours.
+T2
Tripping A2
Tripping B2
Tripping C2
+T2
DA2
DB2
DC2
+T1
Tripping A1
Tripping B1
Tripping C1
+T1
DA1
DB1
DC1
MR
Starting information
MR
Auto-recloser control
MR
MR
INV
+T5
information
information
information
information
information
+T5
NA
NB
NC
DT
MN
+T3
Tripping indication Phase A3
Tripping indication Phase B3
Tripping indication Phase C3
+T3
DA3
DB3
DC3
NA Phase A fault
NB Phase B fault
NC Phase C fault
Tripping
Single Phase fault
PHF
RHF
A4 tripping indication
B4 tripping indication
C4 tripping indication
Multi-phase fault indication
Starting information
Fuse failure information
Auxiliary supply
failure indication
Power swing detection
indication
+T4
Z1
Z2
Z3
Z5
NA
HF presence input
Reception - Remote protection
Common
BDT
VER
TPL
RFF
+T4
Zone 1 tripping signal
Zone 2 tripping signal
Zone 3 tripping signal
Zone 5 tripping signal
NA Phase A fault information
NB Phase B fault information
NC Phase C fault information
Tripping information
Single Phase fault information
Monitoring direction
inversion input
+T6
DA6
DB6
DC6
+T6
Phase tripping indication A6
Phase tripping indication B6
Phase tripping indication C6
NB
NC
DT
MN
DA4
DB4
DC4
PY
MR
FF
MSA
W
Documentation
On request :
- descriptive leaflet : ND 1.6867
- commissioning leaflet : MS 1.6867
- maintenance leaflet : M 1.6867
Overall dimensions
101.6
101.6
76.2
354.8 (8 U)
354.8 (8 U)
8 holes M6
101.6
76.2
101.6
316
23
37.7
37.7
450 min.
466
482.6
465.1
356
(19'')
300
1A
100 3
130 3
50 Hz
5A
200 3
260 3
60 Hz
48 Vcc
110 Vcc
125 Vcc
220 Vcc
250 Vcc
GEC ALSTHOM T&D Protection & Contrle - Avenue de Figuires - 34975 Lattes Cedex FRANCE
Tl : 33 67 20 54 54 - Tlex : 485 093 F - Fax : 33 67 20 54 99
TRANSCOMP Edition 67 92 02 20
N 1.6867 B - 04/96
Note : on leaving the works, and unless the above information is given, model
configuration will be as follows :
Basic model : 3001
Rated current : 5 A (transformable to 1 A)
Rated voltage : 100/ 3 V
Rated frequency : 50 Hz (transformable to 60 Hz)