Guideform Spec EPM 5500P
Guideform Spec EPM 5500P
Guideform Spec EPM 5500P
For CE certification, the meter shall adhere to LVD directive and EMC
directive
the
following
standards
for
atmospheric
Meter shall conform to the IEC 62053-21 class1 for KWh accuracy.
Meter shall provide a true RMS monitoring of Ia, Ib, Ic, In, Van, Vbn,
Vcn, Vab, Vbc, Vca, power factor, frequency, watts, Vars, VA, Wh, Varh
and demand readings for W, Vars, and VA.
Graphic LCD display for the DI status and load current indicator.
User shall be able to set Alarm conditions for parameters. The limit of
maximum 9 parameters selected from 43 parameters can be set alarm
conditions. The over limit value of the parameters and the time of the
event shall be recorded in the meter.
Input /Output
The meter shall accept a power supply input of a wide range, from 100
to 240V ac or 100 to 300V dc with a power consumption of maximum
3W.
The meter must have provision for taking two digital inputs, which
should be optically isolated. PL5500 IO could provide four digital
inputs.
PL5500 IO could provide two digital outputs and two relay outputs. Two
digital outputs could be used to energy pulse outputs or over limit
alarming outputs. When used as an over limit alarm output, the upper
and lower limit, time interval and output port shall be programmable.
Communication
Installation