Energy Automation
7UT6: Low impedance
Restricted Earth Fault
Forum Schutztechnik
s
Global network of innovation
Power Transmission and Distribution
Internal single pole faults close to transformer star point
No. 1 with
Energy Automation
400kV
230kV
Example: Autotransformer 500MVA , 400/230kV, uk12 = 15.8%
Inductivity L ? winding2 ; RF = fault resistance
X ? ? ?L ; I F LV ?
w1
f ?U LV / 3
?f
?X ? R 2F
; I F HV ? I FLV
f ?w2
w1 ? w2 ?(1 ? f)
IF
[p.u.]
IF HV [p.u. HV side]
1
IF LV [p.u. LV side]
IF tot [p.u. LV side]
w2 f
Short circuited winding part f
L2 L3
PF ? I 2Ftot ?R F ; Energy : WF ? I 2Ftot ?R F ?t Trip
PTD EA13 N.M. 7UT6: REF 07/2005
Page 2
Power Transmission and Distribution
Limits of the differential protection
No. 1 with
Energy Automation
(1 of 2)
Earth fault current limited by RE to IEmax = 2000A ; R E >> XTr
20 MVA ; YNd5
~
1L1
Side 1: 132kV
100/1A
/1A
~ 1L2
~
Side 2: 13.8kV
2L1
2L2
0
1L3
InO1 = 87.5A
2L3
InO2 = 837A
RE
/1A
IF ? f
?U
/ 3
f ? U 2N / 3
U / 3
? f ?I Emax and I K ? I F
? f 2 ?I Emax 2N
RE
U1N
U1N
2N
Will the differential protection detect the fault (setting IDiff> = 0.25I/InO , slope 1 = 0.25) ?
(fault location 20% from the star point)
I F ? 0.2 ?2000A ? 400A ;
I K ? 0.2 2 ?2000A
132kV
I ? I F /I nO2 ? 400A/837A ? 0.478 ; I ? I K /I nO1 ? 4.82A/87.5A ? 0.055
1
Io - Elimination : I D Elim ?
0 ? I*K ? I*K ? 1.154 ?I*K ? 0.063I/InO
3
1
1
0.478
Io ? Correction : I D Corr ?
0 ? I *K ? I*K ? I*F ? 0.063I/InO ?
I/InO ? 0.222 I/I nO
3
3
3
*
F
?
?
?13.8kV/ 3 ? ? 4.82A ;
*
K
?
?
PTD EA13 N.M. 7UT6: REF 07/2005
Page 3
Power Transmission and Distribution
Limits of the differential protection
No. 1 with
Energy Automation
(2 of 2)
With the above setting the differential protection (with Io-correction)
would only just fail to pick up!
IF,ID,IK
[p.u.]
IF [p.u. 13.8kV side]
ID Cor Io-correction
ID Elim Io-elimination
IK [p.u. 132kV side]
Diff. pickup at nom. load
Diff. pickup at no load
REF
Example
Short circuited winding part f
In the example at hand, it is therefore advisable to connect a CT with earth
current relay (pick up threshold 200A) in the earth connection of the star-point,
to increase the range of protection coverage to 90%.
This protection however requires a large time delay setting as the earth current
relay in the system must trip faster to maintain selectivity.
PTD EA13 N.M. 7UT6: REF 07/2005
Page 4
Power Transmission and Distribution
7UT6: Restricted Earth Fault Protection (General)
No. 1 with
Energy Automation
The REF measures the Neutral current of the object ( ISP = 3I0 ) and, depending on the
angle (? f ) between 3I0 and the also measured sum of the phase currents
( 3I0 = IL1 + IL2 + IL3 ), decides for internal or external fault.
The sensitivity of the REF is almost independent from the load of the object.
(The sensitivity of the Differential Function especially for high ohm faults will be reduced
by the load due to the slope of its Tripping Characteristic ).
The REF can be stetted to 0.1 I/INO and is therefore more sensitive as the
Differential Protection (even without load).
PTD EA13 N.M. 7UT6: REF 07/2005
Page 5
Power Transmission and Distribution
7UT6: Tripping Characteristic of REF
No. 1 with
Energy Automation
(1 of 3)
IREF> = Setting value (Trip Threshold)
IRest = Restraint current
IREF = 3I0
1) for basic Trip-Area (0 = ? f = 90):
Characteristic_1):
IREF = 3I0
and must be = IREF>
IREF / I REF> = 1 (no restraining current IRest effective)
2) for extended Trip-Area (90 = ? f = 180):
IREF = IREF> + kIRest
where IRest = ( 3I0-3I0 - 3I0+3I0 )
IRest includes the direction
I REF ? I REF ? ? k ??3Io'? 3Io' ' ? 3Io'? 3Io' ' ?? 3Io' ' ? reference, ? (3Io' ' ) ? 0
I REF ? I REF ? ? k ? 3Io'?e j? ? ? 3Io' ' ? 3Io'?e j? ? ? 3Io' '
1?
?
I REF ?
3Io' '
3Io' ' ?
?? ? I REF ? 3Io' ? 3Io'
? k ??? 1?e j? ? ?
? 1 ?e j? ? ?
3Io'
3Io'
3Io'
?
?
I REF ?
?
3Io' '
3Io' ' ?
??
? 1 ? k ??? 1?e j? ? ?
? 1?e j? ? ?
I REF
3Io'
3Io'
?
?
Characteri stic_2) :
I REF
?
I REF ?
?
1 ? k ?? 1?e j? ?
?
1
3Io' '
3Io' ' ?
?
? 1?e j? ? ?
?
3Io'
3Io' ?
for 7UT612 : k 2
for 7UT613/63 k 4
PTD EA13 N.M. 7UT6: REF 07/2005
Page 6
Power Transmission and Distribution
7UT6: Tripping Characteristic of REF
No. 1 with
Energy Automation
(2 of 3)
Figure 2: 7UT6 REF tripping characteristic
I REF
Char. for
? f = 180
I REF ?
4
Tripping
3
Blocking
-0.3
-0.2
-0.1
180 = ? f > 90
Characteristic_2)
0.0
+0.1
+0.2
90 = ? f = 0
Characteristic _1)
3I '0'
3I '0
+0.3
PTD EA13 N.M. 7UT6: REF 07/2005
Page 7
Power Transmission and Distribution
7UT6: Tripping Characteristic of REF
No. 1 with
Energy Automation
Figure 3
?f > 90
3I0-3I0
(3 of 3)
Figure 5
?f < 90
Figure 4
?f =90
-3I0
+3I0
-3I0
IRest
+3I0
-3I0
3I0
+3I0
3I0+3I0
3I0
IRest
3I0
3I0-3I0
3I0+3I0
3I0-3I0
3I0+3I0
? f = 45
3I0
? f = 135
3I0
3I0
IRest = ( 3I0-3I0 - 3I0+3I0 ) = 0
IRest = ( 3I0-3I0 - 3I0+3I0 ) > 0
IRest = ( 3I0-3I0 - 3I0+3I0 ) < 0
(neg. values will be set to 0)
PTD EA13 N.M. 7UT6: REF 07/2005
Page 8
Power Transmission and Distribution
7UT6: REF CT saturation at star point CT
No. 1 with
Energy Automation
(1 of 2)
The star point CT can or even should be weaker designed than the phase Cts !
In case of an external fault and saturation on this CT there will be no false trip.
PTD EA13 N.M. 7UT6: REF 07/2005
Page 9
Power Transmission and Distribution
7UT6: REF CT saturation at star point CT
(2 of 2)
No. 1 with
Energy Automation
PTD EA13 N.M. 7UT6: REF 07/2005
Page 10
Power Transmission and Distribution
Comparison of sensitivity between
Differential Protection and REF
No. 1 with
Energy Automation
38.1 MVA ; Vector group: YNd5
Side 2: 11kV
Side 1: 110kV
2000/1A
200/1A
2L1
1L1
2L2
1L2
2L3
1L3
200/1A
PTD EA13 N.M. 7UT6: REF 07/2005
Page 11
Power Transmission and Distribution
Settings
No. 1 with
Energy Automation
Io-Correction
PTD EA13 N.M. 7UT6: REF 07/2005
Page 12
Power Transmission and Distribution
Fault 1: Internal high ohm Fault L1-E Side 1, without Load (1 of 3)
No. 1 with
Energy Automation
PTD EA13 N.M. 7UT6: REF 07/2005
Page 13
Power Transmission and Distribution
Fault 1: Internal high ohm Fault L1-E Side 1, without Load (2 of 3)
No. 1 with
Energy Automation
With Io-Correction
With Io-Elimination
Idiff ?
0.11 I/InO
Only Ires, no Idiff
for L2,L3
PTD EA13 N.M. 7UT6: REF 07/2005
Page 14
Power Transmission and Distribution
Fault 1: Internal high ohm Fault L1-E Side 1, without Load (3 of 3)
No. 1 with
Energy Automation
Trip Area
Block Area
Iref = actual current, IREF = Setting I REF>, K s=1, IoL = I0, IoSt = I0
PTD EA13 N.M. 7UT6: REF 07/2005
Page 15
Power Transmission and Distribution
Fault 2: Internal high ohm Fault L1-E Side 1, with Load (1 of 3)
No. 1 with
Energy Automation
PTD EA13 N.M. 7UT6: REF 07/2005
Page 16
Power Transmission and Distribution
Fault 2: Internal high ohm Fault L1-E Side 1, with Load (2 of 3)
No. 1 with
Energy Automation
Iref = actual current, IREF = Setting I REF>,
Ks = 1, IoL = I0, IoSt = I0
PTD EA13 N.M. 7UT6: REF 07/2005
Page 17
Power Transmission and Distribution
Fault 2: Internal high ohm Fault L1-E Side 1, with Load (3 of 3)
No. 1 with
Energy Automation
3I0 = 36.49mA = 19.47mA, ? 3I0/ 3I0 = 19.47/140 = 0.139
InO = 200A ? 1000mA, IRef = 140mA, IRef> = 0.1 ? IRef/IRef> = 1.4
PTD EA13 N.M. 7UT6: REF 07/2005
Page 18
Power Transmission and Distribution
7UT6: REF settings
No. 1 with
Energy Automation
proposed value
InS = nominal side current
Increasing the pickup value
I Ref
InO
0.3
1313A
slope = 0.1
0.2
IRef>
0.1
0.5
1.0
1.5
2.0
? I = IL1 + IL2 + IL3 + ISP
2.5
3.0
3.5 ? I InO
nominal
load
(to be handled with care) !!!
PTD EA13 N.M. 7UT6: REF 07/2005
Page 19
Power Transmission and Distribution
Setting the direction of the Star point CT
No. 1 with
Energy Automation
Transformerwinding
L1 Setting for CT-Strpnt in Direct. Of Object
must be correct !
L2
L3
Q7
Q8
7UT612
0230 Earthing Electrode versus
Terminal Q7
Q7
Q8
7UT612
0230 Earthing Electrode versus
Terminal Q7
Q7
0230 Earthing Electrode versus
Terminal Q8
0230 Earthing Electrode versus
Terminal Q8
Q8
7UT612
Q7
Q8
7UT612
Secondary earthing of Star point CT has no influence on the direction
PTD EA13 N.M. 7UT6: REF 07/2005
Page 20
Power Transmission and Distribution
7UT6: versions
No. 1 with
Energy Automation
7UT612
Version 4.0
7UT613/63. 7UT613/63.
Version 4.0 Version 4.6
(Jan. 2006)
Number of
1
Low impedance REF
REF for
Autotransformer
No
Yes
No
PTD EA13 N.M. 7UT6: REF 07/2005
Page 21
Power Transmission and Distribution
Application
Device Configuration
No. 1 with
Energy Automation
0105
0112
0113
M1
S1
Main
protect.
object
7UT613
Y
S2
M2
Starpointbilder
X2
Sides:
S1
High voltage side (HV)
S2
Low voltage side (LV)
Measuring locations 3-phase , assigned
M1 assigned to the main protected object (side 1)
M2 assigned to the main protected object (side 2)
Auxiliary measuring locations 1-phase
X1
assigned to the main protected object (side 1)
X2
assigned to the main protected object (side 2)
X3
not assigned to the main protected object
3 phase Transformer
Enabled
Enabled
Power System Data 1
X1
Protected Object
Differential Protection
REF Protection
CT-Numbers
0211 No. of connected Meas. Loc.
0212 No. of assigned Meas. Loc.
0213 No. of sides
CT-Assign
0222 Assignment at 2 assig.
Meas.Loc./2 sides
0251 Auxiliary CT IX1 is used as
0252 Auxiliary CT IX2 is used as
Transf.
.
0313 Starpoint of Side 1 is
0314 Transf. Winding Connection Side 1
.
0323 Starpoint of Side 2 is
0324 Transf. Winding Connection Side 2
0325 Vector Group Numeral of Side 2
Funct.
0413 REF assigned to
0420 DMT/IDMT Phase assigned to
2
2
2
S1:M1, S2:M2
Side 1 earth
Side 2 earth
Solid Earthed
Y (Wye)
Solid Earthed (!!)
D (Delta)
11
Side 2
Side 1
Setting Group A
Differential Protection-Settings Group A
1211A Diff-Prot. with meas. Earth Curr. S1
1212A Diff-Prot. with meas. Earth Curr. S2
Yes (Io- correct. Side 1)
No
PTD EA13 N.M. 7UT6: REF 07/2005
Page 22
Power Transmission and Distribution
7UT6: REF Interturn fault / terminal earth fault
No. 1 with
Energy Automation
38.1 MVA ; Vector group: YNd5
Side 2: 11kV
Side 1: 110kV
2000/1A
2L1
200/1A
1L1
2L2
1L2
2L3
1L3
1L1
2L2
1L2
2L3
1L3
200/1A
(-)
(+)
? ? = 180 ? no Trip by REF
38.1 MVA ; Vector group: YNd5
Side 2: 11kV
Side 1: 110kV
2000/1A
2L1
200/1A
200/1A
ISP
ISP = 0 ? no Trip by REF
PTD EA13 N.M. 7UT6: REF 07/2005
Page 23
Power Transmission and Distribution
7UT6: REF, testing the characteristic
No. 1 with
Energy Automation
(1 of 3)
Configuration:
Winding 1:
80MVA,110kV
500/1A
500/1A
In ?
S NTr ?I NCTSec
3 ?U NTr ?I NCT Pr im
80000kVA ?1A
? 0.839 A
3 ?110kV ?500 A
(In this case for Io and Io, because all cts are primary 500A)
PTD EA13 N.M. 7UT6: REF 07/2005
Page 24
Power Transmission and Distribution
7UT6: REF testing the characteristic
No. 1 with
Energy Automation
(2 of 3)
Test point 1:
Io = 2 IREF> = 2?0.1?0.839A = 0.168A = constant. Io: at the begin approximate 0.4?0.168A
ej180=0.067A, than reducing step by step until trip? Result: -21mA/168mA = -0.125
Test point 2:
Io = 4 IREF> = 4?0.1?0.839A = 0.336A = constant. Io: at the begin approximate 0.4?0.336A
ej180=0.134A, than reducing step by step until trip? Result: -60mA/336mA ? 0.18
-0.18
TP 2
-0.125
TP 1
PTD EA13 N.M. 7UT6: REF 07/2005
Page 25
Power Transmission and Distribution
7UT6: REF testing the characteristic
No. 1 with
Energy Automation
Test point 1:
Test point 2:
?-21mA
168mA
(3 of 3)
?-60mA
336mA
PTD EA13 N.M. 7UT6: REF 07/2005
Page 26