Siemens protection devices

Selection Guide
for SIPROTEC and Reyrolle
Edition 4

siemens.com/protection

Overview of Siemens Protection Catalogs

Selection
Guide for
SIPROTEC and
Reyrolle
6,3527(&
&RPSDFW 6,3527(&
'9'
',*6,
6,3527(&
7XWRULDO
7XWRULDO

SIPROTEC
Compact
Catalog

SIPROTEC 5
Catalog
Protection,
Automation and
Monitoring

5H\UROOH
'9'

SIPROTEC 4
Catalog
- SIPROTEC easy
- SIPROTEC
series 600
- Communication
- Accessories

Reyrolle
Catalog 1) 2)

 $YDLODEOHRQO\LQHQJOLVK
 ,QSUHSDUDWLRQ

Overview of Siemens protection catalogs

Protection selection guide:


The selection guide offers an overview of the device series of
the Siemens protection devices, and a device selection table.
SIPROTEC Compact catalog:
The SIPROTEC Compact catalog describes the features of the
SIPROTEC Compact series and presents the available devices
and their application possibilities.
SIPROTEC 5 catalog:
The catalog describes the system features and the devices of
SIPROTEC 5.

2 Selection Guide for SIPROTEC and Reyrolle Edition 4

SIPROTEC 4, SIPROTEC series 600, SIPROTEC easy,


communication and accessories:
This catalog describes the features of the device series
SIPROTEC 4, SIPROTEC series 600 and SIPROTEC easy, as
well as their devices. In further chapters, the accessories of
the complete SIPRROTEC family for communication,
auxiliary relays and test equipment are described.
Reyrolle catalog:
This catalog gives an overview of the reyrolle devices.

Contents
Selection Guide for
SIPROTEC and Reyrolle
Edition 4
Invalid: Edition 3

www.siemens.com/protection

Page
Protection Devices Series
SIPROTEC and Reyrolle Relay Families
SIPROTEC 5
SIPROTEC Compact
SIPROTEC 4
SIPROTEC easy and SIPROTEC Compact (series 600)
Reyrolle
Overview, Relay Selection Table
Part 1
Functions
Part 2
Functions (continued)
Further Functions
Hardware Feature
Part 3
Hardware Feature (continued)
Communication

4
5
6
7
8
9

10 to 18
20 to 28

20 to 28

Legal Notice
39

The products and systems described in this catalog


are manufactured and sold according to a certied
management system (acc. to ISO 9001, ISO 14001
and BS OHSAS 18001).

Selection Guide for SIPROTEC and Reyrolle Edition 4 3

Protection Devices
SIPROTEC and Reyrolle Relay Families
Solutions for today's and future power supply systems
for more than 100 years
With the two brands SIPROTEC and REYROLLE, Siemens is the
world market leader in digital protection technology. Prot from
the experience out of an installed base of more than 1 million
devices and 400,000 with IEC 61850.
SIPROTEC has established itself on the energy market for decades as a powerful and complete system family of numerical
protection relays and bay controllers from Siemens.
SIPROTEC protection relays from Siemens can be consistently
used throughout all applications in medium and high voltage.
With SIPROTEC, operators have their systems rmly and safely
under control, and have the basis to implement cost-efcient
solutions for all duties in modern, intelligent and smart grids.
Users can combine the units of the different SIPROTEC device
series at will for solving manifold duties because SIPROTEC
stands for continuity, openness and future-proof design.
As the innovation driver and trendsetter in the eld of protection systems for 100 years, Siemens helps system operators
to design their grids in an intelligent, ecological, reliable and
efcient way, and to operate them economically. As a pioneer,
Siemens has decisively inuenced the development of numerical
protection systems (g. 2). The rst application went into operation in Wrzburg, Germany, in 1977. Consistent integration
of protection and control functions for all SIPROTEC devices was
the innovation step in the 90ies. After release of the communication standard IEC 61850 in the year 2004, Siemens was the
rst manufacturer worldwide to put a system with this communication standard into operation.
How can system operators benet from this experience?

Proven and complete applications


Easy integration into your system
Highest quality of hardware and software

Fig. 2: SIPROTEC Pioneer over generations


4 Selection Guide for SIPROTEC and Reyrolle Edition 4

Fig. 1: Siemens protection family

Excellent operator friendliness of devices and tools


Easy data exchange between applications
Extraordinary consistency between product- and systemengineering

Reduced complexity by easy operation


Siemens as a reliable, worldwide operating partner
Reyrolle
The products of the long-standing British manufacturer Reyrolle
are considered especially powerful and reliable by many markets. With the latest numerical products, Reyrolle as a part of
Siemens shows that the development is being pushed forward,
and that new innovations are continuously being developed
further for the users' benet. In this way, Reyrolle completes the
offerings for protection devices, particularly in Great Britain and
the Commonwealth countries.

Protection Devices
SIPROTEC 5
SIPROTEC 5 the new benchmark for protection, automation
and monitoring
The SIPROTEC 5 series is based on the long eld experience of
the SIPROTEC device series, and has been especially designed for
the new requirements of modern high-voltage systems. For this
purpose, SIPROTEC 5 is equipped with extensive functionalities
and device types. With the holistic and consistent engineering
tool DIGSI 5, a solution has also been provided for the increasingly complex processes, from the design via the engineering
phase up to the test and operation phase.
Thanks to the high modularity of hardware and software, the
functionality and hardware of the devices can be tailored to the
requested application and adjusted to the continuously changing requirements throughout the entire life cycle.
Besides the reliable and selective protection and the complete
automation function, SIPROTEC 5 offers an extensive database
for operation and monitoring of modern power supply systems.
Synchrophasors (PMU), power quality data and extensive operational equipment data are part of the scope of supply.

Fig. 3: SIPROTEC 5 modular hardware

Powerful protection functions guarantee the safety of the


system operator's equipment and employees

Individually configurable devices save money on initial

investment as well as storage of spare parts, maintenance,


expansion and adjustment of your equipment
Arc protection, detection of transient ground fault and
process bus simply integrable and retrofittable
Clear and easy-to-use of devices and software thanks to
user-friendly design
Increase of reliability and quality of the engineering process
High reliability due to consequent implementation of safety
and security
Powerful communication components guarantee safe and
effective solutions
Full compatibility between IEC 61850 Editions 1 and 2
Integrated switch for low-cost and redundant optical and
electrical Ethernet rings
Ethernet redundancy protocols RSTP, PRP and HSR
Efficient operating concepts by flexible engineering of
IEC 61850 Edition 2
Comprehensive database for monitoring of modern power
grids
Optimal smart automation platform for transmission grids
based on integrated synchrophasor measurement units
(PMU) and power quality functions.

Fig. 4: SIPROTEC 5 rear view

The SIPROTEC 5 devices have a basic housing width of


1/3 x 19, and are exibly expandable except of 7xx82.

Fig. 5: Application in the high-voltage system

Selection Guide for SIPROTEC and Reyrolle Edition 4 5

Protection Devices
SIPROTEC Compact
SIPROTEC Compact
Maximum protection-minimum space
Reliable and exible protection for energy distribution and industrial systems with minimum space requirements. The devices
of the SIPROTEC Compact family offer an extensive variety of
functions in a compact and thus space-saving 1/6 x 19" housing.
The devices can be used as main protection in medium-voltage
applications or as back-up protection in high-voltage systems.
SIPROTEC Compact provides suitable devices for many applications in energy distribution, such as the protection of feeders,
lines or motors. Moreover, it also performs tasks such as system
decoupling, load shedding, load restoration, as well as voltage
and frequency protection.
The SIPROTEC Compact series is based on millions of operational
experience with SIPROTEC 4 and a further-developed, compact
hardware, in which many customer suggestions were integrated. This offers maximum reliability combined with excellent
functionality and exibility.

Fig. 6: SIPROTEC Compact

Simple installation by means of pluggable current and


voltage terminal blocks

Thresholds adjustable via software (3 stages guarantee


a safe and reliable recording of input signals)

Easy adjustment of secondary current transformer values


(1 A/5 A) to primary transformers via DIGSI 4

Quick operations at the device by means of 9 freely


programmable function keys

Clear overview with six-line display


Easy service due to buffer battery replaceable at the front
side

Use of standard cables via USB port at the front


Integration in the communication network by means of
two further communication interfaces

Integrated switch for low-cost and redundant optical


Ethernet rings

Ethernet redundancy protocols RSTP, PRP and HSR for


highest availability

Reduction of wiring between devices by means of cross-

Fig. 7: SIPROTEC Compact rear view

communication via Ethernet (IEC 61850 GOOSE)

Time synchronization to the millisecond via Ethernet with


SNTP for targeted fault evaluation

Adjustable to the protection requirements by means of


flexible protection functions

Comfortable engineering and evaluation via DIGSI 4.

Fig. 8: Feeder Protection SIPROTEC 7SC80 with HMI

6 Selection Guide for SIPROTEC and Reyrolle Edition 4

Protection Devices
SIPROTEC 4
SIPROTEC 4 the proven, reliable and future-proof
protection for all applications
SIPROTEC 4 represents a worldwide successful and proven
device series with more than 1 million devices in eld use.
Due to the homogenous system platform, the unique engineering program DIGSI 4 and the great eld experience, the SIPROTEC 4 device family has gained the highest appreciation of users
all over the world. Today, SIPROTEC 4 is considered the standard
for numerical protection systems in all elds of application.
SIPROTEC 4 provides suitable devices for all applications from
power generation and transmission up to distribution and
industrial systems.
SIPROTEC 4 is a milestone in protection systems. The SIPROTEC 4
device series implements the integration of protection, control,
measuring and automation functions optimally in one device.
In many elds of application, all tasks of the secondary systems
can be performed with one single device. The open and futureproof concept of SIPROTEC 4 has been ensured for the entire
device series with the implementation of IEC 61850.

Fig. 9: SIPROTEC 4

Proven protection functions guarantee the safety of the


systems operator's equipment and employees

Comfortable engineering and evaluation via DIGSI 4


Simple creation of automation solutions by means of the
integrated CFC

Targeted and easy operation of devices and software thanks


to user-friendly design

Powerful communication components guarantee safe and


effective solutions

Maximum experience worldwide in the use of SIPROTEC 4


and in the implementation of IEC 61850 projects

Future-proof due to exchangeable communication interfaces


and integrated CFC

Integrated switch for low-cost and redundant optical and


electrical Ethernet rings

Ethernet redundancy protocols RSTP, PRP and HSR.


Fig. 10: SIPROTEC 4 rear view

Fig. 11: SIPROTEC 4 in power plant application

Selection Guide for SIPROTEC and Reyrolle Edition 4 7

Protection Devices
SIPROTEC easy, SIPROTEC Compact (series 600)
SIPROTEC easy
SIPROTEC easy are CT power supplied numerical overcurrent
protection relays, which can be used as line and transformer
protection (back-up protection) in electrical power supply
systems with single-ended supply. They offer denite-time and
inverse-time overcurrent protection functions according to
IEC and ANSI. The comfortable operation via DIP switch is
self-explanatory and simple.

Two-stage overcurrent-time protection


Saving the auxiliary power supply by operation via integrated
current transformer supply

Cost-efficient due to the use of instrument transformers with


low ratings

Tripping via pulse output (DC 24 V / 0.1 Ws) or tripping relay


output

Simple, self-explanatory parameterization and operation via


DIP switch directly at the device

Easy installation due to compact assembly on DIN rail.

Fig. 12: SIPROTEC easy

SIPROTEC Compact (series 600)


The devices of this series are compact, numerical protection
devices for application in medium-voltage or industrial power
supply systems. The corresponding device types are available for
the different applications such as overcurrent-time protection,
line differential protection, transient earth-fault relay or busbar
protection.

Space-saving due to compact design


Reliable process connections by means of solid terminal
blocks

Effective fault evaluation by means of integrated fault


recording and SIGRA 4

Communication interface
Operable and evaluable via DIGSI 4
Different device types available for directional and
non-directional applications.

Fig. 13: SIPROTEC Compact (series 600)

8 Selection Guide for SIPROTEC and Reyrolle Edition 4

Protection Devices
Reyrolle
Reyrolle Withdrawable solutions for distribution grids
Reyrolle has been synonymous with electrical protection devices
in the sectors of sub-transmission, distribution and industrial
applications for decades. Historically, Reyrolle relays, initially
sold mainly in traditional markets, are now sold worldwide as
part of the Siemens protection network.
Since its foundation, Reyrolle has been an innovation driver
in product development based on a strong focus on market,
customer and technology. Worldwide established brand names
such as Solkor and Argus demonstrate this. But there is more:
A wide range of Reyrolle products has determined technological
rsts in the market.
The comprehensive range of Reyrolle products provides the total
protection requirements of distribution markets ranging from
overcurrent protection via transformer protection and voltage
control to a full spectrum of auxiliary and trip relays. The portfolio includes many famous products such as Argus, Duobias,
Solkor, Rho, etc.

Fig. 14: Front view Argus 7SR210

To serve specic needs in industrial applications, a range of


proven products such as Argus overcurrent, Solkor line
differential and Rho motor protection devices is offered.
Through successive generations, Reyrolle numerical products
have been developed to increase value to system operators.
This increase in value is the result of consistent development:

Ease-of-use as a principle our withdrawable product


solutions allow flexible, easy operation through high user
friendliness.
One size fits all the 4U housing height and the latest
generation of numerical products features 1A/5A CT Input,
and some models are provided with universal DC supplies.
Learn once, know all the new product generation provides
a similar look and feel as earlier products. If Reyrolle numerical devices have been previously used, there is a high consistency in both programming and interrogation.
With Reydisp Evolution, a comprehensive software support
toolkit for relay setting, fault interrogation and general
system information is provided. It is backward-compatible
with all previous Reyrolle numerical devices.

Fig. 15: Rear view Argus 7SR210

Selection Guide for SIPROTEC and Reyrolle Edition 4 9

Overview, Relay Selection Table


Functions

Part 1
Siemens Protection Portfolio for all areas of application

Denition of device types based on designation


The devices are easily identied with the aid of a ve-digit abbreviation code. The rst digit
(6 or 7) stands for the classication. The two letters describe the functionality and the last two
digits identify typical properties.
Overview of the main functions

Classication
XX
SIPROTEC devices
KE
MD
RW
SA
SC
SD
SJ
SK
SL
SS
UM
UT
VK
VU
Reyrolle devices
SG
SR
PG

Main functions

Distinguishing features

6 or 7

YY

XX

Main functions
Fault recorder
Bay Controller
Voltage and Frequency Protection
Distance Protection
Feeder Protection
Line Differential Protection
Overcurrent Protection
Motor protection
Line Differntial and Distance Protection
Busbar Protection
Generator Protection
Transformer Protection
Breaker Manangement
High Speed Busbar
Numerical Protection
New Numerical protection
Electromechanical protection

Selection Guide for SIPROTEC and Reyrolle Edition 4 10

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 5

SIPROTEC 4

SIPROTEC 5

SIPROTEC 4

Abbr.

7SA82

7SA86

7SA87

7SA522

7SA61

Functions
Protection functions for 3-pole tripping

3-pole

Protection functions for 1-pole tripping

1-pole

14

Locked rotor protection

I> + V<

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

ANSI

SIPROTEC 4

SIPROTEC 5

Function

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

SIPROTEC 4

SIPROTEC 5

Line differential protection

SIPROTEC 5

Distance protection

7SA63

7SA64

7SD82

7SD86

7SD87

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

Arc-protection

50Ns

Sensitive ground-current protection

INs>

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

59

Overvoltage protection
Peak overvoltage protection, 3-phase, for capacitors

59N

2)

2)

2)

2)

2)

2)

2)

2)

2)

2)

V>

V> cap.

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

2)

2)

2)

2)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

11 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

Reyrolle

I> + V<

Reyrolle

Locked rotor protection

SIPROTEC 5

14

SIPROTEC 5

SIPROTEC 5

1-pole

Reyrolle

3-pole

Protection functions for 1-pole tripping

Reyrolle

Functions
Protection functions for 3-pole tripping

SIPROTEC
600er

7SD80

SIPROTEC 4

Abbr.

High impedance
protection

SIPROTEC 4

SIPROTEC
Compact

Function

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Combined line differential and


distance protection

Line differential protection

7SD610

7SD5

7SD60

7PG2111

7SR18 1)

7SL82

7SL86

7SL87

7SR23

7PG23

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

Arc-protection

50Ns

Sensitive ground-current protection

INs>

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

2)

2)

2)

2)

2)

59

Overvoltage protection

V>

Peak overvoltage protection, 3-phase, for capacitors

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

12 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC
Compact

SIPROTEC
Compact

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC
easy

SIPROTEC
easy

SIPROTEC
600er

SIPROTEC
600er

Overcurrent and feeder protection

Function

Abbr.

7SJ82

7SJ85

7SJ86

7SJ80

7SJ81

7SJ61

7SJ62

7SJ63

7SJ64

7SJ66

7SJ45

7SJ46

7SJ600

7SJ602

Functions
Protection functions for 3-pole tripping

3-pole

Protection functions for 1-pole tripping

1-pole

14

Locked rotor protection

I> + V<

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

2)

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

Arc-protection

50Ns

Sensitive ground-current protection

INs>

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

59

Overvoltage protection

V>

Peak overvoltage protection, 3-phase, for capacitors

2)

2)

2)

2)

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

13 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table

7SR210

7SR220

Functions
Protection functions for 3-pole tripping

3-pole

Protection functions for 1-pole tripping

1-pole

14

Locked rotor protection

I> + V<

SIPROTEC
Compact

7SR191

SIPROTEC
Compact

Reyrolle

7SR45 1)

SIPROTEC 5

Reyrolle

7SR12

SIPROTEC 5

Reyrolle

7SR11

SIPROTEC 5

Reyrolle

Abbr.

Generator and motor protection

Reyrolle

Reyrolle

Function

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Feeder Automation

Reyrolle

Overcurrent and feeder protection

SIPROTEC
Compact

= basic
= optional (additional price)
= not available

7SC80

7SR224

7SK82

7SK85

7UM85 1)

7SK80

7SK81

1)

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

1)

1)

INs>

Arc-protection
50Ns

Sensitive ground-current protection


Intermittent ground-fault protection

Iie>

1)

1)

1)

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

55
59

t=f(I)+V<

Power factor

cos

2)

2)

2)

Overvoltage protection

V>

Peak overvoltage protection, 3-phase, for capacitors

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

14 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

Reyrolle

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

Reyrolle

Function

Abbr.

7UM61

7UM62

7SR17

7UT82

7UT85

7UT86

7UT87

7UT612

7UT613

7UT63

7SR242

Functions
Protection functions for 3-pole tripping

3-pole

Protection functions for 1-pole tripping

1-pole

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Transformer protection

SIPROTEC 4

Generator and motor protection

14

Locked rotor protection

I> + V<

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

Arc-protection

50Ns

Sensitive ground-current protection

INs>

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

59

Overvoltage protection

V>

Peak overvoltage protection, 3-phase, for capacitors

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

15 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

SIPROTEC
600er

SIPROTEC 5

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

7SS85

7SS52

7SS60

6MD85

6MD86

6MD61

6MD63

6MD66

3-pole

1-pole

I> + V<

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

14

Bay controller

SIPROTEC 5

Busbar protection

Function

Abbr.

Functions
Protection functions for 3-pole tripping
Protection functions for 1-pole tripping
Locked rotor protection

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

1)

SOTF

Instantaneous tripping at switch onto fault

50Ns

Sensitive ground-current protection

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

Arc-protection
INs>

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

1)

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

59

Overvoltage protection

V>

Peak overvoltage protection, 3-phase, for capacitors

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

Directional intermittent ground fault protection

Iie dir>

16 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

Reyrolle

SIPROTEC 4

SIPROTEC
Compact

SIPROTEC
600er

Reyrolle

SIPROTEC 5

Fault Recorder

SIPROTEC 4

Voltage and frequency protection

Function

Abbr.

7VK87

7VK61

7VE6

7SR157

7VU683

7RW80

7RW60

7SR158

7KE85

Functions
Protection functions for 3-pole tripping

3-pole

Protection functions for 1-pole tripping

1-pole

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

High speed Busbar


transfer

Synchronizing

SIPROTEC 5

Breaker management

14

Locked rotor protection

I> + V<

21

Distance protection

Z<

21T

Impedance protection for transformers

Z<

24

Overexcitation protection

V/f

25

Synchrocheck, synchronizing function

Sync

27

Undervoltage protection

V<

27TN / 59TN

Stator ground fault 3rd harmonics

V0<,>(3.Harm.)

Undervoltage-controlled reactive power protection

Q>/V<

32

Directional power supervision

P<>, Q<>

37

Undercurrent protection, underpower

I<, P<

38

Temperature supervision

>

40

Underexcitation protection

1/XD

46

Unbalanced-load protection

I2>

46

Negative-sequence system overcurrent protection

I2>, I2/I1>

47

Phase-sequence-voltage supervision

LA, LB, LC

47

Overvoltage protection, negative-sequence system

V2>

48

Starting-time supervision

I2start

49

Thermal overload protection

>, I2t

49H

Hot spot calculation

h>, I2t

50 / 50N

Denite time-overcurrent protection

I>

SOTF

Instantaneous tripping at switch onto fault

Arc-protection

50Ns

Sensitive ground-current protection

INs>

Intermittent ground-fault protection

Iie>

50BF

Circuit-breaker failure protection

CBFP

50RS

Circuit-breaker restrike protection

CBRS

51 / 51N

Inverse time-overcurrent protection

IP, INp

50L

Load-jam protection

I>L

51C

Cold load pickup

51V

Voltage dependent overcurrent protection

t=f(I)+V<

55

Power factor

cos

59

Overvoltage protection
Peak overvoltage protection, 3-phase, for capacitors

2)

V>

V> cap.

59N

Overvoltage protection, zero-sequence system

V0>

59R, 27R

Rate-of-voltage-change protection

dV/dt

60C

Current-unbalance protection for capacitor banks

Iunbal>

60FL

Measuring-voltage failure detection

64

Sensitive ground-fault protection (machine)

66

Restart inhibit

I2t

67

Directional time-overcurrent protection, phase

I>,IP (V,I)

67N

Directional time-overcurrent protection for ground-faults

IN>, INP (V,I)

67Ns

Dir. sensitive ground-fault detection for systems with


resonant or isolated neutral

INs>, (V,I)

67Ns

Transient ground-fault function, for transient and permanent


ground faults in resonant-grounded or isolated networks

W0p,tr>

1)

Directional intermittent ground fault protection

Iie dir>

17 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table

Overview, Relay Selection Table


Functions (continued)
Further fuctions
Hardware Feature

Relay Selection Table


to be continued
on the following pages

Part 2
Siemens Protection Portfolio for all areas of application

Denition of device types based on designation


The devices are easily identied with the aid of a ve-digit abbreviation code. The rst digit
(6 or 7) stands for the classication. The two letters describe the functionality and the last two
digits identify typical properties.
Overview of the main functions

Classication
XX
SIPROTEC devices
KE
MD
RW
SA
SC
SD
SJ
SK
SL
SS
UM
UT
VK
VU
Reyrolle devices
SG
SR
PG

Selection Guide for SIPROTEC and Reyrolle Edition 4 18

Main functions

Distinguishing features

6 or 7

YY

XX

Main functions
Fault recorder
Bay Controller
Voltage and Frequency Protection
Distance Protection
Feeder Protection
Line Differential Protection
Overcurrent Protection
Motor protection
Line Differntial and Distance Protection
Busbar Protection
Generator Protection
Transformer Protection
Breaker Manangement
High Speed Busbar
Numerical Protection
New Numerical protection
Electromechanical protection

Selection Guide for SIPROTEC and Reyrolle Edition 4 19

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

Line differential protection

SIPROTEC 5

Distance protection

Abbr.

7SA82

7SA86

7SA87

7SA522

7SA61

7SA63

7SA64

7SD82

7SD86

7SD87

Functions
Power-swing blocking

Z/t

Trip-circuit supervision

TCS

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Function

68
74TC
78

Out-of-step protection

Z/t

79

Automatic reclosing

AR

81

Frequency protection

f<, f>

81R

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

IN

Further Functions
Measured values

Switching-statistic counters

Logic editor

Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Circuit breaker wear monitoring

Ix, It, 2P

Extended fault recording

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

20 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

Combined line differential and


distance protection

AR

f<, f>

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

Z/t

74TC

Trip-circuit supervision

TCS

78

Out-of-step protection

Z/t

79

Automatic reclosing

81

Frequency protection

81R

Reyrolle

Functions
Power-swing blocking

Reyrolle

68

7PG2111

7SR18 1)

7SL82

7SL86

High impedance
protection

SIPROTEC 5

7SD60

Abbr.

SIPROTEC 5

SIPROTEC
600er

7SD5

Function

SIPROTEC 5

SIPROTEC 4

7SD610

ANSI

Reyrolle

SIPROTEC 4

7SD80

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Reyrolle

SIPROTEC
Compact

Line differential protection

7SL87

7SR23

7PG23

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

Further Functions
Measured values

Switching-statistic counters

Logic editor

Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Extended fault recording

Circuit breaker wear monitoring

IN

Ix, It, 2P

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

21 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC
Compact

SIPROTEC
Compact

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC
easy

SIPROTEC
easy

SIPROTEC
600er

SIPROTEC
600er

Abbr.

SIPROTEC 5

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

SIPROTEC 5

Overcurrent and feeder protection

7SJ82

7SJ85

7SJ86

7SJ80

7SJ81

7SJ61

7SJ62

7SJ63

7SJ64

7SJ66

7SJ45

7SJ46

7SJ600

7SJ602

ANSI

Function

68

Functions
Power-swing blocking

Z/t

74TC

Trip-circuit supervision

TCS

78

Out-of-step protection

Z/t

79

Automatic reclosing

AR

81

Frequency protection

f<, f>

81R

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

IN

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

Further Functions
Measured values

Switching-statistic counters

Logic editor

Inrush-current detection

External trip initiation

2)

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Extended fault recording

Circuit breaker wear monitoring

Ix, It, 2P

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

22 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 5

SIPROTEC
Compact

SIPROTEC
Compact

TCS

SIPROTEC 5

Trip-circuit supervision

Reyrolle

Z/t

74TC

SIPROTEC
Compact

Functions
Power-swing blocking

Reyrolle

68

Reyrolle

Abbr.

Reyrolle

Function

Reyrolle

ANSI

Generator and motor protection

Reyrolle

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Feeder Automation

Reyrolle

Overcurrent and feeder protection

7SR11

7SR12

7SR45 1)

7SR191

7SR210

7SR220

7SC80

7SR224

7SK82

7SK85

7UM85 1)

7SK80

7SK81

78

Out-of-step protection

Z/t

79

Automatic reclosing

AR

81

Frequency protection

f<, f>

81R

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

IN

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

1)

PMU

Synchrophasor measurement

PMU

Further Functions
Measured values

Switching-statistic counters

Logic editor

Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Circuit breaker wear monitoring

Ix, It, 2P

Extended fault recording

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

23 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

Reyrolle

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

Reyrolle

7UM61

7UM62

7SR17

7UT82

7UT85

7UT86

7UT87

7UT612

7UT613

7UT63

7SR242

Z/t

TCS

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Function

68

Functions
Power-swing blocking

74TC

Trip-circuit supervision

Transformer protection

SIPROTEC 4

Generator and motor protection

Abbr.

78

Out-of-step protection

Z/t

79

Automatic reclosing

AR

81

Frequency protection

f<, f>

81R

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

IN

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

Further Functions
Measured values

Switching-statistic counters

Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Circuit breaker wear monitoring

Ix, It, 2P

Logic editor

Extended fault recording

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision


Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

24 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC
600er

SIPROTEC 5

SIPROTEC 4

Bay controller

SIPROTEC 5

Busbar protection

7SS85

7SS52

7SS60

6MD85

6MD86

6MD61

6MD63

6MD66

Z/t

TCS

AR

f<, f>

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Function

Abbr.

68

Functions
Power-swing blocking

74TC

Trip-circuit supervision

78

Out-of-step protection

Z/t

79

Automatic reclosing

81

Frequency protection

81R

IN

Further Functions
Measured values

Switching-statistic counters

Circuit breaker wear monitoring

Ix, It, 2P

Logic editor
Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Extended fault recording

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

25 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

Reyrolle

SIPROTEC 4

SIPROTEC
Compact

SIPROTEC
600er

Reyrolle

SIPROTEC 5

Fault Recorder

SIPROTEC 4

Abbr.

Voltage and frequency protection

SIPROTEC 4

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

High speed Busbar


transfer

Synchronizing

SIPROTEC 5

Breaker management

7VK87

7VK61

7VE6

7SR157

7VU683

7RW80

7RW60

7SR158

7KE85

ANSI

Function

68

Functions
Power-swing blocking

Z/t

74TC

Trip-circuit supervision

TCS

78

Out-of-step protection

Z/t

79

Automatic reclosing

AR

81

Frequency protection

f<, f>

81R

Rate-of-frequency-change protection

df/dt

Vector-jump protection

U>

81LR

Load restoration

LR

85

Teleprotection

86

Lockout

87

Differential protection

87T

Differential protection, Phase angle regulating transformer (single core)

87T

Differential protection, Phase angle regulating transformer (two core)

87T

Differential protection, Special transformers

87C

Differential protection, capacitor bank

87V

Voltage differential protection, capacitor bank

87N

Differential ground-fault protection

Broken-wire detection for differential protection

90V

Automatic voltage control 2 winding transformer

90V

Automatic voltage control 3 winding transformer

90V

Automatic voltage control grid coupling transformer

FL

Fault locator

FL

PMU

Synchrophasor measurement

PMU

IN

Further Functions
Measured values

Switching-statistic counters

Circuit breaker wear monitoring

Ix, It, 2P

Logic editor

Inrush-current detection

External trip initiation

Control

High Speed busbar transfer function

Fault recording of analog and binary signals

Extended fault recording

FSR

Fast-scan recorder

FSR

SSR

Slow-scan recorder

SSR

CR

Continuous recorder

CR

TR

Trend recorder "Power quality recorder (class S)"

TR

1)

PQR

Power Quality Recorder "Power quality recorder (class S)"

PQR

1)

SOER

Sequence-of-events recorder

SOER

ExTrFct

Extended trigger functions

ExTrFct

Monitoring and supervision

Protection interface, serial

No. Setting groups

Changeover of setting group

Circuit breaker test

26 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table

Overview, Relay Selection Table


Hardware Feature (continued)
Communication

Relay Selection Table


to be continued
on the following pages

Part 3
Siemens Protection Portfolio for all areas of application

Denition of device types based on designation


The devices are easily identied with the aid of a ve-digit abbreviation code. The rst digit
(6 or 7) stands for the classication. The two letters describe the functionality and the last two
digits identify typical properties.
Overview of the main functions

Classication
XX
SIPROTEC devices
KE
MD
RW
SA
SC
SD
SJ
SK
SL
SS
UM
UT
VK
VU
Reyrolle devices
SG
SR
PG

Selection Guide for SIPROTEC and Reyrolle Edition 4 27

Main functions

Distinguishing features

6 or 7

YY

XX

Main functions
Fault recorder
Bay Controller
Voltage and Frequency Protection
Distance Protection
Feeder Protection
Line Differential Protection
Overcurrent Protection
Motor protection
Line Differntial and Distance Protection
Busbar Protection
Generator Protection
Transformer Protection
Breaker Manangement
High Speed Busbar
Numerical Protection
New Numerical protection
Electromechanical protection

Selection Guide for SIPROTEC and Reyrolle Edition 4 28

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

I/O

SIPROTEC 4

Hardware Feature
Hardware quantity structure expandable

SIPROTEC 4

Abbr.

SIPROTEC 4

Function

SIPROTEC 5

ANSI

SIPROTEC 5

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Line differential protection

SIPROTEC 5

Distance protection

7SA82

7SA86

7SA87

7SA522

7SA61

7SA63

7SA64

7SD82

7SD86

7SD87

Binary Inputs (max)

11/23

31 3)

31 3)

24

33

33

33

11/23

31 3)

31 3)

Binary Outputs (max) incl. Life contact

46 3)

9/16

46 3)

46 3)

44

34

34

34

9/16

46 3)

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

12

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

8 3)

8 3)

8 3)

8 3)

Voltage Inputs (max)

8 3)

8 3)

8 3)

8 3)

Low Power CT Inputs

Low Power VT Inputs

1/3

1/32/1

1/32/1

1/2; 1/1

1/31/1

1/2; 1/1

1/2; 1/1

1/3

1/32/1

1/32/1

Size (xE)

Small Display (lines)

320x240

320x240

320x240

240x120

240x120

320x240

320x240

320x240

Case (x19'')

Large, graphical Display (Pixel)


Push Buttons

Key Switch

LEDs (max)

16

82

82

16

9/16

16

16

16

82

82

Pluggable terminal blocks

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

PSU Variants

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

RSTP (Ethernet ring redundancy)

PRP V1 (Parallel Redundancy Protocol)

HSR (High available Seamless Ring conguration)

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

29 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

Reyrolle

Reyrolle

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

Reyrolle

Reyrolle

I/O

SIPROTEC
600er

Hardware Feature
Hardware quantity structure expandable

7SD80

SIPROTEC 4

Abbr.

High impedance
protection

SIPROTEC 4

Function

SIPROTEC
Compact

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration
ANSI

Combined line differential and


distance protection

Line differential protection

7SD610

7SD5

7SD60

7PG2111

7SR18 1)

7SL82

7SL86

7SL87

7SR23

7PG23

Binary Inputs (max)

3/7

24

11/23

31 3)

31 3)

19

Binary Outputs (max) incl. Life contact

6/9

33

9/16

46 3)

46 3)

16

Internal RTD Inputs (max)


Transducer inputs (0-20mA) (max)

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

8 3)

8 3)

Voltage Inputs (max)

8 3)

8 3)

Low Power CT Inputs

Low Power VT Inputs

1/6

1/3

1/2; 1/1

1/6

1/3

1/32/1

1/32/1

Size (xE)

E6

E6

E6, E8

E3

Small Display (lines)

Large, graphical Display (Pixel)

320x240

320x240

320x240

Push Buttons

11

Key Switch

LEDs (max)

10

16

18

10

16

82

82

19

Pluggable terminal blocks

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-60;
DV 88-250

DC 24-48;
DC 60-250/
AC 115-230

DC 30-250

Case (x19'')

PSU Variants

DC 24-48;
DC 24-48;
DC 60-125
DC 60-250/ AC
DC 110-250/
115-230
AC 115-230

DC 24-48;
DC 24-48;
DC 60-250/ AC DC 60-250/
115-230
AC 115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

RSTP (Ethernet ring redundancy)

PRP V1 (Parallel Redundancy Protocol)

HSR (High available Seamless Ring conguration)

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

30 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

SIPROTEC
easy

SIPROTEC
easy

SIPROTEC
600er

SIPROTEC
600er

I/O

SIPROTEC 4

Hardware Feature
Hardware quantity structure expandable

SIPROTEC
Compact

Abbr.

SIPROTEC
Compact

Function

SIPROTEC 5

ANSI

SIPROTEC 5

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

SIPROTEC 5

Overcurrent and feeder protection

7SJ82

7SJ85

7SJ86

7SJ80

7SJ81

7SJ61

7SJ62

7SJ63

7SJ64

7SJ66

7SJ45

7SJ46

7SJ600

7SJ602

Binary Inputs (max)

11/23

59 3)

23 3)

3/7/11 1)

3/7

3/8/11

8/11

37

48

36

Binary Outputs (max) incl. Life contact

9/16

33 3)

24 3)

6/9/6 1)

6/9

5/9/7

9/7

19

26

24

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

4 3)

4 3)

4/3

Voltage Inputs (max)

4 3)

4 3)

0/3

3/4

0/1

Low Power CT Inputs

Low Power VT Inputs

0/3

1/3

1/32/1

1/32/1

1/6

1/6

1/3; 1/2

1/3; 1/3

1/2; 1/1

1/31/1

1/3; 1/2

1/6

1/6

Size (xE)

Small Display (lines)

320x240

320x240

320x240

240x120

240x120

240x120

240x120

240x128

Case (x19'')

Large, graphical Display (Pixel)


Push Buttons

Key Switch

LEDs (max)

16

82

82

10

10

16

16

16

Pluggable terminal blocks

PSU Variants

110 to
DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48;
250 V DC,
DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/
115 to
AC115-230 AC115-230 AC115-230 AC115-230 AC115-230 AC115-230 AC115-230 AC115-230 AC115-230
230 V AC

DC24-48; DC24-48;
DC 24-250/ DC60-125 DC60-125
AC 60-230 DC110-250/ DC110-250/
AC115-230 AC115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

RSTP (Ethernet ring redundancy)

PRP V1 (Parallel Redundancy Protocol)

HSR (High available Seamless Ring conguration)

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

31 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC
Compact

Reyrolle

SIPROTEC 5

SIPROTEC 5

SIPROTEC 5

SIPROTEC
Compact

SIPROTEC
Compact

I/O

Binary Inputs (max)

Reyrolle

Hardware Feature
Hardware quantity structure expandable

Reyrolle

Abbr.

Reyrolle

Function

Reyrolle

ANSI

Generator and motor protection

Reyrolle

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Feeder Automation

Reyrolle

Overcurrent and feeder protection

7SR11

7SR12

7SR45 1)

7SR191

7SR210

7SR220

7SC80

7SR224

7SK82

7SK85

7UM85 1)

7SK80

7SK81

19

13

12

43

11/23

27 3)

27 3)

3/7

3/7
6/9

Binary Outputs (max) incl. Life contact

16

14

30

9/16

17 3)

17 3)

6/9

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

4 3)

4 3)

Voltage Inputs (max)

1/4

4 3)

4 3)

0/3

Low Power CT Inputs

Low Power VT Inputs

0/3

Case (x19'')

1/3

1/32/1

1/32/1

1/6

1/6

Size (xE)

E4

E4

E4

E4

E6, E8

E6, E8

E10, E12

Small Display (lines)

Large, graphical Display (Pixel)

320x240

320x240

320x240

Push Buttons

11

11

10

17

Key Switch

LEDs (max)

10

10

10

19

19

32

19

82

82

82

10

10

Pluggable terminal blocks

PSU Variants
DC 24-60; DC 24-60;
DV 88-250 DV 88-250

DC 24-60;
DC 24-48;
DC 24-48; DC 24-48; DC 24-48; DC 24-48; DC 24-48;
DC 88-250/ DC 30-250 DC 30-250 DC 60-250/ DC 30-250 DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/ DC 60-250/
115V
AC115-232
AC115-230 AC115-230 AC115-230 AC115-230 AC115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

1)

1)

RSTP (Ethernet ring redundancy)

1)

1)

PRP V1 (Parallel Redundancy Protocol)

1)

1)

HSR (High available Seamless Ring conguration)

1)

1)

Redundancy Protocols

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

32 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 5

SIPROTEC 4

SIPROTEC 4

SIPROTEC 4

Reyrolle

I/O

SIPROTEC 5

Hardware Feature
Hardware quantity structure expandable

SIPROTEC 5

Abbr.

SIPROTEC 5

Function

Reyrolle

ANSI

SIPROTEC 4

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Transformer protection

SIPROTEC 4

Generator and motor protection

7UM61

7UM62

7SR17

7UT82

7UT85

7UT86

7UT87

7UT612

7UT613

7UT63

7SR242

Binary Inputs (max)

15

15

7 3)

19 3)

23 3)

27 3)

29

19

Binary Outputs (max) incl. Life contact

20

21

7 3)

23 3)

34 3)

38 3)

25

14

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

8 3)

8 3)

12 3)

20 3)

11

14

Voltage Inputs (max)

0 3)

0 3)

4 3)

4 3)

0/4

Low Power CT Inputs

Low Power VT Inputs

1/3; 1/2

1/2; 1/1

1/3

1/32/1

1/32/1

1/32/1

1/3

1/2

1/1

E8, E10

Case (x19'')
Size (xE)

E4

Small Display (lines)

Large, graphical Display (Pixel)

240x120

320x240

320x240

320x240

320x240

240x120

Push Buttons

Key Switch

LEDs (max)

9/16

10

16

82

82

82

16

16

27

Pluggable terminal blocks

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-60;
DC 88-250/
115 V

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 30-250

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

PSU Variants

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

1)

RSTP (Ethernet ring redundancy)

1)

PRP V1 (Parallel Redundancy Protocol)

1)

HSR (High available Seamless Ring conguration)

1)

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

33 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC 4

SIPROTEC 4

I/O

SIPROTEC 4

Hardware Feature
Hardware quantity structure expandable

SIPROTEC 5

Abbr.

SIPROTEC 5

Function

SIPROTEC
600er

ANSI

SIPROTEC 4

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

Bay controller

SIPROTEC 5

Busbar protection

7SS85

7SS52

7SS60

6MD85

6MD86

6MD61

6MD63

6MD66

Binary Inputs (max)

153)

972

3 4)

59

3)

443

Binary Outputs (max) incl. Life contact

33

3)

80

3)
3)

80

37

65
45

153)

370

2 4)

54

21

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

12

12

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

60

192

1 4)

3)

3)

Voltage Inputs (max)

3)

3)

Low Power CT Inputs

Low Power VT Inputs

1/2-1/1; 2x1/1 1) 1/1

1/31/1

1/6 4)

1/32/1

1/32/1

1/2; 1/1

1/2; 1/1

1/1

Size (xE)

Small Display (lines)

320x240

320x240

320x240

240x120

240x120

240x120

Push Buttons

196

Key Switch

LEDs (max)

82

898

82

82

16

16

16

Pluggable terminal blocks

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

Case (x19'')

Large, graphical Display (Pixel)

PSU Variants

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

RSTP (Ethernet ring redundancy)

PRP V1 (Parallel Redundancy Protocol)

HSR (High available Seamless Ring conguration)

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

Further Ethernet protocols on Ethernet modules

34 Selection Guide for SIPROTEC and Reyrolle Edition 4

Overview, Relay Selection Table


= basic
= optional (additional price)
= not available

SIPROTEC
600er

Reyrolle

SIPROTEC 5

I/O

SIPROTEC
Compact

Hardware Feature
Hardware quantity structure expandable

SIPROTEC 4

Abbr.

Reyrolle

Function

Fault Recorder

SIPROTEC 4

ANSI

Voltage and frequency protection

SIPROTEC 4

Device series

1) in preparation
2) via CFC
3) = IO number of a standard variant (increased conguration available using the
SIPROTEC 5 system) / number of current and voltage inputs up to 24 (total)
4) = number of one unit 7SS60. Total number is depending
on system conguration

High speed Busbar


transfer

Synchronizing

SIPROTEC 5

Breaker management

7VK87

7VK61

7VE6

7SR157

7VU683

7RW80

7RW60

7SR158

7KE85

Binary Inputs (max)

31 3)

20

6/14

17

3/7

19 3)

Binary Outputs (max) incl. Life contact

15 3)

46 3)

19

10/18

19

6/9

Internal RTD Inputs (max)

Transducer inputs (0-20mA) (max)

12

20

Analog measured value outputs (0-20mA) (max)

Current Inputs (max)

8 3)

12

Voltage Inputs (max)

8 3)

16

Low Power CT Inputs

Low Power VT Inputs

1/32/1

1/31/2

1/3;1/2

1/1

1/6

1/6

1/32/1

Size (xE)

E4

E4

Small Display (lines)

8
320x240

Case (x19'')

Large, graphical Display (Pixel)

320x240

240x120

240x120

Push Buttons

Key Switch

LEDs (max)

82

9/16

9/16

10

16

10

10

82

Pluggable terminal blocks

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-60;
DC 88-250/115V

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-250/
AC 115-230

DC 24-48;
DC 60-125
DC 110-250/
AC 115-230

DC 24-60;
DC 88-250/115V

DC 24-48;
DC 60-250/
AC 115-230

Communication
Front User Interface

IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

Probus FMS, Slave

Probus DP, Slave

MODBUS TCP

MODBUS RTU SLAVE

PROFINET I/O

DNP3 serial

DNP 3 TCP

IEC 61850-8-1

IEC 61850-9-2

DIGSI

RTD-unit connection

20 mA unit connection

Synchrophasor (IEEE C37.118)

Redundancy Protocols

PSU Variants

RSTP (Ethernet ring redundancy)

PRP V1 (Parallel Redundancy Protocol)

HSR (High available Seamless Ring conguration)

Further Ethernet protocols on Ethernet modules

Time Synchronisation

IEEE 1588 C37.238 prole (PSRC - prole)

Timesync. via integrated GPS module

35 Selection Guide for SIPROTEC and Reyrolle Edition 4

Legal Notice
Indication of conformity

Copyright

This product complies with the directive


of the Council of the European Communities on harmonization of the laws of the
Member States relating to electromagnetic compatibility (EMC Council Directive
2004 / 108 / EC) and concerning electrical equipment for use
within specied voltage limits (Low Voltage Directive
2006 / 95 / EC).

Copyright Siemens AG 2015. All rights reserved.

This conformity has been proved by tests performed


according to the Council Directive in accordance with the
generic standards EN 61000-6-2 and EN 61000-6-4 (for
EMC directive) and with the standard EN 60255-27 (for Low
Voltage Directive) by Siemens AG.

SIPROTEC and DIGSI are registered trademarks of Siemens


AG. Any unauthorized use is illegal. All other designations
in this document can be trademarks whose use by third
parties for their own purposes can infringe the rights of the
owner.

The disclosure, duplication, distribution and editing of this


document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
Registered trademarks

The device is designed and manufactured for application in


an industrial environment.
The product conforms with the international standards of
IEC 60255 and the German standard VDE 0435.
Disclaimer of liability
This document has been subjected to rigorous technical
review before being published. It is revised at regular
intervals, and any modications and amendments are
included in the subsequent issues. The content of this
document has been compiled for information purposes
only. Although Siemens AG has made best efforts to keep
the document as precise and up-to-date as possible,
Siemens AG shall not assume any liability for defects and
damage which result through use of the information
contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of
Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from
time to time.
Document version: 04
Release status: 03.2015

Selection Guide for SIPROTEC and Reyrolle Edition 4 36

Notes

37 Selection Guide for SIPROTEC and Reyrolle Edition 4

Published by and copyright 2015:


Siemens AG
Energy Management
Humboldststr. 59
90459 Nuremberg, Germany
Printed on elementary chlorine-free bleached paper.
All rights reserved.
If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values, dimensions
and weights. Drawings are not binding.
All product designations used are trademarks or
product names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.
Subject to change without prior notice.
The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.
For all products using security features of
OpenSSL the following shall apply:
This product includes software developed by the
OpenSSL Project for use in the OpenSSL Toolkit.
(http://www.openssl.org/)
This product includes cryptographic software
written by Eric Young ([email protected])

siemens.com/protection