Tutorial - Underfloor Air-Conditioning
Tutorial - Underfloor Air-Conditioning
Tutorial - Underfloor Air-Conditioning
1. DEFINITION
Air-conditioning is defined as the simultaneous control of temperature, humidity, air
movement and the quality of the air in the space.
(source: The Trane Company)
2. COMFORT
The Ideal Conditions
For optimum comfort one should have warm feet and a cool head without noticeable
draught. Air velocity in the workspace should not exceed 0.18-0.2 m/s and good air
movement should be maintained to avoid stuffiness and dilute pollutants such as ozone
and formaldehyde.
http://www.flexiblespace.com/bs2.htm
1/8
13/10/2010
The FM Dilemma
Air-conditioning systems have tended to be either central station systems in a variety of
configurations or smaller diversified plants such as fan coil systems. Facilities managers
have been experiencing high costs associated with the maintenance and reconfiguration of
systems above workstations and, on occasions, costly leaks of water have seriously
damaged computer networks. In the drive to achieve economy, systems have tended
towards higher volume/higher temperature differential solutions but this has led to
increased complaints of draughts and noise. Many aspects of office design are now
affected by legislation and operators have the task of adapting systems to meet changing
legislation and office layouts.
The options
Building services engineers have been charged with addressing these issues. As a result,
they have had to reconsider the options available, investigate new systems and use
computers for simulation of air movement patterns, stratification etc. It has been found
that air introduced from a low level offers improved conditions in the workspace while
offering additional benefits in cost and time.
2/8
13/10/2010
Ceiling Condensation
Where there is a high latent load causing high humidity, the possibility of condensation
occurring on cold surfaces of the metal ceiling needs to be checked. Controls can be
incorporated to raise the surface temperature in such conditions, but this in turn reduces
the cooling capacity often at the time it is most needed.
Energy Costs
Displacement ventilation offers a high level of free cooling in mid season. But in mid
winter, when the supply air requires tempering to about 18C, it can be energy
demanding. Restricting the volume to reduce the energy requirement further limits the
cooling capacity.
3/8
13/10/2010
Zonal systems are now receiving a lot of attention from developers and end users.
Generally there are two types: floor void supply - ceiling return (zonal displacement
systems); and floor void supply - floor void return (zonal mixing systems).
Both have their advocates, but in low height office space (2.35-2.6 m) the notion that high
level fume should be exhausted from a high level is somewhat flawed because the amount
of mixing that takes place in such space, caused by occupant movement, door swings,
etc, can render such design intention almost impossible.
Both solutions rely on similar central plant to that of fan coil systems, but have less onfloor engineering.
Underfloor requirements
Such systems can make use of swirl grilles when the cooling load is small (60-80 W/m 2 )
and the supply temperature can be limited to 18C, but with higher loads, swirl grilles
should be replaced by fan assisted terminals with vertical distribution. The vertical
distribution avoids draughts as warmer room air is entrained into the air stream instead of
cooler air being blown across the floor at a low level as in the case of swirl.
4/8
13/10/2010
Return Air
Air returns to the zonal unit via simple return air grilles positioned above the return air
plenum in the raised floor. Fresh air may be introduced into the return plenum or directly
to the unit and exhaust air may be extracted through toilets, kitchens and additionally
through exhaust air grilles at high level if required.
5/8
13/10/2010
Care in design
With low supply temperature conditions it is advisable to run the computer calculation for
condensation and possibly apply insulation and a vapour seal to the underside of the slab.
Maximum supply air to room temperature differentials should not usually exceed 10C.
The velocity of the air should be 1 m/s to minimise temperature pick-up. Paths can be
extended under the floor to 30-35 m.
System noise levels are generally in the region of 32-35 NR.
9. THE BENEFITS
Floor voids need be no more than 300-350 mm high, offering a saving in building
height. In new-build projects, this overall reduction in the height of the building (1015%) can amount to a 5-7% saving in construction cost
(source: Swedish National Pension Fund)
Construction time can be cut by 15-25%
(source: BAA Lynton)
Zonal mixing systems do not require ceiling voids and thus can be used where head
room is limited.
The low-pressure plenum (usually 5-15 Pa) reduces fan power and noise.
Computer simulations indicate energy savings in the order of 25% compared with
VAV systems
(source: Building Simulation)
Computer simulations indicate night-time cooling can achieve energy savings of
about 9% and lower carbon dioxide emissions
http://www.flexiblespace.com/bs2.htm
6/8
13/10/2010
10. A DISADVANTAGE
Zonal units may take up 0.5% of floor space
served, but riser sizes are usually much smaller than
VAV and central displacement systems and floorby-floor plant rooms can be reduced or even
eliminated. Ceiling-based fan coils have no need for
floor-based equipment but require increased
building height and more costly relocation and
maintenance.
Air handling unit
http://www.flexiblespace.com/bs2.htm
7/8
13/10/2010
Advanced Ergonomic
Technologies Ltd
The Center
201-203 London Road
East Grinstead
West Sussex RH19 1HA
Tel: 44 (0)1342 310400
Fax: 44 (0)1342 310401
Mobile: 44 (0) 7785-280908
E/Mail: [email protected]
Homepage: www.FlexibleSpace.com/
AET Homepage
Introduction to FSS
AET Consultancy
Hiross Air Conditioning
Nesite Raised Access Floors
AET Venitzia Range of Carpet Tiles
Electropatent underfloor cabling
Movinord Partitioning
News about Flexible Space
Contacts around the World
Sitemap
This page was last updated: Thu, 08 Jun 2006 15:55:37 GMT
http://www.flexiblespace.com/bs2.htm
8/8