AN1303 A Simple 4-20 Ma Pressure Transducer Evaluation Board
AN1303 A Simple 4-20 Ma Pressure Transducer Evaluation Board
AN1303 A Simple 4-20 Ma Pressure Transducer Evaluation Board
AN1303
INTRODUCTION
The two wire 4 20 mA current loop is one of the most widely
utilized transmission signals for use with transducers in
industrial applications. A two wire transmitter allows signal
and power to be supplied on a single wirepair. Because the
information is transmitted as current, the signal is relatively
immune to voltage drops from long runs and noise from
motors, relays, switches and industrial equipment. The use of
additional power sources is not desirable because the
usefulness of this system is greatest when a signal has to be
transmitted over a long distance with the sensor at a remote
location. Therefore, the 4 mA minimum current in the loop is
the maximum usable current to power the entire control
circuitry. An evaluation board designed to meet these
requirements is shown in Figure 1. A description of this
4 20 mA Pressure Transducer Evaluation Board, as well as
REV 3
AN1303
SENSOR
PRESSURE
PORT
PRESSURE
SOURCE
PRESSURE
SENSOR
TRANSMITTER
CIRCUITRY
TRANSMISSION
LINE
24 VDC
RL
CURRENT
METER
4 20 mA PRESSURE TRANSDUCER
INPUT TERMINALS
A schematic of the 4 20 mA Pressure Transducer
Evaluation Board is shown in Figure 3. Connections to this
evaluation board are made at the terminals labeled (+) and ().
Because this system utilizes a current signal, the power
supply, the load and any current meter must be put in series
with the (+) to () terminals as indicated in the block diagram.
2 mA
3
2
10 11
XDCR1
MPX7100
D2
1N4565A
6.4V @ 0.5mA
R3
39
4
1
R5
50
R2
1K
4
5
R1
750
1/2 W
U1
XTR101
6
3
1 2 14 7 13
R6
100K
12
Q1
MPSA06
+ 4 20 mA OUTPUT
D1
1N4002
C1
0.01F
R4
1M
RETURN
4 20 mA PRESSURE TRANSDUCER
PRESSURE INPUT
The device supplied on this evaluation board is an
MPX2100DP, a high impedance (10 k typ) 15 PSI sensor
which provides two ports. P1, the positive pressure port, is on
top of the sensor and P2, the vacuum port, is on the bottom of
the sensor. The system can be supplied up to 15 PSI of
AN1303
CIRCUIT DESCRIPTION
The XTR101 current transmitter provides two onemilliamp
current sources for sensor excitation when its bias voltage is
between 12 V and 40 V. The MPX2100 series sensors are
constant voltage devices, so a zener, D2, is placed in parallel
with the sensor input terminals. The zener and sensor
combination can be biased with just the two milliamps
available from the XTR101.
The offset adjustment is composed of R4 and R6. They are
used to remove the offset voltage at the differential inputs to
the XTR101. R6 is set so a zero input pressure will result in
the desired output of 4 mA.
R3 and R5 are used to provide the full scale current span of
16 mA. R5 is set such that a 15 PSI input pressure results in
the desired output of 20 mA. Thus the current signal will span
16 mA from the zero pressure output of 4 mA to the full scale
output of 20 mA. To calculate the resistor required to set the
full scale output span, the input voltage span must be defined.
The full scale output span of the sensor is 24.8 mV and is VIN
to the XTR101. BurrBrown specifies the following equation
for Rspan. The 40 and 16 m values are parameters of the
XTR101.
R span
OTHER CONSIDERATIONS
The 4 20 mA Pressure Transducer Evaluation Board has
been designed to demonstrate the performance of the
Motorola MPX2100 pressure sensor in conjunction with a
4 20 mA current transmitter. Several design considerations
should be considered when actually optimizing for an
application.
1. The optional external transistor, Q1, is recommended by
BurrBrown to increase accuracy by reducing temperature change inside the XTR101 package as the output
current spans from 4 mA to 20 mA. Also for power
supply voltages above 24 V, the 750 1/2W resistor, R1,
is recommended to limit the power dissipation in the
MPSA06 to below its 625 mW rating.
2. Keeping lead lengths short in the portion of the circuit
where the span adjust and zero adjust resistors connect
to the XTR101 is recommended to reduce noise pickup
and parasitic resistance.
3. C1 is a bypass capacitor and, therefore, should be
connected across pins 7 and 8 of the XTR101 as close to
the device as possible.
CALIBRATION
1. Connect the evaluation board as shown in the block
diagram of Figure 2.
2. With no pressure connections to the sensor, adjust R6 so
that Iout is 4 mA.
3. Supply 15 PSI to the sensor, (either positive pressure to
the pressure port or vacuum to the vacuum port) and
adjust R5 so that Iout is 20 mA.
4. You may need to repeat steps 2 and 3 to ensure proper
calibration.
CONCLUSION
This circuit is an example of how the MPX2000 series
sensors can be utilized in an industrial application. It provides
a simple design alternative where remote pressure sensing is
required.
AN1303
Table 1. Parts List for 4 20 mA Pressure Transducer Evaluation Board
Designator
Quantity
Description
Rating
1
1
4
4
2
2
C1
Capacitor
0.01 F
D1
D2
1
1
Diodes
100 V Diode
6.4 V Zener
Q1
Transistor
NPN Bipolar
R1
R2
R3
R4
1
1
1
1
Resistors, Fixed
750
1 k
39
1 M
R5
R6
1
1
U1
XDCR1
Manufacturer
Motorola
PHX CONT
Part Number
DEVB126
#1727010
50 V
1A
1N4002
1N4565A
Motorola
MPSA06
Resistors, Variable
50 , one turn
100 K, one turn
Bourns
Bourns
#3386P1500
#3386P1104
Integrated Circuit
Two wire current transmitter
BurrBrown
XTR101
Sensor
High Impedance
Motorola
MPX2100
1/2 W
15 PSI
NOTE: All resistors are 1/4 W with a tolerance of 5% unless otherwise noted. All capacitors are 100 volt, ceramic capacitors with a tolerance
of 10% unless otherwise noted.
4 20 mA PRESSURE TRANSDUCER
R4
DEVB126
REV
R6
R8
U1
XDCR1
R3
Q1
R1
C1
R7
R5
D1
R2
D2
AN1303
COMPONENT
SIDE
AN1303
NOTES
AN1303
NOTES
AN1303
AN1303/D