Introduction
In 1986, Fire Protection Limited began a research programme to develop an entirely new
fire resistant ductwork system.
This programme, which is continuous has resulted in the FLAMEBAR B.W.11 Fire
Resistant Ductwork System being manufactured and supplied worldwide.
As a result of continued growth, Firespray International Limited was formed to carry out
the ongoing research and development programme and also to market FLAMEBAR
products on a global basis. Fire Protection Limited now markets and installs the system
in the United Kingdom.
This Technical Manual has been produced for everyone associated with the design and
installation of fire resistant ductwork systems and illustrates how to satisfy the
requirements of the regulatory bodies. It also clearly emphasises our own commitment to
fire safety.
FLAMEBAR B.W.11 FIRE RESISTANT DUCTWORK
SYSTEMS SATISFY ANY REQUIREMENT
FOR FIRE RATED DUCTWORK FOR VENTILATION,
KITCHEN OR SMOKE EXTRACT APPLICATIONS.
2
Contents
1
Testing requirements - BS 476 Part 24 (1987) and ISO 6944 (1985) Definitions
Page 4
Fire Resistant Ductwork - When and Why
Page 6
2.1
Regulations & Codes in the United Kingdom
FLAMEBAR B.W.11 Fire Resistant Ductwork - Analysis and Performance
Page 8
Page 9
3.1
FLAMEBAR B.W.11 - Single Source Responsibility - Certificate of Conformity
Page 9
3.2
FLAMEBAR B.W.11 - Flexibility in Design
Page 9
3.3
FLAMEBAR B.W.11 - Construction of FLAMEBAR B.W.11 Fire Duct
Page 10
3.4
FLAMEBAR B.W.11 - System Integrity - Ancillary Components
Page 11
3.5
FLAMEBAR B.W.11 - Panel Construction
Page 12
3.6
FLAMEBAR B.W.11 - To BS 7346 Insulation Temperatures
Page 14
3.7
FLAMEBAR B.W.11 - Air Temperatures at Various Distances from Duct
Page 15
3.8
FLAMEBAR B.W.11 - Guide to Fire Protection of Ductwork
Page 16
3.9
FLAMEBAR B.W.11 - Fire Resistance Criteria
Page 18
3.10 FLAMEBAR B.W.11 - Supports and Hangers
Page 18
3.11 FLAMEBAR B.W.11 - Construction Standards
Page 20
Penetration Seals Between Fire Compartments
Page 21
Pro Forma Specification Example
Page 21
Standards
Page 22
FLAMEBAR B.W.11 Fire Resistant Ductwork - System Advantages
Page 23
1. Testing Requirements
British Standard 476 Part 24 (1987)
and ISO 6944 (1985)
BS 476 Part 24 (1987) Fire Tests on building materials and structures.
Part 24. Method for determination of the fire resistance of ventilation ducts
ISO 6944 (1985) Fire resistance tests - Ventilation ducts
The purpose of BS 476 Part 24 (1987) and ISO 6944 (1985) is to measure the
ability of a ductwork system to resist the spread of fire from one fire compartment to
another without the aid of fire dampers. It should be noted that the test relates to a
complete ductwork installation and therefore joints, supports and the fire stopping through
the furnace wall all form an integral part of the test.
ISO 834 : 1975 (E) Fire Resistance Test
Standard Time - Temperature Curve
1200
1100
1000
Temperature OC
900
800
700
600
500
400
300
Furnace Temperature Curve
as Specified in BS 476 Part 24
(1987) & ISO 6944 (1985)
200
100
0
0
20
40
60
80
100
120
140
160
180
200
220
240
Time (Minutes)
Giving temperature rise as a function of time for all BS 476 Part 24 (1987) & ISO 6944
(1985) Fire Tests.
Requirements of British Standard 476
Part 24 (1987) and ISO 6944 (1985)
The fire resistance of Ventilation Ductwork
shall, according to the Standard, be
expressed in Minutes of duration of heating
until failure occurs, according to one or
more of the following criteria.
1. Stability.
2. Insulation.
3. Integrity.
Insulation
Insulation failure shall be deemed to have
occurred when the temperature rises above
ambient temperature on the external face of
the duct outside the area in which the fire
is present, and exceeds either
1. 140 OC as an average value, or
2. 180 OC as a maximum value.
Criteria of Failure
Stability
Stability failure shall be deemed to have
occurred when the Duct specimen collapses
inside or outside the area in which there is
a fire in such a manner that the duct no
longer fulfils its intended function.
Integrity
The presence and the formation of holes or
other openings in the Duct in the room
adjacent to the fire (or through the fire
stopping at the dividing wall) through
which flames or hot gasses can pass, shall
constitute Integrity failure.
Definitions of Types A & B Fire Exposure
The testing standard differentiates between types of fire exposure; two classifications
apply as details below.
Compartment
with Fire
Outbreak
Adjacent Compartment
T1
Temperature
Sensor
Fire Outside
-Duct Type A
Duct Resists
Penetration of
Fire from
Outside
Ventilation or Smoke Extract Opening
- No Fire Penetration from Inside Duct
Adjacent Compartment
T2
Temperature
Sensor
Compartment with Fire Outbreak
Fire Inside
-Duct Type B
Duct Resists Penetration of Fire from Inside
Fire Penetrates
into Duct through
Ventilator or Smoke
Extract Opening
2. Fire Resistant
Ductwork
When and Why
One of the most important factors taken into consideration when designing and
constructing a building is effective compartmentation to limit fire spread throughout the
building. Under normal circumstances compartmentation is maintained by fire dampers
within ductwork systems. However under certain circumstances fire dampers should not
be used and the ductwork itself must provide the same levels of fire resistance as that
afforded by the compartment wall or floor.
Ductwork systems which do not normally contain fire dampers are as follows:
1: Smoke Extract Ducts.
3: Pressurisation Ducts.
2: Car Park Extract Ducts.
4: Kitchen Extract Ducts.
In general terms, any ductwork system that is intended to
operate or has special use under a fire condition and cannot
therefore utilise fire dampers will require a fire rating.
Ventilation systems and applications which have special or operational effect under fire
conditions are as follows:
Mechanical Ventilation System
Mechanical ventilation systems are used to
extract air from a building and to supply
replacement fresh or airconditioned air. The
necessary fans and conditioning
equipment are generally located in separate
plant rooms, often in a basement or on the
roof. The distribution of the air involves
ductwork which may be very large, extend
through the building, penetrate
compartment walls and/or floors and may
have openings in every space through
which it passes.
Without suitable fire precautions, therefore,
ventilation ductwork can provide a route by
which fire, smoke and toxic gases are
enabled to spread rapidly through a building.
Smoke Extraction Systems
Smoke extraction is the evacuation of
products of combustion, such as smoke and
toxic gases from a building, which could
otherwise reduce visibility and impair human
functions. Smoke extraction facilitates the
escape of the building occupants and assists
firefighters in locating the seat of the fire and
extinguishing it.
In situations where smoke clearance by
natural ventilation through windows or other
openings may be difficult e.g. in large or
deep basements or in high rise buildings
without opening windows, ductwork is
required to convey the smoke to a suitable
outlet from the building. In cases where the
natural buoyancy of the combustion products
is not adequate to ensure the required smoke
extraction rate through the ductwork, fan
assisted systems are used. It may also be
necessary to install duct air inlets as part of
the smoke extraction scheme, in order to
provide the replacement air.
If the ductwork incorporated in a smoke
extraction system is wholly contained within
the fire compartment, it must be capable of
resisting the anticipated temperatures
generated during the development of a fire BS
476 Part 24 (1987) and ISO 6944 (1985)
also requires duct which is intended for
smoke extract should retain at least 75% of
its cross sectional area within the fire
compartment. If the ductwork penetrates the
fire resisting barrier, it must also be capable
of providing the same period of fire
resistance.
Dual Ventilation/Smoke Extraction Systems
These serve as a conventional ventilation
system under normal conditions, but are
converted to provide smoke extraction in the
event of fire, thus providing an economical
dual solution.
Car Park Extraction Systems
Car parks which require mechanical
ventilation must have separate and
independent extraction systems, because of
the polluted nature of the extracted air. Due to
the fire risk associated with car parks these
systems should be treated as smoke extract
systems and therefore maintain a minimum of
75% cross sectional area under fire
conditions in accordance with BS 476 Part
24 (1987) and ISO 6944 (1985). Fire
dampers should not be installed in extract
ductwork serving car parks.
Pressurisation Systems
Pressurisation is a method of restricting the
penetration of smoke into certain critical areas
of a building, by maintaining the air at higher
pressures than those in adjacent areas. It
applies particularly to protected stairways,
lobbies, corridors and fire fighting shafts
serving deep basements, as smoke within
these areas would inhibit escape.
A pressurisation system is a special form of
mechanical ventilation system. The air supply
creating the pressurisation must be
maintained for the duration of a fire, fire
dampers cannot be used with the ductwork to
prevent the spread of fire. Any ductwork
penetrating fire resisting barriers should
therefore be fire resistant.
Kitchen Extraction Systems
Non-domestic kitchens are required to have
separate and independent extraction systems,
because of the polluted nature of the extracted
air. Fire dampers should not be installed in
extraction ductwork serving kitchens, any
ductwork penetrating fire resisting barriers
should be fire resistant.
Kitchen extract ductwork presents a particular
hazard as combustible deposits such as
grease are likely to accumulate on internal
surfaces. A fire in an adjacent compartment
through which the ductwork passes could
therefore lead to ignition of these deposits
which may continue through the ductwork
system, possibly prejudicing the safety of the
kitchen occupants. For this reason
consideration should be given to the
insulation performance of kitchen extract
ducts.
Finally, Where possible, access doors, for
cleaning, at distances not exceeding 3m are
recommended.
Escape Corridors and Lobbies
It is a requirement of the Building
Regulations, as defined in BS 5588 Part 9,
Clause 9.2, that any duct crossing an escape
corridor or lobby must be fire rated for
stability, integrity and insulation, for the same
period of time as the compartment through
which it passes. It should be noted that at
least one fire damper will be required if either
side of the escape corridor is constructed with
non-fire rated ductwork.
2.1. Regulations & Codes
in the United Kingdom
Statutory Instruments
England & Wales - Building & the Building Regulations 1991
Statutory Instrument. No 2768
Scotland - Building & the Building Standards (Scotland Regulations) 1990
Statutory Instrument. No 2179 Section 187
Northern Ireland - Building Regulations (Northern Ireland) 1994
Statutory Instrument. No 243
Insurance Requirements
(Association of British Insurers & Lloyds)
Support
Documents
Advisory
Guides
British Standards Institution
(BSI)
Fire Tests
International Organisation for
Standardisation (ISO)
British Standard
Codes
Approved Document B
(England & Wales)
Fire Safety
B1 Means of Escape
B2 Internal Fire Spread
(Linings)
B3 Internal Fire Spread
(Structures)
External Fire Spread
B5 Access & Facilities for
the Fire Services
Technical Standard
(Scotland)
Part D
Structural Fire Precautions
Part E
Means of Escape form Fire
Technical Booklet E
(Northern Ireland)
Fire Safety
BS 5588 Part 9 (1989)
Fire Precautions in the
Design of Construction
of Buildings. Part9.
Code of Practice for
Ventilation & Air
Conditioning Ductwork
BS 476 Part 24 (1987)
Fire Tests on Building
Materials of Structures.
Method for Determination
of the Fire Resistance of
Ventilation Ducts
Design Guide for the
Fire Protection of
Buildings 1996
(Insurers Rules for the
Protection of Building)
ISO6944 (1985)
Fire Resistance Tests
Ventilation Ducts
BS 7346 Part 2 (1990)
Specification for
Powered Smoke & Heat
Exhaust Ventilators
BS 8313 (1989)
Code of Practice for
Accommodation of
Buildings Services
in Ducts
London District
Surveyors Association
BS 476 Part 20 (1987)
Fire Tests on Building
Materials of Structures.
Method for Determination
of the Fire Resistance of
Elements of Construction
(General Principals)
BS 476 Part 21 (1987)
Fire Tests on Building
Materials of Structures.
Method for Determination
of the Fire Resistance of
Loadbearing Elements of
Construction
BS 476 Part 22 (1987)
Fire Tests on Building
Materials of Structures.
Method for Determination
of the Fire Resistance of
Non-Loadbearing
Elements of Construction
Loss Prevention Council
(Fire Safety Guide No1
Fire Safety in Section 20
Buildings 1990)
(Fire Safety Guide No2
Fire Safety in Atrium
Buildings)
Department of Health
Firecodes
HTM81 (Fire Precautions
in New Hospitals)
HTM85 (Fire Precautions
in Existing Hospitals)
HTM88 (Fire Precautions
in NHS Housing for
Mentally Handicapped
HTM94 (Fire Precautions
in New Old Peoples
Homes)
3. FLAMEBAR B.W.11
Fire Resistant Ductwork
Analysis and Performance
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
FLAMEBAR B.W.11 - Single Source Responsibility - Certificate of Conformity
FLAMEBAR B.W.11 - Flexibility in Design
FLAMEBAR B.W.11 - Construction of FLAMEBAR B.W.11 Fire Duct
FLAMEBAR B.W.11 - System Integrity - Ancillary Components
FLAMEBAR B.W.11 - Panel Construction
FLAMEBAR B.W.11 - To BS 7346 Insulation Temperatures
FLAMEBAR B.W.11 - Air Temperatures at Various Distances from Duct
FLAMEBAR B.W.11 - Guide to Fire Protection of Ductwork
FLAMEBAR B.W.11 - Fire Resistance Criteria
FLAMEBAR B.W.11 - Supports and Hangers
FLAMEBAR B.W.11 - Construction Standards
FLAMEBAR B.W.11 Rectangular Fire Duct
3.1. Single Source - Responsibility
- Certificate of Conformity
When considering the use of Fire Resistant Ductwork, issues such as Single Source
Responsibility and Certificates of Conformity are often overlooked. When specifying
FLAMEBAR B.W.11 you are assured that every process from design to installation is
directly controlled.
Single Source Responsibility means exactly what it states, that from design through
manufacture, spray coating and installation there is a single source responsibility.
FLAMEBAR B.W.11 Flat Oval Fire Duct
Furthermore once all the installation is complete and all contractual commitments are
fulfiled a Certificate of Conformity is issued to the client. This confirms the periods
of fire resistance installed and confirms compliance with the relevant criteria of BS
476 Part 24 (1987) and ISO 6944 (1985).
This document underlines our commitment to providing the best and ultimately most
fire safe installations available.
3.2. Flexibility in Design
FLAMEBAR B.W.11 offers complete flexibility in design - rectangular, flat oval and
circular ducts are available.
FLAMEBAR B.W.11 Circular Fire Duct
The construction of the initial galvanised sheet steel duct means that all FLAMEBAR
B.W.11 Fire Ducts have normal standards of air tightness and are therefore easily
capable of being successfully tested.
As well as profile flexibility as depicted in the previous illustrations, FLAMEBAR B.W.11
Fire Ducts can also be supplied as detailed below:
Single Sided
Two Sided
Flat Oval
Three Sided
Four Sided
Circular
Any other
shape
3.3. Construction
FLAMEBAR B.W.11 Fire Duct is constructed from galvanised sheet steel manufactured to
an enhanced standard, then degreased and factory fire sprayed with FLAMEBAR B.W.11
which is a specially formulated water based compound. This contains selected mineral
filters in a low permeability elastomeric binder to a thickness of approximately 1mm to
give a finished product which has been successfully tested for international use under
Cellulosic Fire Conditions in excess of 4 hours duration. Ductwork is produced in sections
and is assembled on site utilising tested fireproof gaskets/sealants.
The unique properties of FLAMEBAR B.W.11 has enabled us to design a low density,
highly durable material which accommodates induced stress arising from extreme and
varying conditions e.g. Climatic Moisture and Structural Loading Variations, and the effect
of thermal shock during a fire.
The completed system has been completed to BS 476 Part 24 (1987) and ISO 6944
10
(1985) up to temperature of 1133 OC, thereby facilitating complete design freedom should
a fire engineering approach be adopted.
3.4. System Integrity
Ancillary Components .
FLAMEBAR B.W.11
Fire Resistant Attenuators
FLAMEBAR B.W.11
Fire Resistant VCDs
FLAMEBAR B.W.11
Fire Resistant Access Doors
FLAMEBAR B.W.11
Cable and Pipe Enclosures
Some of the additional features that can be incorporated in
FLAMEBAR B.W.11 Fire Duct Systems
1. Access Doors.
2. Control Device Housings.
3. Volume Control Dampers.
4. Cable and Pipe Enclosures.
5. Internal Flanging.
6. Penetration Seals between Compartments.
7. Protection can be applied to fans, silencers, etc.
(If suitably constructed)
11
3.5. Panel Construction
FLAMEBAR B.W.11
Fire Rated Ductwork
FLAMEBAR B.W.11 ductwork can either be constructed in flanged lengths of duct, which
are then bolted together to make a run of ducting, or in panel form. This construction is
especially useful for ducts of large cross-section and can be used on any size of duct up
to 25M x 3M.
SOME OF THE FLAMEBAR B.W.11 PANEL CONSTRUCTION SYSTEM BENEFITS
Tested for up to 4 hours Stability, Integrity & Insulation to BS 476 pt 24 (1987)
and ISO 6944 (1985) for Ventilation Fire Duct, Smoke Duct & Kitchen Extract
ductwork.
When insulation rating is required panels are pre-insulated at the factory.
Smooth cleanable internal finish.
Total flexibility in the design and construction of the duct.
Can be sent to site flat packed ready to bolt up.
Lightest fire duct system available.
The panels are delivered to site precoated on the outside face with FLAMEBAR B.W.11 and
are then bolted together incorporating FLAMEBAR intumescent gasket strip to form the
required duct cross-section.
12
Typical Panel Constructed Duct
Examples of Panel
Configurations
U AND PANEL CONFIGURATION
4 L PANEL CONFIGURATION
2 U CONFIGURATION
Typical Methods of Panel
Manufacture
Depending on Fire Resistance, manufacture should be to FLAMEBAR B.W.11
Construction Standards.
TYPE B
PANEL
1m MAX
TYPE A
PANEL
JOINT ANGLES
AND STIFFENERS
FIXED AT SPECIFIED
CENTRES
1m MAX
NOTE:LARGEST AREA
WITHOUT
STIFFENING1M 2
SHEET THICKNESS TO
SPECIFIED STANDARD
SPRAYED WITH
FLAMEBAR B.W.11
2m MAX
DUCT
BOLT TO ADJACENT
TYPE A PANEL
DUCT
MINERAL WOOL THICKNESS
VARIES DEPENDING ON
INSULATION RATING
SHEET THICKNESS
TO SPECIFIED
STANDARD SPRAYED
WITH FLAMEBAR B.W.11
TYPE A PANEL
DUCT
INSIDE
TYPICAL CORNER DETAIL
OF CONSTRUCTED DUCT
TYPE A PANEL
FLAMEBAR B.W.11
FIRE DUCT
SANDWICH PANEL
CONSTRUCTION
WITH VARYING MINERAL
WOOL INSULATION
GSS TRAY
13
3.6. FLAMEBAR B.W.11
to BS 7346 Insulation Temperatures
FLAMEBAR Solution When Lower Insulation
Temperature Required
All FLAMEBAR B.W.11 Fire Ducting has been fully tested to BS 476 Part 24 (1987) and
ISO 6944 (1985) for stability and integrity up to 4 hours. However, where lower
installation temperatures are required due to ducting being rated the same as the smoke
extract fan or a fire engineering consultant having determined a fire engineering solution.
B.W.11 product, either on its own or with the addition
We are able to offer our
of various thicknesses of insulation depending upon the insulation fire rating required.
To satisfy the low temperature smoke requirement, we have tested
B.W.11 duct
without additional insultant to the principles of BS476 Part 24 (ISO 6944) at 400c for 2 hours.
Smoke Extract Duct Test in Accordance with BS 7346 - Fire Inside Duct
Mean Furnace and Duct Surface Temperatures
FIRE TEST Nos 615, 616 & 621
700
650 OC
600 OC
600
BS 7346
TIME - TEMPERATURE CURVE
TEMPERATURE ( OC)
500
FURNACE TEMP
400 OC
400
300 OC
300
250 OC
200
B.W.11
B.W.11 WITH
25mm INSULATION
INSULATION FAIL TEMP. 140 OC + AMBIENT
100
B.W.11 WITH 50mm INSULATION
EXTERNAL TEMPERATURE OF DUCT
0
0
50
100
150
200
250
TIME (MINUTES)
300
350
400
Minimum Periods of Fire Resistance for Fire Rated Ductwork
Example showing a typical fire duct run passing through different fire rated compartments
1st FIRE COMPARTMENT
30 MIN FIRE
RESISTANT DUCT
60 MIN FIRE
RESISTANT DUCT
60 MIN FIRE
RESISTANT DUCT
2nd FIRE COMPARTMENT
3rd FIRE COMPARTMENT
4th FIRE COMPARTMENT
30 MIN FIRE
COMPARTMENT WALL
14
60 MIN FIRE
COMPARTMENT WALL
30 MIN FIRE
COMPARTMENT WALL
From the example, it can be seen that when the fire duct passes from the 2nd to the 3rd fire compartment, the
fire resistance of the duct increases in line with the rating of the fire compartment wall. This rating is not reduced
in the 4th compartment, despite the reduced rating of the fire compartment wall between the 3rd and 4th fire
compartments.
Important Note:
If the fire duct is for extracting smoke, it must also maintain a minimum of 75% of its overall cross-sectional
area over the total length of the duct, including the 1st fire compartment. Therefore smoke extract ductwork in the
1st fire compartment must always be tested to BS 476 Part 24 (1987) for stability and integrity only.
450
3.7. FLAMEBAR B.W.11
Air Temperatures at Various Distances from Duct
Without Additional Insulation
Compartment walls and floors will have a prescribed fire resistance in terms of stability,
integrity and insulation for between 30 and 240 minutes. It is therefore essential for fire
security, that where compartmentation boundaries are penetrated by fire duct, the fire
separation and the performance criteria of the penetration wall or floor is maintained, and
that the duct should not act as a conduit along which fire may spread to other areas.
In all cases, the time period for stability and integrity should be at least equal to that
required by the penetration element. However, controlling Authorities and engineered
solutions have in many circumstances waived the insulation requirement. If the ductwork is
within the first compartment (see example) it will not need to be insulated and if the fire
duct has not been fire insulated for a give period to BS 476 Part 24 (1987), sufficient
distance must be maintained between the fire duct and any adjacent combustible material.
BS 5588 Part 9, Appendix Clause A4, recommends a minimum of 500mm be maintained for
bare metal ductwork.
The graph below gives the air temperature, taken at various distances away from our
FLAMEBAR B.W.11 fire duct. It should be noted that the insulation failure temperature, as
per BS 476 Part 24 (1987), is of a minimum of 140 OC, plus ambient temperature, ie
approximately 160 OC.
FLAMEBAR B.W.11 fireduct without additional insulation
Indicative temperature measurements in air
adjacent to a duct B (fire inside) test to
BS 476 Part 24 (1987) and ISO 6944 (1985).
500
DISTANCE FROM SURFACE OF DUCT IN mm
450
TEMPERATURES TAKEN AT 1 HOUR, 2 HOURS & 4 HOURS.
400
350
300
TIME 120 mins
FURNACE TEMP
1029 OC
250
TIME 240 mins
FURNACE TEMP
1133 OC
200
150
100
TIME 60 mins
FURNACE TEMP
925 OC
50
L.P.C. TEST No TE 87473
0
0
10
20
30 40 50 60 70 80 90 100 110 120 130 140
TEMP OC MEASURED AT VARIOUS DISTANCES FROM DUCT
15
FIRE OUTSIDE DUCT
3.8. FLAMEB
Fire Resista
FIRE DUCT RATED FOR STABILITY
AND INTEGRITY TO PREVENT FIRE
GETTING INSIDE DUCTWORK
Guide to Fire
of Duc
Fire Resistance Periods Afforded by FLAMEBAR B.W.11 Fire Resistant Ductwork
Note Table Designed as Indicative Guide Only - Actual Compartmentation Requirements Must
be Verified by Others
Quoted Periods as Tested in Accordance with BS 476 Part 24 (1987) & ISO 6944 (1985)
1) Insulation - Fire inside duct, temperature rise exceeds either (1) 140 OC as an average
value, or (2) 180 OC as a maximum value on duct surface in compartment adjacent to fire
seat.
2) Insulation - Fire outside duct, temperature rise exceeds either (1) 140 OC as an average
value, or (2) 180 OC as a maximum value on internal duct surface in fire seat.
Yes
3) Insulation - Fire outside duct, temperature rise exceeds either (1) 140 OC as an average
value, or (2) 180 OC as a maximum value on duct surface in compartment adjacent to fire
seat.
Car park
mechanical extract
Pressurisation
systems
Is extract contained
within single fire zone
Will outer face of duct be
close to combustibles,
or in an escape route?
Yes
Yes
No
Minimum Stability &
Integrity ratings
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Does air supply temperature
within duct have to be protected?
Basement below 10m
90 mins
Basement below 10m
60 mins
Will outer face of duct be
close to combustibles,
or in an escape route?
Yes
No
No
Yes
Will outer face of
duct be close to
combustibles, or
in an escape route?
Yes
No
Above ground up
to 5m 30 mins
Above ground up
to 20m 60 mins
Yes
Above ground up
to 20m 90 mins
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
16
Fire resistance (In line with Compartment Criteria)
1
Stability & Integrity
Insulation - Fire Inside Duct
60, 120 or 240 mins 64 minutes
60, 120 or 240 mins 120 minutes
No
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Fire resistance (In line with Compartment Criteria)
3
Stability & Integrity
Insulation - Fire Outside Duct
60, 120 or 240 mins 210 minutes Insulation
60, 120 or 240 mins 240 minutes Insulation
Fire resistance (In line with Compartment Criteria)
2
Stability & Integrity
Insulation - Fire Outside Duct
60, 120 or 240 mins 44 minutes Insulation
60, 120 or 240 mins 60 minutes Insulation
Fire resistance (In line
Stability & Integrity
60, 120 or 240 mins
60, 120 or 240 mins
FIRE INSIDE DUCT
BAR B.W.11
nt Ductwork
FIRE DUCT RATED FOR STABILITY
AND INTEGRITY TO PREVENT FIRE
GETTING OUT OF DUCTWORK
e Protection
ctwork
Will duct system have a fan?
NB. If in doubt use Yes route
No
Will fan operate in the
event of a fire?
For kitchen
extract systems
Will fire have direct access to
the inside of duct? ie. through
vent. grille etc
No
Yes
Yes
Is fire protection
required on outside as
well as inside of duct?
Will outer face of duct
be close to combustibles,
or in an escape route?
Will fan operate to
draw air out of
system to act as
smoke extract
No
Yes
Will outer face of
duct be close to
combustibles, or
in an escape route?
Will fire protection
be required for
smoke inside
duct only?
No
No
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Will fire be on outside
of duct?
Yes
No
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
e with Compartment Criteria)
1
Insulation - Fire Inside Duct
64 minutes
120 minutes
Will outer face of
duct be close to
combustibles, or in
an escape route?
Yes
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
No
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
No
Yes
No
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Fire resistance (In line with Compartment Criteria)
1
Stability & Integrity
Insulation - Fire Inside Duct
60, 120 or 240 mins 64 minutes
60, 120 or 240 mins 120 minutes
Fire resistance (In line with Compartment Criteria)
1
Stability & Integrity
Insulation - Fire Inside Duct
60, 120 or 240 mins 64 minutes
60, 120 or 240 mins 120 minutes
Yes
Fire resistance (In line
with Compartment Criteria)
Stability & Integrity
60, 120 or 240 minutes
Yes
Will outer face of
duct be close to
combustibles, or in
an escape route?
Does air supply
temperature within
duct have to be
protected?
No
No
Yes
Yes
No
Fire resistance (In line with Compartment Criteria)
1
Stability & Integrity
Insulation - Fire Inside Duct
60, 120 or 240 mins 64 minutes
60, 120 or 240 mins 120 minutes
Fire resistance (In line with Compartment Criteria)
3
Stability & Integrity
Insulation - Fire Outside Duct
60, 120 or 240 mins 210 minutes Insulation
60, 120 or 240 mins 240 minutes Insulation
17
3.9. Fire Resistance
Criteria
Application
Fire Exposure
Smoke
Extract
Fire
Fire
Fire
Fire
Fire
Inside
Inside
Inside
Inside
Inside
Fire Duct
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Kitchen
Extract
Fire
Fire
Fire
Fire
Fire
Fire
Fire
Fire
or
or
or
or
or
Outside
Outside
Outside
Outside
Outside
Tested in Accordance with BS 476
Part 24 (1987) and ISO 6944 (1985)
Tested in Accordance
with BS 7346
Time/Temp Heating
Curve
Fire Resistance Time-Minutes
Stability
Integrity
Insulation
Low Temp
Insulation
Time/Mins
Temperatures
up
to OC
Approx. Product
Thickness mm()
240
240
240
240
240
240
240
240
240
240
10
30
60
90
120
210
240
240
-
400
600
650
-
1
25
50
80
100
(0.04)
(1)
(2)
(3.15)
(4)
Inside
Inside
Inside
Inside
Inside
Outside
Outside
Outside
Outside
Outside
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
10
30
60
90
120
15
60
90
210
240
210
240
240
240
240
240
-
400
600
650
400
600
650
-
1
25
50
80
100
1
25
40
50
80
(0.04)
(1)
(2)
(3.15)
(4)
(0.04)
(1)
(1.6)
(2)
(3.15)
Inside
Inside
Inside
Inside
Inside
Outside
Outside
Outside
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
10
30
60
90
120
10
44
60
1
25
50
80
100
1
50
100
(0.04)
(1)
(2)
(3.15)
(4)
(0.04)
(2)
(4)
3.10. Supports and
Hangers
As it is known that tensile strength of steel reduces
with temperature, it has been calculated and tested
by the Loss Prevention Council that based on the
original strength of steel for supports of 430
N/mm 2. Fire duct supports should be sized based
on:Fire Duct rated for 60 minutes 925 OC (1697 OF).
Tensile strength of 15N/mm 2.
Fire Duct rated for 120 minutes 1029 OC (1884 OF).
Tensile strength of 10N/mm 2.
Fire Duct rated for 240 minutes 1133 OC (2071 OF).
Tensile strength of 6N/mm 2.
Weight of FLAMEBAR B.W.11 Fire Duct
Total weight of up to 2 Hour Fire Duct without
insulation = 10.98 kg/m 2. (2.24lb/ft 2)
Total weight of up to 2 Hour Fire Duct with 50 mm
insulation = 16.23 kg/m 2. (3.33lb/ft 2)
Total weight of up to 2 Hour Fire Duct with 100 mm
insulation = 21.48 kg/m 2. (4.40lb/ft 2)
Total weight of up to 4 Hour Fire Duct without
insulation = 14.12 kg/m 2. (2.89lb/ft 2)
Total weight of up to 4 Hour Fire Duct with 50 mm
insulation = 19.37 kg/m 2. (3.97lb/ft 2)
Total weight of up to 4 Hour Fire Duct with 100 mm
insulation = 24.62 kg/m 2. (5.05lb/ft 2)
18
Above weights are based on 1000mm x 1000mm (40 x 40) typical standard ductwork per linear metre.
When designing and testing Fire Resistant Ductwork it is critical that the reduction in
tensile strength of steel under fire load is given adequate consideration. This applies
to hangers (studding) and bearers, but it is equally important that due consideration
is given to the performance of the fixing system under fire load.
It must be recognised that the pull out load of an anchor under fire conditions is
significantly less than at ambient temperature. By specifying FLAMEBAR B.W.11 you
can be confident that these issues have been adequately addressed.
Table Showing Typical Anchor and Hanger Sizes Required for
2hr. Stability and Integrity FLAMEBAR B.W.11 Smoke Duct
Duct Size
Duct area per
metre run
Total weight
per metre
run of duct
+BW11
Bearer
spacing
mm
Weight on
each bearer
Weight on
each anchor
Max test load
that Hilti HKD
anchor will
withstand in
a fire situation
Size of
anchor &
hanger used
to provide
added safety
Sum of 2
sides 600
1.2m 2
14.4 kg
1500
21.6 kg
10.8 kg
30 kg
= 6mm HKD
M8
Sum of 2
sides 800
1.6m 2
19.3 kg
1500
28.95 kg
14.5 kg
30 kg
= 6mm HKD
M8
Sum of 2
sides 1200
2.4m 2
33.65 kg
1500
50.7 kg
25.2 kg
30 kg
= 6mm HKD
M8
Sum of 2
sides 1600
3.2m 2
51.1 kg
1500
76.6 kg
38.3 kg
40 kg
= 6mm HKD
M8
Sum of 2
sides 2000
4.0m 2
65.7 kg
1500
98.5 kg
49.5 kg
80 kg
= 10mm HKD
M10
Sum of 2
sides 3000
6.0m 2
98.7 kg
1500
148 kg
74 kg
80 kg
= 10mm HKD
M12
Sum of 2
sides 4000
8.0m 2
131.5 kg
1500
197 kg
98.5 kg
120 kg
= 12mm HKD
M12
Sum of 2
sides 5000
10.0m 2
202 kg
1500
303 kg
152 kg
300 kg
= 16mm HKD
M16
SUPPORT STEEL
TO SPAN HOLE
SIZING
OF GALLOWS
BRACKET TO
SUIT DUCT
CONCRETE
FLOOR SLAB
Support sizes dependent on
stability and integrity rating
TYPICAL ALTERNATIVE
ARRANGEMENTS FOR
SUPPORTS
50 X 50 R.S.A
FRAME
MINERAL WOOL
Typical Vertical & Horizontal
Support Arrangements
3mm THICK FLAT BAR
CALCIUM
SILICATE
BOARD
Ensure that fixing into slab
is capable of supporting the
weight shown on the chart.
(Note, all parts of anchor
to be steel)
50mm
50mm
N.B. If ordered, several fire stop details can be
provided, please refer to office for details.
19
3.11. Construction
Standards
A series of Construction Standards are produced that directly relate to the requirements
of each individual project. These Standards represent varying periods of fire resistance,
ductwork profile and operational requirement of the duct system (i.e. smoke extract,
ventilation duct or kitchen extract). Detailed below is a typical construction standard.
Typical Construction Standard
Each standard is laid out in a clear and concise way. From these standards it is
possible to easily identify flange requirements, support requirements, dimensional data
etc. It is important to remember that these standards replicate exactly the methods
used in actual fire tests therefore ensuring optimum system performance under the
required fire conditions.
20
4. Penetration Seals
Between Fire Compartments
If specified we can provide fir stopping compartments as part of our installation
service. Detailed below are two typical fire rated ductwork stoppings, as tested to
BS 476 Part 24 (1987) and ISO 6944 (1985).
1) Mineral Wool and Calcium Silicate Board Fire Stopping
HT MINERAL
WOOL PACKING
100 MIN.
SCREW FIXINGS
CALCIUM SILICATE
BOARD ( 30mm THICK )
100 MIN.
SCREW FIXINGS
HT MINERAL
WOOL PACKING
CALCIUM SILICATE
BOARD ( 30mm THICK )
3mm THICK FLAT BAR
ON PENETRATIONS WITH
LONGEST SIDE GREATER
THAN 2m, TIE BAR TO BE
PROVIDED (min 16mm DIA )
FLANGE
50 MAX.
OR WITHIN WALL
50 x 50 R.S.A
2) FLAMEBAR FPS 1000 Fire Stopping
3mm THICK FLAT BAR
FLANGE
50 MAX.
OR WITHIN WALL
50 x 50 R.S.A
ON PENETRATIONS WITH
LONGEST SIDE GREATER
THAN 2m, TIE BAR TO BE
PROVIDED (min 16mm DIA )
5. Pro-Forma
Specification Example
FLAMEBAR B.W.11 Fire Resistant Ductwork to be manufactured by Fire Protection
Limited (or other authorised licensee) for our Ventilation/Smoke/Kitchen Extract/Supply
System to comply with BS 476 Part 24 (1987) & ISO 6944 (1985),
for ........Hours Stability ........Hours Integrity and ........Hours Insulation.
Ductwork to be Rectangular/Flat Oval/Circular construction, complying with Building
Regulations Class 0 requirements.
The Duct to be a composite Fire Duct manufactured to Method 3 of BS 5588 Part 9
factory produced. Once erected, to be pressure tested, if required, by client, to HVCA
Standard DW 143, Pressure Classification Class ........
On Kitchen Extract Ductwork, Access Doors to be installed at a minimum distance
between doors of 3 metres as required by BS 5588 Part 9 (1989).
21
6. Standards
The range of FLAMEBAR B.W.11 Fire Duct has been
tested by the Loss Prevention Council in accordance
with BS 476 Part 24 (1987) and ISO Standard 6944
(1985), for vertical and horizontal ductwork, with fire
inside and outside the duct, in excess of 4 hours
Stability, Integrity and Insulation, for Ventilation
Ductwork, Smoke Extract Ductwork or Kitchen Extract
Ductwork.
FLAMEBAR B.W.11 Fire Duct has also been tested by
the Loss Prevention Council, in accordance with
BS 476 Part 7 (1987) for surface spread of flame in
accordance with the Flame Spread Classification given
in the Standard.
FLAMEBAR B.W.11 Fire Duct has also been tested by
the Loss Prevention Council to BS 476 Part 6 (1989)
for fire propagation, confirming that the product can
be defined as a Class O Material in accordance with
the Building Regulations 1991.
FLAMEBAR B.W.11 Fire Duct has also been tested by
L.U.L. to BS 6853 and satisfied the Fire Safety Code of
Practice requirements for smoke emission and toxic
fume emission.
FLAMEBAR B.W.11 Fire Duct has the U.S.A.
Underwriters Laboratory UL Classification for up to 4
Hr. Fire & Smoke Ductwork.
FLAMEBAR B.W.11 has been tested by Underwriters
Laboratory in the USA to determine compliance with
NFPA 90A (Installation of Air Conditioning and
Ventilating Systems) for flame spread and smoke
development with the following results:
NFPA
Stipulation
BW11 Results
Flame Spread
not to exceed
25
9.4
Smoke
Development no
higher than 50
0.2
Test conducted in accordance with UL Standard 723
Test for Surface Burning Characteristics of Building
Materials (ASTM E84).
FLAMEBAR B.W.11 Fire Duct has also passed the hose
stream test to ASTM - E119 with water pressure of
207 KPa (30 psi) for 2 1/ 2 mins.
Impact Test of FLAMEBAR B.W.11 Fire Duct
Impact test to BS 5669, in which a dart imparts
44.15 joules (32.5 ft pound force) at maximum drop,
resulting in a small indentation which passes under
the criteria of BS 5669. FLAMEBAR B.W.11 Fire Duct
also has undergone impact testing to the requirements
of Appendix A BS 5588 Part 5.
Leakage Testing of FLAMEBAR B.W.11 Fire Duct
The construction and sealing of the Fire Duct System
allows the ductwork to be tested up to Class D high
pressure, if required by the clients specification, which
22
has a leakage limit of .0001 x P 0.65 litres per second
per sq. metre of duct surface area, as laid down by
the HVCA Specification DW 143. Higher pressures and
lower leakage rates can be achieved if required by the
Clients specification.
Exterior Weathering of FLAMEBAR B.W.11 Fire Duct
Duplicate samples were placed on the exterior
weathering frame and left totally exposed from
January 1993. The results so far show:
1. Some dirt pick-up which can be washed off.
2. No mould growth.
3. No chalking.
4. Material has remained totally intact.
Considering the length of time the samples have been
exposed, the material is in good condition.
Artificial Weathering of FLAMEBAR B.W.11 - OUV
Weatherometer
The samples undergoing artificial weathering have
undergone over 22000 hours of alternate UV and
condensation cycling which is extremely excessive in
duration terms, normally 1000 hours is sufficient to
predict whether a material is suitable for exterior/semiexposed conditions. 22000 hours is equivalent to 60
years external exposure.
Expansion of FLAMEBAR B.W.11 Fire Duct
As all steel expands with temperature, there will
naturally be an expansion of Fire Duct under fire
conditions as follows:
At 1100 OC an expansion of 0.01562mm per mm
(0.016 in per in)
At 600 OC an expansion of 0.00852mm per mm
(0.008 in per in)
At 430 OC an expansion of 0.006106mm per mm
(0.006 in per in)
Thermal Properties of FLAMEBAR B.W.11 Fire Duct
U value - thermal transmittance.
BW11 without insulation = 5.0 w/mk 2k
(0.88Btu/ft 2h 0f)
BW11 with 50mm insulation = 0.833 w/m 2k
(0.147Btu/ft 2h 0f)
BW11 with 100mm insulation = 0.48 w/m 2k
(0.08Btu/ft 2h 0f)
Chemical Resistance of FLAMEBAR B.W.11 Fire Duct
The coating has been tested in:
Standard 10% solutions of the following acids:
Hydrochloric, Nitric and Sulphuric.
Standard 10% solutions of the following Alkalies:
Sodium Hydroxide and Potassium Hydroxide.
The following solvents: Xylene and Acetone.
After 10 days total immersion, all the above chemicals
failed to cause a Breakdown of the product structure.
7. System Advantages
Single Source Responsibility
1.
2.
3.
4.
The design of all FLAMEBAR B.W.11 Systems are to a certified standard.
All FLAMEBAR B.W.11 Fire Duct is manufactured and sprayed to QA ISO 9002 Standard.
All FLAMEBAR B.W.11 Fire Duct is erected to QA ISO 9002 Standard.
Certificate of Conformity is issued following final inspection, certifying compliance with all necessary regulations.
Testing
All FLAMEBAR B.W.11 Fire Duct has been tested to:
BS 476 Part 24 (1987) & ISO 6944 (1985) for up to 4 hours Stability, Integrity & Insulation.
BS 476 Part 6 for Fire Propagation Class O
BS 476 Part 7 for surface spread of flame
Weight: FLAMEBAR B.W.11 Fire Duct is the lightest Fire Duct system available.
Shape: FLAMEBAR B.W.11 Fire Duct can be manufactured in Rectangular, Flat Oval or Circular.
Impact Resistance: FLAMEBAR B.W.11 systems are impact resistant to BS 5669 and to BS 5588 Part 5,
Appendix A.
Moisture Absorption: FLAMEBAR B.W.11 systems are non-hygroscopic and have been tested in an artificial
Weatherometer to an equivalent of 60 years external exposure.
Chemical Resistance: FLAMEBAR B.W.11 Fire Duct is chemically resistant to many acids and solvents and
has excellent resistance to chemical attack.
Smoke and Toxic Fume Emission: FLAMEBAR B.W.11 Fire Duct has been tested to BS 6853 for Smoke
Emission and Toxic Fume Emission.
Pressure Testing: FLAMEBAR B.W.11 Fire Duct has the same frictional resistance to GSS ductwork, and can be
pressure tested to 2500 pascals (10 wg) with a leakage rate of less than 0.16 litres per second per m 2 (0.032 ft 3
per minute per ft 2) of surface area.
Anti Drumming: FLAMEBAR B.W.11 Fire Duct has a damping co-efficient to BS AU125(1966) of 19db per
second decay rate.
Inline Plant: Inline Plant can be treated with FLAMEBAR B.W.11, if suitably constructed.
Acoustic Properties: FLAMEBAR B.W.11 Fire Duct achieves a Sound Reduction Index to BS 2750 Part 3
(1980) as tabled below:
Frequency (Hz)
Systems
63
10.2
125
11.7
250
16.7
500
21.7
1K
27.7
2K
32.7
4K
37.7
8K
43.7
dB
B.W.11 + 60kg/m 2,
50mm insulation
11.0
12.5
17.5
22.5
28.5
33.5
38.5
44.5
dB
B.W.11 + 105kg/m 2,
50mm insulation
13.4
14.9
19.9
24.9
30.9
35.9
40.9
46.9
dB
B.W.11
Size: FLAMEBAR B.W.11 Fire Duct is fully certificated for any size of Ductwork in the vertical and horizontal plane
up to 25m x 3m (82 x 10) cross sectional area.
Cleaning: The smooth internal finish of FLAMEBAR B.W.11 Systems enable easy cleaning of the ductwork
therefore it is ideal for kitchen extract duct installations.
Colour: FLAMEBAR B.W.11 Fire Duct without insulation has a monolithic spray texture with natural buff finish.
FLAMEBAR B.W.11 systems can also be overpainted or sprayed with water based paint to obtain any desired
colour.
23