Monitor GE 1900 - 65A
Monitor GE 1900 - 65A
Monitor GE 1900 - 65A
Inputs
The 1900/65A provides four transducer inputs and four temperature inputs.
Software can configure each transducer input to support 2- and 3-wire
accelerometers, velocity sensors or proximity sensors. Each temperature input
supports Type E, J, K, and T thermocouples, and 2- or 3-wire RTDs.
Outputs
The 1900/65A provides six relay outputs. The user can configure the contacts of
these relays to open or close according to the OK, Alert and Danger statuses of any
channel or combination of channels.
The monitor provides four 4-20 mA recorder outputs. Software can configure each
recorder output to output any variable from any channel.
The signal for each transducer input is also available on a dedicated buffered
output.
A Modbus Gateway option is available. This allows the monitor to serve static
variables, statuses, event list, time and date information directly to any Modbus
client, including Distributed Control Systems (DCSs), Supervisory Control and Data
Acquisition (SCADA) systems, Programmable Logic Controllers (PLCs) or System
1. The monitor uses an internal counter and a time reference sent from the
Modbus client/master to generate time and date information. Users can upgrade
monitors ordered without the Modbus Gateway by ordering the 1900/01
Communications Upgrade (see the Ordering Information section). The 1900/65A
provides Modbus via Ethernet and a software-configurable 232/485 serial port.
Configuration
The user defines monitor operation and the Modbus Gateway register map by
creating a configuration file using software running on a laptop or PC and
downloading the file to the monitor through the built-in Ethernet connection. The
1900/65A permanently stores configuration information in non-volatile memory, and
can upload this information to the PC for changes.
Display Module
An optional display/keypad for viewing channel information or making minor
configuration changes allows the 1900/65A to operate as a stand-alone package. If
desired, the user can mount the display up to 75 metres (250 feet) from the Monitor
Module.
Page 1 of 18
Feature List
Acceleration or Reciprocating
Acceleration
Position
Speed
Acceleration and
Reciprocating
Acceleration
Channel Types
Acceleration
Variables and
Reciprocating
Acceleration
Variables
Vibration:
Acceleration
Enveloping:
Specifications
Inputs
Transducer Inputs
Users can configure Channels 1
through 4 to accept input from
acceleration, velocity or displacement
transducers.
Bias Voltage:
Page 2 of 18
Configuration
Options
Vibration
Variables:
Integrated:
Each variable is independently
configured with the following options.
Accuracy
Vibration
Variables:
Peak or RMS
Metric or English units
Filter corner frequencies
Full scale range
Acceleration integrated to velocity
Enveloped
Variable:
Filters
Vibration
Variable:
Enveloping
High-Pass:
Enveloping
Low-Pass:
Enveloped
Variable HighPass:
Velocity and
Reciprocating
Velocity Channel
Type
Velocity Variables
and Reciprocating
Velocity Variables
Vibration:
Bias Voltage:
Greater than Enveloped Variable
high-pass and less than Enveloping
high-pass 4-pole
OK Filter:
Input Impedance
3-wire Voltage
Mode:
Enveloped
Variable LowPass:
Bias Filter:
Bias Voltage:
-24 V
10 k
Configurable Options
Each variable is independently
configured with the following options.
Vibration
Variables:
Peak or RMS
Enveloped:
Page 3 of 18
Vibration
Variables:
Filters
Vibration
Variables:
0.5 Hz to 5.5 kHz, configurable
8-pole high-pass, 4-pole low-pass
Bias Filter:
OK Filter:
Bias Voltage:
Accuracy
Vibration
Variables:
Input Impedance
3-Wire Voltage
Mode:
Radial Vibration
Channel Type
Radial Vibration
Variables
Integrated:
Direct Filter 2:
Direct Filter
Characteristics:
Gap Filter:
-24 V
Vibration
Variables:
0.5 Hz to 4 kHz, configurable
10 k
Full Scale Range
Direct:
The Radial Vibration Channel Type
measures radial shaft motion using
proximity sensors.
Gap:
Accuracy
Vibration
Variables:
Input Impedance
Non-configurable:
Direct:
10 k
Configurable
Options
Gap voltage
Up to three bandpass filtered
amplitude measurements
Page 4 of 18
Thrust Channel
Type
Thrust Variables
Position:
Gap:
Position:
The Thrust Channel Type measures
axial shaft motion using proximity
sensors.
Gap:
Gap, voltage or position
Configurable Options
Position
Variables:
Filters
Direct Filter:
Filters
Direct Filter:
1.2 Hz 1-pole low-pass
Accuracy
Position
Variables:
Input Impedance
Nonconfigurable:
Gap:
OK Filter:
Accuracy
Position
Variables:
Gap:
Gap Filter:
OK Filter:
Configurable
Options
Gap Filter:
Mechanical position
Input Impedance
Non-configurable:
Speed Channel
Type
24 V
Speed Variables
1% of full scale range
10 k
Speed:
Up to four speed measurements
10 k
Gap:
Position Channel
Type
Gap, voltage
Page 5 of 18
Configurable
Options
Gap Filter:
Type J:
Each variable is independently
configured with the following options.
OK Filter:
Events Per
Revolution
EPR:
Accuracy
Speed
Variables:
Input Impedance
Nonconfigurable:
10 Cu
=0.00427:
Type K:
Type T:
Configurable
Options
Units:
Filters
Analog Filter:
0.001 to 1000
100 Pt
=0.00392:
0.5 RPM + 0.015% of reading
Accuracy
All Thermocouple
Types:
10 k
3-Wire RTD
(except 10
Cu):
3-Wire RTD 10
Cu:
2-wire RTD
Types:
50 Hz 1-pole, low-pass
Digital Filter:
120 Ni
=0.00672:
Input Impedance
Thermocouple
Inputs:
>1 M
Page 6 of 18
Maximum Operands
Relay Configuration
Maximum
Adjustment
Resolution
60 seconds
Latching or non-latching
independent of alarm status
0.1 second
50 per relay
60 seconds
Relay Specifications
Type
Single pole, double throw (SPDT)
0.1 second
Maximum Contact
Voltage
Relays
300 Vrms
150 Vdc
Relay Logic
The 1900/65A monitor has six relay
outputs that users can program to
open or close contacts according to
user-defined logic statements. Logic
statements use the OK, Alert and
Danger statuses of any channel, or
combination of channels as inputs.
Minimum Switched
Current
Maximum Switched
Power
100 mA @ 12 Vdc
160 W dc
1500 VA ac
Contact Life
100,000 cycles @ 5 A, 250 Vac
Logical Operators
Logical Operands
Sealing
Insulation
Resistance
Epoxy
Monitor inhibit
Monitor Not OK
Monitor Danger
Monitor Alert
Channel Not OK
Channel Danger
Channel Alert
Variable Danger
Variable Alert
Page 7 of 18
Electrical
Activate Reset
50 k or less (shorted)
De-activate Reset
Maximum Rated
Current
15 mA
Short Circuit
Current
Number of Outputs
Loop Supply
Voltage
Loop Resistance
Accuracy
Update Rate
Resolution
15.1 mA to 23.6 mA
4-20 mA Interface
21 to 24 Vdc
Transducer Supplies
Proportional Value
Reset
50 k or less (shorted)
18 to 36 Vdc
600 maximum
2% over operating temperature range
100 mS
10 A
Clamp Current
Page 8 of 18
Display
Buffered Outputs
Display Module
A single buffered output on the
Display Module provides access to
input Channels 1 through 4. The
signal does not have gain, and is not
scaled. This output is buffered to
provide short circuit and EMI
protection.
Power Requirements
550
Operating Current
Operating Power
Physical
Output Impedance
Bandwidth
40 kHz minimum
Weight
Mounting
DIN Rail Option
Bulkhead Option
Indicates when the monitor is
functioning properly
Weatherproof
Enclosure Option
Alert LED
Indicates an Alert condition
Danger LED
Bypass LED
Channel LED
Indicators
Display Module
OK LED
Monitor Module
Dimensions (L x W
x H)
Display Module
Dimensions (L x W
x H)
550
Bandwidth
Monitor Module
Status LED
18 to 36 Vdc
0.35 A typical, 1.0 A maximum
Monitor Module
Output Impedance
35 mm DIN rail
Bulkhead mounting plate
Page 9 of 18
Software
The 1900 Configuration
Software package contains
everything necessary to install,
configure, and maintain the 1900/65A
monitor.
Features
Environmental
Temperature
Operating
-20 to +70 C
(-4 to +158 F)
Storage
-30 to +90 C
(-22 to +194 F)
Humidity
Operating
95% non-condensing, maximum
Storage
Supported Transducers
Channel Type
Acceleration and
Reciprocating
Acceleration
200350 Accelerometer
330400 Accelerometer
330425 Accelerometer
Velocity and
Reciprocating Velocity
190501 Velomitor
330500 Velomitor
330525 Velomitor
330750 Velomitor
Radial Vibration,
Thrust, and Speed
Position
256 MB RAM
8 MB video card
8x or faster CD-ROM drive
100 MB available hard drive space
FOR REFERENCE ONLY
REFER TO DOCUMENT #173401
Page 10 of 18
EN 61010-1
CE Mark Directives
The 1900/65A monitor has the CE
mark and is approved for installation
within the European Union and
European Environmental Agency
regions. The monitor has been
designed and tested to meet the
following directives.
Safety
Requirements
EMC Standards
This product is tested to meet Council
Directive 89/336/EEC Electromagnetic
Compatibility (EMC) and the listed
standards, in whole or in part,
documented in a technical construction
file. EN61000-6-4 Generic emission
standard, Part 2, Industrial
Environment. EN61000-6-2 EMC
Generic Immunity standard, Part 2,
Industrial Environment.
EMC Directives
EN61000-604
Radiated
Emissions
EN 55011, Class A
Conducted
Emissions
EN 55011, Class A
EN61000-6-2
Electrostatic
Discharge
EN 61000-4-2, Criteria B
Radiated
Susceptibility
EN61000-4-3, Criteria A
Electrical Fast
Transient
Surge
Capability
Conducted
Susceptibility
Low Frequency
Conducted
Susceptibility
EN 61000-4-4, Criteria B
North American
EN 61000-4-5, Criteria B
EN61000-4-6, Criteria A
European
IEC 60945, Criteria A
@-20C Ta 70C
II 3G Ex nA [nL] IIC T4
Page 11 of 18
Ordering Information
1900/65A General Purpose Equipment Monitor
1900/65A-AXX-BXX-CXX-DXX-EXX
A: Power Option
B: Display Option
C: Mounting Option
00
18 to 36 Vdc
01
00
No display
01
02
03
Display with 10
unassembled PVC cable
04
05
Display with 10
unassembled TEF cable
06
07
Display with 50
unassembled PVC cable
08
09
Display with 50
unassembled TEF cable
10
11
12
13
14
15
16
17
00
None
01
Page 12 of 18
01
98
99
Update (CD)
B: Communications Option
01
Modbus communications
01
02
E: Communications Option
00
None
01
Modbus communications
Page 13 of 18
Accessories
Use the part numbers listed in this section to order spare parts or additional components for your 1900/65A General Purpose
Monitor.
Part Number
Description
167699-02
173400-01
172250-01
173089-01
02200794
02200121
168374
168495
168547-0010-01-01
168547-0010-01-02
168547-0010-02-01
168547-0010-02-02
168547-0050-01-01
168547-0050-01-02
168547-0050-02-01
168547-0050-02-02
168547-0100-01-01
168547-0100-01-02
168547-0100-02-01
168547-0100-02-02
168547-0250-01-01
168547-0250-01-02
168547-0250-02-01
168547-0250-02-02
168628
168629
168944
02295055
02245002
172555
169825-01
Training CD
Page 14 of 18
Dimensions
Note: All dimensions shown in millimeters (inches) except as noted.
Page 15 of 18
Page 16 of 18
Page 17 of 18
Page 18 of 18