Auto Transformer Connection

This document discusses the auto transformer connection. An auto transformer consists of a single winding that acts as both the primary and secondary winding, with a common connection point that allows adjustment of the output voltage. Auto transformers have advantages like reduced material costs compared to two-winding transformers due to shared windings. However, they cannot be used for all three-phase connections and have higher short circuit currents. Auto transformers are commonly used as voltage regulators and boosters in power transmission systems.

Uploaded by

Himdad Tahir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
871 views4 pages

Auto Transformer Connection

This document discusses the auto transformer connection. An auto transformer consists of a single winding that acts as both the primary and secondary winding, with a common connection point that allows adjustment of the output voltage. Auto transformers have advantages like reduced material costs compared to two-winding transformers due to shared windings. However, they cannot be used for all three-phase connections and have higher short circuit currents. Auto transformers are commonly used as voltage regulators and boosters in power transmission systems.

Uploaded by

Himdad Tahir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

(OHFWULFDO1RWHV

$UWLFOHV
SharingAbstracts,NotesonvariousElectricalEngineeringTopics.

$XWR7UDQVIRUPHU&RQQHFWLRQ
MAY9,2012 9COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2012/05/09/AUTOTRANSFORMER
CONNECTION/#COMMENTS)

 $XWR7UDQVIRUPHU&RQQHFWLRQ
AnOrdinaryTransformerconsistsoftwowindingscalledprimarywindingandsecondarywinding.Thesetwowindingsare
magneticallycoupledandelectricallyisolated.Butthetransformerinwhichapartofwindingsiscommontobothprimaryand
secondaryiscalledAutoTransformer.
InAutoTransformertwowindingsarenotonlymagneticallycoupledbutalsoelectricallycoupled.Theinputtothetransformer
isconstantbuttheoutputcanbevariedbyvaryingthetapings.
Theautotransformerisboththemostsimpleandthemostfascinatingoftheconnectionsinvolvingtwowindings.Itisusedquite
extensivelyinbulkpowertransmissionsystemsbecauseofitsabilitytomultiplytheeffectiveKVAcapacityofatransformer.
Autotransformersarealsousedonradialdistributionfeedercircuitsasvoltageregulators.TheconnectionisshowninFigure

(https://electricalnotes.files.wordpress.com/2012/05/111.png)
Theprimaryandsecondarywindingsofatwowindingtransformerhaveinducedemfinthemduetoacommonmutualfluxand
henceareinphase.Thecurrentsdrawnbythesetwowindingsareoutofphaseby180.Thispromptedtheuseofapartofthe
primaryassecondary.Thisisequivalenttocommonthesecondaryturnsintoprimaryturns.
Thecommonsectionneedtohaveacrosssectionalareaoftheconductortocarry(I2I1)ampere.
TotalnumberofturnsbetweenAandCareT1.AtpointBaconnectionistaken.SectionABhasT2turns.Asthevoltsperturn,
whichisproportionaltothefluxinthemachine,isthesameforthewholewinding,V1:V2=T1:T2
WhenthesecondarywindingdeliversaloadcurrentofI2AmperethedemagnetizingampereturnsisI2T2.Thiswillbe
counteredbyacurrentI1flowingfromthesourcethroughtheT1turnssuchthat,I1T1=I2T2
AcurrentofI1ampereflowsthroughthewindingbetweenBandC.ThecurrentinthewindingbetweenAandBis(I2I1)
ampere.ThecrosssectionofthewiretobeselectedforABisproportionaltothiscurrentassumingaconstantcurrentdensityfor
thewholewinding.Thussomeamountofmaterialsavingcanbeachievedcomparedtoatwowindingtransformer.The
magneticcircuitisassumedtobeidenticalandhencethereisnosavinginthesame.Toquantifythesavingthetotalquantityof
copperusedinanautotransformerisexpressedasafractionofthatusedinatwowindingtransformerAs
copperinautotransformer/copperintwowindingtransformer=((T1T2)I1+T2(I2I1))/T1I1+T2I2
copperinautotransformer/copperintwowindingtransformer=1(2T2I1/(T1I1+T2I2))
ButT1I1=T2I2so
TheRatio=1(2T2I1/2T1I1)=1(T2/T1)
Thismeansthatanautotransformerrequirestheuseoflesserquantityofcoppergivenbytheratioofturns.Thisratio
thereforethesavingsincopper.
Asthespaceforthesecondwindingneednotbethere,thewindowspacecanbelessforanautotransformer,givingsomesaving
inthelaminationweightalso.Thelargertheratioofthevoltages,smalleristhesavings.AsT2approachesT1thesavingsbecome
significant.Thusautotransformersbecomeidealchoiceforcloseratiotransformations.

(https://electricalnotes.files.wordpress.com/2012/05/24.png)
TheautotransformershowninFigureisconnectedasaboostingautotransformerbecausetheserieswindingbooststheoutput
voltage.Caremustbeexercisedwhendiscussingprimaryandsecondaryvoltagesinrelationshiptowindingsinanauto
transformer.
Intwowindingtransformers,theprimaryvoltageisassociatedwiththeprimarywinding,thesecondaryvoltageisassociated
withthesecondarywinding,andtheprimaryvoltageisnormallyconsideredtobegreaterthanthesecondaryvoltage.Inthecase
ofaboostingautotransformer,however,theprimary(orhigh)voltageisassociatedwiththeserieswinding,andthesecondary
(orlow)voltageisassociatedwiththecommonwinding;butthevoltageacrossthecommonwindingishigherthanacrossthe
serieswinding.

/LPLWDWLRQRIWKHDXWRWUDQVIRUPHU
Oneofthelimitationsoftheautotransformerconnectionisthatnotalltypesofthreephaseconnectionsarepossible.For
example,theYandYconnectionsarenotpossibleusingtheautotransformer.TheYYconnectionmustshareacommon
neutralbetweenthehighvoltageandlowvoltagewindings,sotheneutralsofthecircuitsconnectedtothesewindingscannotbe
isolated.
Aautotransformerconnectionistheoreticallypossible;however,thiswillcreateapeculiarphaseshift.Thephaseshiftisa
functionoftheratiooftheprimarytosecondaryvoltagesanditcanbecalculatedfromthevectordiagram.Thisphaseshift
cannotbechangedoreliminatedandforthisreason,autotransformersareveryseldomconnectedastransformers.

$GYDQWDJHVRIWKHDXWRWUDQVIRUPHU
Thereareconsiderablesavingsinsizeandweight.
TherearedecreasedlossesforagivenKVAcapacity.
Usinganautotransformerconnectionprovidesanopportunityforachievinglowerseriesimpedancesandbetterregulation.Its
efficiencyismorewhencomparedwiththeconventionalone.
Itssizeisrelativelyverysmaller.
Voltageregulationofautotransformerismuchbetter.
Lowercost
Lowrequirementsofexcitationcurrent.
Lesscopperisusedinitsdesignandconstruction.
Inconventionaltransformerthevoltagestepuporstepdownvalueisfixedwhileinautotransformer,wecanvarytheoutput
voltageasperoutrequirementsandcansmoothlyincreaseordecreaseitsvalueasperourrequirement.

'LVDGYDQWDJHVRIWKHDXWRWUDQVIRUPHU
Theautotransformerconnectionisnotavailablewithcertainthreephaseconnections.
Higher(andpossiblymoredamaging)shortcircuitcurrentscanresultfromalowerseriesimpedance.
Shortcircuitscanimpressvoltagessignificantlyhigherthanoperatingvoltagesacrossthewindingsofanautotransformer.
Forthesamevoltagesurgeatthelineterminals,theimpressedandinducedvoltagesaregreaterforanautotransformerthanfora
twowindingtransformer.
Autotransformerconsistsofasinglewindingaroundanironcore,whichcreatesachangeinvoltagefromoneendtotheother.In
otherwords,theselfinductanceofthewindingaroundthecorechangesthevoltagepotential,butthereisnoisolationofthe
highandlowvoltageendsofthewinding.Soanynoiseorothervoltageanomalycominginononesideispassedthroughtothe
other.Forthatreason,Autotransformersaretypicallyonlyusedwherethereisalreadysomesortoffilteringorconditioning
aheadofit,asinelectronicapplications,orthedownstreamdeviceisunaffectedbythoseanomalies,suchasanACmotorduring
starting

$SSOLFDWLRQV
UsedinbothSynchronousmotorsandinductionmotors.
Usedinelectricalapparatustestinglabssincethevoltagecanbesmoothlyandcontinuouslyvaried.
TheyfindapplicationasboostersinACfeederstoincreasethevoltagelevels.
UsedinHVSubstationduetofollowingreasons.
1. Ifweusenormaltransformerthesizeoftransformerwillbeveryhighwhichleadstoheavyweight,morecopperandhighcost.
2. ThetertiarywindingusedinAutotransformerbalancessinglephaseunbalancedloadsconnectedtosecondaryanditdoesnot
passontheseunbalancedcurrentstoPrimaryside.HenceHarmonicsandvoltageunbalanceareeliminated.
3. TertiarywindingintheAutoTransformerbalancesampturnssothatAutotransformerachievesmagneticseparationliketwo
windingtransformers.
About these ads (https://wordpress.com/about-these-ads/)

<RX0D\/LNH

FILEDUNDERUNCATEGORIZED


*UDYLW\LV
SHUVRQDOL]LQJWKHLQWHUQHW'LVFRYHU
KRZWKH\GRLWD\HDUDJR
JUDYLW\FRP*UDYLW\FRP
*UDYLW\FRP VSRQVRUHG 

AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

5HVSRQVHVWR$XWR7UDQVIRUPHU&RQQHFWLRQ
vilasksays:
May10,2012at7:49am
DearSir,Thanksforconsolidatingtheinformationontransformerstypeofconnection,Incidentallyifsomelightcanbethrown
onthetypeofvectorgroups&theirselectionforspecifictypeofapplicationsitshallbeofimmenseimportancefromacademic
pointofview.
SecondlyIwouldliketoknowinregardtoDOLstarters(notprovidedwithSinglePhasingpreventor)whytheOLRdoesnot
protectthemotorsfromgettingdamagedonsinglephasing.
Reply
SyedRizwansays:
May15,2012at1:45pm
Ialsowanttoknowaboutvectorgroups.Ihavesearchedalotbutcouldnotfindthatwhytransformersinusetodayhavevector
groupswithYd11orDy11andnotYd01orDy01??
Reply
ByjuRamachandrnsays:
July1,2012at7:56am
DearMr.Parmar
IwanttoknowabouttheREFconnectionandCTrationsforautotransformer100MVA,220KV/110KV
Reply
PremalKayasthsays:
July18,2012at5:17am
DeraJiignesh,

GreatWorkLookingformoreInformation.
Kindlyuploadsomethingusefulinfoaboutelectricaldesigning,Uhavethatbtwantsmore.
Regards,
Premal
Reply
Muthusays:
March30,2013at1:55pm
Whenatwowindingtransformerisconnectedasanautotransformeritsefficiencyunderfullloadis?
Answerme
Reply
natnaelshiferawsays:
October11,2013at7:54am
howcanbeachieveanautotransformer
Reply
Jignesh.Parmarsays:
October11,2013at2:35pm
bygivingorder!!!!.NotgettingPoint.
Reply
hamidsays:
December22,2013at9:39pm
Q.changetransformersbetweenphases(r,s,t)isimportantorno?
Reply
Jagatsays:
February14,2015at3:30pm
howtoidentifytheserviclinesofapole
Reply