Power Flex Multistage Controller
Power Flex Multistage Controller
POWERFLEX
Voltage Module
DESCRIPTION OF OPERA
TION
OPERATION
The Fisher Pierce Multi-Step Series Control is intended for use with multiple capacitor racks, typically
found in substation applications. The controls can be purchased in either 2 or 3 step configurations. They
are available in Var, Voltage or Line Current configurations.
The control will operate (close) starting with the first step (top module) then activate the second and third
(if purchased) after a fixed time delay. This ensures proper sequencing on capacitors. When opening
capacitors, the sequence is reversed.
ORDERING INFORMA
TION FOR MUL
TI-STEP CONTROLLERS
INFORMATION
MULTI-STEP
TO ORDER: FOLLOW THE MODEL NUMBER EXAMPLES AS SHOWN, THEN SELECT FROM THE T
ABLES NUMBERED 1 THROUGH 8
TABLES
5 6
J 6
3 2 3 2 3 4 5
D 35 D 35 D W J
DESCRIPTION
Code
7 8
6 B
DESCRIPTION
Code
W
B
TABLE
6
6
7 8
6 B
CL
TR
CL
TR
STEP 3
TYPE
2406 Voltage
4604* VAr, use Fisher Pierce Series 1301 standard line post
sensor, 3, 4W, Wye system
CL
STEP 2
TR
LN
STEP 1
JUMPER CONNECTIONS:
Isolated Output, no jumper 7 to 8
(term 8 = switching voltage)
TABLE 6. ENCLOSURE*
Code
3
6
2
DESCRIPTION
Aluminum, 8w x 7d x 18h
Structural foam, 9.25w x 8.5d x 15.25h
None
35
36
37
38
39
40
64
DESCRIPTION
Voltage
Line current, use with 4844
Line current, use with 4846
VAr, use with 4604
VAr, use with 4608
VAr, use with 4609
VAr, use with 4620
TABLE 7. OPERA
TING INFORMA
TION
OPERATING
INFORMATION
Code
3
5
6
8
DESCRIPTION
240V, 50Hz, 5A fuse
120V, 50Hz, 5A fuse
120V, 60Hz, 5A fuse
120V, 60Hz, 10A fuse
DESCRIPTION
Step Controller
D
B
TIME
60 seconds (standard)
20 seconds (standard)
Refer to page 4.
10
11
C.S.
12
NT
SPECIFICA
TIONS FOR MUL
TI-STEP CONTROLLERS
SPECIFICATIONS
MULTI-STEP
SENSING MODULES
Input V
oltage Range:
Voltage
105 to 135Vac, 60 Hz
200 to 260 Vac, 50 Hz
HIpot T
est: 1800 Vac, 1 second. ANSI C62.41 1974
Test:
0
Operating T
emperature: -30 to + 60 C
Temperature:
0
0
-22 to + 140 F
Close Counter: Pulse operated. All close operations
Type
Input
Range
Accuracy
Voltage
V.T.
105-135 Vac
+/- 1 Vac
Current
1301 Ser.
3-500 Aac
+/- 3% setting
+/- 3% range
Current
C.T.
VAr
1301 Ser.
0-300 A lag
+/- 3% setting
0-450 A lead
+/- 3% range
C.T.
0-1 A reactive
+/- 5% range
0.5 Amp
(lead/lag)
VAr
Close
Step #1
Trip
Step #2
Close
Step #2
Trip
Step #3
+/- 3% Setting
+/- 3% Range
Step #1
0.5-5Aac
Close
Step #3
Trip
Line Voltage
Current Input
(C.T. or current sensor for
Var or current control)
Neutral
MECHANICAL DA
TA
DAT
90 Libbey Parkway
eymouth, MA 02189 U.S.A.
Parkway,, W
Weymouth,
Tel: (781) 340-0700 Fax: (781) 340-0728
www
.fisherpierce.com
www.fisherpierce.com
Fisher Pierce, 1997 FP008C - 1197-S-S
4000 East 1
16th St., Cleveland, Ohio 44105-4398 USA
116