Optimisation - of - Water Treatment System
Optimisation - of - Water Treatment System
Drinking-water Treatment
Systems
Resources for the Drinking-water
Assistance Programme
Contents
1
Introduction
2.1
2.2
2.3
2.4
2
6
6
6
10
4.1
4.2
4.3
4.4
4.5
10
10
12
14
18
Minimisation
River intakes
Infiltration galleries
Bores
Springs
Improving Pre-treatment
21
5.1
5.2
21
22
Roughing filters
Raw water storage
25
6.1
6.2
25
27
Cartridge filters
Media filters
Improving Disinfection
32
7.1
7.2
32
36
Chlorination
Ultra violet light
39
41
10 Worked Examples
42
iii
List of Tables
Table 1:
Table 2:
Table 3:
Table 4:
Table 5:
Table 6:
Table 7:
Table 8:
Table 9:
Table 10:
Table 11:
Table 12:
Table 13:
12
14
17
20
22
23
24
27
30
35
38
40
41
List of Figures
Figure 1:
Figure 2:
Figure 3:
Figure 4:
Figure 5:
Figure 6:
Figure 7:
Figure 8a:
Figure 8b:
Figure 9a:
Figure 9b:
Figure 10a:
Figure 10b:
Figure 11:
Figure 12:
Figure 13:
Figure 14:
Figure 15:
Figure 16:
Figure 17:
iv
1
3
4
10
12
15
18
21
21
25
25
28
28
28
28
33
36
42
43
44
Introduction
This booklet provides information about the supply of safe drinking-water to small water
supplies serving fewer than 5000 people.
The intention of optimisation is to achieve the most effective and efficient use of a water
treatment plant which includes getting the best out of each piece of equipment that is
part of the supply as well as operating and managing the supply in a way that produces
the best quality of water possible.
Part of optimisation is to look at each piece of equipment and make sure it is working as
well as it can. But, in addition to this concern with the contribution of individual parts of
the plant, it is important to focus on the overall performance of the plant. This is
because the performance of each part of the plant depends on the performance of the
parts that come before it. For example, the performance of the ultra violet (UV)
disinfection unit in Figure 1 will depend on the turbidity level of the water leaving the
cartridge filter. In turn, the performance of the cartridge filter will be dependent on the
performance of the multimedia filter system. All parts of the system will perform better
if they are run for long periods of time, or even continuously, rather than being stopped
and started.
Figure 1: Schematic diagram of a treatment process
Tank
Sodium Hypochlorite
dosing system
UV
Cartridge
Filters
Multimedia
Pressure filter
Township
Pump
Stream
Optimisation aims to improve the quality or quantity of water that is delivered from a
water supply. It can be achieved most easily if a logical and consistent approach is
adopted.
2.1
The first step is to systematically gather information about the system and how it
performs. Examples of useful information are as follows.
1.
Before making any changes to the system or how it is used, it is important to properly
understand the layout and interrelationships among all of the pieces of equipment. A
schematic drawing of the plant can help to work out the way the treatment process
works (see Figure 2). It should include the method of collecting information that
provides evidence of how well it is operating. Some plant problems are directly related
to the design, some are related to operation.
The diagram needs to show the treatment steps in order, where the flow goes and
where measurements are taken.
For each process the objectives, such as quality, flow, pressure and level, need to be
listed. For example, for a cartridge filter, which would normally have a turbidity target,
measurements may be taken for turbidity, upstream pressure and downstream
pressure. The turbidity could be measured by taking an onsite grab sample, a sample
for laboratory analysis or using a permanently installed meter.
Each measurement place should be included on the diagram.
Multimedia
Filter
Cartridge
Filter
Differential
Pressure
Turbidity
monitor
UV
Disinfection
Distribution
2.
UV Intensity
Sensor
Visual observations
Daily records of operational settings and activities are also useful in diagnosing the
causes of performance problems. In addition, keeping a record of operations and
maintenance can assist in having a reminder that something needs doing, especially if
it is something that happens only infrequently.
Here are some areas that the records should cover:
water quality data
water production / demand
changes to plant operation
consumption of power and or other resources
timing of maintenance.
The records should include who did the work, why and when they did it and what they
did. It is useful to include the targets that need to be achieved alongside the values that
are being recorded.
4.
Evaluation
Each part of the plant operation needs to be looked at in terms of when it happens and
what effects it has. Ideally data would be gathered over a long period. It may also be
useful to collect other information or take measurements over a shorter period.
If data (or a trend) can be shown on a graph, then changes in performance can be seen
clearly and possibly related back to see what caused a problem. It is also helpful to
draw related data on the same chart so that the relationships can be seen easily. For
example, you might draw a graph of plant flow and filter turbidity over a day to see
whether the flow is affecting the turbidity (see Figure 3).
Figure 3: Trend of turbidity over time
3
2.5
Flowrate
Turbidity
2
1.5
1
0.5
0
08:00
12:00
16:00
20:00
00:00
04:00
08:00
5.
Once you have an idea of what affects plant or process performance, the areas in
which there is potential to make improvements or adjustments will be clearer. It may be
necessary to plan how to adjust the process to test a theory. If there is a risk to water
quality, then the water used should be run to waste rather than put into supply.
The following is an example of information that might be recorded at a small water
treatment plant where water is filtered though a multimedia filter and a cartridge filter,
then disinfected with UV light. The choice of what to record and when depends on the
particular circumstances including what risks apply to the water supply.
Reading
Unit
12/5/08
0915
13/5/08
1030
14/5/08
0900
mm
12
River level
1.2
2.5
1.8
105060
106991
108925
(1725)
(1931)
(1934)
(Difference)
Multimedia filter backwash time
time of day
0930
1100
1000
kPa
250
230
250
kPa
100
60 (replaced cartridge)
200
UV intensity meter
OK
OK
OK
OK
Cleaned lamp
OK
0.5
0.5
0.4
Example 2:
mg/l
Reading
Unit
12/5/08
0915
13/5/08
1030
14/5/08
0900
NTU
0.5
50
18
NTU
0.3
0.8
Checked system pressure
reading, cartridge was unloading
0.6
E. coli test
CFU/100 mL
2.2
When optimising a plant, it is helpful to pay close attention to the parts of the plant that
have the most impact on performance. The most important areas are called critical
points.
A critical point is a point in the treatment process at which, if the operators do their job
well, the likelihood of good water quality is increased. Conversely, if a poor job is done
at this point, there is a higher likelihood of poor water quality.
To be a critical point there must be something that can be measured and for which
acceptable limits can be set. A target should be set that will lead to action before
there is an unacceptable deterioration in water quality.
The critical point should be monitored sufficiently often to reveal any failures in a
timely manner.
There should be procedures in place to correct any deviation from the target value.
2.3
No plant can be operated at its optimum without a good operator who is available when
needed. An operator should have the right support and training. They need to have
delegated authority to get things done and back-up to cover for time off.
For example, support could come from someone operating another water supply
nearby. It could be helpful to arrange regular meetings to form a relationship and share
resources.
Operator training is important if a water supply is to improve. While training is available
from formal courses, the benefits of informal collaboration with other operators should
not be overlooked.
A vital part of the support of operators is creating manuals and documentation so that
someone with no more than an overview of the process can pick up operation. Good
documentation is important because sometimes the person who is picking up the water
treatment role may normally have a different role (eg, as a teacher or an interested
volunteer) and is faced with the task unexpectedly.
2.4
Risk management
The Ministry of Health promotes the process of risk management planning of public
health risks to control the hazards to a water supply. This process is an important part
of plant optimisation.
The public health risk management plan will have identified situations that have the
potential to make the water unsafe or stop the flow of water. Such situations might be
routine events like contamination of the source (eg, a landslide upstream of the intake),
pump failure, power failure or a broken water main. They will also include uncommon
events like backflow, natural disasters, chlorine gas leaks and fire.
Preventive measures will have been identified. They will outline how these problems
will be managed around to prevent contamination when the event arises.
A contingency plan is a plan to be followed should the preventive measures fail to
prevent a hazard. Issues that should be considered include public warnings, access to
the plant site, back-up personnel, repairs to equipment and use of alternative
equipment.
One of the hazards that can affect a water supply is vandalism. Sufficient security
needs to be in place to deter a wayward child. A determined adult is very difficult to
protect against.
Plant maintenance and performance checking are very important if the plant is to
operate reliably. Maintenance will extend the useful life of equipment and will help to
avoid breakdowns and emergencies. Performance checks will demonstrate whether
equipment is deteriorating before it becomes critical.
Routines for maintenance tasks should be planned in advance and described in
procedures. The purpose of this process is to ensure that work is not forgotten and that
there is a system to allow others to step in when needed. Worksheets can be used as
a reminder to do the work and as a record after the work is completed.
Here are some rules of thumb for good plant maintenance.
Keep everything clean, orderly and organised. This sets the scene for careful
operation and pride in the supply. A water treatment plant should be viewed as a
food factory that is producing 24 hours per day. A high standard of hygiene should
be set for the water treatment plant.
Develop a plan for plant operation and follow it. Of course the plan can be modified
when needed.
Follow an inspection and lubrication routine for each piece of equipment. Schedules
and procedures should follow manufacturers recommendations unless experience
can demonstrate that they should be changed. Historically many problems have
been due to misunderstanding or failing to follow these recommendations.
Keep records of maintenance and repair for each piece of equipment. These
records will show which items of equipment are difficult and expensive to operate
and maintain as well as acting as a reminder to check on regular maintenance
issues.
Establish a plan for maintenance of the plant structures. Cleaning, painting and
repair are important for long service-life. Usually water is treated in wet, corrosive
conditions and protective coatings need to be periodically repaired. The failure to
repair concrete surfaces can expose reinforcing steel, eventually weakening the
structure.
Good plant records can be extremely valuable when making plans to improve plant
performance, or when deciding on replacements for failed equipment. Example 3
below shows the sort of information that might be entered into a maintenance record.
Example 3:
Equipment data
Manufacturer, model, serial number, power rating, maximum flow rate, etc
Date
Record
Operator initials
25-01-07
AM
10-02-07
AM
20-02-07
PE
28-02-07
PE
10-03-07
AM
11-03-07
PE
4.1
Minimisation
4.2
River intakes
River intakes can take a number of forms but generally include a weir to control the
water level and a screened intake to withdraw the water (see Figure 4). Behind the
screen there is likely to be a stilling chamber to collect sediment so that it does not
accumulate in downstream pipework.
Figure 4: Common features of a river intake
Screen
Weir
Stilling Chamber
River Flow
Outlet
10
Operating targets
The design of the structure and the screens needs to remove floating debris, fish and
sediment such as sand and gravel. The location needs to be selected either to make
use of natural scour holes and the way that watercourses transport sediment, or to
minimise the effort needed to clear away deposited material.
Water quality records
Records for the intake may be required as part of the resource consent conditions.
Details may include, for example:
abstraction flow rate
residual flows
impact on watercourse of cleaning screens and scouring away sediment
effectiveness of fish passage
river conditions, including:
river levels
turbidity
Escherichia coli (E. coli).
Inspection (and recording)
The inlet should be checked at appropriate intervals for:
accumulation of debris on the screen and in the sand trap and pipework
seepage and bypassing of water
valve and penstock condition
corrosion of steelwork
erosion undermining the structure (this must be repaired immediately)
cracks in the concrete structure.
Maintenance (and recording)
The screen and stilling chamber (sand trap) will normally need regular cleaning to
remove debris. Any damage will also need to be repaired. The amount of work
required will depend on the river conditions.
Valves and penstocks need to be operated through their range at regular intervals to
prevent seizing. Instruments such as those recording water level and turbidity will need
regular calibration.
If the system incorporates a mechanical system to clear debris such as air blowers,
then these will need maintenance as well.
Table 1 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case.
11
Table 1:
Indicator
Possible problem
Solution
Changing watercourse
4.3
Runoff
Infiltration galleries
12
Operating targets
The design of infiltration galleries should strike a balance between ensuring good flow
into the gallery and achieving a degree of water treatment by filtration and adsorption
on to the sediments. Some galleries will remove large material like leaves and silt but
have no real effect on turbidity and other contamination. Others will considerably
reduce the turbidity of the water and make a real difference to the water quality. The
operating target for the gallery will depend on raw water quality, river bed conditions
and groundwater levels.
Water quality and quantity records
Records should cover intake performance against resource consent limits, for example:
abstraction flow rate
residual flows
impacts on watercourse of scouring away sediment from the river bed.
Gallery outlet conditions to be recorded include:
turbidity
E. coli.
Inspection (and recording)
Flow rates should be monitored for any unusual reduction or increase in flow that might
relate to the condition of the gallery.
The condition of the structure and equipment should be checked regularly. The
inspections should include:
looking at the general condition of the base of the pump well, inlet pipes, mounting
brackets, covers and hatches
checking the general condition of the pumps, flow meters, level switches and valves.
It is difficult to estimate the amount of sediment in the pipes simply by looking, given
that the pipes are below the water level. Instead it may be possible to detect the need
for cleaning by a larger draw down than normal within the pump well (if there is one) for
a given pumping rate.
Maintenance (and recording)
A significant problem for infiltration galleries is blockage of the perforated pipes with fine
sediment. Although many infiltration galleries are equipped with a reverse pumping
feature, or air blowers, sediment can still cause problems.
Regardless of any previous sediment problems in gallery pipes, it is a good idea to clean
out all these pipes every two years or so. If no sediment, or very little, is found, then the
regular cleaning could be reduced accordingly. Clearly it is essential to have an easy
means of access to galleries so that this periodic cleaning of sediment is possible.
13
Sometimes it is necessary to hire a digger to scarify the bed of the river to free up the
sediment so that water can flow more freely to the gallery. Obviously, care must be
taken not to damage the gallery! The local regional council should also be consulted
about its requirements.
Table 2 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case.
Table 2:
Indicator
Possible problem
Solution
Media becoming
blocked
Pump failure
Screen or pipework
becoming blocked
4.4
Bores
A bore is a well drilled into an aquifer (see Figure 6). There is often a screen at the
bottom that supports the material around the bore. If the water flows to the surface
without any need for pumping, the well is called artesian.
Normally a bore pump is needed to lift the water to the surface. These pumps are
powered by an electric motor that is designed to be submerged. The pump unit is
placed above the motor and under a check valve.
The top of the bore at ground level called the bore head or wellhead needs to be
constructed in such a way that surface water is prevented from entering the bore and
contaminating the bore water. This can be done by constructing a concrete apron
around the bore which slopes away from the centre where the bore pipe comes up. It is
important that the concrete apron does not have any cracks or holes which would allow
surface water infiltration.
14
Operating targets
Operating targets will depend on the bore design and the nature of the aquifer. If the
bore has secure status under the Drinking Water Standards, then a target of zero
contamination indicated by E. coli testing will be used to be sure that the water is safe.
Secure bores are generally deep if the aquifer is unconfined (no impervious layer
above it). If the bore does not have secure status, then the water needs to be treated
to remove or destroy microbial contaminants.
Treating bore water to achieve targets for chemical contamination is common. This
treatment is most often for one or more of turbidity, iron, manganese, corrosivity eg
carbon dioxide and sulphide.
The bore also needs to be operated to prevent excessive draw down of the water level
(which could damage the bore and pump) and to comply with resource consent limits
on abstraction rates. Care should be taken if the flow rate is to be increased
significantly, such as by installing a larger pump.
Water quality and quantity records
Records should be taken of intake performance against resource consent limits, for
example:
abstraction flow rate and volume
well level.
15
16
Table 3:
Indicator
Possible problem
Solution
E. coli detected in
groundwater that has
been assessed to
have secure status
Water contaminated by
sampling technique
Contaminated water
entering well from surface
Contamination of aquifer
Sand in well
discharge and/or
excessive pump
impeller wear
Cavitation caused by
inadequate pump
submergence
Sudden change in
flow rate
Change in turbidity or
colour
Pump vibration
A leaking pipe
Damaged pump
17
Indicator
Possible problem
Solution
Gradual decline in
pump flow rate
4.5
Springs
A spring is a place where water wells up out of the ground from an aquifer. Normally, if
the water is being collected for drinking, a chamber is placed around the point where
the water reaches the surface to protect it against surface contamination. Because the
water is at the surface or drawn from near the surface it is easily contaminated, both by
infiltration into the ground, and at the spring outlet (Figure 7).
Figure 7: Contamination of spring water
18
Operating targets
The level of treatment required for spring water depends on the risks associated with
the spring. Spring water is normally considered to be at risk from pathogens, and
spring structures need to be operated and maintained to prevent contamination.
Chemicals found in spring water are generally similar to those found in groundwater but
less likely to be present. Operating targets will depend on the spring design and the
nature of the aquifer.
Water quality records
Keep a record of:
performance against resource consent limits for example, abstraction flow rate and
volume
A washout valve should be opened regularly and the accumulated silt removed.
Any leaks into the chamber from the ground outside it must be repaired urgently.
Damage caused by erosion or by the soil settling could undermine the structure and
should be repaired.
When structural components (timber, steel and concrete) deteriorate, they should be
repaired.
Vegetation around the spring should be managed, as roots can find their way into the
aquifer and collection box, causing damage.
19
Table 4 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case.
Table 4:
Indicator
Possible problem
Solution
Increase in turbidity or
flow after rain
20
Improving Pre-treatment
5.1
Roughing filters
In New Zealand, the most common forms of roughing filters are steel screens, disc
filters (see Figure 8a) and media filters (as described in Section 6.2).
In general, the size of the openings controls the size of the particles that will be
removed and, as the openings get smaller, more pressure is lost. Either manual or
automatic flushing may be used to clear debris.
Another type of roughing filter is a horizontal flow gravel media roughing filter, which
operates primarily by settling out particles on to the media (see Figure 8b).
Figure 8a: Disc filter
Operating targets
Roughing filters will not remove fine sediment. However, although they can only
remove coarse material, they can still reduce the load on the treatment processes that
come later. For example, pre-filtration upstream of cartridge filters can reduce how
often the cartridge needs to be replaced.
Water quality and quantity records
Record operating conditions and water quality including:
water level
21
flow
backwash intervals
pressure loss
inlet/outlet turbidity.
Indicator
Possible problem
Solution
No difference in suspended
solids between upstream
and downstream samples
Damaged filter
Check filter
Blocked filter
Lack of flow
5.2
Raw water storage can be used to improve water quality in a number of ways.
1.
When untreated water is stored, the larger sediments will settle to the bottom
rather than go on to treatment , improving the quality of the water that is treated.
2.
Water storage can be used to allow the intake to be turned off when source quality
is poor. This process is called selective abstraction.
Raw water storage is not the only option. Treated water storage can also be used to
improve a drinking water supply. There are advantages and disadvantages of using
treated and untreated water storage and the two types of storage are compared in
Table 6 below. Treated water storage is covered in section 8.
22
Table 6:
Type of storage
Advantages
Disadvantages
Selective abstraction
Treated water storage
Operating targets
If turbidity is to be reduced to a significant degree, raw water needs to be stored for at
least one week or a coagulant must be dosed to increase the rate of settling.
Performance depends on many factors, including physical layout, turbulence and water
quality.
If the storage is used to allow the plant to remain off line during periods of heavy
contamination, then it must be a size that will allow time for the source water to
improve. A target should be set for maximum water turbidity, above which water would
not be taken for raw water storage and treatment.
Operating requirements for treated water storage are discussed in Section 8.
Water quality and quantity records
Keep a record of operating conditions and water quality, including:
water level
flow
inlet/outlet turbidity (and any other parameters being targeted)
stored water quality
overflow rate.
Inspection (and recording)
The tank or pond should be checked at appropriate intervals for:
accumulation of sediment, floating debris, vegetation, oil, scum, biological growths
seepage and bypassing of water
valve operation
23
physical condition.
Indicator
Possible problem
Solution
24
Filters physically remove particles, including protozoa, from the water. In many plants,
filtration is the only barrier to protozoa such as cryptosporidium. Therefore filters need
to be operating well at all times and their optimisation is particularly important.
A very low turbidity target is set for filters acting as a barrier to protozoa because it has
been found that this corresponds to good protozoa removal.
6.1
Cartridge filters
A cartridge filter consists of one or more filter elements which slot into a housing. The
cartridge can be made of a rigid or a flexible material and has to be thrown away when
it becomes blocked.
Cartridge filters are well suited to small water systems because they are simple and are
inexpensive provided that the cartridges do not need to be replaced too often (see
Figures 9a and 9b).
Figure 9a: Cartridge filter system
Operating targets
The size of the particles that have to be removed is related to the size of the holes in the
filter cartridge that allow the water to pass through. Filter cartridges are described as
having a pore size that is absolute or nominal. If a pore size is 5 microns absolute, then it
will remove all particles larger than 5 microns. If it is 5 microns nominal then it will remove
most of the particles that are larger than 5 microns. Probably about 90%. A maximum
pore size of 1 microns absolute is needed to remove protozoan cysts such as giardia and
cryptosporidium. Filter cartridges need to meet NZS4348 (1995) to confirm that the
cartridge removes protozoa effectively.
25
For the removal of inorganic material from the water, the following size ranges are
relevant:
clay, < 2 microns (ie, 0.002 mm)
silt, 220 microns
fine sand, 20200 microns.
Clearly a 3 micron filter will not remove very fine material such as clay, so water dirty
with clay will remain dirty. To reduce the turbidity due to clay, even 0.5 microns
absolute is sometimes insufficient and such small pore sizes can quickly block. To
reduce turbidity it will be necessary to try different pore sizes to find the size best suited
to the source water.
Water quality and quantity records
Keep a record of operating conditions and water quality, including:
inlet/outlet pressure
flow
inlet/outlet turbidity (and other parameters being targeted).
Inspection (and recording)
The filters should be checked at appropriate intervals for:
initial head loss or pressure differential (measured at start-up) compare with normal
figure and manufacturers specification: if it is lower than normal, there may be a leak
in one of the seals
cartridge condition
rise in pressure differential (or fall in outlet pressure) as the water passes through the
filter(s). The pressure differential will gradually increase as the filter blocks. If
pressure differential drops suddenly, then the filter may have burst, or it may have
unloaded some of the particles that it has collected.
26
Table 8:
Indicator
Possible problem
Solution
Excessive flows to an
individual filter
Ruptured cartridge
By concentrating particles in
one area, cartridge filters
can contribute to growth of
non-coliform bacteria
Refit cartridge
6.2
Media filters
In a media filter, particles in the water are removed by being trapped between grains of
sand or other material. Some are removed by simple straining but very small particles
can also be removed by attachment to the filter grains (see Figures 10a and 10b).
Because these particles are only loosely attached to the grains, the filter must be
operated very carefully to avoid disturbing the particles allowing them to pass further
through the filter. Regular and effective backwashing is also important to prevent
particles escaping from the filter material. Normally a chemical coagulant is dosed
27
28
Operating targets
Well-run, well-designed filters with pre-treatment can achieve very good quality water
with turbidity of less than 0.1 nephlometric turbidity units (NTU). Good performance for
a small-scale plant with fewer resources for operation and monitoring would be having a
filtered water turbidity of less than 0.3 NTU. With good pre-treatment, the operator can
achieve long and predictable filter runs, generally lasting more than 24 hours, before a
backwash is required.
The ideal backwash rate is specific to the size and density of the filter media. The
backwash process does not wash the filter media absolutely clean so there is an initial
turbidity spike when the filter is restarted. A useful procedure is to run the filtered flow
to waste for a period when the filter returns to service.
To optimise performance, it is necessary to:
remove as much of the particulate matter as possible by correct pre-treatment of the
water
avoid disturbing the particulate matter that has been collected in the filter
operate the filter with as little change to the flow rate as possible
backwash the filter effectively, and at the right time.
Water quality and quantity records
Keep a record of operating conditions and water quality (for each filter), including:
coagulant dose
pH
alkalinity
outlet turbidity
filter flow
head loss across media
water level in filter (gravity type only).
Inspection (and recording)
Some evaluation techniques that can be used to optimise the running of a filter are:
visual inspection during operation and particularly during backwash
comparing the length of filter runs.
Many elements of visual inspection are only possible for gravity filters as it is not
practical to view a pressure filter while it is running.
Maintenance (and recording)
Common maintenance tasks are:
filter bed cleaning
29
Table 9 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case. The shaded parts of the table are
more appropriate to larger systems, particularly rapid gravity filters and systems where
a coagulant is dosed. For small supplies, usually only the unshaded areas would need
to be considered.
Table 9:
Indicator
Possible problem
Solution
Visible mudballs or
cracking
Inadequate backwashing
Excessive flows to an
individual filter
Backwashing problems on
an individual filter
Backwash unable to
remove mud and silt
30
Indicator
Possible problem
Solution
31
Improving Disinfection
7.1
Chlorination
Dosing chlorine is an excellent method for killing bacteria and viruses in water. In water
supplies it is normally dosed as chlorine gas or as sodium hypochlorite. It can be
purchased as a liquefied gas in steel cylinders with a 68 kg capacity. Chlorine gas is
corrosive when in contact with moisture and is especially destructive to electrical
equipment. Thus sodium hypochlorite is often favoured over chlorine gas for small
systems. Sodium hypochlorite is much easier and safer to handle for a less
experienced operator. Calcium hypochlorite is also used in some small supplies.
For disinfecting water efficiently, high disinfectant concentrations work best because
they will kill microbes quickly. Unfortunately a very high concentration of chlorine can
make the water unpleasant to drink, as well as producing chemical reactions with
organic material in the water that lead to by products which over long periods of time
can be of significance to human health. For this reason, we tend to dose lower
concentrations and store the water for long enough for the chlorine to act. The lower
the chlorine concentration is, the longer the chlorine takes to disinfect the water. As a
rule of thumb, at typical chlorine concentrations, there should be at least half an hours
storage with no short circuiting before the first outlet to a water consumer.
Operating targets
The chlorine dose must be large enough so that, after the reaction with the water, there
is enough left over for a free chlorine residual in the water distribution system.
The pH has an impact on the effectiveness of the chlorine. When chlorine is dissolved
into water, it splits into two forms. The most useful disinfecting form is hypochlorous
acid (HOCl). Although varying slightly with temperature, about 78 percent of the
chlorine is in this active form at pH 7.0, but the proportion drops to only 28 percent at
pH 8.0 (see Figure 13). It is important that chlorine is dosed when the pH of the water
is at 7.0 and before anything causes the pH to increase. The pH should be kept below
8 through out the whole distribution system.
32
Figure 13: Relationship between pH and the form that chlorine takes in water
100%
All of the chlorine
is in the 'active'
form.
90%
80%
70%
60%
50%
40%
30%
None of the
chlorine is in the
'active' form.
20%
10%
0%
4
10
11
pH
Particles in the water can shelter microbes from the effect of the chlorine. For this
reason the water needs to be clean prior to disinfection. Ideally the turbidity should be
less than 1 NTU.
Water quality records
Traditionally, faecal contamination is detected by E. coli testing, however we have to
wait for up to 24 hours for the results of E. coli testing. We can test the chlorine
concentration to find out if we have a sufficient amount of chlorine to kill pathogens, and
get a result immediately. So when chlorine is used, testing it gives an immediate
indication of the level of disinfection being provided.
33
Keep records of operating conditions and water quality in the treated water and at
strategic points in the network, including:
free available chlorine concentration
pH
turbidity
E. coli.
Inspection (and recording)
The system needs to be inspected regularly to establish that it continues to be reliable.
There are two main issues that need to be covered.
1.
The accuracy of the dose rate needs to be confirmed to make sure that the correct
dose and residual are being achieved. The easiest way to confirm this is with an
on-line instrument but this may not be affordable in a small supply. Test kits are
also available to test the residual chlorine manually.
2.
It is good to calculate the usage of chlorine and compare it with the volume of water
treated. Then calculate the amount of chlorine used per cubic meter of water produced.
This is called a mass balance calculation.
Maintenance (and recording)
Common maintenance tasks are:
calibrating instruments
safety inspections, including testing for chlorine gas leaks in the case of a chlorine
gas system
changing chlorine cylinders (but never unaccompanied and always with personal
protective equipment).
34
Possible problem
Solution
Free available
chlorine declines
over time even
though the dose rate
is the same
pH is too high
35
Indicator
Possible problem
Solution
The sodium
hypochlorite pump
runs but no liquid is
pumped
7.2
Operating targets
As with chlorination, UV disinfection needs clean water to work well; particulate matter
in the water can shield the pathogens from the UV light. The turbidity of the water to be
disinfected should be less than 1 NTU.
The efficiency with which UV light passes through water can be tested by measuring
UV transmittance at 254 nm (the wavelength that is used to inactivate pathogens). This
36
transmittance should be more than 80 percent. It may be reduced by, for example,
organic material in the water. The concentration of such absorbing substances would
have to be reduced by treatment before UV could be used.
UV systems should be equipped with a UV intensity sensor which checks the UV level
in the unit to ensure a high enough dose is being provided to inactivate pathogens.
These systems need to be fitted with a shutdown switch to stop plant flow if the UV
intensity level drops too low.
Water quality records
Although requirements vary with the size of the supply, monitoring of operating
conditions and water quality may include:
UV intensity
UV transmittance
flow rate (total)
flow rate (each reactor) can be a flow restrictor for supplies
turbidity
lamp replacement hour meter
lamp outage
ballast temperature.
Inspection (and recording)
The unit should be checked at appropriate intervals for:
lamp operation and intensity
cleanliness of the quartz sleeve
lamp hours completed
any unusual noises from ballast cooling fans
valve operation.
Maintenance (and recording)
Common maintenance tasks are:
cleaning the lamps so that sufficient light passes into the water
replacing a lamp when UV intensity falls below the minimum needed for disinfection,
or when the lamp has operated for the rated number of hours, or when it fails
Table 11 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case.
37
Possible problem
Solution
UV
intensity
low
Replace lamps.
Decrease in UV transmittance of
the water the minimum
acceptable value is usually 80%
Lamp not
working
38
Storage facilities are needed to provide enough water for a given period so that the
plant can run at a more constant rate rather than have to match the water demand at all
times over a 24-hour period. They are also needed in case a failure interrupts the
supply from the treatment plant.
Operating targets
The size of the storage tank needed depends on the particular needs of the community
but the capacity for at least two days of water at the average flow rate is a good target.
Enough water must also be stored to provide:
time for the operator to arrive and fix problems at the plant when there is a
breakdown factor in more time if there is no automatic alarm to alert the operator to
problems
a buffer against times when a lot more water is used, such as during holiday periods
in a tourist destination or for fire fighting.
entry points for contamination, such as broken screens on the vents or roof, water
infiltration
39
One good way to remove sludge from the bottom of a tank, if it cannot be emptied
easily, is to use a swimming pool vacuum cleaner or a simple siphon.
Rough surfaces or crevices in the walls need to be prevented, or eliminated as soon as
possible, as these are a haven for slimes and biofilms, which can shield some
pathogens from chlorine. The risks are particularly high at the air-to-water interface and
on scum lines or rings.
Any work that involves entering the tanks must be treated as a confined space entry
and requires special standards for worker safety. The Department of Labour should be
consulted about this procedure.
Table 12 describes some important indicators of maintenance problems that may arise,
and identifies one or more solutions in each case.
Table 12: Problems and solutions related to maintaining water storage systems
Indicator
Possible problem
Solution
Poor mixing
Deterioration in water
quality when water levels
low; possible taste and
odour issues
40
Table 13 below lists some people and places that can provide more information.
Table 13: Sources of further information
Source
Expertise
TAP facilitators
All aspects
Operational advice
Regional council
Regional council
Capabilities of a particular
suppliers equipment
Water treatment
Environmental consultants
Master plumbers
Plumbers
For more detail, see also the Guidelines for Drinking-water Quality Management for
New Zealand (Ministry of Health 2005) available online at
http://www.moh.govt.nz/moh.nsf/indexmh/drinkingwaterinnz-assistanceprogramme
Chapter 1: Introduction
Chapter 2: Management of Community Supplies
Chapter 3: Water Sources
Chapter 4: Selection of Water Source and Treatment
Chapter 5: General Microbiological Quality
Chapter 6: Bacteriological Compliance (E. coli)
Chapter 7: Virological Compliance
Chapter 8: Protozoal Compliance
Chapter 9: Cyanobacterial Compliance
Chapter 10: Chemical Compliance
Chapter 11: Radiological Compliance
Chapter 12: Treatment Processes, Pretreatment
Chapter 13: Treatment Processes, Coagulation
Chapter 14: Treatment Processes, Filtration and Adsorption
Chapter 15: Treatment Processes, Disinfection
Chapter 16: The Distribution System
Chapter 17: Monitoring, Water Treatment and Drinking-water
Chapter 18: Aesthetic Considerations
Chapter 19: Small, Individual and Roof Water Supplies
41
10 Worked Examples
The following worked examples illustrate the techniques used for optimising water
treatment processes. Each is a real life scenario that draws on one of the preceding
problems and solutions tables.
Scenario 1: E. coli detected in groundwater that has been assessed to have
secure status
A simple bore takes water from an aquifer 40 m below ground level (see Figure 15).
The bore feeds water to a reservoir and is then pumped directly into supply. The bore
has been assessed previously to be secure but a routine water quality test produces a
positive result for E. coli.
Figure 15: Groundwater from a simple bore water system (Scenario 1)
Bore
To local community
Ground Water
Submersible
Pump
A secure bore should be free of pathogenic organisms due to its design and the nature
of the aquifer that supplies the water. When bacteria are detected in water from a
secure bore, it is a matter for serious concern and needs to be reported to a drinking
water assessor (DWA).
Table 3 (in Section 4.4) has addressed this indicator and the problems that may be
underlying it.
a.
The bacteriological sampling technique requires skill and care to avoid contaminating
the sample with organisms in the environment and on the hands of the sampler.
Making a mistake with sampling technique can lead to doubts as to the secure status of
the bore and concern in the community if a boil water notice is issued.
Because of the risks involved, if a positive result for E. coli is obtained from a secure
bore, the DWA must be informed.
b.
Because bores penetrate directly into an aquifer, water can track down the inside or the
outside of the bore casing to reach the clean groundwater below.
42
c.
There is a slight possibility that bacteria could be found in an aquifer that was previously
uncontaminated. For example, contaminated water could leak back into the bore and
pollute the aquifer at disused bores and monitoring bores where there is not continuous
water flow out of bore (which would purge it).
Scenario 2: High filtered water turbidity from a cartridge filter system
Cartridge filter systems rely on the simple entrapment of particles in, or on, the porous
structure of the cartridge (see Figure 16). In this scenario the operator has noticed that
the filtered water turbidity has become consistently high.
Figure 16: Cartridge filter system (Scenario 2)
Inlet
Pressure
Outlet
Pressure
Table 8 (Section 6.1) has addressed this indicator and the problems that may be
underlying it. Below is a more detailed explanation of the possible problems and their
solutions.
a.
The filter pore size would normally be selected when the filters are installed and would
not be changed afterwards. However, the situation may have changed in the
catchment such that there is now a need to remove smaller particles than previously (a
landslide in the catchment may have led to a high silt/clay load, for example). In this
case a cartridge with smaller pores may help to improve performance.
43
b.
As cartridge filters collect particles and become more clogged, the difference in
pressure between upstream and downstream can increase. This pressure difference
increases the force on the particles on the filter, with the result that some of them are
forced through. In this case, the cartridge should be replaced straight away.
c.
A ruptured cartridge obviously means that the water is getting little or no treatment.
There will be little or no difference in pressure between the upstream and downstream
sides of the filter. In this case, too, the cartridge should be replaced straight away.
Scenario 3: UV intensity decreasing
A small water supply uses a UV unit for disinfection (see Figure 17).
Figure 17: UV disinfection unit (Scenario 3)
Greensand
pressure filter
Bore
UV
Ground Water
Pump
Water is pumped from a bore and is high in manganese. A greensand filter reduces
manganese levels to improve the taste of the water.
The UV intensity sensor has activated a low-level alarm but the reason for the alarm
has not been identified yet. The community has been told to boil water before drinking
it, while the reason for the problem is located. The regular bacteriological testing is now
giving positive results for E. coli.
Table 11 (Section 7.2) has addressed this indicator and the problems that may be
underlying it. Below is a more detailed explanation of the possible problems and their
solutions.
a.
Iron and manganese will cause staining on the quartz sleeve at levels as low as
0.3 mg/L and 0.05 mg/L respectively. Pre-treatment is required to eliminate this
problem.
44
Therefore, if the greensand filter is not removing sufficient manganese, black deposits
will build up on the sleeves. These deposits can be wiped off, sometimes with the aid
of a chemical. The equipment supplier will provide instructions on this procedure.
Reasons for the poor manganese removal should be investigated. For example, the
greensand media may need to be regenerated with potassium permanganate.
The sleeve should be checked at regular intervals to ensure that it remains clean.
As an aside, hard waters can also lead to scaling, similar to the scaling inside kettles.
b.
The intensity of the light that a UV disinfection lamp gives off declines with age. The
lamp supplier will rate the lamp for a certain number of hours (for example, 10,000
hours). If the lamp has been running for more than the rated number of hours, it may
be time to replace the lamp.
c.
45