PDS MonitorAndControl SW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

DeltaV Product Data Sheet

January 2013 Page 1

Monitor and Control Software

Monitor and Control Software

DeltaV allows you to use the right control langauge for the right control task.

IEC61131-3 languages
Built-in FOUNDATION fieldbus technology

Performs calculations on data from external


sources

Control in the field, controller, or both

Features protecting and hiding of control


strategies

Scalable software meets any needs

Features class-based configuration

Integrates multi-vendor real-time data into


your DeltaV system

Features advanced unit management


Features advanced control

www.DeltaV.com

DeltaV Product Data Sheet


January 2013 Page 2

Introduction
Are you looking for a control system that allows you to use
standard control languages and functions? Do you want to
use different control languages that are appropriate for the
control task within the same strategy? Do you want a
control system that permits you to design where and how
you perform monitoring and control, rather than forcing
you to fit within the constraints of a fixed architecture? A
DeltaV system gives you all this and more. Choose from
IEC61131-3 control languages and FOUNDATION fieldbus
function blocks to design your monitoring and control
strategies.
Need to consolidate your PLC, legacy systems, and
gauging systems into a single operator interface? OPC
may be used to tear down the barriers between your
legacy control systems and your DeltaV system. The
DeltaV system provides you with a real-time database
where you can store third-party data for use anywhere
within the DeltaV system. You can display, trend, alarm
and even use it in control strategies. Whats more, you
choose the location that is best for integrating the data into
the DeltaV system, the workstation or the controller.
This document details the monitoring and control functions
supported by a DeltaV system. These functions can run on
DeltaV Application Stations and controllers and many of
the function blocks may be assigned to run within
FOUNDATION fieldbus devices

Benefits
Uses IEC61131-3 control languages. A DeltaV
system supports three languages, so you can always use
the tools most appropriate for the job. Function Block
Diagrams (FBD), Sequential Function Charts (SFC), and
Structured Text (ST) are all available, making control
strategy development both intuitive and easy.

Built-in FOUNDATION fieldbus functionality. These


function blocks are used throughout the DeltaV system.
Control strategies are developed, using these standardsbased blocks that minimize development time and
maximize the systems performance. Many functions (like
override control, tracking, and state control) are built into
these powerful blocks. Plus, with Fieldbus, you get
decreased wiring costs and improved instrument
diagnostics.

Control in the field, controller, or both. Design


control strategies to meet your application requirements.
Then decide where each block executes: in the controller,
in the field devices, or both.

Scalable software meets any needs. As your needs


grow, your DeltaV system is ready to expand with you.
Additional capacity and even additional control
functionality can be added online while you continue to
control your process. Your entire configuration remains

Monitor and Control Software


intact; you simply add to existing control strategies with
the newly available functions or configure new control
modules to take advantage of higher capacity.

Integrates multi-vendor data. Bring data into your


DeltaV system for control, display, and historical purposes.
When executing in the controller, the monitoring software
uses Classic I/O, HART, FOUNDATION fieldbus, PROFIBUS
DP, AS-i bus, DeviceNet and serial interfaces to access
data. Running in workstations, OPC technology provides
Data Acquisition control software with fast connections
and data transfers to and from any system.
Performs calculations on data from external
sources. Now you can put the data from an existing
system to work for you in the DeltaV system. All DeltaV
applications can access and use the external data as if it
were native DeltaV data. And because you can execute
function blocks directly in the workstation, you can really
put this external data to work for you.

Features protecting and hiding of control


strategies. Access to library items like module templates
and class definitions can be restricted by to enforce
project standards. The internal structure of modules can
be hidden to protect intellectual property.

Features class-based configuration. Build module


class definitions for commonly used control (e.g. motors,
valves) and equipment (e.g. valve header) modules. All
modules that are created from a definition inherit changes
that are made to the definition.

Features advanced unit management (AUM). Use


powerful DeltaV unit modules and aliasing to write generic
logic in control and equipment modules. This will simplify
configuration management where there are similar
equipment units or trains. Refer to the Advanced Unit
Management product data sheet for further details.

Features advanced control. Use DeltaV Fuzzy to


improve performance of non-linear or noisy loops. The
optional DeltaV Tune makes adjusting the Fuzzy rules and
PID parameters a snap. Simply run the tuning wizard and
your loop is optimized. For more demanding process
control requirements, you can use Model Predictive
Control or DeltaV Neural. Refer to the Advanced Control
product data sheets for details.

DeltaV Product Data Sheet


January 2013 Page 3

Product Description
DeltaV Monitoring and Control Software uses standard
IEC61131-3 control languages, as well as FOUNDATION
fieldbus function blocks to support strategy development.
These strategies may be graphically assembled and
modified using standard drag-and-drop techniques.
Strategy development is visually intuitive, making it easy
for first-time users to quickly become productive. Contextsensitive, online help is available for all functions. The
IEC61131-3 control languages include Function Block
Diagramming (FBD), Sequential Function Charts (SFC),
and Structured Text (ST). Typical uses of each language
are listed on page 4.

Control Language Typical Usages


Function Block Diagram (FBD)
Monitoring and alarming
Continuous calculations
Analog control (pressure, temperature, flow)
Motor and block valve control
Totalizers
Sequential Function Chart (SFC)
Charging systems
Startup/shutdown control
Batch sequences (fill, mix, heat, dump)
Structured Text (ST)
Advanced math functions
Complex calculations
Interlock condition detection
If-then-else decisions
Looping
Bit manipulations

Monitor and Control Software


Function Block Diagrams. Your DeltaV system uses
Function Block Diagrams to implement continuously
executing calculations, process monitoring, and control
strategies. Graphical wires are used to connect the
different blocks within a diagram. Each wire transfers one
or more pieces of data. All communications throughout the
DeltaV system are handled automatically. DeltaV function
blocks are implemented using the structure specified by
the FOUNDATION fieldbus standard, but they are also
enhanced to provide greater flexibility in control strategy
design. FOUNDATION fieldbus -compliant Function Blocks
enable you to take advantage of control in the field. You
design control strategies that best meet your control
application requirements. Then, decide whether the
function blocks controlling the process run in the
controller, field devices, or both.

Sequential Function Charts. This language enables


you to configure operator-independent time-variant
actions. SFCs are best at controlling strategies with
multiple states. They can be used for sequencing and
simple batch applications.
An SFC comprises a series of steps and transitions. Each
step contains a set of actions that affect the process.
Transitions determine when processing moves on to the
next step(s). Both single-stream and parallel execution of
logic is supported within SFCs.

Structured Text. With structured text you can write


sophisticated calculations using a wide array of algebraic
and trigonometric functions and operators. In addition, you
can build complex logic expressions using conditional and
iterative structures.

Data Acquisition. Display, trend, alarm, and use thirdparty data as if it were native DeltaV data. Now you can
put the data from an existing system to work for you in a
DeltaV system. All DeltaV applications can access and
use the external data as if it were native DeltaV data. The
data can be used on any DeltaV workstation. It can also
be integrated into control strategies, consolidated into
reports, historized, and much more. Whether your
application uses the workstations OPC server or the
controllers I/O subsystemonce accessed, the real-time
database makes the data immediately available
throughout the DeltaV system. In runtime, the exception
reporting mechanism moves the data to the appropriate
system application. The global configuration database
makes management and use of this data easy.

DeltaV Product Data Sheet


January 2013 Page 4

Monitor and Control Software

Section 1: Function Blocks


Math Blocks
Absolute*
Provides the absolute value of an integer or floating point input
Add*
Sums the values of two to sixteen inputs and generates an output value.
Arithmetic*
Provides standard algorithms for : Flow Compensation Linear, Flow Compensation Square Root, Flow
Compensation Approximate, Btu Flow, Traditional Multiply and Divide, Average, Summer, Fourth Order
Polynomial, and Simple HTG Compensate Level
Comparator*
Compares two values for the conditions greater than, less than, equal, not equal, and generates an
output for each comparison (GT, LT, EQ, NEQ). It also checks whether the primary input is within the
range defined by two inputs.
Divide*
Divides one input value by another input value and generates an output value.
Integrator*
Integrates one or two variables over time. The block compares the integrated or accumulated value to
pre-trip and trip limits and generates discrete output signals when the limits are reached.
Multiply*
Multiplies two to sixteen inputs and generates an output value.
Subtract*
Subtracts one input value from another input value and generates an output value.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 5

Monitor and Control Software


Input/Output Blocks

Alarm Detection*
Creates a set of standard alarms (HI_HI, HI, LO, LO_LO) on any system parameter. AI and PID blocks
have this function built-in.
Analog Input*
Accesses a single analog measurement value and status from an I/O channel. The input value can be a
transmitters 4-20mA signal, the digitally communicated FOUNDATION fieldbus block, or the digitally
communicated primary or non-primary variable from a HART transmitter.
Analog Output*
Assigns an analog output value to a field device through a specified I/O channel or Fieldbus device.
Discrete Input*
Accesses a single discrete measurement value and status from a two-state field device and makes the
processed physical input available to other function blocks.
Discrete Output*
Takes a binary setpoint and writes it to a specified O/O channel to produce an output signal.
Fieldbus Multiplexed Discrete Input
Accesses discrete input values from two-state field devices and makes the processed physical inputs
available through eight discrete output parameters.
Fieldbus Multiplexed Analog Input
Used to make up to 8 input parameters available to the Fieldbus I/O subsystem.
H1 Carrier Multiple Discrete Input
Accesses a DI card on the H1 carrier device and makes the individual channels available as in an 8-bit
integer output.
H1 Carrier Multiple Discrete Output
Takes an 8-bit integer and writes it to the individual channels of a DO card on the H1 carrier device.
Fieldbus Multiplexed Analog Input
Used to connect to higher density Fieldbus transmitters.
Fieldbus Multiplexed Analog Output
Used to connect up to 8 analog output signals for Fieldbus devices supporting this function block.
Pulse Input*
Converts the rate parameter on the Pulse Input card to a value in engineering units.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 6

Monitor and Control Software


Timer and Counter Blocks

Counter*
Generates a discrete output value of True (1) when the count reaches a specified trip value. The block
functions as an increment or decrement counter.
Off-delay Timer*
Delays the transfer of a False (0) discrete input value to the output by a specified time period.
On-delay Timer*
Delays the transfer of a True (1) discrete input value to the output by a specified time period.
Retentive Timer*
Generates a True (1) discrete output after the input has been True for a specified time period. When the
reset input is set True, the elapsed time and the output value are reset.
Timed Pulse*
Generates a True (1) discrete output for specified time duration when the input makes a positive (Falseto-True) transition. The output remains True even when the input returns to its initial discrete value; it
returns to its original False value only when the output is True longer than the specified time duration.
Date Time Event*
Generates a pulse at a preset date and time or at preset time intervals
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 7

Monitor and Control Software


Logic Blocks

Action*
Evaluates a single structured text expression when the input value is True. Mathematical functions,
logical operators, and constants may be used in the expression.
AND*
Generates a discrete output value based on the logical AND of two to sixteen discrete inputs.
Bi-directional Edge Trigger*
Generates a True (1) discrete pulse output when the discrete input makes a positive (0-to-1, False-toTrue) or a negative (1-to-0, True-to-False) transition since the last execution of the block. If there has
been no transition, the discrete output of the block is False.
Boolean Fan Input*
Generates a discrete output based on the weighted binary sum, binary coded decimal (BCD)
representation, transition state, or logical OR of 1 to 16 discrete inputs.
Boolean Fan Output*
Decodes a binary weighted floating point input to individual bits and generates a discrete output value
for each bit (as many as sixteen outputs).
Condition*
Evaluates a single structured text expression and generates a discrete output value when the
expression is evaluated True (1) for longer than a specified time period.
Device Control
Provides setpoint control for multi-state discrete devices, such as motors, pumps, and block valves.
Multiplexer*
Selects one input value from up to 16 input values and places it at the output.
Negative Edge Trigger*
Generates a True (1) discrete pulse output when the discrete input makes a negative (1-to-0, True-toFalse) transition since the last execution of the block. If there has been no transition (or a positive
transition), the discrete output of the block is False (0).
NOT*
Logically inverts a discrete input signal and generates a discrete output value. When the input is True
(1), the output is False (0). When the input is False, the output is True.
OR*
Generates a discrete output value based on the logical OR of 2 to 16 discrete inputs. When one or more
of the inputs is True (1), the output is set True (1).
Positive Edge Trigger*
Generates a True (1) discrete pulse output when the discrete input makes a positive (0-to-1, False-toTrue) transition since the last execution of the block. If there has been no transition (or a negative
transition), the discrete output of the block is False (0).
Reset/Set Flip-flop*
Generates a discrete output value based on NOR logic of Reset and Set inputs. If the Reset input is
False (0) and the Set input is True (1), the output is True. The output remains True regardless of the Set
value until the Reset value is True. When Reset becomes True, the output is False.

DeltaV Product Data Sheet


January 2013 Page 8

Monitor and Control Software


Logic Blocks

Set/Reset Flip-flop*
Generates a discrete output value based on NAND logic of Set and Reset inputs. When the Reset input
is False (0) and the Set input is True (1), the output is True. The output remains True until the Reset
input is True and the Set input is False. When the Reset input is True, the output is equal to the Set
input.
Transfer*
Selects one of two analog input signals and transfers the selected input to the output after a specified
time. The transfer from one input to another is smoothed with a linear ramp.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet

Monitor and Control Software

January 2013 Page 9

Analog Control Blocks


Bias/Gain
Provides adjustable gain capability by computing an output value from a bias setpoint, an input, and a
gain value.
Calc*
Allows you to specify an expression that determines the blocks output. Mathematical functions, logical
operators, constants, parameter references, and I/O reference values may be used in the expression.
Expressions are written using IEC 61131-3 Structured Text. See section 3 for Structured Text details.
Control Selector
Selects one of three control signals to perform override control to a PID function block.
Dead time*
Introduces a pure time delay in the value and status used in a signal path between two function blocks.
Fieldbus Input Selector Extended
Selects the first good, minimum, maximum, middle, or average of up to eight input signals. Supports
operator-selected, mode, and signal disable.
Filter*
Applies an equation to filter changes in the input signal and generates a smooth output signal.
Input Selector*
Selects the first good, minimum, maximum, middle, or average of up to four input signals. Supports
operator-selected, mode, and signal disable.
Lead/Lag*
Provides dynamic compensation for an input value. The block can apply a lead time function, a lag time
function, or a combination of the two. A specified gain is applied to the compensated value and the value
is high/low-limited based on the block mode.
Limit*
Limits an input value between two reference values.
Manual Loader
Allows the block output to be set by an operator.
PID
Combines all the necessary logic to perform analog input channel processing, proportional-integralderivative (PID) control, and analog output channel processing within one function block.
Ramp*
Creates a ramping output signal to increase or decrease a variable toward a specified target value at a
defined rate.
Rate Limit*
Limits the rate of change of the output value to specified limits. Also provides the derivative of the input
signal.
Ratio
Applies an adjustable ratio setpoint to achieve a desired input/output relationship.
Scaler*
Provides scaling and dimensional consistency between two values of different engineering units. The
block converts the input value to the specified scale and generates an output value.

DeltaV Product Data Sheet


January 2013 Page 10

Monitor and Control Software


Analog Control Blocks

Signal Characterizer*
Characterizes or approximates any function that defines an input/output relationship. The function is
defined by configuring as many as twenty X, Y coordinates. The block interpolates an output value for a
given input value using the curve defined by the configured coordinates. Two separate analog input
signals can be processed simultaneously to give two corresponding separate output values using the
same defined curve.
Signal Generator*
Produces an output signal used to simulate a process signal.
Signal Selector*
Selects the maximum, minimum, or average of as many as sixteen input values and places it at the
output.
Splitter
Takes a single input and calculates two outputs based on specified coordinate values.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 11

Monitor and Control Software


Advanced Control Blocks

Fuzzy Logic
Easy to use alternative to PID control. Useful in non-linear and noisy processes. Also very suited to
handling unmeasured disturbances.
Inspect*
Monitors plant area control performance statistics for viewing, trending and history collection. Also
provides for programmatic enable/disable of performance monitoring based on equipment or unit state.
Model Predictive Control* (basic and professional)
Model Predictive constrained multi-variable controller for processes with, interacting variables, difficult
dynamics, multiple constraints, and throughput optimization.
Related Blocks
MPC Process Simulator*
Allows the process to be simulated to verify the model.
MPC Input Reference*
Easily connect input parameters (controlled variables, disturbance variables, and constraint
variables) from multiple loops in a single MPC strategy. Useful for implementing MPC in a
supervisory fashion.
MPC Output Reference*
Easily connect output parameters (manipulated variables) from multiple loops in a single MPC
strategy. Useful for implementing MPC in a supervisory fashion.
MPC Analyzer template*
Used to pre-process sampled analyzer measurements before feeding them into the MPCPro
block.
Neural Network*
Build virtual sensors for on-line qualitative property estimation. Use anywhere samples are taken for
analysis, or in place of or back-up to continuous analyzers.
Related Blocks
Lab Entry*
Allows operator input of offline laboratory analysis results to be used in training the neural
network. Sample time and test results are easily logged right from the operator interface.
Diagnostic*
The Diagnostic function block provides a method to monitor device alerts from non-fieldbus assets.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 12

Monitor and Control Software


Advanced Functions Blocks

Analog Voter
Monitors a number of analog input values and determines if there are enough votes to trip. If a
configured number of the inputs vote to trip, the block trips, and the output of the block is set to zero (0).
Discrete Voter
Monitors a number of discrete input values and determines if there are enough votes to trip. If a
configured number of the inputs vote to trip, the block trips, and the output of the block is set to zero (0).
Cause and Effect Matrix
Incorporates interlock and permissive logic for one or more final control elements. Up to 16 Causes
(inputs) and up to 16 Effects (outputs) can be configured using the function blocks matrix.
State Transition
Implements a user-defined state machine. The state machine describes the possible states, and the
transitions between those states, that can occur.
Step Sequencer
Associates system states with actions to drive outputs based on the current state.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 13

Monitor and Control Software


Energy and Metering Blocks

Isentropic Expansion*
Calculates the final enthalpy for isentropic expansion of steam to a given pressure for given entropy. If
the entropy-pressure point lies in the two-phase region, the combined enthalpy of steam and water for
constant entropy is provided. Steam quality (% moisture) and steam temperature are also calculated.
Saturated Steam Properties*
Calculates steam enthalpy, entropy, specific volume and pressure for saturation conditions specified by
a given temperature.
Saturated Temperature*
Calculates steam temperature at saturation give steam pressure.
Steam Density Ratio*
Calculates the square root of the ratio of steam density to the density of steam at the calibration
conditions of the flow meter.
Steam Properties*
Calculates steam enthalpy, entropy and specific volume for a give gauge pressure and a given
temperature.
Water Enthalpy*
Calculates enthalpy of water for a specified temperature.
Water Entropy*
Calculates entropy of water for a specified temperature.
Flow Metering in SI units*
Calculates mass flow, volumetric flow and energy flow for orifice and turbine meters.
Flow Metering in US units*
Calculates mass flow, volumetric flow and energy flow for orifice and turbine meters.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet


January 2013 Page 14

Monitor and Control Software


Special Items

Custom Block Tool*


Adds various block types
Composite Block*
A grouping of individual function blocks. Composites can be of the Linked or Embedded type.
Module Block*
A block on the diagram that represents another module within the system. It allows direct
connection of parameters between this module and the referenced module.
Physical Block Tool
Used to add Foundation fieldbus blocks directly to the diagram instead of adding a standard I/O block
and then converting it.
Input Parameter*
A value from another function block, a sequential function chart (SFC), or a field device supplied to a
module for use in execution.
Internal Read Parameter*
A value used within a module that supplies an output for connection to I/O or other module parameters.
Internal Write Parameter*
A value used within a module that supplies an input for connection to I/O or other module parameters.
Output Parameter*
A value calculated or triggered by the module and sent to other diagrams or field devices.
*Allowed to run in a workstation-based controller

DeltaV Product Data Sheet

Monitor and Control Software

January 2013 Page 15


Section 2: Sequence Function Chart Tools

SFC Tools
Input Parameter
A value from another function block, a sequential function chart (SFC), or a field device supplied to a
module for use in execution. Automatically available when the Module Block is used on another
modules diagram.
Internal Read Parameter
A value used within a module that supplies an output for connection to I/O or other module parameters.
Internal Write Parameter
A value used within a module that supplies an input for connection to I/O or other module parameters.
Output Parameter
A value calculated or triggered by the module and sent to other function blocks, SFCs, or field devices.
Automatically available when the Module Block is used on another modules diagram.
Step
An element of an SFC that contains a set of actions. The actions define the rules and the behavior of the
step. The step manages the execution of the actions they contain.
Termination
A transition that specifies a condition that represents a logical end to a sequence.
Transition
An element of a SFC that allows the sequence to proceed from one step to the next if a transition
condition is met. A transition condition is the result of evaluating a Boolean expression.
Sequence
A number of steps and transitions linked together.

DeltaV Product Data Sheet

Monitor and Control Software

January 2013 Page 16


Section 3: Structured Text Instructions

Functions

The DeltaV system uses IEC 61131-3 Structured Text to


create custom functions. The language uses operators,
functions, statements and operands in expressions. The
Action, Condition, Calc blocks and SFCs use expressions.
Any system parameter may be referenced by these
expressions.

ABS (x)

Absolute value of x

EXP

Exponential of x

EXPT (x, y)

Raise x to the power of y

Operators

FRACT (x)

Fractional part of a number

LN (x)

Natural logarithm of x

LOG (x)

Log base 10 of x

LOG2 (x, y)

Log base y of x

MAX (x, y)

Maximum of x and y

MIN (x, y)

Minimum of x and y

ROUND (x)

Round x to the nearest float

SQRT (x)

Square root of x

TRUNC (x)

Floor function

Operator

Description

Unary minus

Unary plus

! , NOT

Logical NOT

Bitwise NOT

OR

Logical OR

XOR

Logical Exclusive OR

AND

Logical AND

Bitwise OR

Bitwise XOR

&

Bitwise AND

Equality

!= , <> , ~=

Inequality

<

Less than

>

Greater than

<=

Less than or equal to

>=

Greater than or equal to

Add

String concatenation

Subtract

Multiply

Math

Description

Trig

Description

ACOS (x)

Arc cosine of x

ASIN

Arc sine of x

ATAN

Arc tangent of x

COS

Cosine of x

SIN(x)

Sine of x

TAN (x)

Tangent of x

Bitwise

Description

ROL(x,y) / ROTL Rotate x to the left by y positions


ROTL16(i,n)

Rotate i to the left by n bits for a 16


bit integer

ROR(x,y) / ROT Rotate x to the right by y positions


ROTR16(i,n)

Rotate i to the right by n bits for a 16


bit integer

Divide

SHL(x,y)

Shift x left by y positions, no carry

MOD , %

Modulus (remainder)

SHR(x,y)

Shift x right by y positions, no carry

**

Raise to power

ASR16(i,n)

?:

Conditional evaluation

Arithmetic shift right n bits by I


positions for a 16 bit integer

STBT(i,b,n)

Set bit n in integer i to boolean


value b

Time

Description

time_to_str

converts a time value to a time string

str_to_time

converts a time string to a time value

DeltaV Product Data Sheet

Monitor and Control Software

January 2013 Page 17

Miscellaneous.

Outputs are floating-point-with-status data types that


may be wired from function block parameter
connectors or written from action expressions.

Input device signal tags (DSTs) are references to


signals and also contain signal status data.

Constants- predefined, unchangeable values in


expressions. These constants let you test values
against DeltaV system values without having to know
their internal representations. The DeltaV system
supports the constants listed below:

Description

EUP(e,p0,p100)

Conversion from
engineering units to
percent

PEU(p,p0,p100)

Conversion from
percent to engineering
units

Option Explicit

Forces all local


variables to require
explicit declaration

Logevent(x)

Logs the event string


specified

Constant

Description

GOOD

Good status

BAD

Bad status

Selstr(n,s1,s2,s3,s4,s5)

Returns the nth string.

TRUE

Boolean True

Sysstat(x)

Download, Power fail,


and switchover event
flags

FALSE

Boolean False

UNC

Uncertain status

Returns the base


portion of a path string.

LIMITED CONSTANT

Limited constant status

LIMITED HIGH

Limited High status

LIMITED LOW

Limited Low status

AUTO

Automatic mode

CAS

Cascade mode

IMAN

Initializing Manual mode

LO

Local Override mode

MAN

Manual mode

OS

Out of Service mode

RCAS

Remote Cascade mode

ROUT

Remote Out mode

Basepath(path_string)

Statements
Statement

Description

End of statement separator

:=

Assignment

IfThen
ElseEnd_if

Conditional execution

While...Do
End_While

Looping function

Exit

Exits the innermost While loop

VarEnd_var

Declare variables

Capacity

Option Explicit

Force variables to be declared

REM

Single line comment

(**)

Comment (multi-line)

Your DeltaV system provides the exact monitoring and


control functions your application requires. The software is
also scalable in size. The system is sized according to the
number of device signal tags (DSTs) and SCADA tags. A
DST is a signal used as a measured variable or controlled
output. A SCADA tag is a value brought into the DeltaV
system for monitoring, display, alarming and history
collection.

Operands

Named set constants in the form


SetName:ValueName.

Inputs are floating-point-with-status data types that


may be wired to function block parameter connectors
or used in expressions.

Classic I/O supports only one signal per device. HART,


FOUNDATION fieldbus, PROFIBUS DP, ASi bus and serial
communications can support multiple signals per device,
but in most cases only 1 DST is counted for system sizing
purposes. OPC communications can support multiple
tags per server.

DeltaV Product Data Sheet

Monitor and Control Software

January 2013 Page 18


System Specifications
Hardware

MD, MD Plus, MX, SD, or SX


Controllers

Capacity
SCADA tags
Device signal tags

25000 per workstation


30000 per system

Data source

Classic I/O (AI, AO, DI, DO)


HART (AI, AO)
FOUNDATION fieldbus
PROFIBUS DP, AS-i bus,
DeviceNet, Serial, OPC

Ordering Information
Controller function licensing is based on the number and type of I/O connected. The license limits are enforced on a systemwide basis and not on a per controller basis. For details, refer to the Controller Licensing white paper.

License Type

Model Number

License Size (DSTs)

DI

VE3111Sxxxxx

xxxxx = 00025 to 30000

DO

VE3112Sxxxxx

xxxxx = 00025 to 30000

AI

VE3113Sxxxxx

xxxxx = 00025 to 30000

AO

VE3114Sxxxxx

xxxxx = 00025 to 30000

ProfessionalPLUS Station, for


v11.3 and earlier systems

VE2101Sxxxxx

xxxxx = 00025 to 30000

ProfessionalPLUS Station, for


v12.3 and later systems

VE2101Sxxxxx-1

xxxxx = 00025 to 30000

DeltaV Product Data Sheet


January 2013 Page 19

Monitor and Control Software

Related Products

Redundancy. Controller redundancy provides you


with added reliability for critical applications.

DeltaV Fuzzy. For difficult-to-control loops, fuzzy


logic technology enables more robust control than
standard PID algorithms. It improves loop
performance by providing faster, tighter control with
minimal overshoot and settling time. Fuzzy logic is
ideal for controlling non-linear process loops, as well
as improving control of simple loops.

DeltaV Neural. Provide a continuous indication of


lab analysis of difficult measurements.

DeltaV InSight. An advanced process monitoring


system that instantly identifies under-performing
loops, provides comprehensive loop performance
analysis tools, and allows easy tuning of control
loops.

DeltaV Predict. Obtain greater process throughput


to maintain plant operation at measurable operating
constraints.

DeltaV Simulate. Development environment


including simulation on a PC.

Mimic. This is tie-back and dynamic simulation


software integrated with your DeltaV configuration.
Simulates the controllers I/O without requiring any
modifications to your control strategies

AMS Device Manager. Provides predictive


diagnostics and full asset management capabilities
including calibration, documentation, and device
configuration for HART, FOUNDATION fieldbus,
Profibus DP, and WirelessHART devices.

To locate a sales office near you, visit our website at:


www.EmersonProcess.com/DeltaV
Or call us at:
Asia Pacific: 65.6777.8211
Europe, Middle East: 41.41.768.6111
North America, Latin America:
+1 800.833.8314 or
+1 512.832.3774

For large power, water, and wastewater applications


contact Power and Water Solutions at:
www.EmersonProcess-powerwater.com
Or call us at:
Asia Pacific: 65.6777.8211
Europe, Middle East, Africa: 48.22.630.2443
North America, Latin America: +1 412.963.4000

Emerson Process Management 2013. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.

www.DeltaV.com

You might also like