digitalFALCON NET II
digitalFALCON NET II
NET II
*)
TABLE OF CONTENTS
1 MEASUREMENT
10
10
11
11
12
12
12
14
15
15
16
16
4.1 Start-up
16
17
18
18
18
19
19
19
20
20
20
21
21
22
22
24
25
26
26
6.2 Mounting
26
26
27
28
28
7.2 Notification
28
29
FALCON NET II
-1-
March 06
Preface
The digital FALCON NET II is a remote traffic detector for wide area applications. It is possible
to have a maximum cable length up to 1 km (at maximum data transmission rate of 115,2 kbaud)
and to connect up to 15 detectors on a single 2-wire data bus.
The Falcon Net II is based on an encapsulated planar transceiver module with one 11 x 11
antenna and integrated pre-amplifier, which makes the HF module insensitive to electrostatic
discharges.
The HF transmitting wave guide gun module of the Falcon Net I was replaced by a low power
PHEMT-transistor directly wired to the antenna on one circuit board (planar structure) leading to
a total detector consumption below 1.5 Watt.
For development purposes or if there is only a RS232 interface port available we offer a
microprocessor controlled adapter, to convert the binary data protocol on the RS485 network side
to an ASCII protocol for a two-point RS232 adapter to host connection.
The adapter is delivered in two versions, one for development purposes in the laboratory and one
for the outdoor use in traffic station cabinets. The outdoor version has a rigid housing, a electrical
isolated RS485 field side and a overvoltage protected RS485 field interface.
In august 2005 the analog amplifier with 4 amplification steps, has been extended to 16
amplification steps to allow a finer detection field and distance range adjustment. The position of
the baudrate switch and the net adress selector and some electrical ratings changed.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-2-
March 06
1 Measurement
1.1 Detected movement direction
The detected movement direction is controlled by the software parameter DIR (see chapter 2).
The detector works uni- or bi-directional. In unidirectional mode you have to chose between
oncoming or leaving traffic detection.
The measurement data of the unidirectional mode are always given with the function byte D for
data, see chapter 3.4, equal which direction is set. Movements in the not selected direction are
not processed in the unidirectional mode. Herewith the digital Falcon Net II is compatible to the
modes and the data output of the unidirectional working digital Falcon Net.
In bi-directional mode the measurement data are given with the function bytes O for oncoming
vehicles and L for leaving vehicles, see chapter 3.4. Therefore the detection of vehicles driving
in the opposite direction, so-called ghost drivers is possible.
Default ex works: Bi-directional detection
Due to the reason that the new antenna of the digital Falcon Net II has a very high side lobe
suppression the danger of side lobe detections is avoided. In practice the measurement of too low
speeds for high leaving vehicles due to a sidelobe detection is excluded.
But still exists the problem of ghost detections due to extreme heavy rain, hail and snowfall,
which can occur when leaving (bi-directional) traffic is processed in an overhead installation,
because short vertical downward movements in the environment causes a negative speed vector
(= a leaving object) towards the detector parallel to the beam axis.
Attention: Do not reduce the values for the parameter RSEG and MSEG below standard settings
when detecting leaving (bi-directional) traffic in overhead installations. These parameter filter
out short movements. Do not raise the parameter sensitivity (SENS) above standard settings.
By the way the capability of detecting both directions does not mean to detect traffic from a
sidefire position at a trunkroad with one detector in both directions with the accuracy stated in
these manual. One detector per lane is a general rule for good counting accuracy.
1.2 Distance range
Depending on the parameter SENS (analog sensitivity), MSEG (motion segment) and RSEG
(response segment), see also chapter 2, a distance range of 50 till 80 m can be reached in a
frontal measurement of a passenger car.
For typical counting applications a high distance range is of minor interest, because
measurements with small (flat, < 30) measurement angles mean large radar shadows between
vehicles and therefore bad discrimination of single vehicles. In most applications a measurement
angle of 45 with a measurement distance of 5 till 10 meters above ground overhead for multilane applications or in sidefire position with a measurement distance of 1 till 5 meters for single
lane applications (in one direction) is best choice.
The high distance performance guarantees safe and accurate detection also under rough weather
conditions like fog, rain, hail, snowfall, ... etc., causing fading losses and distortions.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-3-
March 06
Maximum Error
Measurement angle 45
Measurement angle 60
3 km/h
5 km/h
3%
5%
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-4-
March 06
Remarkably for this antenna is the very high side lobe suppression of more than - 25 dB.
In order to qualify the area of detection in a
certain distance the formula
lC = lA + d x 2 x tan (D / 2 )
with
distance
lA
length of antenna
lC
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-5-
March 06
In most applications the mounting will be lateral beside a single lane road, or directly overhead
above multi-lane roads.
Installation overhead,
vertical plane
Installation lateral,
horizontal plane
If measurement angle M is bigger than the half detection angle D / 2 then the measured speed
value has to be corrected
V real = Vmeasured / (cos ( M D / 2))
For arriving vehicles the detection angle must be subtracted, for leaving vehicles it must be
added to the measurement angle. If the measurement angle M is smaller than the half detection
angle (D/2 = 5.5 for the patch antenna) then M D/2 is set to 0 and V real = Vmeasured .
Analogous looks the formula if M > D / 2 in the horizontal and in the vertical plane
V real = Vmeasured / (cos ( MH D / 2) x cos ( MV D / 2))
with
MH
MV
The digital Falcon Net II software includes two program variables ADJFA and ADJFB, for
arriving and leaving traffic for the user to correct the measured speed values separate for each
moving direction for any real installation.
Typically the measurement angle is chosen at 45 this guarantees good results for speed,
reflection values and counting. For measurement angles above 60 the vector component of
the speed towards the detector gets too small for an acceptable measurement error. Below
30 the radar shadow behind large vehicles cause vehicle discrimination errors.
The default value for ADJFA (ADJFB) is set to 1.296 (1.572) corresponding to a 45
measurement angle for oncoming (leaving) vehicles.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-6-
March 06
with
and tGAP > 8 * TD the lowest measurable speed under a measurement angle of 45 is
vmin = 4 * /( tGAP * cos (39.5) )
what means if GAPL=10 and tGAP=100ms then vmin= 2.3 km/h.
1.7 Reflection value, vehicle length and type classification
The reported reflection or profile value of a vehicle depends on the physical dimensions of the
vehicle and is independent of the vehicle speed.
Drawing 2
The dominant parameters of the reflection value are the length of a vehicle, the mounting angle
and the distance to the lane (detector height), but also the height of the vehicle if you measure
overhead, respectively the width if you measure lateral have an influence on the profile value.
With the simplifications that the vehicle height is neglected and the detection height is the
runway ground it can be said that the reflection distance length is
lel = lF + b
with
lF - vehicle length
b - passed beam distance
This is the so-called electrical length of the vehicle in the radar beam.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-7-
March 06
with
- measurement angle
c - absolute speed of light, 300000 km/s
f0 - transceived frequency, 24.125 GHz
fD - Doppler frequency
v - object speed in the radar field
FALCON NET II
-8-
March 06
Due to the made simplifications and that real vehicles do not reflect for 100 %, measured values
might be some per cent lower than the calculated, despite they are very well suited for vehicle
type classification.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
-9-
March 06
A real installation overhead 7,5 meter above ground gave following results:
vehicle type classes
Reflection value
up to 180
cars
180 - 480
480 - 700
700 - 900
900 - 1400
* the measurements with Falcon Net II, 11 x 11 patch antenna, mounting angle 45 ,SENS = 3
The classification of large motorbikes can cause problems due the fact that large motorbikes
reach the length of small cars and therefore the classes are overlapping. As well busses can not
be detected as an extra class because they reach the same length (size) as trucks.
The numeric range of the reflection value is: 1 ... 65535 units
For better classification accuracy a post processing filter for vehicle data was programmed.
Particularly semitrailer trucks with glasfever roofs may partly absorb the microwaves completely
with the result of a truck split in two or three small vehicle parts. The filter adds this typical
pattern together again. Beside that the filter forces a splitting of too large vehicles, which result e.
g. of trucks driving in very short distance to each other. The filter may delay the data output up to
600 ms.
The classification error for a measurement at 45 measurement angle and classification in two
classes with passenger car like vehicles and truck like vehicles is within following limits
according to the German TLS (Technische Lieferbedingungen fur Streckenstationen):
Class
cars
1 minute
10
< 20 %
cars
1 minute
> 10
< 10 %
cars
1 hour
trucks
1 minute
10
< 35 %
trucks
1 minute
> 10
< 20 %
trucks
1 hour
<3%
<5%
Attention: Although we made the examples for several measurement angles the intended
use of the detector is at a measurement angle of 45 !
1.8 Inter-vehicle net time gap
Inter-vehicle net time gap means the time between the last vehicle left the radar beam and the
detection of the next vehicle. Net time gap because the time a vehicle needs to pass the radar
beam is not included (this would be the headway).
The calculated net gap time is corrected for the time interval of the response segment at the
measured speed and for the vehicle end detection timeout (see also chapter 2). The resulting
value is a multiple of 10 ms units.
Range of net time gap: 0 ... 65535 units
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 10 -
March 06
The Falcon Net adapter delivers the value as an ASCII value in seconds, therefore the range is
0,00 - 655,35 seconds.
The first value after any reset, every parameter change or request and values out of range
(overflows) are always set to null. After 655,35 seconds without any vehicle detection the net
time gap is reset to 0,00.
1.9 Detector self test
If no vehicle is detected for 322,68 seconds automatically a detector self test is performed.
Analog
amplifier
HF-Unit
Analog /
digital
converter
30 MHz
data
processing
CPU
2048 Hz
Testoscillator
Including the high frequency transceiver the whole data processing circuitry is tested. Only in
case of a test failure an error message is send, see also chapter 3.4.3.
The system is occupied maximum 5 ms with the automatic self test and a vehicle detection might
be delayed for this time period.
This test can also be forced by a user parameter request, the correct result must always be 45, see
also next chapter.
Function
Range
Default
ADJFA
0.001 9.999
1.296
ADJFB
0.001 9.999
1.572
SENS
1 - 16
15
RSEG
5 - 80 cm
40
MSEG
5 - 40 cm
20
GAPL
5 - 255
10
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 11 -
March 06
Parameter
Function
Range
Default
DETE
0/1
CRC
0-2
DIR
1-3
45
TEST
The underline letter in the parameter column of the table above is the code letter for the function
byte in the Falcon Net II binary data block format (see chapter 3.4) and the ASCII data format of
the RS485-RS232 Falcon Net II Adapter (see chapter 4.2).
The default settings fit for the most standard applications.
The parameter set (except baudrate and detector address see chapter 5.8) is EEPROM based.
Every change gets effective immediately.
For the check of the integrity of the EEPROM based parameter set an also EEPROM based CRC
error checksum is used, the check is done every power-on, parameter change or request.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 12 -
March 06
Meaning
9 10 11 12 13
start byte uppercase B(hex 42)
B
X
W X
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 13 -
March 06
Meaning
9 10 11 12 13
B N . N N N
X E
R X E
M X E
G X E
D X E
C X E
X E
X E
V N . N N
?
ADJFA
ADJFB
SENS
RSEG
MSEG
GAPL
Detection Off/On
DIR
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 14 -
March 06
The best explanation for the use of the table are some representative examples:
- 42 21 0C 07 4D 01 24
- 42 00 23 06 3F 4D
Host no. 35 asks all detectors for the setting of the Parameter
MSEG, the next example could be one of the responses
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 15 -
March 06
Meaning
Meaning
Remarks
Watchdog Reset
Power Fail
EEPROM-CRC error
Meaning
Remarks
10
11
illegal value
12
unknown function
13
unknown parameter
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 16 -
March 06
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 17 -
March 06
If there are connected network detectors, powered up at the same time, you should get the
detector startup messages as well:
M;1;01
M;2;01
M;3;01
M;n;01
If you get garbled messages or nothing on your terminal, check the baudrate and other data
transmission parameters ( 8 data , No parity, 1 stop bit).
4.2 Adapter detector data output
The data are delivered as follows:
M; d ; d
F ; d ; d
W; d ; d
P ; d ; A f
P ; d ; B f
P ; d ; S d
parameter SENS 1 16
P ; d ; R d
parameter RSEG 5 - 80 cm
P ; d ; Md
parameter MSEG 5 - 40 cm
P ; d ; G d
P ; d ; D d
P ; d ; C d
P ; d ; I d
P ; d ; T d
P ; d ; V f
D ; d ; d ; f
measured data unidirectional modes (oncoming or leaving) speed in km/h, reflection value, net gap 0.00-655.35 s
O ; d ; d ; f
L ; d ; d ; f
All binary detector data values are reformatted by the adapter and delivered as ASCII decimal or
float values, the length of the ASCII strings depends on the data and address values ( 1-15).
The LRC or CRC checksums for binary data blocks on the RS485 network is tested and the
receipt (detector address) is given. For the RS 232 side no checksum is supported.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 18 -
March 06
For the description of the parameters see chapter 2 Falcon Net II program parameter set, for the
description of error and message numbers see chapter 3.4.2 general messages and warnings and
chapter 3.4.3 error messages.
4.3 Adapter detector parameter input or request
The command line input to initialize or change the detector parameter set is as follows:
Start letter A, detector address, P, parameter type, parameter value
The command line request to get the data of the detector parameter set is as follows:
Start letter A, detector address, ?, parameter type
For the parameter type the underlined letter of the parameter name, see tables chapter 2 and 3.4,
for example D for DETE (Detection on/off) has to be used.
- Example 1:
Set the parameter SENS = 2 for detector no. 8:
A8PS2
- Example 2:
Request the parameter setting of ADJFA for all detectors: A0?A
For the description of the parameters see chapter 2 Falcon Net II program parameter set, for the
description of the detector addressing see chapter 3.3 network addressing.
All lowercase input letters are automatically converted to uppercase by the adapter. The
backspace character can be used to delete wrong characters in the adapter input line buffer. Input
lines must be completed with carriage return or line feed (<Enter> key).
There is no time limit for the completion of an input string. Data messages from the detectors
may split an command insertion on a connected terminal.
4.4 Adapter parameter, Escape sequences
When receiving an ESC (1B hex) character a short listing of Escape sequences is send from the
adapter to a connected terminal
! Selection
! C-CRC
! D-Delimiter
! E-Echo
Inserting C, D, E selects the options prescribed in the following chapters. Automatic
programming sequences may send ESC and selection character without delay and ignore the
menus.
Be aware that the following interior parameters of the adapter are volatile and get lost after power
down.
4.4.1 Terminal echo
Every data input character from a connected terminal is echoed (start-up default). You can switch
off the echo with the input sequence ESC E (1B 45 hex) and the adapter message
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 19 -
March 06
! echo off should appear. This is a toggle switch, therefore repeating the action switches the echo
on again. The escape sequences by themselves are never echoed.
4.4.2 Delimiter, output data field separation
The default delimiter (;, semicolon) for the data output can be changed. The escape sequence
ESC D delimiter changes the so far delimiter to the new one. Following delimiters are possible:
horizontal tab (0B hex), space (20 hex), colon (2C hex) and semicolon (hex 3B).
Especially for a tabular formatted data output the horizontal tab delimiter will be of interest.
4.4.3 Checksum selection for the network data protocol
Several network data block checksum types are supported, see chapter 3.4.1. The escape
sequence ESC C (1B 43 hex) activates a menu, where the checksums can be chosen:
! Select Checksum:
! 0 - LRC
! 1 - CRC 11021 hex
! 2 - CRC 8408 hex
! Choose 0,1 or 2? 2
! CRC 8408 set
After selection the current active checksum for the adapter is changed as well as the checksums
for all detectors in the network.
After power-on the adapter starts always with the LRC checksum. Meanwhile the detectors start
with the former EEPROM parameter set checksum. Therefore the adapter checksum must be
toggled immediately after the power-on message of the adapter if the detectors use the CRC-type
checksums to enable network communication.
4.5 Adapter error messages
Error messages
! Adapter RS232 line too long
Meaning
The input line length was more than 18
characters, for this reason the line was
erased
Though the RS485 FIFO input buffer is 60
data blocks deep, an overrun occurred, you
need to increase the RS232 data
transmission speed or take out some
detectors of the net
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 20 -
March 06
11 x 11
Doppler-Radar
24.125 GHz, K-band
100 mW EIRP, 5 mW directed
Type of Detection:
Measurement
Installation Angle
45
RS485-RS232
Falcon Net II
Adapter II
Height
91 mm
25 mm
Width
122 mm
67 mm
Depth
120 mm
91,5 mm
Weight
1000 g
150 g
Drawing 3- Housing bottom
After loosing the 4 screws of the cover, 4 holes for M4 screws are visible near the edges of the
main housing, positioned in the corners of a 106 x 82 mm rectangle, see also drawing 1.
Typically the detector will be mounted to a location specific adapter fixture by using these holes.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 21 -
March 06
Cable gland
PG9
Cable gland
PG7
Male socket
Binder 723
Protection class
IP 68
IP68
IP65
IP68 *
Cable diameter
6 - 9 mm
4 - 6 mm
5 or 6 mm
Delivery term
standard
on demand
on demand
on demand
* External sockets have IP 68 protection class but only if locked with the coupling connector.
The dual cable gland (PG11) is used for the pass through of two cables through the housing if the
communication/power supply cable shall be wired through directly from detector to detector.
This dual cable glands do not have a traction relief.
The coupling connector for the Binder 723 socket can be delivered on demand.
Cables for outdoor purposes, ultraviolet light resistive are made of polyurethane, other cables
will degenerate after several years. Calculate the voltage drop if a detector net is powered from a
remote power supply before choosing the cable. As mentioned before at minimum a shielded
twisted pair cable should be used to get optimal data transfer performance.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 22 -
March 06
RS485-RS232 Adapter II
Microcontroller:
Program Memory:
16 KB ROM + 1 KB SRAM
16 KB ROM + 1 KB SRAM
Interface Standard:
RS 485
RS485, RS232
Data Output
Network Topology
2-wire bus
2-wire bus
Transmission Procedure
CSMA/CD
NET II
Series-connected protective
diode
RS485-RS432 Adapter II
Series-connected protective
diode @ 12 Volt
Zener-diode @ 5 Volt
Varistor 38 V,
Suppressor-diode 28.5 V
(600 W, 1 ns response time)
Zener-diode 5V6
Miniature fuse 1 A
8 kV contact discharge
8 kV contact discharge
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 23 -
digital FALCON
Ratings
March 06
NET II
RS485-RS432 Adapter II
MIN
TYP
MAX
MIN
TYP
MAX
Units
12V Input
12
36
12
16
5V (regulated) Input
4.5
5.5
60*
75*
90*
100*
mA
Voltage supply:
Current @ 12 Volt
Ripple voltage (12V)
f < 100 Hz
f < 1 kHz
100
100
mV
f < 10 kHz
20
100
mV
2.4
13
25
-13
Diff. Voltage A, B
2.4
13
25
-13
100
100
Input sensitivity
mV
Driver load
120
60
120
60
-60
60
-60
60
mA
-30
30
RS232 driver:
Driver load
Temperature Range
MTBF @ 70 C
-40
+85
7.3
70
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 24 -
March 06
Ground
+ Vcc
terminal
terminal
10
RxD
TxD
Ground
+ 5V Input
+ 12V Input
10
Ground
+ 5V Input
+ 12V Input
terminal
terminal
To supply power to the Adapter use either the 5 Volt or the 12 Volt Input at the RS232 or the
RS485 connector. The power pins ( 9 and 10 ) at the RS232 connector are not connected at the
standard RS232 PC connectors, in doubt check your I/O Card description for the pin connections
of your RS232 PC or terminal interface to avoid short circuits.
The 5 Volt Input powers the digital circuits and the microprocessor directly and the supply
voltage has therefore to be stabilised.
FALCON NET II
- 25 -
March 06
The data transfer speed has to be set for all detectors and hosts on the network bus identically.
The detector data transfer speed can only be set to fixed rates (see table below) by the baudrate
dip switch located in the upper right corner on the pcb, see drawing above. The baudrate dipswitch setting gets effective after the next detector
Switch no. 1 Switch no. 2 Baudrate
power-on.
On
On
9600
Default setting ex factory:
9600 Baud
On
Off
Off
Off
On
Off
19200
57600
115200
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 26 -
March 06
Start
Power on
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 27 -
March 06
Falcon
no. 1
Falcon
no. 2
Falcon
no. n
In-house prewired detectors with one cable to additional connector boxes at the mounting spot
T-connected with the combined
RS485 interface
bus/power supply cable. Thick
and
wires with large cross sections
230V AC/DC
Power supply
are possible in between
connecting boxes. No wiring
Falcon
Falcon
Falcon
and opening of detectors on the
no. 1
no. 2
no. n
mounting site, still quite easy
replacement. Higher material
costs for connector boxes. Normal cable glands PG7 or PG9 or male socket connectors are
used, see chapter 5.4.
As above but with one
cable for the power
supply and one for data
bus connected to the
detector cables in the
connector box. Best
choice for long distances.
RS485 interface
and
230V AC/DC
Power supply
power cable
data bus cable
Falcon
no. 1
Falcon
no. 2
Falcon
no. n
Dont forget to note which cable pass through the housing you need when you order the
detectors, see chapter 5.4.
The maximum bus cable lengths depend highly on cable quality (twisted pair, copper wire cross
section and shielding) and on the necessary data transfer speed. Cable lengths of 1km @ 115200
Baud are standard, data cable lengths of 10 km @ 9600 Baud have also been implemented by
customers.
The possibility to operate an already existing network additionally with the Falcon Net II data
protocol had been realized by customers. Although the Falcon network ignores all messages not
fitting in the data protocol frame the interference and the drop of data transfer capacity must be
tested in every new application.
The use of repeaters for very long distances is limited due to the Falcon network data protocol
handshake timing and the signal propagation delay of cable and repeater. The handshake
response must reach the detector within 5 ms, see chapter 3.5.
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 28 -
March 06
Declaration of Conformity
in accordance with the Directive 1999/5/EC (R&TTE Directive)
The manufacturer:
Intended purpose:
Type:
Radio equipment
Equipment class:
Complies with the essential requirements of article 3 of the R&TTE directive, when used for its intended
purpose:
- Health and safety requirements pursuant to article 3.1a, according low voltage directive 73/23/EEC
- Protection requirements concerning electromagnetic compatibility article 3.1b, according electromagnetic
compatibility directive 89/336/EEC
- Air interface of the radio systems pursuant to article 3.2
Harmonised standards applied:
EN 60950-2: 2001
EN 55022: 1998 + A1: 2000
EN 61000-6-2/-4: 2001
EN 300440-1(V1.3.1)/-2(V1.1.1)
EN 301489-1/-3(V1.4.1)
Address:
Via traffic controlling
Maybachstra e 39
D-51381 Leverkusen
Place, date of issue: Leverkusen, 19. April 2005
Name and signature: Dipl.-Ing. (FH) J. Ge ler
7.2 Notification
The digital Falcon Net II was tested by an accredited test laboratory according the standards ETSI
EN 300440 and ETSI EN 301489 and can be operated within the European Community
including Norway.
Additional national licences concerning EMC or radio emission matters are not necessary within
the European Community, restrictions concerning the operation of the Falcon Net II are not
known.
The notification according EC directive 1999/5/EG (R&TTE) Article 6.4 has been done in the
following countries (till the 17.02.04):
Germany, France, Great Britain, Italy, Luxembourg, Netherlands, Norway1, Austria and Sweden
If the country where you like to operate the system is not listed, please contact us, we will make
the necessary notification then as soon as possible.
for "short range devices" till 100 mW EIRP in the band 24.0 till 24.25 GHz not necessary, see Norway Post and
Telecommunication Authority, Regulation no. 1399 of 20 December 2000 on Authorised Frequency Use
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50
FALCON NET II
- 29 -
March 06
via traffic controlling GmbH - Maybachstr. 39 - 51381 Leverkusen Phone +49-2171-5049-30 Fax: -50