Air Handling Unit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 96

CLCH-DS-9

February 1999

CLCH-DS-9

Second Printing

T-Series Climate Changer


Air Handlers
Sizes 3 through 100

American Standard Inc. 1999

Contents

Features and Benefits

Applications

10

Selection Procedure

28

Quick Select

29

Unit Sizes

34

General Data

66

Jobsite Connections

81

Mechanical Specifications

92

Features
and
Benefits
The T-Series Climate Changer Air Handler
Technology, Tradition, and the Total Comfort Solution
The newest addition to Tranes worldclass line of Climate Changer air
handlers is a central-station air handler
designed to meet a wide range of
customer needs in outdoor
applications.
The T-Series Climate Changer air
handler (TSC) unites the latest in
manufacturing technology with Tranes
long-standing tradition of engineering
excellence. Tranes design engineers
created a new outdoor air handler that
incorporates such features as
component flexibility and ease of
application, integrated standard control
options, industrial design, weathertight
integrity and technological
manufacturing advances. All of this
combined with the expertise of Tranes
sales engineers makes the T-Series
Climate Changer air handler more than
just part of your HVAC systemits part
of Tranes Total Comfort Solution.

Controls specifically designed for the T-Series, installed in a


factory environment by Trane technicians include:
End devices
Motor controllers
Variable frequency drives
Unit-mounted DDC controllers
Traq damper ventilation control module
Standard turnkey controls package that is fully UL Listed

A variety of fan options, including plug,


forward curved, airfoil and Tranes
Model Q vaneaxial fan for acoustically
sensitive applications.

Integrated, fully-enclosed
control panel for starters,
variable frequency drives
and unit-mounted
controllers.

A wide range of high-efficiency


heating and cooling coils.

Features
and
Benefits
Common T-Series Climate
Changer Air Handler
Configurations:

Horizontal draw-thru, vertical (down)


draw-thru or blow-thru units
Return or exhaust fan economizer
systems
Internal face-and-bypass applications
Complete factory packaged control
systems for fast track projects

Ultra-low-leak dampers are standard.


Inlet hoods with moisture eliminators.

Standard double-wall panels with two-inch


closed-cell insulation provide superior thermal
performance (as high as R12), comparable to
three inches of conventional 1 lb/ft3 insulation.

Traq damper airflow-monitoring


station for control and measurement of
outdoor air to meet ASHRAE Standard
62-89 guidelines.

Numerous filtration options,


including pleated media,
cartridge and bag filters.

Features
and
Benefits
Design Advantages
Form and Function
The T-Series Climate Changer air
handlers form is the result of extensive
evaluation of both customer needs and
the requirements of an outdoor unit.
Trane designed a unit roof that is
positively sloped and overhangs all
four sides of the air handler. This allows
for complete water drainage (no
rust-promoting puddles), while the
overhang keeps hard-driving rain away
from the top of the access doors. To
further improve integrity, all unit joints
are sealed and fastened with a
galvanized steel joint strip.

Galvanized steel joint strip between two


roof sections of the T-Series Climate
Changer.

The T-Series door utilizes a newly


designed latch with a single handle.
This allows for easier access, while
helping ensure a positive seal across
the entire door frame in both draw-thru
and blow-thru applications.

The TSCs handle is surface-mounted,


rather than piercing through the door,
eliminating the possibility for water
entry and improving the thermal
performance of the door. The latching
mechanism is equipped with features
that meet OSHA safety requirements,
and can be locked to limit entry.
When installed on a roof curb, the
T-Series Climate Changer air handler
becomes an integral part of the roof.
The inverted U-channel that forms the
base of the unit rests on a gasketed
roof curb, reducing the chance of
leakage.
Unit Construction
Another advantage of the T-Series
Climate Changer air handler is its
phosphatized, galvanized steel
formulated panels with rigid,
closed-cell insulation. This allows for
fewer seams, while providing the unit
with unsurpassed panel strength and
deflection resistance. The TSC is
capable of operation at static pressures
of +6/ -4", while the closed-cell
insulation provides an R-value of 12 as
standard!

Versatility Is Standard

The T-Series Climate Changer air


handler is one of the industrys most
versatile, cataloged rooftop air
handlers. Trane can provide options to
meet almost any need in an outdoor
central station air handler, and with
standard product options.
Standard TSC Features:
heavy-duty, unitized construction
closed-cell insulation with R-value up
to 12
pitched, double-wall roof
double-wall interior panels
solid, galvanized steel floor
double-wall doors with a new
single-handle design
insulated, galvanized or stainless steel
drainpans pitched in two-planes to
help ensure positive drainage
ultra low-leak dampers
inlet hood with moisture eliminator
exhaust hood
painted external unit casing in
accordance with the ASTM B117
salt-spray test

Access door with surface-mounted single


handle door latch and tempered glass
window.

Trane offers a wide variety of fans and


motors, all available with factory-mounted
controls.

Choice of Fans
An extensive array of fan types and
options, including inlet guide vanes
and variable frequency drives for
modulation in variable air volume
systems, further enhances the TSCs
versatility. Trane offers a wide variety of
fans and motors, all available with
factory-mounted controls.
Now you can choose the fan that best
satisfies each jobs supply, exhaust or
return fan needs:
double-width/double-inlet (DWDI)
centrifugal fans in forward-curved (FC),
backward-inclined (BI) or airfoil (AF)
configurations
single-width/single-inlet (SWSI) plug
fans
airfoil vaneaxial fans (Model Q)
Each fan is rated in accordance with
ARI Standard 430 to ensure cataloged
performance. All DWDI fans are ARI
Standard 430 certified.

Features
and
Benefits
Optimized Coils
Flexibility also characterizes the
T-Series Climate Changer air handlers
coil offerings. The variety of types,
sizes, arrangements and materials
available lets you select a coil
optimized for your applications
specific pressure drop and capacity
requirements.
Options include:

1- to 10-row, 1/2- or 5/8-inch OD chilled


water coils
1- or 2-row, 1/2 or 5/8-inch OD hot
water coils
2- to 8-row, 1/2- or 5/8-inch OD
refrigerant coils
1-row, 1-inch OD, distributing-type
(non-freeze) steam coils
infinitely-variable fin spacing
stainless-steel coil casing
copper fins
red brass tubes
Delta-Flo E and Delta-Flo H,
Prima-Flo and Sigma-Flo fin surfaces
baked phenolic coatings
header drain and vent connections
fully drainable coils
half, full and dual serpentine circuited
water coils
standard, intertwined and face-split-

Integral controls cabinet for starters,


variable frequency drives and unit
controllers

circuited refrigerant coils.

All standard heating and cooling coils


are engineered and manufactured at
Tranes air handling systems
manufacturing facility. Cataloged coil
performance is certified in accordance
with ARI Standard 410.
Optional Features:
exhaust or return fan economizers
direct space pressurization control
additional full-sized, gasketed, doublewall doors
air blenders
factory mounted and run-tested
controls
versatile access section lengths to meet
specific needs
assorted filtration options
external pipe cabinet
full array of pre- and final filter sections
extended grease lines
single-point power on most sizes
heat-recovery coils (outside the scope
of ARI Standard 410s certification)

Turnkey Controls Solutions

T-Series Climate Changer air handlers


offer one of the industrys most
comprehensive factory-packaged
control systems. Turnkey control
packages (factory-mounted and tested
systems) help lower installation cost
and risk while dramatically improving
quality and reliability. The advantage of
having Trane technicians install
controls (specifically designed for your
TSC unit) in a controlled factory
environment simply cant be matched
with field mounting by a local electrical
technician. The entire air handler
control system is engineered,
mounted, wired and tested before the
unit leaves the factory.

Tranes factory-mounted and tested


controls and end devices save time and
money at the jobsite.

Factory installed and tested turnkey


components include:
starter packages (control power
transformer, starter)
variable-frequency drive packages
(control power transformer, starter,
That means:
Control components are properly sized, VFD, disconnect)
disconnects
selected and laboratory-tested for
unit-mounted DDC controllers
optimal system performance.
Trained technicians install the controls control valves
reliable jackshaft-driven electronic
under ideal conditions using
actuators for dampers and inlet
state-of-the-art equipment, eliminating
guide-vanes
costly field coordination and
installation.
temperature, humidity and pressure
sensors
Each control system is fully tested
low-limit switches
before it leaves the factory. A
computer-based test station simulates fan and filter status switches
actual operating conditions, supervises high- and low-pressure switches
the unit controller, drives the actuators single-point power on both high and
low voltage wiring
and surveys the input and output
devicesall to help assure trouble-free
installation and reliable operation when
your T-Series Climate Changer air
handler reaches the job site.

Features
and
Benefits
Integrated Comfort System
Compatibility

The T- Series Climate Changer air


handlers turnkey control package
provides standalone air handler
operation. But it can also be part of a
complete line of control systems that
includes unit controllers and Tracer
building management systems to
integrate and magnify your control
capabilities. When joined by a simple,
single twisted-wire pair, they constitute
a Trane Integrated Comfort system
(ICS) a powerful system architecture
that unites Trane HVAC equipment,
direct digital control and building
management into a single control
strategy.

What that means to owners, facility


managers, designers and contractors
is:
Single-source responsibility equipment
and controls engineered for each other
and provided by a single manufacturer
simplify job-site coordination efforts
and reduce installation time, expense
and risk.
Comprehensive monitoring and
diagnostic capabilities Trane
engineers its unit-mounted controls to
provide the highest level of useful
information possible. Our family of
sophisticated Tracer building
management systems coordinates this
information and provides a powerful
tool for scheduling preventive
maintenance, reducing equipment
downtime and controlling service
expense.

System optimization Tracer enables

information-sharing and complex


control strategies, such as ventilation
reset, throughout the HVAC system. It
also helps ensure that each subsystem
operates in the most efficient manner
possible while continuing to satisfy
current loads. The result is reduced
building energy consumption through
effective operation of the entire HVAC
system.

BACnet

The communication protocol for Tracer


Summit, Tranes premier building
automation system, is based on
ASHRAE/ANSI BACnet Standard
135-1995. BACnet is a standard,
open-communications protocol that
allows both integration (connectivity of
equipment and controls purchased
from multiple suppliers) and
interoperability (information-sharing
between independent and dissimilar
systems within a building or campus).
Indoor ConcernsOutdoor Solutions
The building industry is continuously
evolving and the rate of change is
accelerating. Technological, economic,
regulatory and environmental factors
are very different now than they were
just a few years ago. The T-Series
Climate Changer air handlers
standard and custom capabilities help
you address todays multifaceted
design issues especially indoor air
quality (IAQ) and ASHRAE Standard 62
while providing the versatility to
adapt to tomorrows challenges.
ASHRAE 62-1989
Basically, ASHRAE Standard 62
requires that an air handling system
must bring sufficient outdoor air (OA)
into the building, filter the air and
control microbial growth. However,
applying these principles could mean
greater energy consumption, larger,
noisier units and increased risk of coil
freeze-up. The T-Series Climate
Changer air handler lets you configure
unique IAQ-ready air handling
solutions that address all of these
concerns.

A Tracer Summit building automation


system offers facility managers the control
they need.

Internal view of Tranes patented Traq


Damper for measurement and control of
outdoor air.

Controlling Ventilation Airflow


Tranes exclusive airflow-monitoring
solution, the Traq damper, allows
direct measurement and control of
outdoor (or return) airflow, and is
installed and tested at the factory for
ease of use. When applied as part of a
Tracer Summit-based Integrated
Comfort system, ventilation airflow
can be controlled dynamically and
documented to verify compliance with
ASHRAE Standard 62. Factorymounted and tested to reduce
installation and start-up costs, the Traq
damper also requires significantly less
straight duct than traditional airflowmonitoring stations.
Inhibiting Microbial Growth
The T-Series Climate Changer air
handler can be selected with features
that minimize microbial growth
through proper condensate
management, humidity control and
easy access for regular maintenance
and cleaning, including:
non-corroding drain pans sloped in two
directions to assure positive drainage
dehumidification solutions (e.g., low
sensible-heat-ratio coil selections, or
100% outdoor air units in conjunction
with other Trane airside products)
full-size access doors and access
sections in 11 to 60-in. lengths for
cleaning of internal components
antimicrobial treatments for drain pans
and filters

Features
and
Benefits
Removing Airborne Contaminants
Effectively controlling particulate and
gaseous contaminants by reducing
their concentrations to acceptable
levels or removing them from the
airstream altogether is another key to
ensuring good indoor air quality. That
necessitates proper filter selection.
Tranes T-Series Climate Changer air
handler can be equipped with a variety
of filtration options:
pleated media with 20- to 95-percent
efficiency (ASHRAE Standard 52-1976)
bag or cartridge filters with 65- to 95
percent efficiency (ASHRAE Standard
52-1976)
antimicrobial-treated filters

Recovering Energy
Increased ventilation airflow increases
heating and cooling loads, and
ultimately, operating costs. Bringing in
more fresh air when outdoor
temperatures are low also increases
the risk of damaging coils. Airside
energy recovery addresses both
concerns by salvaging heat from the
exhaust airstream to precondition
outdoor air entering the building. A coil
runaround loop may be used in
conjunction with other Trane products
to achieve a more energy-efficient air
handling system. See your local Trane
sales engineer for more details.

Providing Quiet Comfort


Acceptable space sound levels
enhance occupant comfort and
productivity. However, system designs
that promote good IAQ can adversely
affect acoustics: unlined ductwork, air
handlers with solid double-wall
construction, and increased fan static
pressures (resulting from the addition
of energy recovery and increased
filtration) can magnify the buildings
background sound.
Controlling noise at its source is the
most cost-effective solution for
providing quiet comfort in the space.
This source attenuation can
eliminate the need for duct-mounted
silencers and thereby lower fan
operating costs (by reducing system
static pressure). But to control source
noise, you must choose:
The rightfan FC, BI, AF, plug or
Model Q
The right casing construction use
solid or perforated double-wall
The right unit configuration possibly
add an inlet or discharge plenum
All of the above choices should be
based on AMCA 300 tested data and a
working knowledge of acoustics. Trane
has the tools (such as the Trane
Acoustics Program [TAP]) and
expertise to help with your acousticallysensitive jobs. Consult your local Trane
engineer for assistance.

Trane offers a wide variety of filtration


options for the T-Series Climate Changer air
handler.

Total Quality for a Total


Solution

The T-Series Climate Changer air


handler combines comprehensive
performance certification by the Air
Conditioning and Refrigeration Institute
(ARI) with thorough laboratory testing
and advanced manufacturing methods.
Together, these elements help assure
that each T-Series Climate Changer air
handler operates predictably and
reliably throughout its life. Unlike other
rating methods that check fan
performance alone, T-Series Climate
Changers are performance-tested in
accordance with ARI Standard 430 in a
certification process that evaluates the
entire air handler on the basis of
airflow, static pressure, fan speed and
brake horsepower. Heating and cooling
coils are rigorously tested in
compliance with ARI Standard 410 to
assure that they also deliver cataloged
performance.
The T-Series Climate Changer air
handler and its standard options are
listed by Underwriters Laboratories Inc.
This product has been evaluated by UL
and meets the applicable U.S. and
Canadian safety standards.
Modifications to the TSC may affect UL
Listing. Consult your local Trane office
for further information.
Our state-of-the-art manufacturing
facility employs a system of Total
Quality Checks and verifications at
each work station to ensure consistent
high quality. And through the use of
Demand Flow Technology (DFT) in
our manufacturing facilities, we can
better serve you by providing greater
product flexibility, ever improving
product quality and shorter
manufacturing cycles.

Applications

An air handling unit (AHU) is exactly


what its name implies: a device that
handles - that is, moves and/or
conditions -air. It accomplishes this
based on the functions required by a
given application, as well as the
arrangement of components
necessary for those functions.
An outdoor central-station air
handler, such as the T-Series Climate
Changer air handler, has the added
requirement of operating in an
outdoor environment, while still
meeting all other system needs.

The T-Series Climate Changer air


handler can accommodate an
extraordinary degree of design
versatility, but in order to apply that
versatility to each unique situation, a
designer must:
Apply the T-Series Climate Changer
air handler in a manner consistent
with good HVAC design practices.
Understand ASHRAE Standard
62-1989, Ventilation for Acceptable
Indoor Air Quality, as it applies to air
handler function and layout.
Know how specific T-Series Climate
Changer air handler applications can
address design requirements, with
arrangements optimized for job
requirements, thermal performance
and acoustical performance.

With these objectives in mind, the


applications section is divided into
three topics that present application
considerations for effective T-Series
Climate Changer air handler design: air
handler functions and tasks,
arrangements and component
features.
Consult your local Trane sales engineer
for additional application assistance.

Air Handler Functions


To properly lay out an air handling unit,
the designer must focus on its
function(s) in the context of the
application. Those functions are
heavily influenced by outdoor air (OA)
requirements which, in turn, depend on
the condition of the outdoor air (i.e.,
sensible temperature, relative humidity
and cleanliness).
The steps below summarize the
procedure for establishing a particular
applications OA requirements:
1
Calculate the total system supply
airflow using accepted HVAC design
practices. Base this calculation on
space load and the temperature
difference between space and supply
air.

2
Determine the total amount of
ventilation air needed: this is the OA
required to comply with the ventilation
requirements of ASHRAE Standard
62-89 or to make up for air leaving
the building via fixed exhausts (e.g.,
lavatory fans, lab hoods, exfiltration
and any air used for indoor combustion
processes), whichever is larger. In most
cases, ventilation air volume should
equal exhaust air volume to maintain
proper building pressurization and air
volume.
3
Finally, having established the amount
of outdoor air and total supply air
required, quantify the return air volume
and percentage of outdoor air.

10

Note: If you are configuring a variable


air volume system (VAV), refer to Trane
publication CLCH-S-26 for information
on optimizing system operation.
Contact your Trane sales engineer for
more information. Together, these
airflow requirements dictate the type of
air handler(s) needed and the tasks that
must be performed.

Applications

Basic Air-Handling Tasks


Mix and Recirculate Air to the
Occupied Space
Generically termed standard air
handling units (Figure A-1), these air
handlers collect air from the occupied
space, mix it with outdoor air, treat it
and discharge it into the supply
airstream.

Bring In Outdoor Air and


Treat It

An air handler dedicated to treating


outdoor air is referred to as an outdoor
air unit, but may also be called a
makeup air unit in instances where
outdoor air is brought in to replace air
exhausted locally from lavatories,
kitchens, etc. See Figure A-2. Outdoor
air units either discharge air directly
into the occupied space or serve as a
pre-conditioner for other air handling
units downstream. For example, a
pre-conditioning outdoor air unit
might pretreat outdoor air before it
reaches other standard air handlers,
effectively removing the outdoor air
load from the standard air handlers.

Maintain Proper Building


Pressurization

An important aspect of meeting


outdoor air requirements is equalizing
outdoor air and exhaust air volumes to
maintain proper building
pressurization. Building pressurization
is an air-handling strategy that
regulates pressure differences across
the building envelope and between
zones or rooms by adjusting the
amount of air supplied and removed.
The goal of this strategy is to:

Assure proper distribution of

conditioned and ventilation air


throughout the occupied space.
Avoid discomfort due to temperature
stratification and drafts.
Prevent infiltration of unconditioned
air.
Confine odors and contaminants to
specific areas within the building.

Figure A-1 - Standard Air Handling Unit

Applications with clean outdoor air and


low to medium humidity levels may be
effectively served by a standard air
handling unit.

Expel Air from the Building

An exhaust unit is an air handler that


does nothing more than collect air from
the occupied space and discharge it
outside the building. Remember: to
balance building pressure, any outdoor
airflow entering the building must
approximate the exhaust airflow
leaving the building.

Figure A-2 - Make-Up Air Unit

11

Building envelope pressurization is


typically achieved by incorporating
either an exhaust fan and mixing box or
a return fan and economizer in the air
handlers design. A brief summary of
their respective operating
characteristics and application
considerations follows. Careful analysis
is required to determine which
approach best suits each applications
unique requirements. To better
understand the differences between
exhaust-fan and return-fan systems,
consult your local Trane sales engineer
or refer to Building Pressurization
Control (Trane publication AM-CON-17).

Applications

Exhaust Fan Economizer


Figure A-3 depicts a typical T-Series
Climate Changer air handler with an
exhaust fan and mixing box. To
balance the amount of air exhausted
from the building with the amount of
air brought in, the exhaust fan
modulates, running at full capacity only
when the economizer brings in 100
percent outdoor air. When the mixing
box is at minimum and the exhaust fan
is idle, dampers on the mixing box
close to prevent outdoor air from being
drawn into the air handler through the
exhaust section. The
exhaust-fan-and-mixing box
combination provides strict space
pressurization control, as long as the
supply fan is sized to handle total
system static pressure. First cost and
operating cost are usually lower than
the return-fan-and-economizer
alternative (exhaust fans require less
capacity than return fans and run
less often).
Application Considerations:
Size the supply fan to handle the static
pressure requirements of the higher of
the following:
1
100 percent outside air operation (i.e.,
OA ductwork, OA damper, filters, coils
and other accessories in the outdoor
airstream, plus supply duct static
pressure drop) or
2
100 percent return air operation (i.e.,
RA ductwork, RA damper, filters, coils
and other accessories in the
recirculated airstream, plus supply duct
static pressure drop).
Size the exhaust fan to handle
100 percent of the return air (i.e., return
duct, exhaust duct and shutoff damper)
when the unit is in full economizer
mode.
Control exhaust airflow to maintain the
outdoor/indoor static pressure
differential within design limits.
Control the outdoor air and return air
dampers to act in a complementary
fashion (prevent simultaneous closing);
otherwise, serious equipment damage
could result.

Return Fan Economizer


Figure A-4 depicts a typical T-Series
Climate Changer air handler with a
return fan and economizer. The return
fan typically runs continuously to
balance the amount of air supplied to
and removed from the occupied space.
While this approach makes precise
space pressurization control more
difficult, it is better suited to
applications with high return static
pressures than the exhaust fan
alternative; if the supply fan is unable
to handle the total system static
pressure, the return fan is sized to
overcome the return ducts external
static pressure. Of course, the return
fans larger size and constant operation
also mean higher first and operating
costs.

Figure A-3 - Exhaust Fan Economizer System

Figure A-4 - Return Fan Economizer System

12

Application Considerations:

Size the supply fan to handle the static

pressure requirements of 100 percent


outside air operation (i.e., OA ductwork,
OA damper, filters, coils and other
accessories in the outdoor airstream,
plus supply-duct static pressure).
Size the return fan to handle the static
pressure requirements of 100 percent
exhaust air operation (i.e., return duct,
exhaust duct and exhaust damper).
Control the return fan to maintain the
outdoor/indoor static pressure
differential within design limits.
Control the outdoor air and return air
dampers to act in a complementary
fashion (prevent simultaneous closing);
otherwise, serious equipment damage
could result.

Applications

Barometric Relief Economizer


Figure A-5 depicts a typical T-Series
Climate Changer air handler with a
barometric relief economizer.
Barometric relief offers some positive
space pressure control. The equipment
consists of an economizer section with
a damper in the return air path that
opens upon an increase in pressure
difference between the space and the
outside.
The supply fan must over-pressurize
the space to allow for proper operation
of the barometric damper. It should
only be used in systems that have
extremely low return air static
requirements. In other systems, it is
recommended that a powered system
such as return fan or exhaust fan
economizer be used instead of
barometric relief.
Application Considerations:

Size the supply fan to handle

100 percent outside air operation (i.e.


OA hood, OA dampers, filters, coil(s)
and other accessories, plus supply air
ductwork).
Set up system for maximum delivery at
100 OA economizer mode. Turn on all
remote exhaust fans. Measure the
space static pressure, and adjust
barometric relief damper to produce a
slight positive space pressure.
Only when the unit is at or near
100 percent OA (return air damper is
closed) will the exhaust section become
sufficiently pressurized to open the
barometric damper.

Providing Adequate
Ventilation Airflow

ASHRAE Standard 62-1989 specifies a


per-person outdoor air requirement of
15 to 20 cfm in commercial office
spaces. (Other types of occupied spaces
such as operating rooms require even
higher ventilation rates.) It also
mandates provision for measuring the
amount of outdoor air brought into the
building as proof of compliance.
Consequently, its important to include
a means of monitoring airflow in your
T-Series Climate Changer air handler
designs.
Direct measurement of airflow
i.e., either a factory-mounted Traq
damper assembly or a duct mounted
hot-wire-anemometer or pitot-tube
monitoring station provides greater
accuracy and reliability than indirect
monitoring methods such as
mixed-temperature or tracer-gas
calculations, fan-inlet monitors,
fixed-position dampers or
fixed-differential pressure plates.
See AHU Components: Mixing Box
Section later in this section for a brief
summary of the Traq dampers
operating characteristics and
application considerations.

Meeting ASHRAE
Requirements

ASHRAE Standard 62-89 sets minimum


ventilation rates and defines acceptable
indoor air quality (IAQ) to avoid
adverse health effects. It also presents
general system and equipment
requirements for outdoor airflow, air
distribution, design documentation and
microbial growth control. In short,
Standard 62 dramatically impacts the
design, layout and arrangement of the
air handler and its components.

Figure A-5 - Barometric Relief Unit

13

Protecting Hydronic Coils


from Freezing

Bringing more outdoor air into the air


handler to satisfy Standard 62s
ventilation requirement increases the
likelihood of air stratification. If a layer
of air below freezing moves through
the air handler, it can damage
unprotected hydronic cooling and
heating coils. Traditionally, a low-limit
thermostat (or freeze-stat) installed
on the entering-air side of the cooling
coil trips when it detects a dangerously
low air temperature. That stops the
supply fan, closes the outdoor air
damper and ultimately degrades the
buildings indoor air quality.
Its important to design the air handler
so that it effectively treats the required
amount of outdoor air regardless of
temperature without risking coil
damage, tripping the low-limit
thermostat or compromising indoor air
quality. Following are several means of
providing coil protection. Choose the
technique that best suits the
applications requirements.
Drain the coils. This approach requires
fully drainable coils, vent and drain
connections on every coil, plus shutoff
valves to isolate them from the
chiller(s).
Add glycol to the cooling system water
to lower its freezing point.
Preheat the outdoor airstream with a
steam coil, hot-water coil or
energy-recovery device to raise its
temperature above freezing and
eliminate any entrained snow before it
reaches the cooling coil.
Introduce ventilation air downstream of
the cooling coil with dual-path or
bypass techniques.
Use an air blender to improve mixing
of the outdoor and recirculated
airstreams.

Applications

Control Particulate and


Gaseous Contaminants

ASHRAE Standard 62-1989 emphasizes


the importance of including appropriate
filters in the air handling system to
control particulate (e.g., dust, fibers)
and gaseous (e.g., oxidants,
formaldehyde) contaminants.
Controlling Particulates
To provide good indoor air quality, both
the Environmental Protection Agency
(EPA) and ASHRAE recommend that
the concentration of particulate matter
in the air not exceed 0.05 to 0.07 mg/m3.
While Standard 62 doesnt set specific
particulate filtration guidelines, other
design manuals recommend filtration
levels of 90 percent arrestance and 40
to 60 percent dust spot efficiency for
new air handlers. Filters with dust spot
efficiencies greater than 50 percent
remove most microorganisms from the
passing airstream. National, state or
local codes established by government
bodies or occupational groups may
dictate more specific or stringent
filtration requirements for a building,
depending on its type and/or location.
Trane offers several types of particulate
filters including pleated, bag and
cartridge that allow you to match
filtration efficiency with the application
needs. See AHU Components: Filter
Section for selection and application
considerations.

Controlling Gases and Vapors


The presence of undesirable gases and
vapors (particularly formaldehyde,
radon, oxidants and volatile organic
compounds [VOCs]) can be harmful to
a buildings occupants, materials and
contents. Controlling VOC
concentrations is particularly
challenging: hundreds of them are
present, few are unique to any one
source, and there are many potential
sources, some of which emit several
VOCs.
Therefore, a common way to control
gaseous contaminants is to dilute them
with outdoor air. This approach is
especially appealing since many VOCs
defy individual treatment. However, it is
only practical if the quality of the
outdoor air is suitable and if the
resulting supply airflow is consistent,
appropriate and mixes effectively with
the air in the occupied space.
Proper Filter Placement
For effective particulate and gas phase
filtration:
Do not place filters downstream of a
blow-thru cooling coil; otherwise moist
air (fog) from the cooling coil may
develop and saturate the filter.
Provide easy access to encourage
regular filter maintenance.
Locate filters away from potentially
damaging high air velocities. A diffuser
is required downstream of a fan in final
filter configurations.

14

Discouraging Microbial
Growth

While filtration effectively removes a


number of common particulate and
gaseous contaminants from the
building environment, microbiological
or microbial contaminants like molds,
fungi and bacteria are sometimes too
small to be filtered entirely from the
airstream. Designing the air handler to
include screens on intake and exhaust
openings, an interior steel liner and
easy access to heat exchanging
components for cleaning purposes
helps control microbial growth.
Antimicrobial coatings and regular
cleaning and disinfecting with
nonpolluting cleansers are also
beneficial. However, none of these
measures totally eliminates the growth
of ever-present microorganisms.
Consequently, water management
becomes another important means of
combatting microbial contaminants.

Applications

Water Management

Cooling coils collect water from the


passing airstream as they cool and
dehumidify it. This condensed
moisture should be removed to reduce
the likelihood of microbial growth.
Follow these guidelines when
designing the air handler:
Reduce moisture carryover by sizing
the cooling coils for proper airflow
velocities at the given conditions and
coil fin selection.
Specify drain pans sloped in two
directions to eliminate moisture
collecting level seams and promote
positive drainage. All T-Series
drainpans are double sloped.
Properly size condensate traps as
shown in Figure A-6.
Promote cleanability i.e., provide
adequate space around the unit, easily
removable access panels, and solid
interior steel lining to isolate insulation
from the airstream and facilitate
cleaning.
Specify antimicrobial coatings for filter
and drain pan surfaces where moisture
is likely to collect. (Though cooling coil
surfaces collect water, too, treatment
with an antimicrobial coating is
discouraged; such coatings greatly
reduce the coils wetting characteristics
and may cause moisture carryover at
velocities as low as 200 fpm.)

Humidification

Low relative humidities (below 30


percent) in the occupied space are
undesirable because they necessitate
higher supply air temperatures for
thermal comfort, promote static
electricity and may favor the
transmission of airborne infections
such as influenza. Raising the space
humidity to an appropriate level
requires a humidifier to inject water
particles into the passing airstream.
To avoid promoting microbial growth,
the units design must assure that the
injected water is fully absorbed within
the air handler without collecting on its
walls or components.
Three types of commercial humidifiers
are generally used in central air
handling systems: wetted media,
atomized water and steam. Of these,
ASHRAE Standard 62-1989 prefers
steam as the moisture source for
humidifiers. Its low temperature and
pressure make it easy to introduce
directly into the passing airstream, and
encourage complete absorption in a
short distance.

Figure A-6
Positive Pressure Trapping

15

Negative Pressure Trapping

Applications

AHU Arrangements
Draw-Thru or Blow-Thru

Here are common air handler


arrangements, along with general
application considerations for each.

Horizontal Draw-Thru

(Figure A-7) Traditional arrangement


for air handlers.
Accepted system design practices are
generally the only restrictions on its
application. Note: When using a Model
Q fan or plug fan section, provide a
medium blank section between the
coil/filter and the fan for proper air
distribution.

Single-Zone Blow-Thru

(Figure A-8) This arrangement places a


coil section downstream of a fan
section.
To promote proper air distribution
through each section and reduce the
risk of moisture carryover:
For units with FC, BI, AF or plug-type
fan sections: Add a medium blank
section or diffuser between the fan and
coil, or a diffuser between the fan and
final filter.
For units with FC, BI or AF-type fan
sections: Add a blank section with a
drain pan (i.e., medium for unit sizes 03
to 10; medium-large for sizes 12 to 14;
large for sizes 17 to 100) or a moisture
eliminator immediately downstream of
the cooling-coil section.
Blow-thru configurations with Q-fans
require factory approval.

Figure A-7 - Single Zone Draw-Thru Unit

Optimizing an Arrangement
for Acoustical Performance

Designers are often challenged to


select and arrange the air handler
components so that the inlet, discharge
and casing-radiated fan generated
sound power levels help create a quiet
space. To accomplish this, the designer
must choose the right fan and
determine whether additional unit
attenuation is necessary.
Choosing the Right Fan
Obviously, the quieter the noise source
(in this case, the fan), the less
attenuation is needed along sound
transmission paths. Selecting a quieter
fan often increases the initial cost of the
air handler, but can be a cost-effective
system solution because it:
Reduces the need for path attenuation
(e.g., silencers) by diminishing the
sound level along all transmission
paths
Reduces energy consumption (i.e., a
fan is normally quietest when running
at the most efficient point on its
operating curve), providing operating
cost savings to offset the initial cost.
Trane acoustical tests have shown that
a fans sound power (Lw) level depends
on three factors: its type/design, its
operating point on the fan curve and its
application requirements (e.g., critical
octave band frequency). Table A-1 and
Table A-2 compare the inlet and outlet
sound power levels of four different
fans. Together, these charts
demonstrate that fan inlet sound is not
equivalent to fan outlet sound. More
importantly, they underscore the need
to obtain accurate, ARI 260 tested
sound data from the manufacturer so
that appropriate source and/or path
attenuation methods can be applied.

Figure A-8 - Single Zone Blow-Thru Unit

The T-Series Climate Changer air


handler gives designers a choice of
many different fan types. AHU
Components: Fan Section later in this
section summarizes each fans
application considerations and
acoustical characteristics.

16

Applications

110

100
27-in. FC Centrifugal Fan w/Housing (699 rpm)

39-in. AF Centrifugal Plug Fan w/o Housing


(980 rpm)
27-in. AF Centrifugal Fan w/
Housing (1340 rpm)

80

36-in. Q AF Vaneaxial Fan


(1441 rpm)

70

100

Sound Power, Lw dB

Sound Power, Lw dB

90

39-in. AF Centrifugal Plug Fan w/o Housing (980 rpm)


27-in. FC Centrifugal Fan w/Housing (699 rpm)
36-in. Q AF Vaneaxial Fan (1441 rpm)
27-in. AF Centrifugal Fan w/Housing (1340 rpm)

90

80

70

60

60

50
63

125

250

500

1k

2k

4k

8k

63

125

Frequency, Hz

T-Series Climate Changer air handlers


adopt a building-block approach to
air handler design. Each building
block or section contains one or more
components that serve a specific
purpose unique to each application.
The air-handling functions needed,
along with the desired layout and
arrangement, ultimately determine
what sections the air handler must
include.

Moisture Eliminator

Used to remove entrained water from


the passing airstream, this section is
typically used immediately
downstream of a cooling coil section in
blow-thru arrangements (not required
with plug-type fan sections) to prevent
moisture carryover. It may also be used
in draw-thru arrangements if the coil
carryover velocity is exceeded.

Mixing Box

The mixing box section typically


combines the incoming outdoor air
with recirculated return air collected
from the occupied space, and is
commonly included in an air handlers
design to improve the mixture of
outdoor and recirculated return airflow.
When equipped with a Traq damper
assembly, the mixing box section
permits direct measurement of outdoor
airflow to verify compliance with
ASHRAE Standard 62-1989.

500

1k

2k

4k

8k

Frequency, Hz

Table A-1 Comparison of Discharge Sound Power by Fan Type

AHU Components

250

Table A-2 Comparison of Inlet + Casing Sound


Power by Fan Type

Traq Damper Option

Designed to measure and modulate


outdoor airflow, the Traq damper
assembly consists of one to six
butterfly-type dampers. Each dampers
bell-mouth inlet guides air uniformly
through a flow-sensing ring that
accurately measures total and static
pressure from 15 to 100 percent of
nominal flow. The damper assemblys
ventilation control section (VCM)
produces a 2 to 10 VDC signal
proportional to airflow, recalibrates
itself once every 60 seconds and
automatically adjusts for temperature
variations.
Application Considerations:

Connecting a Traq damper equipped air


handler to a building automation
system such as a Tracer building
management system permits: (a)
dynamic calculation of the outdoor air
needed to adequately ventilate a multispace VAV system and reset the
outdoor air set point accordingly to
save energy; (see Trane publication
CLCH-S-26) and (b) trend logs and
custom reports to document
compliance with ASHRAE Standard 62.

17

Runaround Loop

(Figure A-9) A runaround loop consists


of two finned-tube coils (air to-water
heat exchangers) piped together; one
coil resides in the outdoor airstream
and the other in the exhaust airstream.
An expansion tank, pump, three-way
temperature control valve and working
fluid (usually an inhibited solution of
ethylene glycol and water) complete
the recovery system.
Since the outdoor and exhaust
airstreams need not be adjacent, the
runaround loop provides design
versatility well-suited to building
renovations at a lower first cost than
other methods of energy recovery.
Complete separation of the airstreams
also eliminates the risk of
cross-contamination.
Application Considerations:

Recovery is limited to sensible energy


with an effectiveness that typically
ranges from 60 to 65 percent.
Together, the two finned-tube coils
may contribute approximately 0.3 to
0.6 in. wg to system static pressure.

Applications

Application Considerations:

Economizer Section

Gas-phase filters must be designed

This section provides a path for return


air to be exhausted, allowing the
system to provide natural, nonmechanical cooling when outdoor air
conditions are suitable. See
Figure A-9.

Air Blender Section

The air blender section contains air


mixing baffles or blenders that rotate
the passing airstreams, boosting their
velocities for improved mixing. It is
usually placed immediately
downstream of a mixing box section,
and should always be positioned
upstream of filters and coils.
Application Considerations:
Blender face velocity should be in the
range of 500 to 2000 fpm for proper
mixing.
When operated at temperatures within
its design range, an air blender may
eliminate the need for preheat.
Space is required both upstream and
downstream of the blender to allow
complete air mixing. (The standard
design of the air blender section
satisfies these spatial requirements.)

Filter Section

This section removes contaminants


from the passing airstream to improve
indoor air quality. See AHU Functions:
Comply with ASHRAE Standard
62-1989 earlier in this section.

Particulate Filters

Options include high-performance


pleated, bag or cartridge filters. All of
these filters have a continuous
operating range of 0 to 150 F. Factors to
consider when determining the proper
degree of filtration are:
Required cleanliness. Higher filter
efficiencies cost more, but provide
cleaner air and better system
performance. Many design manuals
recommend filtration levels of
90 percent arrestance and 40 to 60
percent efficiency for new air handlers.
National, state and local codes may
also specify filter performance.
Operating resistance to airflow (i.e.,
pressure drop). Filter resistance and
first cost may increase with efficiency.
Available space. High filtration
efficiencies require more space (lower
velocity) and may enlarge the air
handlers footprint.
Maintenance. A high degree of filtration
can lower cleaning costs in the
occupied space.

Air blenders for coil protection are


available in sizes 3-100 of the T-Series
Climate Changer

Application Considerations:

Exceeding the filters face velocity limit

will increase its resistance (as well as


fan energy consumption) and
necessitate more frequent
maintenance or replacement.
Exercise special care to avoid moisture
carryover whenever final filters are
used. Never place the filter section
downstream of a cooling coil without
providing an intervening source of
reheat (e.g., fan motor).
Treating filter media with an
antimicrobial coating can reduce the
likelihood of microbial contamination.

(tuned) for the specific contaminants


to be removed.
Gas-phase filters are expensive i.e.,
first cost is high, and the additional fan
energy required to overcome the extra
pressure drop increases the air
handlers operating cost.
Effective filtration requires low velocity
airflow, increasing the air handlers
length/footprint.
Humidity impairs filtration efficiency. As
with particulate filters, never place a
gas-phase filter section downstream of
a cooling coil without providing an
intervening source of reheat (e.g., fan
motor).

Access/Blank Section

Incorporate access or blank sections in


the air handler design to provide
access to internal components for
cleaning, maintenance and service, or
to promote proper airflow through the
unit.

Coil Section

Coil sections temper all (full-face) or


part (modified-size) of the passing
airstream by heating, cooling or
dehumidifying it with a factory
mounted coil. To select the right coil for
an applications unique requirements,
optimize its capacity, face velocity,
pressure drop and construction.

Gas-Phase Filters

Equipping the filter section with a


carbon or potassium-permanganate
filter bed will reliably remove a variety
of odors and gases (excluding carbon
monoxide and carbon dioxide) from
the airstream.

Available coils fall into two categories:


/2-inch unit coils are designed
exclusively for use in T-Series Climate
Changer air handlers. They have
1
/2-inch OD tubes; designers can choose
either 0.016 and 0.025-inch tube walls,
and specify 2 to 8 rows.

Figure A-9 - Unit with Economizer and Coil Run-Around Loop

18

Applications

Although they offer fewer options than


5
/8-inch shipping coils, 1/2-inch unit
coils have a lower first cost and larger
face area; they also require less
distance (section length) reducing the
air handlers footprint.
in
5/8-inch shipping coils can be applied
either T-Series Climate Changer air
handlers or built-up air handling
systems. Typified by 5/8-inch OD tubes,
these coils can be configure with 1 to
12 rows, and 0.020, 0.024, 0.035 or
0.049-inch tube walls.
Other coil options available include
copper fins, stainless steel casings and
1-inch OD steam coils. Compared to
unit coils, shipping coils offer greater
design versatility; however, they have a
higher first cost, a smaller face area and
require a longer section to promote
proper air distribution.
Application considerations for chilled
water and direct expansion (DX) coils:
Size the coil to prevent moisture
carryover due to high airflow velocities.
Velocities up to 600 fpm a re acceptable
depending on air conditions and coil fin
arrangement.
Properly size the condensate trap to
provide positive drainage; see
Figure A-9.
Specify two-way-sloped drain pans to
eliminate level seams and promote
condensate flow directly to the drain
outlet. Consider stainless steel
construction to prolong drain pan life.
Provide adequate freeze protection for
chilled water coils; see AHU
Functions: Comply with ASHRAE
Standard 62-1989 earlier in this
section.
Application considerations for hot
water coils:
Heating with hot water presents an
attractive alternative for buildings
without a ready source of steam
Providing effective freeze protection is
more difficult for hot-water preheat
coils than it is for steam. To minimize
the risk of coil freeze-up, use
face-and-bypass dampers and operate
the coil at full capacity.

Application considerations for steam


coils:
Properly pipe and trap the coil to
provide positive drainage.
Steam coils are less susceptible to
freeze-up than hot water coils. Trane
steam distribution coils use steam
pressure to blow condensate from the
coil. For additional freeze protection,
use face-and-bypass dampers and
operate the coil at full capacity.

Face-and-Bypass Damper
Section

Designed to divert airflow around a


coil, the face-and-bypass section can be
used to control humidity or provide
freeze protection for hydronic coils.
Choose from the following damper
section configurations:
Internal Face-and-Bypass Dampers
Typically used immediately upstream
of a modified-size (i.e., less than
100 percent airflow) coil, this option
enables temperature control while
operating the preheat coil at full flow.
The dampers modulate to bypass air
around the heating coil when the
outdoor air temperature is warm
enough to preclude freezing.

Application considerations:

To ensure full airflow coverage across

downstream coil banks, provide extra


distance after the modified-size coil
section.
The bypass in an internal face-andbypass damper section is not designed
for 100 percent nominal airflow. For
applications that require 100 percent
bypass, contact your local Trane sales
engineer.
Integral Face-and-Bypass Damper
and Coil
This custom option, offered in
horizontal and vertical coil tube
arrangements, encloses the coil fins
between dual dampers. If heat is
needed, these dampers open;
otherwise, they remain closed to
prevent coil wiping on the leaving
side of the coil and avoid unwanted
heat pickup.
Application Considerations:

Vertical coil tube arrangements

promote condensate removal and


afford better freeze protection.
Extra distance is required downstream
of this section to promote proper air
distribution and reduce stratification.

Fan Section

Designers can choose from five fan


types to tailor the air handlers
performance to application
requirements; Table A-3 summarizes
and compares the characteristics and
application considerations of these fans.
When evaluating the merits of each fan
type, consider the applications
volumetric rate of airflow, static
pressure, required sound characteristics
and available space, as well as the
nature of the load and how the occupied
space is used.

Face-and-Bypass damper in the T-Series


Climate Changer air handler

19

To verify that a specific fans


performance will satisfy design
requirements, see catalog supplements
CLCH-CS-7A and CLCH-CS-7C. The fan
curves published there include casing
effect. These supplements also discuss
how ductwork connections, air density,
fan/motor heat, drive losses and use of
high-performance (> 65 percent
efficient) filters affect fan performance.

Applications

accomplished in one of two ways: with


a variable-frequency drive (VFD) that
adjusts fan speed and airflow by
varying motor speed or with fan
mounted inlet guide vanes (IGV) that
limit the amount of air entering the fan.
Of these methods, VFD modulation is
the quietest and most energy efficient;
it can also prolong the life of the fan
motor by soft starting it. FC fan IGV
modulation provides reliable operation
at a lower first cost. Avoid using IGVs
on other fan types.

Fan Control Method

Depending on the control method


used, the air handler fan will provide
either a constant or variable volume of
supply air. In a constant volume (CV)
system, the fan delivers a consistent
amount of air; cooling and/or heating
devices adjust the temperature of that
air for occupant comfort. Since the fan
runs at constant horsepower under all
load conditions, system operating costs
are higher than those of a variable air
volume system.
A variable air volume (VAV) system
provides occupant comfort by
delivering a fluctuating amount of
constant temperature air; usually,
supply duct static pressure determines
how much air the fan provides. Varying
fan horsepower with building load can
offer substantial energy savings and
reduce the buildings airflow
requirements. Airflow modulation is

Application Consideration:

Regardless of the fan control method

Table A-3 Fan Summary Chart

(CV or VAV) used, it is important to


provide a means of monitoring
outdoor airflow. Over time, filter
loading and other system effects can
change static pressures and eventually
reduce airflow including ventilation
airflow below the design volume
flow rate.

Diffuser Section

Designed to provide even airflow, the


diffuser section is typically used
immediately upstream of a final-filter or
coil section.

Plenum Section

Before leaving the air handler, supply


air is sometimes discharged into a
plenum section; the airstreams rapid
expansion as it passes into the plenum
reduces turbulence and creates an end
reflection that dampens low-frequency
sound. Two configurations enable
supply-duct connections from any side;
unless otherwise noted, all are
available with two-inch, insulated
casing walls of solid construction.

FC Fan
Centrifugal, housed
Double
Radial

BI Fan
Centrifugal, housed
Double
Radial

AF Fan
Centrifugal, housed
Double
Radial

Model Q Fan
Vaneaxial
Single
Axial

Low to Medium
(0-5 in. wg)
Low
Medium
400-1,200
Curved
Significant air
turbulence that
quickly abates; little
blade-tone noise.

High
(4-8 in. wg)
Medium
Medium-high
1,000-2,600
Flat
Significant air
turbulence; strong
blade tones in 250-Hz
octave band.

High
(4-8 in. wg)
Medium
Medium-high
1,000-2,600
Airfoil
Significant air
turbulence; strong
blade tones in 250-Hz
octave band.

Medium
(2-5 in. wg)
High
Low
1,400-2,900
Airfoil
Little turbulence;
quiet at hard-to
-attenuate low
frequencies.

Suggested source
attenuation

Add a discharge
plenum.

Avoid using
inlet vanes.

Avoid using
inlet vanes.

Space required directly


upstream of fan in
draw-thru arrangements
Space required directly
downstream of fan in
blow-thru arrangements
When to use?

None

None

None

Avoid using
inlet vanes.
Add a discharge
plenum
Medium blank

Medium blank
or diffuser section.
Low- to medium
-pressure applications.

Medium blank
or diffuser section.
High-pressure
applications.

Medium blank
or diffuser section
High-pressure
applications.

Fan Type
Inlet
Airflow direction
Optimal Pressure Range
First Cost (Relative)
Operating Cost (Relative)
Typical RPM range
Blade shape
Acoustical characteristics

Not available.
Quiet applications,
especially
6,000-50,000 cfm.

Notes.
1. Add duct takeoff losses from the plug/plenum fan section to external static pressure; see catalog supplement CLCH-CS-7A for details.
2. The plug fans uniform discharge velocity may eliminate the need for supply-air ductwork turns and diffusers.

20

Plug Fan
Unhoused
Single
Pressurized, all
direction
Medium
(2-5 in. wg)
High
Medium
600-1,200
Airfoil
High inlet noise,
but lower discharge
noise than FC, BI and
AF fans due to uniform
discharge velocity and
plenum effect.
Add a discharge plenum
or inlet duct silencer.
Medium blank

Medium blank
section.
Multiple-ductarrangement
applications. (1, 2)

Applications

Humidification Section

ASHRAE Standard 62-1989 suggests


maintaining a relative humidity of no
less than 30 percent to provide a
comfortable, healthy indoor
environment. The T-Series Climate
Changer air handlers humidification
section is a custom option that uses
dry steam to add moisture to the air.
Factory mounting within the air handler
lowers the humidifiers installed cost
and keeps moisture out of the supply
duct, while factory provided controls
provide accurate, reliable performance.

Additional T-Series Climate Changer


Air Handler Arrangements

Application Considerations:

Never position the humidification

section immediately downstream of a


housed fan or blow-thru coil section.
Extra dispersion distance may be
needed if the humidification section is
placed upstream of a final filter or
electric heat coil.
Vertical airflow turns immediately
upstream and downstream of the
humidification section necessitate a
large section.
Humidification for the T-Series Climate
Changer air handler is available as a
custom option by contacting the
factory

Inlet Hood Considerations

The Trane inlet hood accessory for the


T-Series Climate Changer air handler
line includes moisture eliminators.
Eliminator face velocities below 950
fpm will avoid pulling water through
the eliminator fins and into the unit. It is
possible for moisture to be carried over
into the unit when elimination face
velocities are above 950 fpm.

21

Applications

T-Series Outside Air Inlet Hood CFM


Limitations
Each T-Series unit has a rated nominal
cfm (a #3 for example is 1,500 cfm).
These nominal cfms allow for an
engineer to quickly base his unit size
requirements. Although this is the
nominal cfm of a given unit, each unit
is capable of producing more cfm, until
something limits the ability of the unit
to meet this higher cfm requirement
such as coil face velocity, filter face
velocity or the outside air inlet hood
eliminator velocity.
The eliminator in the inlet hood is rated
to a maximum of 950 feet per minute.
Above this limit, there is a high
probability of bringing rain water or
snow into the unit, which could migrate
to the conditioned space below. When
selecting units for your application,
remember not to undersize a unit to the
point that the inlet hood eliminators
can not handle the outside air cfm
requirements.
In Table A-4 are the maximum cfms for
the inlet hoods on the back and sides of
a mixing module and the side inlet
hoods on an economizer module.

Table A-4 Inlet Hood CFM Limitations


Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Back Inlet
Hood
2,337
3,876
4,341
8,949
9,614
10,193
13,870
14,288
17,755
20,786
25,251
28,756
31,825
41,116*
46,217*
57,152*

Mixing Module
1 Side
Inlet Hood
1,862
1,976
2,384
3,135
3,752
4,314
5,111
5,776
6,773
8,303
9,547
10,858
13,528
18,078
21,517
26,191

2 Side
Inlet Hoods
3,724
3,952
4,769
6,270
7,505
8,626
10,222
11,552
13,547
16,606
19,095
21,717
27,056
36,157
43,035
52,383

Economizer Module
Single
Dual
Inlet Hood
Inlet Hoods
1,862
3,724
1,976
3,952
2,384
4,769
3,135
6,270
3,752
7,505
4,314
8,626
5,111
10,222
5,776
11,552
6,773
13,547
8,303
16,606
9,547
19,095
10,858
21,717
13,528
27,056
18,078
36,157
21,517
43,035
26,191
52,383

*For units with Traq dampers located in the back inlet position of a mixing module, use the two-sided inlet hood limits for
a mixing module.

Example:
Assume you are selecting a #10 exhaust fan economizer unit at 5,000 cfm and .5
ESP consisting of:
Exhaust damper module
Fan module
Mixing module
Medium access module
Angle filter module
Heating coil module
Cooling coil module
Fan module
Specification requires that no more than 50 percent of the cfm will come from
outside air. In this example, the unit could be supplied with one-sided inlet hood,
as the maximum cfm through one-sided hood is 3,135.
If 100 percent outside air capability were specified, then the unit would need to be
supplied with two-sided inlet hoods.

22

Applications

Outside Air Inlet Hood Requirements


(Separation Distance)
Many specifications require that there
be a minimum distance between the
point that outside air enters an air
handler and the roof of a building. This
distance is to minimize the possible
introduction of contaminants into the
conditioned air.
ASHRAE 62-89 recommends that there
be at least 9 (or 8 above maximum
snow depth) separation from the roof
to the outside air intake, however,
some specifications, specifically for
units in the health care industry require
at least 36 of separation distance.
When you are configuring T-Series
units you need to be sure that the unit
in conjunction with a roofcurb will
meet the specifications requirements
on separation distance.

Mixing Module with Back Inlet Hood

Mixing Module with Side Inlet Hood

Below is a table that lists the distance


from the baseline of the unit to the
bottom of the outside air inlet hood for
mixing modules with either a back
hood or side hood, and for the side
inlet hoods for the economizer module.
Inlet Hood Separation Distance From
Baseline of Unit (Inches)
Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

A
6
81/2
121/4
93/4
133/4
153/4
14
181/2
19
19
221/2
221/2
341/2
407/8*
50*
57*

B
61/8
75/8
71/2
111/2
113/8
91/2
7
8
71/2
93/8
115/8
141/2
143/4
185/8
205/8
151/2

C
61/8
75/8
71/2
111/2
113/8
91/2
7
8
71/2
93/8
115/8
141/2
143/4
185/8
205/8
151/2

*For units with Traq dampers located in the back inlet


position of a mixing module, use the B side inlet hood
dimension for a mixing module.

23

Economizer Module with Side Inlet Hood(s)

Applications

T-Series Humidification Module Option


ASHRAE Standard 62-1989 suggests
maintaining a relative humidity of no
less than 30 percent to provide a
comfortable, healthy indoor
environment. With the T-Series
Climate Changer air handler, a factory
mounted steam humidifier is available
as a custom option. Factory mounting
within the air handler lowers the
humidifiers installed cost and keeps
moisture out of the supply duct.

Application Considerations:
Never position the humidifier
immediately downstream of a housed
fan or blow-thru coil module.
Additional dispersion distance may be
needed if the humidifier is placed
upstream of a final filter. To prevent
condensation formation, the relative
humidity leaving the humidifier should
not exceed 83 percent.

Table A-5 T-Series Humidification Module Requirements


Unit Size
Maximum Capacity (lbs./hr)
at 10 to 30 psig
Humidifier Module Size
Dispersion Space Module Size
Unit Size
Maximum Capacity (lbs./hr)
at 10 to 30 psig
Humidifier Module Size
Dispersion Space Module Size

Table A-5 lists the modules required to


both house the humidifier and
dispersion space and maximum
capacity of the humidifier at nominal
cfm, and 10 to 30 psig steam pressure.
A drain pan and an external piping
cabinet is required on the module
housing the humidifier and can be
added to the dispersion space module,
when specified. An optional access
door can be added when specified to
the dispersion space module.

3
50

6
85

8
95

10
125

12
200

14
215

17
320

21
410

Medium
Medium

Medium
Medium

Medium
Medium

Medium
Medium

Medium
Medium

Medium
Medium

Medium
Medium

Medium
Medium

25
510

30
600

35
740

40
775
850(1)

100
775
1620(1)

Medium
Medium

Medium
Medium

Medium
Medium

66
775
1575(2)
1620(3)
Small
Small

80
775
1620(1)

Medium
Medium

50
775
1090(2)
1575(3)
Small
Small

Small
Qty 2
Small(4)

Small
Qty 2
Small(4)

(1) 15 to 30 psig
(2) 15 psig
(3) 20 or 30 psig
(4) One small module upstream of humidifier and one small module downstream of humidifier module.

24

Applications

T-Series Humidifier Piping Locations


Sizes 3 to 66

Table A-6 Humidifier Dimensions


Sizes 3 to 66
Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66

M
15
15
15
15
15
15
15
15
15
15
16
16
14
14

G
9
9
9
9
9
9
9
9
9
9
9
9
7
7

F
3
6
93/8
77/8
67/8
77/8
67/8
61/8
63/8
63/8
9
9
11
197/8

C
15
18
21
21
271/8
271/8
33
39
45
45
507/8
507/8
567/8
68

Note:
1. All dimensions are in inches

* = 1/2 for Size 3

T-Series Humidifier Piping Locations


Sizes 80 and 100

Table A-7 Humidifier Dimensions


Sizes 80 to 100
Unit Size
80
100

L
43
43

Note:
All dimensions are in inches

25

C
14
14

L
31
31
31
31
31
31
31
31
31
31
32
32
29
29

Applications

Integral Face and Bypass Coil Option


T-Series units are available with an
optional integral face and bypass coil
or vertical integral face and bypass coil.
These coils are capable of maintaining
a constant heating discharge air
temperature regardless of variations in
entering air temperatures, with full
steam pressure of hot water flow on
the coils at all times. Integral face and
bypass coils consist of rectangular
aluminum fin (.010 thick) elements,
with 5/8 O.D. .035 thick copper tubes
completely enclosed in a 14-gauge
galvanized steel casing, with 16-gauge
dampers. Dampers are arranged to
completely enclose and isolate the
heating coil elements when no
temperature rise is required. Holes in
the unit casing for supply and return
connections are factory provided to

Tables A-8 and A-9 list the modules


required to house the integral face and
bypass coil, and the downstream
module required for proper air mixing
space. External piping cabinets are
required on both modules. An optional
access door can be added to the
downstream module on units with an
integral face and bypass coil. On units
with a vertical integral face and bypass

Table A-8 T-Series Module Requirements for Integral Face and Bypass Coils
Unit Size
Integral Face and Bypass
Module Size
Downstream Module Size

coil, an access door must be included


in the downstream module to facilitate
field piping of the supply and return
connections on the coil.

facilitate field piping of the coils.


Factory mounted electric, electronic or
pneumatic actuators are available
when specified. Integral face and
bypass are available for unit sizes 6
through 100. Vertical integral face and
bypass are available for unit sizes 21
through 100. Integral face and bypass
coils are not available on a size 3
T-Series unit.

It is recommended that a factory


selection of a coil be made based on
the scheduled performance, prior to
configuring a T-Series unit with an
integral face and bypass coil, so as to
determine whether the unit should be
configured around an integral face and
bypass or vertical integral face and
bypass coil.

10

12

14

17

21

Not Available
Not Available

Large
Medium

Large
Medium

Large
Small

Large
Small

Large
Small

Large
Small

Large
Small

25

30

35

40

50

66

80

100

Large
Small

Large
Small

Large
None Required

Large
None Required

Large
None Required

Med/Lrg
Small

Med/Lrg
Small

Med/Lrg
Small

12

14

17

21

Unit Size
Integral Face and Bypass
Module Size
Downstream Module Size

Table A-9 T-Series Module Requirements for Vertical Integral Face and Bypass Coils
Unit Size
Vertical Integral Face and Bypass
Module Size
Downstream Module Size

Unit Size
25
Vertical Integral Face and Bypass
Module Size
Large
Downstream Module Size
Medium

10

Not Available
Not Available

Large
Medium

30

35

40

50

66

80

100

Large
Medium

Med/Lrg
Medium

Med/Lrg
Medium

Med/Lrg
Medium

Med/Lrg
Medium

Med/Lrg
Medium

Med/Lrg
Medium

26

Applications

HEPA Filter Module Arrangement


HEPA filters are available in the T-Series unit as a custom option. Table A-10 lists
the minimum length modules to be included in a T-Series configuration for service
access and for housing the HEPA filters. If HEPA filters are in the downstream
position on a T-Series unit, a discharge plenum module needs to be included after
the blank module.

Table A-10 HEPA Filter Module Arrangement


Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Access
Module
Size(1)
Large
Large
Large
ML
ML
ML
ML
ML
ML
ML
ML
ML
Medium
Medium
Medium
Medium

Blank
Module
Size(2)
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Small
Small
Small
Small

Ft2 of
Filter
Area
4
6
7
10
14
14
16
16
24
28
34
40
54
65
80
102

Note:
1. Access door required for filter removal.
2. Minimum size module required to house HEPA filters.

27

24 x 24
1
1

6
6
6
8
12
10
20
8

12 Deep 99.97% HEPA Filters


Size () and Quantity
24 x 12
12 x 24
30 x 24
1
1

1
1
2
2
3

2
2
2
2

1
2
2
2

24 x 30

2
2

3
4
5
5

12

Selection
Procedure
Selection Procedure

1
Use specified maximum coil face
velocity (typically 500 fpm for cooling,
700 fpm for heating) along with unit
cfm and coil type to select unit size
from the Quick Select Chart on page 29.
2
Go to the Unit Data (pages 34-65),
select the modules required for the
system and obtain dimensions and
weights for the modules.
3
Select coils by using the Trane coil
selection programs.
4
Obtain damper and filter area and
pressure drop data from Unit Data
pages. Include coils, filters, dampers,
plenum, face and bypass, external
static pressure, etc. Sum the total static
pressure for all modules.
For design filter pressure drop, Trane
recommends finding a pressure drop
that is halfway between clean and dirty
conditions. This is done to limit cfm
fluctuation from design conditions as
filters load up. Filter pressure drop data
in Unit Data are shown at mid-life
values.
5
Use the design cfm and total static
pressure to choose a fan from the fan
curves in the catalog supplements,
CLCH-CS-7A, 7B and 7C.
6
Determine the fan brake horsepower
and rpm and motor horsepower.
(Account for belt and drive losses by
adding 2 to 6 percent to the brake
horsepower.)

Selection Example

Specified Conditions
Horizontal draw-thru configuration,
1/2 tube coils, double wall
construction
scfm = 7,000
external sp = 1.85 in wg.
max cooling face velocity = 550 fpm
Summer Design
coil entering air temperature
= 80 F DB/67 F WB
coil leaving air temperature
= 55 F DB/54 F WB
entering chilled water temperature
= 45 F
water temperature rise = 10 F
Winter Design
coil entering air temperature = 20 F
coil leaving air temperature = 85 F
entering water temperature = 200 F
water temperature drop = 20 F
Procedure
1
Using a 1/2 Unit Coil at 500 fpm to
enter the Quick Select Chart on page 29
returns the following:
Size 12 = 6150 cfm
and
Size 14 = 7100 cfm
Design cfm = 7000
Select Size 14.
2
Select modules and obtain dimension
and weights
Mixing Box:
L = 34 inches
H = 48.75 inches
W = 74 inches
Wt. = 443 lbs.
Cartridge Filter:
L = 24 1/2 inches
H = 48.75 inches
W = 74 inches
Wt. = 266 lbs.
Small Horizontal Coil:
L = 11 inches
H = 48.75 inches
W = 74 inches
Wt. = 255 lbs.
Medium Access:
L = 15 1/2 inches
H = 48.75 inches
W = 74 inches
Wt. = 105 lbs.
Medium Horizontal Coil:
L = 15 1/2
H = 48.75 inches
W = 74 inches
Wt. = 476 lbs.

28

Q-Fan:
L = 40 inches
H = 48.75 inches
W = 74 inches
Wt. = 751 lbs.
Note: Total unit length includes above
lengths plus six inches to account for
unit end panels (three inches each
end).
3
Select cooling coil.
6-row type UW coil with 114 fpf and no
turbulators.
APD = .64 Inches wg.
Select heating coil.
2-row type UW coil with 72 fpf and no
turbulators.
APD = .18 inches wg
4
Sum static pressures:
Inlet Hood:
.14
Mixing Box Dampers:
.05
85% Eff. 12 Cart. Filter:
1.00
Small Horizontal Coil:
.18
Medium Horizontal Coil:
.64
External Static Pressures:
1.85
TOTAL =
3.86
5
Refer to CLCH-CS-7C to find the
appropriate fan curve/rpm table. There
are two Q-fan options in this unit size,
the Q or R. Using the recommendations given in the applications section,
select the R fan (21.5 Q-fan).
6
Determine the fan brake horsepower
and rpm and motor horsepower.
bhp = 6.98 x 1.03 = 7.18
rpm = 2579

Quick
Select
All T-Series Climate Changer air
handler air handler coils are ARI 410
certified. The convention for the coil
connection side is as follows: Stand at
the leaving air side of the coil, with the
air blowing in your face. Typical face
velocities are 350 to 500 fpm for
cooling and 500 to 700 fpm for
heating.
1/2-inch Unit Coils
may be selected for chilled water, hot
water or direct expansion applications.
These coils maximize the available
face area in the section with these
options: .016 and .025-inch tube wall
thickness, stainless steel casing and
baked phenolic coating.
Type UW:
Chilled water or hot water
Single-row serpentine
General purpose
Type UU:
Chilled water or hot water
Dual-row serpentine
Low water pressure drop
High GPM
Available in sizes 12 to 100
Type UF:
Refrigerant
Standard, intertwined and horizontal
Split circuiting available
5/8-inch or 1-inch Shipping Coils
May be selected for chilled water, hot
water, refrigerant or steam
applications. These coils offer
industrial-type options such as:
Copper fins, .020, .024, .035 and .049inch tube wall thicknesses, stainless
steel coil casings and baked phenolic
coating. Available coil types include:
W, WA, WC, WD, D, DD, K, P2, P4, P8,
NS and F.
Full:
Standard face area for 5/8-inch and
1-inch coils.
Modified:
Smallest face area for 5/8-inch and
1-inch coils for use in internal face and
bypass dampers or low capacity
applications.

Table Q-1 1/2" Unit Coil Quick Select Chart


Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Coil Area
(sq. ft)
3.32
5.86
7.54
9.64
12.30
14.20
16.80
20.80
24.40
29.00
34.10
39.30
49.43
65.63
78.75
100.40

350
1162
2051
2639
3374
4305
4970
5880
7280
8540
10150
11935
13755
17301
22971
27563
35140

450
1494
2637
3393
4338
5535
6390
7560
9360
10980
13050
15345
17685
22244
29534
35438
45180

Coil Face Velocity (FPM)


CFM
500
550
1660
1826
2930
3223
3770
4147
4820
5302
6150
6765
7100
7810
8400
9240
10400
11440
12200
13420
14500
15950
17050
18755
19650
21615
24715
27187
32815
36097
39375
43313
50200
55220

600
1992
3516
4524
5784
7380
8520
10080
12480
14640
17400
20460
23580
29658
39378
47250
60240

650
2158
3809
4901
6266
7995
9230
10920
13520
15860
18850
22165
25545
32130
42660
51188
65260

700
2324
4102
5278
6748
8610
9940
11760
14560
17080
20300
23870
27510
34601
45941
55125
70280

600
1650
2628
3900
4998
6780
7260
8820
9900
11880
14160
18084
20826
28614
37800
45678
58164

650
1788
2847
4225
5415
7345
7865
9555
10725
12870
15340
19591
22562
30999
40950
49485
63011

700
1925
3066
4550
5831
7910
8470
10290
11550
13860
16520
21098
24297
33383
44100
53291
67858

600
1098
1752
2928
3750
5400
5802
7980
9060
10200
12180
12750
14700
21798
29928
36228
45828

650
1190
1898
3172
4063
5850
6286
8645
9815
11050
13195
13813
15925
23615
32422
39247
49647

700
1281
2044
3416
4375
6300
6769
9310
10570
11900
14210
14875
17150
25431
34916
42266
53466

Typical face velocities include: 350-500 fpm for cooling, 500-700 fpm for heating.

Table Q-2 Full Shipping Coil Quick Select Chart


Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Coil Area
(sq. ft)
2.75
4.38
6.50
8.33
11.30
12.10
14.70
16.50
19.80
23.60
30.14
34.71
47.69
63.00
76.13
96.94

350
963
1533
2275
2916
3955
4235
5145
5775
6930
8260
10549
12149
16692
22050
26646
33929

450
1238
1971
2925
3749
5085
5445
6615
7425
8910
10620
13563
15620
21461
28350
34259
43623

Coil Face Velocity (FPM)


CFM
500
550
1375
1513
2190
2409
3250
3575
4165
4582
5650
6215
6050
6655
7350
8085
8250
9075
9900
10890
11800
12980
15070
16577
17355
19091
23845
26230
31500
34650
38065
41872
48470
53317

Typical face velocities include: 350-500 fpm for cooling, 500-700 fpm for heating.

Table Q-3 Modified Shipping Coil Quick Select Chart


Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Coil Area
(sq. ft)
1.83
2.92
4.88
6.25
9.00
9.67
13.30
15.10
17.00
20.30
21.25
24.50
36.33
49.88
60.38
76.38

350
641
1022
1708
2188
3150
3385
4655
5285
5950
7105
7438
8575
12716
17458
21133
26733

29

450
824
1314
2196
2813
4050
4352
5985
6795
7650
9135
9563
11025
16349
22446
27171
34371

Coil Face Velocity (FPM)


CFM
500
550
915
1007
1460
1606
2440
2684
3125
3438
4500
4950
4835
5319
6650
7315
7550
8305
8500
9350
10150
11165
10625
11688
12250
13475
18165
19982
24940
27434
30190
33209
38190
42009

Quick
Select
All sections are available as a standard section for unit sizes 3 to 100 unless otherwise specified.
All sections pictured in elevation view unless otherwise specified.
Hoods are not available as a separate section. (Must be ordered as part of an inlet or exhaust section.)

Section
Size
Small
Medium
Med-Lrg
Large

Unit
3-100-I
3-100-J
10-100-K
3-100-L

Section
Size
Small
Medium
Med-Lrg
Large

Unit
3-100-M
3-100-N
10-100-O
3-50-P

30

Quick
Select
Table Q-4 Section Dimensions (inches) and Weights (pounds)
Trane Unit Size

A- Filter / Mixing
B- Economizer

Height
Width
Length (L)
Weight (lbs)

C- Exhaust
D- Air Blender
E- Flat Filter
F- Angled Filter
G- Bag Filter
H- Cartridge Filter
I- Sm Blank / Inspection
J- Med Blank Access
K- M-L Blank Access
L- Large Blank / Access
M- Small Coil
Weight includes 2 row UW
N- Medium Coil
Weight includes 8 row UW
O- M-L Coil
Weight includes 10 row W
P- Large Coil
Weight includes 10 row W
Q- Moisture Eliminator
R- Internal Face / Bypass
S- Face Damper
T- Front Horiz Disch Fan
Weight includes Type A Fan
U- Bottom Vert Disch Fan
Weight includes Type A fan
V- Diffuser
W- Discharge Plenum
X- Side Inlet Hood
add to Width
Y- Back Inlet Hood
add to Length
Z- Exhaust Hood
add to Width or Length
Unit end panels
add to Length

3
32.5
37
36*
225
49
314
15.5
88
40.25
191
11
71
24.75
154
36
189
24.75
143
11
47
15.5
62

24.75
105
11
117
15.5
182

24.75
323
11
59
15.5
98
15.5
98
60.75
560
60.75
560
15.5
74
24.75
92

6
35
50
27.25
232
49
377
15.5
105
42.75
242
11
84
27.25
199
41
248
27.25
181
11
56
15.5
75

27.25
137
11
151
15.5
250

27.25
439
11
80
15.5
129
15.5
129
68.25
750
68.25
750
15.5
91
27.25
118

8
38.75
54
31
270
49
419
15.5
115
46.5
279
11
91
31
232
44
281
31
213
11
61
15.5
80

31
164
11
170
15.5
294

31
568
11
93
15.5
144
15.5
144
75
845
75
845
15.5
98
31
135

10
41.75
66
34
367
60.5
582
15.5
134
49.5
355
11
109
24.5
242
34
285
24.5
218
11
71
15.5
95
24.5
161
34
218
11
210
15.5
363
24.5
649
34
720
11
147
15.5
185
15.5
185
58.5
845
69.5
916
15.5
114
34
195

12
45.75
70
34
393
60.5
637
15.5
145
49.5
380
11
122
24.5
261
38
323
24.5
235
11
76
15.5
101
24.5
171
34
232
11
238
15.5
431
24.5
788
34
864
11
167
15.5
200
15.5
200
62.5
968
73.5
1045
15.5
122
34
204

14
48.75
74
34
443
60.5
677
15.5
154
49.5
399
11
130
24.5
290
40
372
24.5
266
11
80
15.5
105
24.5
179
34
243
11
255
15.5
476
24.5
842
34
923
11
182
15.5
230
15.5
230
64.5
1034
75.5
1113
15.5
130
34
209

17
52.75
80
34
490
60.5
740
15.5
167
49.5
431
11
140
24.5
312
44
426
24.5
284
11
85
15.5
113
24.5
192
34
261
11
285
15.5
539
24.5
967
34
1054
11
202
15.5
252
15.5
252
68.5
1176
79.5
1261
15.5
143
34
224

21
57.25
82
34
526
60.5
827
15.5
187
49.5
477
11
157
24.5
338
48.5
511
24.5
317
11
95
15.5
125
24.5
212
34
289
11
323
15.5
641
24.5
1142
34
1234
11
231
15.5
281
15.5
281
73
1357
84
1451
15.5
163
34
252

25
63.5
84
40
624
60.5
902
15.5
201
55.5
562
11
164
24.5
355
54.75
579
24.5
334
11
100
15.5
132
24.5
221
40
361
11
353
15.5
722
24.5
1298
40
1465
11
254
15.5
306
15.5
306
54.75
1238
65.75
1338
15.5
173
40
318

30
35
40
50
63.5
72.75 72.75 85
97
102
115
126
40
48
48
48
687
933
1025 1148
72
72
84
84
1118 1291 1544 1785
15.5
16
16
19
219
265
283
399
55.5
39
34.5
43.5
614
822
888
1080
11
11.5
11.5
14.5
177
235
249
365
24.5
31
31
31
389
545
590
684
54.75 48
48
48
632
698
752
852
24.5
31
31
31
368
494
538
621
11
11.5
11.5
14.5
108
130
139
221
15.5
16
16
19
143
169
181
269
24.5
31
31
31
241
334
364
429
40
48
48
48
393
541
584
662
11
11.5
11.5
14.5
390
448
487
757
15.5
16
16
19
824
891
1017 1444
24.5
31
31
31
1483 1759 1982 2550
40
48
48
48
1664 1986 2222 2804
11
11.5
11.5
14.5
289
347
385
554
15.5
16
16
19
343
425
480
645
15.5
16
16
19
343
425
480
645
54.75 62
62
68.5
1502 2289 2447 2879
65.75 73.5
73.5
73.5
1610 2419 2586 3100
15.5
16
16
19
192
293
322
45
40
48
48
48
337
472
511
571

66
97
141
49
1367
96
2147
19
464
48
1257
14.5
432
29.5
797
49
1046
29.5
761
14.5
252
19
307
29.5
472
49
775
14.5
933
19
180
29.5
3372

14.5
710
19
753
19
753
84
3972
83
3972
49
913
49
651

80
100
112
124.5
141
156
54
60
1511 1817
96
96
2382 2984
19
19
506
572
48
58.5
1386 1640
14.5
14.5
477
546
29.5
29.5
839
964
54
60
1163 1414
29.5
29.5
798
911
14.5
14.5
262
288
19
19
319
350
29.5
29.5
491
538
54
60
870
1056
14.5
14.5
1040 1237
19
19
2143 2608
29.5
29.5
3884 4738

14.5
14.5
786
928
19
19
852
1002
19
19
852
1002
92
96
4822 5628
84
92
4822 5628
54
60
1029 1257
54
60
769
928

17.1
28
17.1
32

17.4
29
17.1
46

19.8
35
17.1
51

19.2
41
20.5
93

21.7
49
20.5
99

24.1
57
20.5
104

28.4
70
24
138

30.3
79
24
141

34.5
96
27.6
172

33.3
105
27.6
197

37.6
124
31.2
238

35.8
131
31.2
266

43.1
170
31.2
291

48.4
220
34.6
368

56.4
273
38.2
414

67.2
352
41.2
505

17.1
20

17.4
21

19.8
25

19.2
28

21.7
33

24.1
39

28.4
49

30.3
55

34.5
67

33.3
70

37.6
84

35.8
85

43.1
113

48.4
144

56.4
183

67.2
242

6
83

6
113

6
130

6
178

6
200

6
217

6
247

6
283

6
312

6
362

6
448

6
497

6
603

6
797

6
887

6
105

Notes:
Remember to add to the 6" unit end panels (3" on each end) shown above to got the correct unit length.
*#3 mixing boxes w/o filters are only 24.75" long.
Q fans are only available in front horizontal configuration. Add a discharge plenum for down discharge.
Starter/ disconnects are standard on all fan modules.
Dimensions and weights do not include roof curbs, piping cabinets, field installed equipment, etc.
Trane reserves the right to change / improve products and dimensions without notification.

31

Quick
Select
1. Size air handling unit. Use Tranes Customer Direct Service (C.D.S.) coil selection program to select coils based on capacity requirements and coil type
(1/2", 5/8", 1", or reduced area). Choose unit size based on cfm. This chart shows unit sizes, coil areas, and cfms at 500 fpm. For other face velocities,
Trane Unit Size = Coil Area (ft2) = CFM / max face velocity (fpm).
Trane Unit Size
3
6
8
10
12
14
1/2" Coil Area (UWUU,UF)(ft2)
3.32
5.86
7.54
9.64
12.30
14.20
CFM at 500 fpm
1,660
2,930
3,770
4,820
6,150
7,100
2
5/8" and 1" Coil Area (ft )
2.75
4.38
6.50
8.33
11.30
12.10
CFM at 500 fpm
1,375
2,190
3,250
4,165
5,650
6,050
5/8" and 1" Reduced Area Coil (ft2)
1.83
2.92
4.88
6.25
9.00
9.67
CFM at 500 fpm
915
1,460
2,440
3,125
4,500
4,835
Note: 6 row UU coils are not available.
2. Size coil section. Unit size, coil type, and coil rows determine small, medium, medium-large, or large coil section.
Trane Unit Size
3
6
8
10
12
14
1/2" Coils - max rows
Small Coil Section
2
2
2
2
2
2
Medium Coil Section
8
8
8
8
8
8
Medium Large Coil Section

8
8
8
Medium Large Coil w/ Access

8
8
8
5/8" and 1" Coils - max rows
Small Coil Section
2
2
2
2
2
2
Medium Coil Section
4
4
4
4
4
4
Medium Large Coil Section

8
8
8
Medium Large Coil w/ Access

4
4
4
Large Coil Section
10
10
10
8
8
8
Note: 6 row UU coils are not available.
3. Select filter type and check face velocities. Face velocity = CFM / filter area.
Trane Unit Size
3
6
8
10
12
14
Flat Filter Area (ft2)
3.5
5.6
6.9
9.7
13.3
15
Angled Filter Area (ft2)
5.6
8.9
11.1
13.9
16.7
26.7
2
Bag / Cartridge Filter Area (ft )
3.3
5.6
6.7
9.3
10
14.7

17
16.80
8,400
14.70
7,350
13.30
6,650
17
2
8
8
8
2
4
8
4
8
17
18.1
28.9
16.7

4. Design the air handling system. Choose all the required sections.
5. Select a fan. Estimate system static pressure requirements and select a fan. Refer to unit data pages for T-Series Climate Changer air handler section
pressure drops.
Trane Unit Size
3
6
8
10
12
14
Design CFM
1,660
2,930
3,770
4,820
6,150
7,100
Fan Type A - Low Pressure
Fan Size / Type
9 1/2 FC
12 1/4 FC
13 1/2 FC
15 FC
16 1/2 FC
18 1/4 FC
Max TSP/RPM
2.5/1800
2.5/1403
2.5/1273
2.5/1146
2.5/1042
2.5/942
Motor HP Range (ODP)
1/6-2
1/4-5
1/2-5
1-5
1-7 1/2
1-7 1/2
Outlet Area (ft2)
0.84
1.90
2.31
2.79
3.39
4.14
Fan Type B - Medium Pressure
Fan Size/ Type
9 1/2 FC
10 1/2 FC
12 1/4 FC
13 1/2 FC
15 FC
16 1/2 FC
Max TSP/RPM
5/2800
5/2365
5.0/2027
5/1839
5/1655
5/1505
Motor HP Range (ODP)
1-5
1-5
1-7 1/2
1-7 1/2
1-10
1-10
Outlet Area (ft2)
0.65
1.41
1.90
2.31
2.79
3.39
Fan Type C - High Pressure
Fan Size / Type

13 1/2 BI
15 BI
16 1/2 BI
Max TSP/RPM
8/3536
8/3183
8/2894
Motor HP Range (ODP)
1-7 1/2
1-15
1-15
Outlet Area (ft2)
2.31
2.79
3.39
Fan Type P - Plenum (Plug) Fan
Fan Size/ Type

Max TSP/RPM
Motor HP Range (ODP)
Outlet Area (ft2)
Fan Type Q - Quiet Airfoil Vaneaxial (Q Fan, smaller diameter)
Fan Size/ Type

19 Q-Fan
19 Q-Fan
Max TSP/RPM
6/3145
6/3145
Motor HP Range (ODP)
1/2-7 1/2
1/2-7 1/2
Outlet Area (ft2)
2.30
2.30
Fan Type R - Quiet Airfoil Vaneaxial (Q Fan, larger diameter)
Fan Size/ Type

21 1/2 Q-Fan 21 1/2 Q-Fan


Max TSP/RPM
6/2780
6/2780
Motor HP Range (ODP)
1/2-10
1/2-10
Outlet Area (ft2)
2.88
2.88

17
8,400
20 FC
2.5/859
1-10
5.05
18 1/4 FC
5/1360
1-15
4.14
18 1/4 BI
8/2616
1-20
4.14

21 1/2-Fan
6/2780
1/2-10
2.88
24 1/2 Q-Fan
6/2380
1/2-15
3.73

6. Overall air handling unit dimensions and weights can be totaled from the sections detailed on page 31.
7. Factory mounted, wired, and tested starter/disconnects are standard. Similar disconnect and VFD/disconnect packages are available. Also consider factory mounted,
wired, and tested DDC control systems to minimize construction cycles and jobsite coordination.
8. Review and finalize selections using the fan curve catalog CLCH-CS-7A, and/or the Customer Direct Service (C.D.S.) computer selection programs.
9. Contact the local Trane office with questions or to order air handling systems.

32

Quick
Select

21
20.80
10,400
16.50
8,250
15.10
7,550

25
24.40
12,200
19.80
9,900
17.00
8,500

30
29.00
14,500
23.60
11,800
20.30
10,150

35
34.10
17,050
30.14
15,070
21.25
10,625

40
39.30
19,650
34.71
17,355
24.50
12,250

50
49.43
24,715
47.69
23,845
36.33
18,165

66
65.63
32,815
63.00
31,500
49.88
24,940

80
78.75
39,375
76.13
38,065
60.38
30,190

100
100.40
50,200
96.94
48,470
76.38
38,190

21

25

30

35

40

50

66

80

100

2
8
8
8

2
8
8
8

2
8
8
8

2
8
8
8

2
8
8
8

2
8
8
8

2
8

2
8

2
8

2
4
8
4
8

2
4
8
4
8

2
4
8
4
8

1
4
8
6
8

1
4
8
6
8

3
6
8
6
8

3
6
8

3
6
8

3
6
8

21
20
31.1
22

25
25
38.9
24

30
29.1
47.2
28

35
31.9
63.9
30.7

40
36.1
72.2
36

50
48.3
80.6
54.8

66
68.6
108.3
73.3

80
83.1
137.5
80.7

100
104.7
161.1
106.9

21
10,400

25
12,200

30
14,500

35
17,050

40
19,650

50
24,715

66
32,815

80
39,375

100
50,200

22 3/8 FC
3/972
1-10
5.16

25 FC
3/811
1-10
6.70

25 FC
3/811
1-20
6.70

27 5/8 FC
3/698
5-25
8.08

30 1/4 FC
3/664
5-25
9.79

33 FC
3/580
5-30
11.69

33 FC
6/760
10-60
11.69

40 1/4 AF
5/996
15-50
20.14

44 1/2 AF
5/901
15-60
24.62

20 FC
5/1241
1-15
5.05

22 3/8 FC
5/1273
1-20
5.16

22 3/8 FC
5/1273
1-25
5.16

25 FC
5/1062
5-30
6.73

27 5/8 FC
5/905
5-30
8.08

30 1/4 FC
5/870
5-40
9.79

36 1/2 AF
8/1413
15-75
16.54

36 1/2 AF
8/1413
20-75
16.54

40 1/4 AF
11/1281
25-100
20.14

20 BI
8/2387
1-25
5.05

22 1/4 BI
8/2146
1-25
6.30

22 1/4 BI
8/2146
1-30
6.30

24 1/2 AF
8/2148
5-40
7.46

27 AF
8/1910
5-50
9.05

30 AF
8/1719
5-60
11.17

33 AF
8/1562
20-75
13.51

33 AF
8/1562
20-75
13.51

36 1/2 AF
8/1413
30-100
16.54

29 1/8 AF
6/1886
2-15

32 3/8 AF
6/1611
3-20

35 9/16 AF
6/1643
3-25

35 9/16 AF
6/1643
5-30

39 3/8 A
6/1412
5-30

43 7/16 AF
6/1334
5-40

52 7/8 AF
6/968
7 1/2-50

58 1/2 AF
6/875
7 1/2-60

64 3/4 AF
6/791
10-75

24 1/2 Q-Fan
6/2380
1/2-15
3.73

27 Q-Fan
6/2160
1/2-15
4.54

30 Q-Fan
6/1940
3/4-20
5.60

33 Q-Fan
6/1822
1-25
6.78

33 Q-Fan
6/1822
1-25
6.78

36 1/2 Q-Fan
6/1647
1-30
8.30

40 1/4 Q-Fan
6/1636
1 1/2-40
10.09

44 1/2 Q-Fan
6/1485
2-50
12.33

27 Q-Fan
6/2160
1/2-15
4.54

30 Q-Fan
6/1940
3/4-20
5.60

33 Q-Fan
6/1822
1-25
6.78

36 1/2 Q-Fan
6/1647
1-30
8.30

36 1/2 Q-Fan
6/1647
1-30
8.30

40 1/4 Q-Fan
6/1492
1 1/2-40
10.09

44 1/2 Q-Fan
6/1352
2-50
12.33

33

Unit
Sizes
Table 3-1 Coil Data
1/2" Unit Coils
UW, UF
Shipping Coils
Full
Modified

Area (Ft2)
3.32

Qty-Size
1-2 1x23

2.75
1.83

1-18x22
1-12x22

Table 3-2 Coil Availability


Module Size
Small
Medium
Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-2 Row
1-4 Row
1-10 Row

Table 3-3 1/2" Unit Coil Water


Connection Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

UW
21
1 1/2
1 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 03

Sections
Filter / Mixing (4)
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank / Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
36
49
15.5
40.25
11
24.75
36
24.75
11
15.5
24.75
11
15.5
24.75
11
15.5
15.5
60.75
60.75
15.5
24.75
17.1
17.1
17.1
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.
4. Mixing module without filter is 24.75 in length.

All dimensions are in inches.

34

Weight (lbs.)
225
314
88
191
71
154
189
143
47
62
105
117
182
323
59
98
98
560
560
74
92
28
32
20
83

Unit
Sizes
Table 3-4 Unit Pressure Drops (inches WG)

Size 03

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
1.75
.87
1.90

400
.03
.02
.04

Damper Face Velocity (FPM)


500
600
700
.04
.06
.08
.03
.05
.06
.06
.09
.12

800
.10
.08
.16

900
.12
.10
.20

1000
.15
.12
.25

1100
.19
.15
.30

1200
.22
.18
.36

Exhaust or Economizer Return Dampers

Area (ft2)
.87

600
.05

800
.09

1200
.20

1400
.27

1600
.35

1800
.46

2000
.55

2100
.60

Internal Face and Bypass


Face Area
Bypass Area
Face Damper

Area (ft2)
1.51
1.51
3.60

400
.05
.05
.04

800
.18
.18
.15

900
.23
.23
.19

1000
.28
.28
.23

1100
.34
.34
.28

1200
.40
.40
.33

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
3.32
3.32

400
.01
.13

600
.03
.32

650
.03
.38

700
.04
.44

750
.04
.52

800
.05
.60

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood
Face Velocity (FPM)

Area (ft2)

.300
.04

500
600
700
.07
.10
.14
.07
.10
.14
.06
.08
.11
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.17
.21
.26
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

700
.20

800
.26

850
.29

900
.33

950
.36

1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

1.96
2.46
Area (ft2)
1.46

1000
.07

Area (ft2)
3.50
20x25

200

5.60
2-16x25
3.30
20x24

1000
.13

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
* Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 3-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range

Fan Type
A
B
1660
1660
9 1/2 FC
9 1/2 FC
2.5/1800
5/2800
3/4
3/4
3/4
.84
1/6-2

1 3/16
1 3/16
1 3/16
.65
1-5

35

Unit
Sizes
Table 6-1 Coil Data

1/2" Unit Coils


UW,UF
Shipping Coils
Full
Modified

Area (Ft2)
5.86

Qty-Size
1-23x36

4.38
2.92

1-18x35
1-12x35

Table 6-2 Coil Availability


Module Size
Small
Medium
Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-2 Row
1-4 Row
1-10 Row

Table 6-3 1/2" Unit Coil Water


Connection Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW
23
1 1/2
1 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 06

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
27.25
49
15.5
42.75
11
27.25
41
27.25
11
15.5
27.25
11
15.5
27.25
11
15.5
15.5
68.25
68.25
15.5
27.25
17.4
17.1
17.4
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

36

Weight (lbs.)
232
377
105
242
84
199
248
181
56
75
137
151
250
439
80
129
129
750
750
91
118
29
46
21
113

Unit
Sizes
Table 6-4 Unit Pressure Drops (Inches WG)
Ultra Low Leak Dampers
Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
3.01
1.46
3.20
Area (ft2)
Exhaust or Economizer Return Dampers 1.46

400
.02
.02
.04
600
.05

Internal Face and Bypass


Face Area
Bypass Area
Face Damper

Area (ft2)
2.25
2.25
5.40

400
.04
.04
.03

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
5.86
5.86

400
.01
.13

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

2.08
4.08
Area (ft2)
2.28

1000
.07

Area (ft2)
5.60
2-20x20

200

8.90
4-16x20
5.60
2-20x20

Size 06

Damper Face Velocity (FPM)


500
600
700
.03
.05
.06
.03
.04
.05
.06
.09
.12
800
1000
1200
.08
.12
.18
500
600
700
.06
.09
.13
.06
.09
.13
.05
.08
.10
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.17
.21
.26
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15
Face Velocity (FPM)
1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM
(Max. RPM and BHP)

1
1
1
1.41
1-5

10.0/3.5

5.7/2.9

22.5/7.8

19.6/6.5

1000
.13
.11
.25
1800
.40

1100
.15
.13
.30
2000
.45

1200
.18
.16
.36
2100
.54

800
.16
.16
.14

900
.21
.21
.17

1000
.26
.26
.21

1100
.31
.31
.26

1200
.37
.37
.31

600
.03
.32

650
.03
.38

700
.04
.44

750
.04
.52

800
.05
.60

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

Fan Type
A
B
2930
2930
12 1/4 FC
10 1/2 FC
2.5/1403
5/2365
1
1
1
1.90
1/4-5

900
.10
.09
.20
1600
.31

.27
.52
.52
.51

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 6-5 Fan Data

800
.08
.07
.16
1400
.24

Torques are shown for open/closed operation at 2000 and


3000 fpm fan outlet velocity.

37

Unit
Sizes
Table 8-1 Coil Data
1/2" Unit Coils
UW,UF
Shipping Coils
Full
Modified

Area (Ft2)
7.54

Qty-Size
1-27x40

6.50
4.88

1-24x39
1-18x39

Table 8-2 Coil Availability


Module Size
Small
Medium
Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-2 Row
1-4 Row
1-10 Row

Table 8-3 1/2" Unit Coil Water


Connection Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW
27
1 1/2
1 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 08

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
31
49
15.5
46.5
11
31
44
31
11
15.5
31
11
15.5
31
11
15.5
15.5
75
75
15.5
31
19.8
17.1
19.8
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

38

Weight (lbs.)
270
419
115
279
91
232
281
213
61
80
164
170
294
568
93
144
144
845
845
98
135
35
51
25
130

Unit
Sizes
Table 8-4 Unit Pressure Drops (Inches WG)

Size 08

Damper Face Velocity (FPM)


500
600
700
.03
.04
.06
.03
.04
.05
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
3.40
1.84
3.60

400
.02
.02
.04

Exhaust or Economizer Return Dampers

Area (ft2)
1.84

600
.04

800
.07

1000
.11

Internal Face and Bypass


Face Area
Face Damper

Area (ft2)
4.22
7.60

400
.04
.03

500
.06
.05

600
.08
.07

Bypass Area

Area (ft2)
2.48

1400
.59

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
7.54
7.54

400
.01
.13

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12 Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12 Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95*/. Eff.

2.51
4.57
Area (ft2)
2.76

1000
.07

Area (ft2)
6.90
2-20x25

200

11.10
4-20x20
6.70
2-20x24

800
.08
.07
.16

900
.10
.09
.20

1000
.12
.11
.25

1100
.15
.13
.30

1200
.18
.16
.36

1200
.13

1400
.21

1600
.27

1800
.35

2000
.44

2100
.48

700
.11
.10

800
.14
.13

900
.18
.16

1000
.23
.20

1100
.27
.24

1200
.32
.29

1600
1800
2000
.77
.97
1.20
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.17
.21
.26
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.46

2400
1.73

2600
2.03

2800
2.36

3000
2.71

600
.03
.32

650
.03
.38

700
.04
.44

750
.04
.52

800
.05
.60

700
.20

800
.26

850
.29

.900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 8-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM
(Max. RPM and BHP)

Fan Type
A
B
3770
3770
13 1/2 FC
12 1/4 FC
2.5/1273
5.0/2027
1
1
1
2.31
1/2-5

13/16
13/16
13/16
1.90
1-7 1/2

10.9/3.9

10.0/3.5

24.5/8.7

22.5/7.8

Torques are shown for open/closed operation at 2000 and


3000 fpm fan outlet velocity.

39

Unit
Sizes
Table 10-1 Coil Data
1/2" Unit Coils
UW,UF
Shipping Coils
Full
Modified

Area (Ft2)
9.64

Qty-Size
1-27x51

8.33
6.25

1-24x50
1-18x50

Table 10-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 10-3 1/2" Unit Coil Water


Connection Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

UW
27
1 1/2
1 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 10

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank / Access
Medium Large Blank/ Access
Large Blank / Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI/ AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI/ AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
34
60.5
15.5
49.5
11
24.5
34
24.5
11
15.5
24.5
34
11
15.5
24.5
34
11
15.5
15.5
58.5
69.5
15.5
34
19.2
20.5
19.2
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

40

Weight (lbs.)
367
582
134
355
109
242
285
218
71
95
161
218
210
363
649
720
147
185
185
845
983
916
1055
114
195
41
93
28
178

Unit
Sizes
Table 10-4 Unit Pressure Drops (Inches WG)

Size 10

Damper Face Velocity (FPM)


500
600
700
.02
.03
.04
.03
.04
.05
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
7.60
2.47
8.00

400
.01
.02
.04

Exhaust or Economizer Return Dampers

Area (ft2)
2.47

600
.04

800
.07

1000
.11

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
7.60
9.80

400
.03
.03

500
.05
.05

600
.07
.07

Bypass Area

Area (ft2)
3.17

1400
.58

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
9.64
9.64

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6' Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

3.30
9.42
Area (ft2)
3.86

1000
.07

Area (ft2)
9.70
2-20x25
1-16x25

200

13.90
4-20x25
9.30
3-12x24
1-20x24

800
.06
.06
.16

900
.07
.08
.20

1000
.09
.10
.25

1100
.11
.12
.30

1200
.13
.14
.36

1200
.16

1400
.21

1600
.27

1800
.35

2000
.44

2100
.48

700
.10
.09

800
.13
.12

900
.16
.15

1000
.20
.19

1100
.24
.23

1200
.29
.27

1600
1800
2000
.76
.96
1.18
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.43

2400
1.70

2600
2.00

2800
2.32

3000
2.66

600
.03
.46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
;85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 10-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
4820
15 FC
2.5/1146

Fan Type
B
4820
13 1/2 FC
5/1839

C
4820
13 1/2 BI
8/3536

1 3/16
1 3/16
1 3/16
2.79
1-5

1 3/16
1 3/16
1 3/16
2.31
1-7 1/2

1 11/16
1 11/16
1 11/16
2.31
1-7 1/2

14.1/5.0
31.9/11.4

10.9/3.9
24.5/8.7

38.0
40.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

41

Unit
Sizes
Table 12-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Area (Ft2)
12.30

1-32x55

11.30
9.00

1 -30x54
1-24x54

Table 12-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 12-3 1/2" Unit Coil Water


Connection Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
32
2
2
3/8

SShipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 12

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank / Access
Medium Large Blank / Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (0)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
34
60.5
15.5
49.5
11
24.5
38
24.5
11
15.5
24.5
34
11
15.5
24.5
34
11
15.5
15.5
62.5
73.5
15.5
34
21.7
20.5
21.7
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as Inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

42

Weight (lbs.)
393
637
145
380
122
261
323
235
76
101
171
232
238
431
788
864
167
200
200
968
1212
1084
1143
1045
1288
122
204
49
99
33
200

Unit
Sizes
Table 12-4 Unit Pressure Drops (inches WG)

Size 12

Damper Face Velocity (FPM)


500
600
700
.02
.03
.04
.02
.03
.04
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
8.15
3.01
8.50

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
3.01

600
.04

800
.06

1000
.10

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
8.15
12.80

400
.03
.03

500
.05
.04

600
.07
.06

Bypass Area

Area (ft2)
3.40

1400
.58

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
12.30
12.30

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

3.95
10.12
Area (ft2)
5.14

1000
.07

Area (ft2)
13.30
6-16x20

200

16.70
6-20x20
10.00
3-20x24

800
.06
.05
.16

900
.07
.07
.20

1000
.09
.09
.25

1100
.11
.10
.30

1200
.13
.12
.36

1200
.14

1400
.19

1600
.24

1800
.31

2000
.40

2100
.44

700
.10
.09

800
.13
.11

900
.16
.14

1000
.20
.18

1100
.24
.22

1200
.28
.26

1600
1800
2000
.75
.95
1.17
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.42

2400
1.69

2600
1.98

2800
2.30

3000
2.64

600
.03
.46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.

Table 12-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
6150
16 1/2 FC
2.5/1042

B
6150
15 FC
5/1655

Fan Type
C
6150
15 BI
8/3183

Q
6150
19 Q-Fan
6/3145

R
6150
21 1/2 Q-Fan
6/2780

13/16
13/16
1 3/16
3.39
1-7 1/2

1 7/16
17/16
1 7/16
2.79
1-10

1 15/16
1
1 15/16
2.79
1-15

15/16
15/16
15/16
2.30
1/2-7 1/2

13/16
13/16
13/16
2.88
1/2-10

18.0/6.4
40.5/14.4

14.1/5.0
31.9/11.4

38.0
40.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

43

Unit
Sizes
Table 14-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Area (Ft2)
14.20

1-35x59

12.10
9.67

1-30x58
1-24x58

Table 14-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 14-3 1/2" Unit Coil Water


Connection Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
35
2
2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 14

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
81 / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
34
60.5
15.5
49.5
11
24.5
40
24.5
11
15.5
24.5
34
11
15.5
24.5
34
11
15.5
15.5
64.5
75.5
15.5
34
24.1
20,5
24.1
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

44

Weight (lbs.)
443
677
154
399
130
290
372
266
80
105
179
243
255
476
842
923
182
230
230
1034
1298
1133
1192
1113
1378
130
209
57
104
39
217

Unit
Sizes
Table 14-4 Unit Pressure Drops (Inches WG)

Size 14

Damper Face Velocity (FPM)


500
600
700
.02
.03
.04
.02
.03
.04
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
8.70
3.56
9.10

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
3.56

600
.03

800
.05

1000
.09

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
10.88
13.70

400
.03
.03

500
.05
.04

600
.07
.06

Bypass Area

Area (ft2)
3.51

1400
.58

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
14.20
14.20

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

4.54
10.73

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

Area (ft2)
5.85

1000
.07

Area (ft2)
15.00
3-16x20
3-20x20

200

26.70
12-16x20
14.70
2-12x24
2-20x24
1-24x24

800
.06
.05
.16

900
.07
.06
.20

1000
.09
.07
.25

1100
.10
.09
.30

1200
.12
.11
.36

1200
.12

1400
.16

1600
.21

1800
.27

2000
.34

2100
.39

700
.09
.09

800
.12
.11

900
.15
.14

1000
.18
.18

1100
.22
.21

1200
.27
.25

1600
1800
2000
.76
.96
1.18
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.43

2400
1.70

2600
2.00

2800
2.32

3000
2.66

600
.03
46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 14-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0 WC)
3000 FPM (Max. RPM and BHP)

A
7100
18 1/4 FC
2.5/942

B
7100
16 1/2 FC
5/1505

Fan Type
C
7100
16 1/2 BI
8/2894

Q
7100
19 Q-Fan
6/3145

R
7100
21 1/2 Q-Fan
6/2780

1 3/16
1 3/16
1 3/16
4.14
1-7 1/2

1 7/16
1 7/16
1 7/16
3.39
1-10

1 15/16
1
1 15/16
3.39
1-15

15/16
15/16
15/16
2.30
1/2-7 1/2

1 3/16
1 3/16
13/16
2.88
1/2-10

23.1/8.3
52.2/18.6

18.0/6.4
40.5/14.4

44.0
50.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

45

Unit
Sizes
Table 17-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

Sections

Area (Ft2)
16.80

Qty.-Size
1-37x65

14.70
13.30

1-33x64
1-30x64

Table 17-2 Coil Availability


1/2" Unit Coils
2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 17-3 1/2" Unit Coil Water


Connection Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

Size 17

UW/UU
37
2
2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Ban Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank / Access
Medium Large Blank / Access
Large Blank / Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
34
60.5
15.5
49.5
11
24.5
44
24.5
11
15.5
24.5
34
11
15.5
24.5
34
11
15.5
15.5
68.5
79.5
15.5
34
28.4
24
28.4
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

46

Weight (lbs.)
490
740
167
431
140
312
426
284
85
113
192
261
285
539
967
1054
202
252
252
1176
1497
1312
1455
1261
1582
143
224
70
138
49
247

Unit
Sizes
Table 17-4 Unit Pressure Drops (Inches WG)

Size 17

Damper Face Velocity (FPM)


500
600
700
.02
.03
.04
.02
.03
.03
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
12. 29
4.11
12.80

400
.01
.02
.04

Exhaust or Economizer Return Dampers

Area (ft2)
4.11

600
.03

800
.05

1000
.07

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
11.94
17.80

400
.03
.03

500
.05
.04

600
.07
.06

Bypass Area

Area (ft2)
3.85

1400
.57

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
16.80
16.80

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Elf.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

5.38
14.60
Area (ft2)
6.60

1000
.67

Area (ft2)
18.10
4-20x20
2-20x25

200

28.90
8-16x20
4-16x25
16.7 0
6-20x20

800
.05
.05
.16

900
.06
.06
.20

1000
.07
.06
.25

1100
.09
.07
.30

1200
.11
.09
.36

1200
.11

1400
.14

1600
.18

1800
.23

2000
.27

2100
.31

700
.09
.08

800
.12
.11

900
.15
.14

1000
.18
.17

1100
.22
.20

1200
.26
.24

1600
1800
2000
.75
.95
1.17
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.42

2400
1.68

2600
1.98

2800
2.29

3000
2.63

600
.03
.46

650
.03
.54

700
.04
63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.97
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 17-5 Fan Data


Design
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
8400
20 FC
2.5/859

B
8400
18 1/4 FC
5/1360

Fan Type
C
8400
18 1/4 BI
8/2616

Q
8400
21 1/2 Q-Fan
6/2780

R
8400
24 1/2 Q-Fan
6/2380

1 7/16
1 7/16
1 7/16
5.05
1-10

1 11/16
1 11/16
1 11/16
4.14
1-15

2 3/16
1
2 3/16
4.14
1-20

1 3/16
1 3/16
1 3/16
2.88
1/2-10

1 3/16
1 3/16
1 3/16
3.73
1/2-15

24.0/9.0
54.0/19.5

23.1/8.3
52.2/18.6

54.0
60.00

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

47

Unit
Sizes
Table 21-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Area (Ft2)
20.80

Qty-Size
1-45x67

16.50
15.10

2-18x66
1-33x36

Table 21-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 21-3 1/2" Unit Coil Water


Connection - Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

45
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 21

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small. Blank / Inspection
Medium Blank / Access
Medium Large Blank/ Access
Large Blank / Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Planum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
34
60.5
15.5
49.5
11
24.5
48.5
24.5
11
15.5
24.5
34
11
15.5
24.5
34
11
15.5
15.5
73
84
15.5
34
30.3
24
30.3
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

48

Weight (lbs.)
526
827
187
477
157
338
511
317
95
125
212
289
323
641
1142
1234
231
281
281
1357
1743
1745
1598
1669
1451
1838
1839
163
252
79
141
55
283

Unit
Sizes
Table 21-4 Unit Pressure Drops (Inches WG)

Size 21

Damper Face Velocity (FPM)


500
600
700
.02
.03
.04
.01
.02
.03
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Dampers
Side Damper (each)
Protective Grate

Area (ft2)
12.65
4.79
13.10

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
4.79

600
.03

800
.05

1000
.06

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
15.07
21.10

400
.03
.03

500
.04
.04

600
.06
.06

Bypass Area

Area (ft2)
3.97

1400
.57

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
20.80
20.80

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
2" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

6.08
15.04
Area (ft2)
7.72

1000
.07

Area (ft2)
20.00
4-20x20
4-16x20

200

31.10
4-16x20
8-16x25
22.00
3-20x24
3-24x24

800
.05
.04
.16

900
.06
.05
.20

1000
.07
.05
.25

1100
.09
.06
.30

1200
.11
.08
.36

1200
.09

1400
.12

1600
.16

1800
.21

2000
.25

2100
.28

700
.08
.08

800
.11
.10

900
.14
.13

1000
.17
.16

1100
.21
.19

1200
.25
.23

1600
1800
2000
.75
.95
1.17
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.41

2400
1.68

2600
1.97

2800
2.29

3000
2.63

600
.03
.46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 21-5 Fan Data


A
10400
22 3/8 FC
3/972
17/16
17/16
17/16
5.16
1-10

Design CFM
Size /Type
Max TSP/RPM
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
25.0/9.5
3000 FPM (Max. RPM and BHP) 56.0/21.0

B
10400
20 FC
5/1241
1 11/16
1 11/16
1 11/16
5.05
1-15

Fan Type
C
P
10400
10400
20 BI
29 1/8 AF
8/2387
6/1886
27/16
17/16
13/16
1 7/16
27/16
1 7/16
5.05
1-25
2-15

Q
10400
24 1/2 Q-Fan
6/2380
1 3/16
13/16
1 3/16
3.73
1/2-15

R
10400
27 Q-Fan
6/2160
17/16
1 7/16
1 7/16
4.54
1/2-15

24.0/9.0
54.0/19.5

66.0
74.0

68.0
89.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

49

Unit
Sizes
Table 25-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
24.40

Qty-Size
1-51x69

19.80

Modified

17.00

1-18x68
1-24x68
2-18x68

Table 25-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 25-3 1/2" Unit Coil Water


Connection - Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
51
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 25

Sections
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank / Access
Large Blank / Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face/ Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
60.5
15.5
55.5
11
24.5
54.75
24.5
11
15.5
24.5
40
11
15.5
24.5
40
11
15.5
15,5
54.75
65.75
15.5
40
34.5
27.6
34.5
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

50

Weight (lbs.)
902
201
562
164
355
579
334
100
132
221
361
353
722
1298
1465
254
306
306
1238
1666
1705
1581
1696
1338
1766
1804
173
318
96
172
67
312

Unit
Sizes
Table 25-4 Unit Pressure Drops (Inches WG)

Size 25

Damper Face Velocity (FPM)


500
600
700
.02
.02
.03
.01
.02
.02
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
15.94
5.61
16.40

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
5.61

600
.02

800
.04

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
18.36
24.60

400
.03
.03

500
.04
.04

600
.06
.06

Bypass Area

Area (ft2)
4.08

1400
.59

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
24.40
24.40

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

7.13
18.69
Area (ft2)
8.96

1000
.07

Area (ft2)
25.00
4-20x25
4-16x25

200

38.90
4-20x20
8-20x25
24.00
6-24x24

800
.04
.03
.16

900
.05
.04
.20

1000
.07
.05
.25

1100
.08
.05
.30

1200
.10
.06
.36

1200
.08

1400
.10

1600
.14

1800
.18

2000
.22

2100
.24

700
.08
.08

800
.11
.10

900
.13
.13

1000
.17
.16

1100
.20
.19

1200
.24
.22

1600
1800
2000
.78
.98
1.21
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.47

2400
1.75

2600
2.05

2800
2.38

3000
2.73

600
.03
.46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.95
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 25-5 Fan Data


A
12200
25 FC
3/811

Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
1 11/16
Opposite Drive Side
1 11/16
Shaft Size
1 11/16
2
Outlet Area (Ft )
6.70
Motor HP Range
1-10
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
26.5/10.0
3000 FPM (Max. RPM and BHP) 59.7/22.5

B
12200
22 3/8 FC
5/1273

Fan Type
C
12200
22 1/4 BI
8/2146

P
12200
32 3/8 AF
6/1611

Q
12200
27 Q-Fan
6/2160

R
12200
30 Q-Fan
6/1940

2 3/16
1
2 3/16
5.16
1-20

2 11/16
1 7/16
2 11/16
6.30
1-25

1 11/16
1 11/16
1 11/16
3-20

1 7/16
1 7/16
1 7/16
4.54
1/2-15

1 7/16
1 7/16
1 7/16
5.60
3/4-20

25.0/9.5
56.0/21.0

90.0
100.0

81.0
119.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

51

Unit
Sizes
Table 30-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
29.00

Qty-Size
1-51x82

23.60

Modified

20.30

1-18x81
1-24x81
2-18x81

Table 30-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-2 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 30-3 1/2" Unit Coil Water


Connection Sizes (inches)
Header Height
supply
Return
Drain and Vent

UW/UU
51
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 30

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI/ AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
40
72
15.5
55.5
11
24.5
54.75
24.5
11
15.5
24.5
40
11
15.5
24.5
40
11
15.5
15.5
54.75
65.75
15.5
40
33.3
27.6
33.3
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

52

Weight (lbs.)
687
1118
219
614
177
389
632
368
108
143
241
393
390
824
1483
1664
289
343
343
1502
1889
1852
1839
1955
1610
1997
1960
192
337
105
197
70
362

Unit
Sizes
Table 30-4 Unit Pressure Drops (Inches WG)

Size 30

Damper Face Velocity (FPM)


500
600
700
.02
.02
.03
.01
.02
.02
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
18.75
6.99
19.30

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
6.99

600
.02

800
.03

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
21.69
29.00

400
.03
.02

500
.04
.04

600
.06
.05

Bypass Area

Area (ft2)
4.82

1400
.56

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
29.00
29.00

400
.01
.21

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

8.74
21.88
Area (ft2)
11.70

1000
.07

Area (ft2)
29.10
8-16x25
2-20x25

200

47.20
12-20x20
4-20x25
28.00
6-24x24
2-12x24

800
.04
.03
.16

900
.05
.04
.20

1000
.06
.05
.25

1100
.07
.05
.30

1200
.09
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

700
.08
.07

800
.10
.10

900
.13
.12

1000
.16
.15

1100
.19
.18

1200
.23
.22

1600
1800
2000
.74
.93
1.15
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.26
.32
.39
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.39

2400
1.66

2600
1.95

2800
2.26

3000
2.59

600
.03
.46

650
.03
.54

700
.04
.63

750
.04
.72

800
.05
.82

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 30-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0 WC)
3000 FPM (Max. RPM and BHP)

Fan Type
C
P
14500
14500
22 1/4 BI
35 9/16 AF
8/2146
6/1643

Q
14500
30 Q-Fan
6/1940

R
14500
33 Q-Fan
6/1822

23/16
5.16
1-25

2 11/16
17/16
2 11116
6.30
1-30

1 11/16
1 11/16
1 11/16
3-25

17/16
1 7/16
1 7/16
5.60
3/4-20

1 7/16
17/16
17/16
6.78
1-25

25.0/9.5
56.0/21.0

90.0
100.0

97.0
141.0

A
14500
25 FC
3/811

B
14500
22 3/8 FC
5/1273

1 11/16
1 11/16
1 11/16
6.70
1-20

23/16

26.5/10.0
59.7/22.5

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

53

Unit
Sizes
Table 35-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
34.10

Qty-Size
1-57x86

30.14

Modified

21.25

1-18x85
1-33x85
2-18x85

Table 35-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 35-3 1/2" Unit Coil Water


Connection - Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
57
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 35

Sections
FiIter /Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face I Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vortical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
48
72
16
39
11.5
31
48
31
11.5
16
31
48
11.5
16
31
48
11.5
16
16
62
73.5
16
48
37.6
31.2
37.6
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

54

Weight (lbs.)
933
1291
265
822
235
545
698
494
130
169
334
541
448
897
1759
1986
347
425
425
2289
2389
1426
2842
3018
2419
2518
1555
293
472
124
238
84
448

Unit
Sizes
Table 35-4 Unit Pressure Drops (Inches WG)

Size 35

Damper Face Velocity (FPM)


500
600
700
.01
.02
.03
.01
.02
.02
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
22.46
8.22
23.90

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
8.22

600
.02

800
.03

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
22.46
32.80

400
.03
.02

500
.04
.04

600
.06
.05

Bypass Area

Area (ft2)
8.49

1400
.55

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
34.10
34.10

400
.01
.53

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media;
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

10.05
26.58
Area (ft2)
13.20

1000
.07

Area (ft2)
31.90
6-20x25
4-16x25

200

63.90
12-20x25
8-16x25
30.70
6-24x24
2-24x20

800
.04
.03
.16

900
.05
.04
.20

1000
.06
.05
.25

1100
.07
.05
.30

1200
.08
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

700
.08
.07

800
.10
.09

900
.13
.12

1000
.16
.15

1100
.19
.18

1200
.23
.21

1600
1800
2000
.72
.91
1.12
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.35

2400
1.61

2600
1.89

2800
2.19

3000
2.52

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 35-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
17050
27 5/8 FC
3/698

B
17050
25 FC
5/1062

Fan Type
C
17050
24 1/2 AF
8/2148

P
17050
35 9/16 AF
6/1643

Q
17050
33 Q-Fan
6/1822

R
17050
36 1/2 Q-Fan
6/1647

2 3/16
1
2 3/16
8.08
5-25

2 7/16
1 3/16
2 7/16
6.73
5-30

2 3/16
1 7/16
2 15/16
7.46
5-40

1 15/16
1 7/16
1 15/16
5-30

17/16
1 7/16
1 7/16
6.78
1-25

1 11/16
1 11/16
1 11/16
8.30
1-30

115/46
200/104

26/10
59/22

31/7
70/17

110.0
162.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

55

Unit
Sizes
Table 40-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
39.30

Qty-Size
1-57x99

34.71

Modified

24.50

1-18x98
1-33x98
2-18x98

Table 40-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 40-3 1/2" Unit Coil Water


Connection - Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
57
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 40

Sections
Filter/ Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank / Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI/ AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
48
84
16
34.5
11.5
31
48
31
11.5
16
31
48
1.5
16
31
48
11.5
16
16
62
73.5
16
48
35.8
31.2
35.8
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

56

Weight (lbs.)
1025
1544
283
888
249
590
752
538
139
181
364
584
487
1017
1982
2222
385
480
480
2447
2556
1494
2982
3158
2586
2695
1633
322
511
131
266
85
497

Unit
Sizes
Table 40-4 Unit Pressure Drops (Inches WG)

Size 40

Damper Face Velocity (FPM)


500
600
700
.01
.02
.03
.01
.02
.02
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
25.03
9.43
27.30

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
9.43

600
.02

800
.03

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
25.03
36.50

400
.03
.02

500
.04
.04

600
.06
.05

Bypass Area

Area (ft2)
9.46

1400
.57

Accessories
Moisture Eliminator
Diffuser

Area(ft2)
39.30
39.30

400
.01
.53

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

11.43
30.27
Area (ft2)
14.80

1000
.07

Area (ft2)
36.10
4-20x25
8-16x25

200

72.20
8-20x25
16-16x25
36.00
8-24x24
2-24x12

800
.03
.03
.16

900
.04
.04
.20

1000
.05
.05
.25

1100
.06
.05
.30

1200
.08
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

700
.08
.07

800
.10
.09

900
.13
.12

1000
.15
.14

1100
.19
.17

1200
.22
.21

1600
1800
2000
.74
.94
1.16
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.41

2400
1.67

2600
1.97

2800
2.28

3000
2.62

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.5

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 40-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
19650
30 1/4 FC
3/664

B
19650
27 5/8 FC
5/905

C
19650
27 AF
8/1910

27/16
13/16
27/16
9.79
5-25

27/16
13/16
27/16
8.08
5-30

150/65
220/120

115/46
200/104

Fan Type

P
19650
39 3/8 AF
6/1412

Q
19650
33 Q-Fan
6/1822

R
19650
36 1/2 Q-Fan
6/1647

23/16
1 7/16
37/16
9.05
5-50

1 15/16
1 7/16
1 15/16
5-30

17/16
1 7/16
1 7/16
6.78
1-25

1 11/16
1 11/16
1 11/16
8.30
1-30

46/11
103/25

128.0
181.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.

57

Unit
Sizes
Table 50-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
49.43

Qty-Size
2-32x110

47.69

Modified

36.33

1-30x109
1-33x109
2-24x109

Table 50-2 Coil Availability


Module Size
Small
Medium
Medium Large
Coil
Medium Large
Coil w/ Access

1/2" Unit Coils


2 Row
2-8 Row

Shipping
Coils
1-3 Row
1-4 Row

2-8 Row

1-8 Row

2-8 Row

1-4 Row

Table 50-3 1/2' Unit Coil Water


Connection - Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
2-32
2
2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 50

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank / Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
48
84
19
43.5
14.5
31
48
31
14.5
19
31
48
14.5
19
31
48
14.5
19
19
68.5
83
19
48
43.1
31.2
43.1
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

58

Weight (lbs.)
1148
1785
399
1080
365
684
852
621
221
269
429
662
757
1444
2550
2804
554
645
645
2879
3154
1758
3505
3704
3100
3374
1979
445
571
170
291
113
603

Unit
Sizes
Table 50-4 Unit Pressure Drops (Inches WG)
Ultra Low Leak Dampers
Back or Bottom Damper
Side Dam per (each)
Protective Grate

Area (ft2)
27.86
12.03
30.10

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
12.03

600
.02

Bypass Area

Area (ft2)
36.52
49.30
Area (ft2)
10.53

400
.02
.02
140
.56

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
49.43
49.43

400
.01
.53

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Internal Face and Bypass*


Face Area
Face Damper

Air Blenders
Filters**
Flat Filters
2 Throwaway
2" Pleated Media
4 Pleated Media
Permanent
Angled Filters
2 Throwaway
2 Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

14.24
33.50

Damper Face Velocity (FPM)


500
600
700
.01
.02
.02
.01
.02
.02
.06
.09
.12

1000
.07

Area (ft2)
48.30
12-20x25
3-16x20

200

54.80
8-24x24
6-24x20
1-20x20

800
.03
.03
.16

900
.04
.04
.20

1000
.05
.05
.25

1100
.06
.05
.30

1200
.07
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

000
.18

2100
.19

500
600
700
.04
.05
.07
.03
.05
.07
1600
1800
2000
.73
.93
1.14
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

800
.09
.09
2200
1.38

900
.12
.11
2400
1.65

1000
.14
.13
2600
.93

1100
.17
.16
2800
2.24

1200
.21
.19
3000
2.57

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

800
.03

Area (ft2)
19.80

80.60
20-20x25
4-16x25

Size 50

1000
.05

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.93
.91
.63
.66
.72

.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 50-5 Fan Data

Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
24715
33 FC
3/580

B
24715
30 1/4 FC
5/870

C
24715
30 AF
8/1719

2 7/16
1 3/16
2 7/16
11. 69
5-30

2 11/16
1 7/16
2 11/16
9 .79
5-40

215/100
310/180

150/65
220/120

Fan Type

P
24715
43 7/16 AF
6/1334

Q
24715
36 1/2 Q-Fan
6/1647

R
24715
40 1/4 Q-Fan
6/1492

2 7/16
1 11/16
3 15/16
11.17
5-60

2 3/16
1 7/16
2 3/16

5-40

1 11/16
1 11/16
1 11/16
8.30
1-30

1 11/16
1 11/16
1 11/16
10.09
1 1/2-40

62/15
142/35

160.0
227.0

NA

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity. For plug fans torques shown at 4.0 WC and at Max. RPM and BHP.

59

Unit
Sizes
Table 66-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Area (Ft2)
65.63

Qty-Size
2-37x126

63.00
49.88

3-24x126
1-24x126
1-33x126

Table 66-2 Coil Availability


Module Size
Small
Medium
Medium Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-3 Row
1-6 Row
1-8 Row

Table 66-3 1/2" Unit Coil Water


Connection - Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
2-37
2
2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 66

Sections
Filter/ Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank /Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
49
96
19
48
14.5
29.5
49
29.5
14.5
19
29.5
49
14.5
19
29.5
14.5
19
19
84
84
49
49
48.4
34.6
48.4
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

60

Weight (lbs.)
1367
2147
464
1257
432
797
1046
761
252
307
472
775
933
1850
3372
710
753
753
3972
4398
3922
4961
5128
3972
4398
3922
913
651
220
368
144
797

Unit
Sizes
Table 66-4 Unit Pressure Drops (inches WG)
Ultra Low Leak Dampers
Back or Bottom Damper
Side Damper (each)
Protective Grate

Size 66

Damper Face Velocity (FPM)


500
600
700
.01
.02
.02
.01
.02
.02
.06
.09
.12

Area (ft2)
36.05
15.92
40.30

400
.01
.01
.04

Area (ft2)
Exhaust or Economizer Return Dampers 15.92

600
.02

800
.03

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
51.42
64.30

400
.02
.02

500
.03
.03

600
.05
.05

Bypass Area

Area (ft2)
16.91

1400
.43

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
65.63
65.63

400
.01
.53

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

19.03
43.28
Area (ft2)
27.41

1000
.07

Area (ft2)
68.60
2-16x25
4-16x20
6-20x25
12-20x20
108.30
12-20x25
24-20x20

200

73.30
12-20x24
12-20x20

800
.03
.03
.16

900
.03
.04
.20

1000
.04
.05
.25

1100
.05
.05
.30

1200
.06
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

700
.07
.06

800
.09
.08

900
.11
.10

1000
.13
.13

1100
.16
.15

1200
.19
.18

1600
1800
2000
.56
.71
.87
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.06

2400
1.26

2600
1.48

2800
1.71

3000
1.97

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

-37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 66-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Drive
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
32815
33 FC
6/760

B
32815
36 1/2 AF
8/1413

C
32815
33 AF
8/1562

2 7/16
1 7/16
2 7/16
11.69
10-60

2 7/16
1 7/16
3 15/16
16.54
15-75

215/100
310/180

113/27
256/63

Fan Type

P
32815
52 7/8 AF
6/968

Q
32815
40 1/4 Q-Fan
6/1636

R
32815
44 1/2 Q-Fan
6/1352

2 7/16
1 7/16
3 15/16
13.51
20-75

2 7/16
1 7/16
2 7/16

7 1/2-50

1 11/16
1 11/16
1 11/16
10.09
1 1/2-40

1 15/16
1 15/16
1 15/16
12.33
2-50

84/20
189/46

217.0
289.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity. For plug fans torques shown at 4.0" WC and at Max. RPM and BHP.

61

Unit
Sizes
Table 80-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full

Area (Ft2)
78.75

Qty-Size
2-45x 126

76.13

Modified

60.38

1-24x126
1-30x126
1-33x126
2-18x126
1-33x126

Table 80-2 Coil Availability


Module Size
Small
Medium
Medium Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-3 Row
1-6 Row
1-8 Row

Table 80-3 1/2" Unit Coil Water


Connection - Sizes (inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
2-45
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting..

Size 80

Sections
Filter/ Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank/ Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
54
96
19
48
14.5
29.5
54
29.5
14.5
19
29.5
54
14.5
19
29.5
14.5
19
19
92
92
54
54
56.4
38.2
56.4
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

62

Weight (lbs.)
1511
2382
506
1386
477
839
1163
798
262
319
491
870
1040
2143
3884
786
852
852
4822
4649
5497
4822
4649
1029
769
273
414
183
887

Unit
Sizes
Table 80-4 Unit Pressure Drops (Inches WG)
Ultra Low Leak Dampers
Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
40.90
19.26
44.90

400
.01
.01
.04

Exhaust or Economizer Return Dampers

Area (ft2)
19.2

600
6.02

Bypass Area

Area (ft2)
61.29
79.20
Area (ft2)
16.91

400
.02
.02
1400
.43

Accessories
Moisture-Eliminator
Diffuser

Area (ft2)
78.75
78.75

400
.01
.53

Inlet Hoods
Inlet Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

Internal Face and Bypass*


Face Area
Face Damper

22.65
48.65

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eft.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

Area (ft2)
28.86

1000
.07

Area (ft2)
83.10
4-16x25
8-16x20
6-20x25
12-20x20
137.50
30-20x25
12-16x25

200

80.70
6-20x24
6-20x20
6-24x24
6-24x20

Size 80

Damper Face Velocity (FPM)


500
600
700
.01
.01
.02
.01
.02
.02
.06
.09
.12

800
.03
.03
.16

900
.03
.04
.20

1000
.04
.05
.25

1100
.05
.05
.30

1200
.06
.06
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

500
600
700
.03
.05
.06
.03
.04
.06
1600
1800
2000
.56
.71
.87
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

800
.08
.08
2200
1.06

900
.10
.10
2400
1.26

1000
.13
.12
2600
1.48

1100
.15
.15
2800
1.71

1200
.18
.18
3000
1.97

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
.52

400

450

500

550

600

800
.03

1000
.05

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.56
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 80-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
39375
40 1/4 AF
5/996

B
39375
36 1/2 AF
8/1413

Fan Type
C
39375
33 AF
8/1562

P
39375
58 1/2 AF
6/875

Q
39375
44 1/2 Q-Fan
6/1485

2 3/16
1 7/16
3 7/16
20.14
15-50

2 7/16
1 7/16
3 15/16
16.54
20-75

2 7/16
1 7/16
3 15/16
13.51
20-75

2 11/16
1 7/16
2 11/16
7 1/2-60

1 15/16
1 15/16
1 15/16
12.33
2-50

100/62
216/140

113/27
256/63

84/20
189/46

262.0
361.0

Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.
For plug fans torques at shown 4.0" WC and at Max. RPM and BHP.

63

Unit
Sizes
Table 100-1 Coil Data
1/2" Unit Coils
UW,UU,UF
Shipping Coils
Full
Modified

Area (Ft2)
100.40

Qty-Size
2-51x141

96.94
76.38

3-33x141
2-24x141
1-30x141

Table 100-2 Coil Availability


Module Size
Small
Medium
Medium Large

1/2" Unit Coils


2 Row
2-8 Row
-

Shipping
Coils
1-3 Row
1-6 Row
1-8 Row

Table 100-3 1/2" Unit Coil Water


Connection - Sizes (Inches)
Header Height
Supply
Return
Drain and Vent

UW/UU
2-51
2 1/2
2 1/2
3/8

Shipping coil connections are located on page 71.


See pages 71-80 for refrigerant coil connections and
circuiting.

Size 100

Sections
Filter / Mixing
Economizer
Exhaust
Air Blender
Flat Filter
Angled Filter
Bag Filter
Cartridge Filter
Small Blank / Inspection
Medium Blank/ Access
Medium Large Blank/ Access
Large Blank/ Access
Small Coil
Medium Coil
Medium Large Coil
Large Coil
Moisture Eliminator
Internal Face / Bypass
Face Damper
Front Horizontal Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Q Fan (Q)
Q Fan (R)
Bottom Vertical Discharge Fan
FC Fan
BI / AF Fan
Plenum Fan
Diffuser
Discharge Plenum
Side Inlet Hood
Back Inlet Hood
Exhaust Hood
Unit End Panels

Length (inches)
60
96
19
58.5
14.5
29.5
60
29.5
14.5
19
29.5
60
14.5
19
29.5
14.5
19
19
96
96
60
60
67.2
41.2
67.2
6

1. Access module weights include one access door.


2. Fan module weights include largest ODP motor without IGV.
3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.

All dimensions are in inches.

64

Weight (lbs.)
1817
2984
572
1640
546
964
1414
911
288
350
538
1056
1237
2608
4738
928
1002
1002
5628
5585
5628
5585
1257
928
352
505
242
1051

Unit
Sizes
Table 100-4 Unit Pressure Drops (Inches WG)

Size 100

Damper Face Velocity (FPM)


500
600
700
.01
.01
.02
.00
.00
.00
.06
.09
.12

Ultra Low Leak Dampers


Back or Bottom Damper
Side Damper (each)
Protective Grate

Area (ft2)
51.40
23.88
56.10

400
.01
.00
.04

Exhaust or Economizer Return Dampers

Area (ft2)
23.88

600
.02

800
.03

1000
.05

Internal Face and Bypass*


Face Area
Face Damper

Area (ft2)
76.64
99.90

400
.02
.02

500
.03
.03

600
.04
.04

Bypass Area

Area (ft2)
18.96

1400
.42

Accessories
Moisture Eliminator
Diffuser

Area (ft2)
100.40
100.40

400
.01
.53

Inlet Hoods
Inlet-Hood w/ Moisture Eliminator
Side Inlet Hood
Back Inlet Hood

Area (ft2)

300
.04

27.57
60.16

Air Blenders
Filters**
Flat Filters
2" Throwaway
2" Pleated Media
4" Pleated Media
Permanent
Angled Filters
2" Throwaway
2" Pleated Media
Permanent
Cartridge/Bag Filters*
6" Cartridge - 65% Eff.
6" Cartridge - 85% Eff.
6" Cartridge - 95% Eff.
12" Cartridge - 65% Eff.
12" Cartridge - 85% Eff.
12" Cartridge - 95% Eff.
Bag - 65% Eff.
Bag - 85% Eff.
Bag - 95% Eff.

Area (ft2)
37.70

1000
.07

Area (ft2)
104.70
20-16x25
4-16x20
10-20x25
2-20x20
161.10
40-20x25
8-20x20

200

106.90
8-20x24
20-20x20
5-24x20
2-24x24

800
.02
.00
.16

900
.03
.00
.20

1000
.03
.00
.25

1100
.04
.00
.30

1200
.05
.00
.36

1200
.06

1400
.09

1600
.11

1800
.14

2000
.18

2100
.19

700
.06
.06

800
.08
.07

900
.10
.09

1000
.12
.12

1100
.15
.14

1200
.17
.17

1600
1800
2000
.55
.70
.87
Accessory Face Velocity (FPM)
450
500
550
.01
.02
.03
.67
.83
1.00
Inlet Hood Face Velocity (FPM)
400
500
600
.06
.10
.15

2200
1.05

2400
1.25

2600
1.46

2800
1.70

3000
1.95

600
.03
1.19

650
.03
1.40

700
.04
1.62

750
.04
1.86

800
.05
2.12

700
.20

800
.26

850
.29

900
.33

950
.36

1800
.24

2000
.30

2200
.37

2400
.44

2600
-.52

400

450

500

550

600

Face Velocity (FPM)


1200
1400
1600
.10
.14
.18
Filter Face Velocity (FPM)
250
300
350

.27
.52
.52
.51

.29
.54
.53
.51

.30
.55
.54
.52

.32
.57
.56
.52

.34
.59
.57
.53

.37
.62
.59
.53

.39
.64
.61
.54

.67
.64
.55

.70
.66
.56

.27
.52
.51

.29
.54
.51

.30
.55
.52

.32
.57
.52

.34
.59
.53

.37
.62
.53

.39
.64
.54

.67
.55

.70
.56

.56
.61
.63
.79
.80
.81
.53
.54
.55

.58
.65
.68
.82
.82
.84
.55
.57
.59

.84
.85
.87
.57
.59
.62

.88
.89
.92
.60
.63
.67

.91
.93
.97
.63
.66
.72

.96
.98
1.03
.66
.71
.78

1.00
1.03
1.09
.70
.75
.84

1.06
1.09
1.16
.74
.81
.91

1.11
1.15
1.24
.79
.86
.99

**Filter pressure drops are based on mid-life data.


Do not exceed maximum filter face velocities shown.
Actual pressure drops may be less than shown due to variations in filter brands.
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local Trane engineer.
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.

Table 100-5 Fan Data


Design CFM
Size/Type
Max TSP/RPM
Bearing Size
Drive Side
Opposite Drive Side
Shaft Size
Outlet Area (Ft2)
Motor HP Range
IGV Torque (Inch-Lb.)
2000 FPM (4.0" WC)
3000 FPM (Max. RPM and BHP)

A
50200
44 1/2 AF
5/901

Fan Type
B
50200
40 1/4 AF
8/1281

C
50200
36 1/2 AF
8/1413

P
50200
64 3/4 AF
6/791

2 7/16
1 7/16
3 7/16
24.62
15-60

2 15/16
1 7/16
1 7/16
20.14
25-100

2 15/16
1 7/16
4 1/2
16.54
30-100

2 15/16
1 11/16
2 15/16
10-75

124/80
278/181

100/62
216/140

113/27
256/63

330.0
446.0

Torques are shown for open/closed operation at 2000 and 3000 FPM fan outlet velocity.
For plug fans torques shown at 4.0 WC and at Max. RPM and BHP.

65

General
Data
T-Series External Piping Cabinet
Table G-1 lists the T-Series external
piping cabinet sizes by unit size, and
cabinet depth, and Table G-2 lists
external cabinet weights. If external
cabinets are ordered on contiguous
modules, on the same side of the unit
(I.E. small coil module, medium access
module, medium coil module, with
external cabinets on the RH side on
each module), then the external cabinet
must be the same depth on each
module. External cabinets are available
as an option on coil, access, face and
bypass, and eliminator modules.

In addition, if a module is ordered with


an access door and an external cabinet,
the module access door cannot be on
the same side of the unit as the
external cabinet.
Space inside the piping cabinets may
limit the ability to house control valves,
balancing valves, etc., along with coil
piping. The actual required space
needs to be verified when configuring
a unit.

Table G-1 External Cabinet Length and Width


Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Small
11
11
11
11
11
11
11
11
11
11
11
11
14
14
14
14

Module Size/Cabinet Length (inches)


Medium
Medium-Large
15
NA
15
NA
15
NA
15
24
15
24
15
24
15
24
15
24
15
24
15
24
16
31
16
31
19
31
19
29
19
29
19
29

Table G-2 External Cabinet Weights (lbs.)


Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Reduced
63
67
72
77
82
85
91
99
108
108
131
131
162
184
210
231

Small
Standard
94
99
107
113
122
126
134
145
157
157
188
188
237
270
307
338

Extended
125
132
142
150
161
166
177
191
207
207
246
246
312
355
404
444

Reduced
71
75
81
86
92
95
101
109
119
119
145
145
186
210
239
263

Medium
Standard
104
109
117
124
133
137
146
157
170
170
205
205
264
299
339
373

Large
24
27
31
34
34
34
34
34
40
40
48
48
48
49
54
60

Extended
136
143
154
162
173
179
190
204
221
221
264
264
342
388
439
482

66

Reduced
15
15
15
15
15
15
15
15
15
15
16
16
19
19
19
19

Reduced

112
120
124
132
141
154
154
193
193
230
257
292
322

Cabinet Depth (inches)


Standard
Extended
31
46
31
46
31
46
31
46
31
46
31
46
31
46
31
46
31
46
31
46
32
48
32
48
38
52
38
52
38
52
38
52

Medium-Large
Standard Extended
- Not Available - Not Available - Not Available 154
195
164
208
169
214
180
227
192
242
208
262
208
262
258
322
258
322
313
396
351
445
398
503
437
551

Reduced
88
98
112
128
136
141
149
159
185
185
231
231
273
307
362
417

Large
Standard
124
136
153
172
183
189
200
213
244
244
302
302
363
409
477
543

Extended
159
174
195
217
230
237
250
267
304
304
372
372
453
510
591
670

General
Data
T-Series Perforated Double Wall
Weight Add
Table G-3 lists the additional weight
that should be added to a T-Series
discharge plenum module, when 2
perforated double wall is included.
Discharge plenum weights can be
found in the T-Series quick select chart.
Module floor, access door(s)
(if ordered), or side discharge wall(s)
(if ordered) are not covered with a 2
perforated liner.
Table G-3 T-Series Perforated Double Wall Weight Add
Unit Size
Perforated Weight Add (lbs.)

3
39

6
46

8
53

10
63

12
74

14
86

17
101

21
119

Unit Size
Perforated Weight Add (lbs.)

25
139

30
163

35
191

40
224

50
262

66
308

80
361

100
423

T-Series Curb Weight


The 14 standard curb for a T-Series
unit weighs 10 lbs per linear foot. To
calculate the total curb weight, add the
unit length and width, multiply by two,
and then multiply by 10 lbs, or use the
table below to calculate the curb
weight.
Table G-4 Curb Weights
Unit Size
Curb End Weight (lbs)
Curb Size Weight

3
61.6

6
8
10
12
14
17
21
83.3
90
110
116.6
123.3 133.28 136.6
Take total unit length in inches, and multiply by 1.67 lbs and
add to the above curb end weight

Unit Size
Curb End Weight (lbs)
Curb Size Weight

25
139.9

30
35
40
50
66
80
100
161.6
169.9
191.6
209.9
234.9
234.9 259.9
Take total unit length in inches, and multiply by 1.67 lbs and
add to the above curb end weight

Example Size #21 T-Series unit with mixing module, small coil module, medium access module, medium coil module,
and fan module (down discharge), total unit length is 166. Total curb weight would be 413.8 lbs ((166 x 1.67) + 136.6).

67

General
Data
T-Series Traq Damper Sizes and
Quantities
Table G-5 lists sizes and quantities of
back and side Traq dampers by unit
size. Back Traq dampers are available
only on mixing modules. Side Traq
damper(s) are available on mixing
modules, and in the 2nd outside air
damper location in an economizer
module. Traq dampers cannot be
ordered in both the side and back
damper position of a mixing module,
or in the bottom damper position of a
mixing module. Traq dampers are not
available in the 1st outside air damper
position, the return air damper
position, or in the exhaust air damper
position of an economizer module.
Table G-5 T-Series Traq Damper Sizes and Quantities
Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Back Traq Dampers


Diameter()
Quantity
13
1
13
2
13
2
13
3
16
3
16
3
16
3
20
2
24
2
20
3
24
3
24
3
28
3
28
4
28
5
28
6

68

Side Traq Dampers (per side)


Diameter()
Quantity
13
1
13
1
13
1
16
1
16
1
16
1
13
2
13
2
16
2
16
2
20
2
28
1
20
2
24
2
28
2
24
3

General
Data
T-Series Traq Damper Air Pressure
Drops
Table G-6 is to be used for calculation
of Traq damper pressure drops, when
located in the back position of a mixing
module. Table G-7 is to be used for
calculation of Traq damper pressure
drops, when located in the side(s) of a
mixing module, or in the 2nd outside air
damper location in an economizer
module.
Table G-6 Back Traq Damper Area and Pressure Drop
Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Damper
Area (Ft2)
.9
1.8
1.8
2.7
4.1
4.1
4.1
4.3
6.2
6.5
9.4
9.4
12.8
12.6
17.1
18.8

800
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04

900
.05
.05
.05
.05
.05
.05
.06
.05
.05
.04
.05
.05
.05
.05
.05
.05

1000
.07
.06
.07
.07
.06
.06
.07
.06
.06
.06
.06
.07
.07
.06
.06
.07

1100
.08
.07
.08
.08
.07
.07
.08
.07
.08
.07
.07
.08
.08
.07
.07
.08

1200
.09
.08
.10
.09
.08
.09
.10
.08
.09
.08
.09
.10
.10
.08
.08
.10

1300
.11
.10
.11
.11
.10
.10
.12
.10
.11
.09
.10
.11
.11
.10
.10
.11

Air Velocity through Damper


1400
.13
.11
.13
.13
.11
.12
.13
.12
.13
.11
.12
.13
.13
.12
.12
.13

1500
.15
.13
.15
.15
.13
.14
.15
.13
.15
.12
.14
.15
.15
.13
.13
.15

1600
.17
.15
.17
.17
.15
.16
.18
.15
.17
.14
.16
.17
.17
.15
.15
.17

1700
.19
.17
.20
.19
.16
.18
.20
.17
.19
.16
.18
.19
.19
.17
.17
.19

1800
.21
.19
.22
.21
.18
.20
.22
.19
.21
.18
.20
.22
.21
.19
.19
.22

1900
.25
.21
.24
.24
.21
.22
.25
.21
.23
.20
.22
.24
.24
.21
.21
.24

2000
.26
.23
.27
.26
.23
.25
.28
.24
.26
.22
.25
.27
.26
.24
.24
.27

2100
.29
.26
.30
.29
.25
.27
.30
.26
.29
.24
.27
.29
.29
.26
.26
.29

2200
.31

2300
.34

.33
.32
.27
.30
.33
.29
.32
.26
.29
.31
.32
.29
.29
.31

.36
.35
.30
.32
.35
.32
.35
.29
.32
.34
.35
.32
.32
.34

1900
.24
.24
.24
.24
.24
.24
.21
.21
.21
.21
.21
.21
.21
.21
.21
.24

2000
.26
.26
.26
.26
.26
.26
.23
.23
.24
.24
.24
.24
.24
.24
.24
.27

2100

2200

.29
.29
.29
.29
.29
.26
.26
.26
.26
.26
.26
.26
.26
.26
.29

2300
*

.32
.32
.32
.32
.29
.29
.28
.28
.29
.29
.29
.29
.29
.31

.35

2400
.36

2500
.39

.39
.38

*
.41

.35
.38
.35
.38
.32
.35
.37
.38
.35
.35
.37

.38
.41
.38
.41
.34
.38
.41
.41
.38
.38
.40

* - Exceeds maximum inlet hood velocity

Table G-7 Side Traq Damper Area and Pressure Drop


Unit
Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Damper
Area (Ft2)
.92
.92
.92
1.40
1.40
1.40
1.85
1.85
2.79
2.79
4.36
4.28
4.36
6.28
8.56
9.42

800
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04
.04

900
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05
.05

1000
.07
.07
.07
.07
.07
.07
.06
.06
.06
.06
.06
.06
.06
.06
.06
.07

1100
.08
.08
.08
.08
.08
.08
.07
.07
.07
.07
.07
.07
.07
.07
.07
.08

1200
.09
.09
.09
.09
.09
.09
.08
.08
.08
.08
.08
.08
.08
.08
.08
.10

1300
.11
.11
.11
.11
.11
.11
.10
.10
.10
.10
.10
.10
.10
.10
.10
.11

Air Velocity through Damper


1400
.13
.13
.13
.13
.13
.13
.11
.11
.12
.12
.12
.12
.12
.12
.12
.13

1500
.15
.15
.15
.15
.15
.15
.13
.13
.13
.13
.13
.13
.13
.13
.13
.15

1600
.17
.17
.17
.17
.17
.17
.15
.15
.15
.15
.15
.15
.15
.15
.15
.17

1700
.19
.19
.19
.19
.19
.19
.17
.17
.17
.17
.17
.17
.17
.17
.17
.19

1800
.21
.21
.21
.21
.21
.21
.19
.19
.19
.19
.19
.19
.19
.19
.19
.22

.35
.35
.32
.32
.31
.31
.32
.32
.32
.32
.34

2400

2500

.38
*
.38
.38
.35
.35
.34
.34
*
.35
.35
.35
.35
.37

.41
.41
.41
.38
.38
*
.37
.39
.39
.38
.38
.40

* - Exceeds maximum inlet hood velocity


Note
Damper area and velocity are per each side on a mixing module with side Traq dampers, or the area and velocity through the 2nd outside air damper position on an economizer module.

69

General
Data
T-Series VFD Input Line Current Requirements
Table G-8 addresses the input line current requirements for a T-Series factory
mounted VFD. The line current is for each VFD on the unit.
Table G-8 T-Series VFD Line Input Requirements
Motor Horsepower
1
1
2
3
5
7
10
15
20
25
30
40
50
60
75
100
For units with controls, add the
following to the supply fan VFD

200
6.3
10.9
10.9
14.8
22.3
31.1
39.4
55.6
70.8
85.2
97.7
124.7

Voltage
230
5.8
9.2
9.2
12.4
18.7
26.2
33.2
46.9
60.0
81.2
81.2
102.4
123.0

1.8

460
2.9
4.9
4.9
6.7
10.0
14.1
17.8
25.0
32.1
38.9
44.2
57.3
68.5
86.6
106.2
138.2
.9

Typical T-Series VFD Layout


1. Drive
2. Keypad
3. Key operated drive-off or
drive-off-bypass(a) switch
4. Terminal strip
5. Transformer 100va(a),
500va(b), or 2Kva (C)
6. Main disconnect switch(C)
7. Drive disconnect switch
8. Electronic overload(a)
9. Drive fuses
10. Bypass contactors(a)
(a) - only when ordered with
bypass
(b) - only when ordered with
controls
(c) - future option

70

General
Data
Table G-9 Shipping Coil Water and Steam Connection Sizes
Coil Type
W,WA
W
D,DD,WD,K
P2
P4
P8
WC
WC
WC
NS
NS
NS

Header Height
18,24,30,33
42,48,54
18,24,30,33
18,24,30
18,24,30
18,24,30
18
24
30,33
18
24
30,33

Supply
2 1/2
2 1/2
2 1/2
3/4
1
1 1/4
1
1 1/4
2 1/2
2
2 1/2
3

Return
2 1/2
2 1/2
2 1/2
3/4
1
1 1/4
1
1 1/4
1 1/2
1
1 1/4
1 1/4

Drain/Vent
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1
1 1/4
1 1/4

All fittings have female threads.


Table G-10 5/8 Type F Refrigerant Coil Connections (Inches)
Header
Height
18

24

30

33

Circuiting
Full
Half
Quarter
Eighth
Sixteenth
Full
Half
Quarter
Eighth
Full
Half
Quarter
Eighth
Sixteenth
Full
Half
Quarter
Eighth

No. of
Circuiting
12
6
3
2
1
16
8
4
2
20
10
5
4
2
22
11
7
3

Same end connections only.


1. 6-circuit connection is 1 1/8-inches, 5-circuit is 7/8 inches.

71

1 Distributor
Liquid
Suction
1 3/8
2 1/8
1 1/8
2 1/8
7/8
1 5/8
7/8
1 3/8
5/8
5/8
N/A
N/A
1 1/8
2 1/8
7/8
1 5/8
7/8
1 3/8
N/A
N/A
1 3/8
2 1/8
7/8
2 1/8
7/8
1 5/8
7/8
1 3/8
N/A
N/A
1 3/8
2 1/8
1 1/8
2 1/8
7/8
1 5/8

2 Distributors
Liquid
Suction
1 1/8
2 1/8
7/8
1 5/8
N/A
N/A
5/8
5/8
N/A
N/A
1 1/8
2 1/8
7/8
1 3/8
7/8
1 3/8
5/8
5/8
1 3/8
2 1/8
7/8
2 1/8
N/A
N/A
7/8
1 3/8
5/8
5/8
1 3/8
2 1/8
Note 1
2 1/8
7/8
1 5/8
N/A
N/A

General
Data
Table G-11 UF Refrigerant Coil Connections (Inches)
Unit
Size
3

Header
Height
21

Rows
4,6,8
4,6
4

23

4,6,8
4,6
4

8,10

27

4,6,8
4,6
4

12

32

4,6,8
4,6
4

14

35

4,6,8
4,6

17

37

4,6,8
4,6

21

45

4,6,8
4,6

25,30

51

4,6,8
4,6

Dist.
Tube
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16

No.
Circuits
16
16
8
8
4
4
18
18
9
9
4
4
21
21
10
10
5
5
25
25
12
12
6
6
27
27
13
13
29
29
14
14
35
35
17
17
40
40
20
20

1 Distributors
Liquid
Suction

Circuiting
Full
Half
Qtr.
Full
Half
Qtr.
Full
Half
Qtr.
Full
Half
Qtr.
Full
Half
Full
Half
Full
Half
Full
Half

Notes:
Number of connections Size (Inches)
1. 1- 5/8, 1- 7/8
2. 1-1 1/8 and 1-1 3/8
3. 3-1 3/8 and 1-1 5/8
4. 3 7/8 and 1-1 1/8
5. 3 5/8 and 1 7/8

72

1 1/8
1 1/8
7/8
5/8

1 5/8
1 5/8
1 3/8
1 3/8

1 1/8
1 1/8
7/8
5/8

1 5/8
1 5/8
1 3/8
1 3/8

1 1/8
1 1/8
7/8
7/8

1 5/8
1 5/8
1 3/8
1 3/8

1 3/8
1 1/8
1 1/8
7/8

1 5/8
1 5/8
1 5/8
1 3/8

1 3/8
1 1/8

1 5/8
1 5/8

2 Distributors
Liquid
Suction
1 1/8
1 5/8
1 1/8
1 5/8
7/8
1 3/8
5/8
1 3/8
7/8
1 3/8
5/8
1 3/8
1 1/8
1 5/8
1 1/8
1 5/8
7/8
1 3/8
Note 1
1 3/8
7/8
1 3/8
5/8
1 3/8
Note 2
1 5/8
1 1/8
1 5/8
7/8
1 3/8
7/8
1 3/8
7/8
1 3/8
5/8
1 3/8
1 3/8
1 5/8
1 1/8
1 5/8
1 1/8
1 3/8
7/8
1 3/8
7/8
1 3/8
5/8
1 3/8
1 3/8
1 5/8
1 1/8
1 5/8
1 1/8
1 3/8
7/8
1 3/8
1 1/8
7/8

1 3/8
1 3/8

1 1/8
1 1/8

1 5/8
1 5/8

1 1/8
1 1/8

1 5/8
1 5/8

4 Distributors
Liquid
Suction

1 1/8
Note 4

Note 3
Note 3

1 1/8
1 1/8
7/8
Note 5
1 1/8
1 1/8
7/8
7/8

1 5/8
1 5/8
1 3/8
1 3/8
1 5/8
1 5/8
1 3/8
1 3/8

General
Data
Table G-12 UF Refrigerant Coil Connections (Inches)
Unit
Size
35,40

Header
Height
57

Rows
4,6,8
4,6

50

2-32

4,6,8
4,6
4

66

2-37

4,6,8
4

80

2-45

4,6,8
4

100

2-51

4,6,8
4,6

Dist.
Tube
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16
1/4
3/16

No.
Circuits
45
45
22
22
50
50
24
24
12
12
58
58
29
29
70
70
35
35
80
80
40
40

2 Distributors
Liquid
Suction

Circuiting
Full
Half
Full
Half
Qtr.
Full
Half
Full
Half
Full
Half

Notes:
Number of connections Size (Inches):
1. 2 7/8, 2-1 1/8
2. 6-1 3/8 and 2-1 5/8

73

1 3/8
1 1/8

1 5/8
1 5/8

1 3/8
1 1/8
1 1/8
1 1/8

1 5/8
1 5/8
1 3/8
1 3/8

4 Distributors
Liquid
Suction
1 3/8
1 5/8
1 1/8
1 5/8
Note 1
1 3/8
7/8
1 3/8
1 3/8
1 5/8
1 1/8
1 5/8
1 1/8
1 3/8
7/8
1 3/8
7/8
1 3/8
5/8
1 3/8
1 1/8
7/8

1 3/8
1 3/8

1 1/8
1 1/8

1 5/8
1 5/8

1 1/8
1 1/8

1 5/8
1 5/8

8 Distributors
Liquid
Suction

1 1/8
Note 3

Note 2
Note 2

1 1/8
1 1/8
7/8
Note 4
1 1/8
1 1/8
7/8
7/8

1 5/8
1 5/8
1 3/8
1 3/8
1 5/8
1 5/8
1 3/8
1 3/8

General
Data
Coil Circuiting
Standard circuiting on Type UF coils
means that the number of distributors
is minimized. In the cases where more
than one distributor is required, the coil
is horizontally split (so as the coil is
unloaded, sections of the face of the
coil are de-energized).
Intertwined circuiting means that each
distributor feeds alternating tubes
along the whole face of the coil.

Table G-13 Type UF Coil Circuiting


Unit
Size
3
6
8,10
12
14
17
21
25,30
35,40
50
66
80
100

Coil
Rows
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8
4
6
8

Dist.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3/1
3/1
3/1
1/3
1/3
1/3
4
4
4
3/1
3/1
3/1
2/2
2/2
2/2
6/2
6/2
6/2
2/6
2/6
2/6
8
8
8

Full
A

Cir/Dist.
8
8
8
9
9
9
10/11
10/11
10/11
12/13
12/13
12/13
13/14
13/14
13/14
7/8
7/8
7/8
8/9
8/9
8/9
10
10
10
11/12
11/12
11/12
12/13
12/13
12/13
7/8
7/8
7/8
8/9
8/9
8/9
10
10
10

This results in the full face of the coil


(half for sizes 17 to 40) remaining
energized under part-load conditions.
The terms Full, Half and Quarter
refer to the number of tubes in a coil
row which are fed refrigerant: Full - all
the tubes, Half- half, etc. The refrigerant
in a half-circuited coil makes twice as
many passes through the coil as the
refrigerant in a full circuited coil. The
notation 3/1 for distributor and

STANDARD
Half
B
Dist.
Cir/Dist.
1
8
1
8

Quarter
C
Dist.
Cir/Dist.
1
4

1
1

9
9

1
2

4
9

1
1

10
10

1
1

12
12

1
1

13
13

2
2

7
7

2
2

8/9
8/9

2
2

10
10

2
2

11
11

2
2

12
12

4
4

7
7

2/2
2/2

8/9
8/9

4
4

10
10

74

Dist.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3/1
3/1
3/1
1/3
1/3
1/3
4
4
4
3/1
3/1
3/1
2/2
2/2
2/2
6/2
6/2
6/2
2/6
2/6
2/6
8
8
8

Full
A

Cir/Dist.
8
8
8
9
4/5
9
10/11
10/11
10/11
12/13
12/13
12/13
13/14
13/14
13/14
7/8
7/8
7/8
8/9
8/9
8/9
10
10
10
11/12
11/12
11/12
12/13
12/13
12/13
7/8
7/8
7/8
8/9
8/9
8/9
10
10
10

11/12 for circuits per distributor


means that 3 distributors feed 11
circuits each, and that 1 distributor
feeds 12 circuits. All coil circuiting
tables follow this convention. The
circuiting presented here is by unit size.
Unit sizes 50 to 100 have two stacked
Type UF coils.

INTERTWINED
Half
B
Dist.
Cir/Dist.
2
4
2
4

Quarter
C
Dist.
Cir/Dist.
2
2

4/5

2
2

5
5

2/3

2
2

6
6

2
2

6/7
6/7

2
2

7
7

3/1
3/1

4/5
4/5

4
4

5
5

2/2
2/2

5/6
5/6

4
4

6
6

4
4

7
7

6/2
6/2

4/5
4/5

8
8

5
5

General
Data
Table G-14 Type F Coil Circuiting Full
Unit
Size
3,6

Header
Height
18

8,10

24

12,14

30

17

33

21

2-18

25,30

1-18
1-24
1-18
1-33

35,40
50
66
80
100

1-30
1-33
3-24
1-24
1-30
1-33
3-33

Coil
Rows
2,3
4
6,8
2,3,4
6,8
2
3,4
6,8
2,3
4,6
8
2,3
4
6,8
2,3,4
6,8
2,3
4,6
8
2,3
4,6
8
2,3,4
6,8
2,3
4,6
8
2,3
4,6
8

Dist.
1
1
1
2
2
2
2
2
2
2
2
2
2
2
1/2
1/2
1/2
1/2
1/2
2/2
2/2
2/2
6
6
2/2/2
2/2/2
2/2/2
6
6
6

Full
A

Cir/Dist.
12
12
12
8
8
10
10
10
11
11
11
12
12
12
12/8
12/8
12/11
12/11
12/11
10/11
10/11
10/11
8
8
8/10/11
8/10/11
8/10/11
11
11
11

Half
B
Dist.
Cir/Dist.
1
6
1
6
1
6
1
8
1
8
1
10
1
10
1
10
1
11
1
11
1
11
2
6
2
6
2
6
2
6/8
2
6/8
2
6/11
2
6/11
2
6/11
2
10/11
2
10/11
2
10/11
3
8
3
8
3
8/10/11
3
8/10/11
3
8/10/11
3
11
3
11
3
11

STANDARD
Quarter
C
Dist.
Cir/Dist.
1
3
1
3
1
3
1
4
1
4
1
5
1
5

Eighth
D
Dist.
Cir/Dist.
1
2
1
2
1

1
1

4
4

1
1

7
7

2
2
2
2
2
2
2

3
3
3
3/4
3/4
3/7
3/7

2
2

2
2

2
2

5/7
5/7

4/3

3
3
3
3

4
4
4/5/7
4/5/7

2/4/3

3
3

7
7

The notation 1/2 for distributor and 12/8 for circuits per distributor means that 1 distributor feeds 12 circuits and that 2 distributors feed 8 circuits each.

75

Sixteenth
E
Dist.
Cir/Dist.
1
1

General
Data
Table G-15 Type F Coil Circuiting Full
Unit
Size
3,6

Header
Height
18

8,10

24

12,14

30

17

33

21

2-18

25,30

1-18
1-24
1-18
1-33
1-30
1-33
3-24

35,40
50
66
80
100

1-24
1-30
1-33
3-33

Full
A

Half
B
Dist.
Cir/Dist.
2
3
2
3
2
4
2
4
2
5
2
5
2
5
2
5/6
2
5/6
4
3
4
3
2/2
3/4
2/2
3/4

HORIZONTAL SPLIT
Quarter
C
Dist.
Cir/Dist.

Coil
Rows
2,3,4
6,8
2,3,4
6,8
2
3,4
6,8
2,3,4,6
8
2,3,4
6,8
2,3,4
6,8

Dist.
2
2
2
2
2
2
2
2
2
4
4
2/2
2/2

2,3,4,6,8

2/2

6/11

2/1/1

3/5/6

2,3,4,6,8
2,3,4
6,8

2/2
6
6

10/11
8
8

3/1
6
6

5/6
4
4

6
6

2
2

2,3,4,6,8
2,3,4,6,8

2/2/2
6

8/10/11
11

2/3/1
3/3

4/5/6
5/6

3/3

3/4

Cir/Dist.
6
6
8
8
10
10
10
11
11
6
6
6/8
6/8

76

2
2

2
2

3/4

Eighth
D
Dist.
Cir/Dist.
2
1
2

2
2

2
2

Sixteenth
E
Dist.
Cir/Dist.

General
Data
Table G-16 Type F Coil Circuiting Full
Full
1/2
Unit
Hdr Coil
A
B
Size
Ht. Rows Dist. Cir/Dist. Dist. Cir/Dist.
3,6
18
4
2
12
2
6
6,8
2
12
2
6
8,10
24
4
4
8
2
8
6,8
4
8
2
8
12,14 30
4
4
10
2
10
6
4
10
2
10
8
4
10
2
10
17
33
4
4
11
2
11
6,8
4
11
2
11
21
2-18
4
4
12
4
6
6,8
4
12
4
6
25,30 1-18
4
2
12
2
6
1-24
4
8
2
8
6,8
2
12
2
6
4
8
2
8
35,40 1-18
4
2
12
2
6
1-33
4
11
2
11
6,8
2
12
2
6
4
11
2
11
50
1-30
4
4
10
2
10
1-33
4
11
2
11
6,8
4
10
2
10
4
11
2
11
66
3-24
4
12
8
6
8
6,8
12
8
6
8
80
1-24
4
4
8
2
8
1-30
4
10
2
10
1-33
4
11
2
11
6,8
4
8
2
8
4
10
2
10
4
11
2
11
100 3-33
4
12
11
6
11
6,8
12
11
6
11

Full- 1/2
A/B
Dist. Cir/Dist.
1/1
12/6
3

10

11

2/2

12/6

1/1
3

12/6
8

1/1
3

12/6
11

3
3

10
11

3
3
3

8
10
11

11

1/2-Full
B/A
Dist. Cir/Dist.
1/1

6/12

3
3

10
10

11

2/2

6/12

1/1
3

6/12
8

1/1
3

6/12
11

3
3

10
11

3
3
3

8
10
11

11

VERTICAL SPLIT
1/2- 1/4

77

1/4- 1/2

Dist. Cir/Dist. Dist. Cir/Dist.


1/1
6/3
1/1
3/6
1/1
8/4
1/1
4/8
1/1
10/5
1/1
5/10
1/1
5/10
1/1
11/7
1/1
7/11
2/2
6/3
2/2
3/6
1/1
6/3
1/1
8/4
1/1
3/6
1/1
4/8
1/1
6/3
1/1
11/7
1/1
3/6
1/1
7/11
1/1
10/5
1/1
11/7
1/1
5/10
1/1
7/11
3/3
8/4
3/3
4/8
1/1
8/4
1/1
10/5
1/1
11/7
1/1
4/8
1/1
5/10
1/1
7/11
3/3
11/7
3/3
7/11

1/4- 1/4
Dist. Cir/Dist.
2
3
2
3
2
4
2
4
2
5
2
5
2
5
2
7
2
7
4
3
4
3
2
3
2
4
2
3
2
4
2
3
2
7
2
3
2
7
2
5
2
7
2
5
2
7
6
4
6
4
2
4
2
5
2
7
2
4
2
5
2
7
6
7
6
7

1/4- 1/8
Dist. Cir/Dist.

1/1

5/4

1/8- 1/8
Dist. Cir/Dist.

2
2

4
4

General
Data
Table G-17 Type F Coil Circuiting Modified
Unit
Size
3,6

Header
Height
12

8,10

18

12,14

24

17

30

21

33

25,30,
35,40

2-18

50

2-24

66

1-24
1-33

80

2-18
1-33

100

2-24
1-30

Coil
Rows
2,3,4,6
8
2,3
4
6,8
2,3,4
6,8
2
3, 4
6, 8
2,3
4,6
8
2,3
4
6,8
2,3,4
6,8
2,3
4,6
8
2,3
4,6
8
2,3
4,6
8

Full
A
Dist.
Cir/Dist.
1
8
1
8
1
12
1
12
1
12
2
8
2
8
2
10
2
10
2
10
2
11
2
11
2
11
2
12
2
12
2
12
4
8
4
8
2/2
8/11
2/2
8/11
2/2
8/11
1/2
12/11
1/2
12/11
1/2
12/11
4/2
8/10
4/2
8/10
4/2
8/10

Half
B
Dist.
Cir/Dist.
1
4
1
4
1
6
1
6
1
6
1
8
1
8
1
10
1
10
1
10
1
11
1
11
1
11
2
6
2
6
2
6
2
8
2
8
2
8/11
2
8/11
2
8/11
1/2
6/11
1/2
6/11
1/2
6/11
2/1
8/10
2/1
8/10
2/1
8/10

STANDARD
Quarter
C
Dist.
Cir/Dist.
1
2
1
2
1
3
1
3
1
3
1
4
1
4
1
5
1
5

Eighth
D
Dist.
Cir/Dist.
1
1
1
1

2
2

1
1

4
4

1
1

7
7

2
2
2
2
2
2
2

3
3
3
4
4
4/7
4/7

2
2

2
2

2/3

1/2
1/2

3/7
3/7

1/2

2/3

2/1
2/1

4/5
4/5

2/1

2/4

The notation 2/2 for distributor and 8/11 for circuits per distributor means that 2 distributors feed 8 circuits each and that 2 distributors feed 11 circuits each.

78

Sixteenth
E
Dist. Cir/Dist.
1

General
Data
Table G-18 Type F Coil Circuiting Modified
Unit
Size
3,6
8,10

Header
Height
12
18

12,14

24

17

30

21

33

25,30
35,40
50

2-18

66

1-24
1-33
2-18
1-33
2-24
1-30

80
100

2-24

Coil
Rows
2,3,4,6,8
2,3,4
6,8
2,3,4
6,8
2
3,4
6,8
2,3,4,6
8
2,3,4
6,8
2,3,4
6,8
2,3,4,6
8
2,3,4,6,8
2,3
4,6,8

Full
A
Dist.
Cir/Dist.
2
4
2
6
2
6
2
8
2
8
2
10
2
10
2
10
2
11
2
11
4
6
4
6
4
8
4
8
2/2
8/11
2/2
8/11
4/2
4/2
4/2

6/11
8/10
8/10

Half
B
Dist.
Cir/Dist.
2
2
2
3
2
3
2
4
2
4
2
5
2
5
2
5
2
5/6
2
5/6
4
3
4
3
4
4
4
4
2/1/1
4/5/6
2/1/1
4/5/6
4/1/1
4/2
4/2

3/5/6
4/5
4/5

79

HORIZONTAL SPLIT
Quarter
C
Dist.
Cir/Dist.
2
1
2
1
2
2

2
2

3/4

4
4
2/1/1

2
2
2/3/4

Eighth
D
Dist.
Cir/Dist.

2
2

2
2

4/2

1/2

Sixteenth
E
Dist. Cir/Dist.

General
Data
Table G-19 Type F Coil Circuiting Modified
Full
1/2
Unit
Hdr Coil
A
B
Size
Ht. Rows Dist. Cir/Dist. Dist. Cir/Dist.
3,6
12
4
2
8
2
4
6,8
2
8
2
4
8,10
18
4
2
12
2
6
6,8
2
12
2
6
12,14 24
4
4
8
2
8
6,8
4
8
2
8
17
30
4
4
10
2
10
6
4
10
2
10
8
4
10
2
10
21
33
4
4
11
2
11
6,8
4
11
2
11
25,30 2-18
4
4
12
4
6
35,40
6,8
4
12
4
6
50
2-24
4
8
8
4
8
6,8
8
8
4
8
66
1-24
4
4
8
2
8
4
11
2
11
1-33 6,8
4
8
2
8
4
11
2
11
80
2-18
4
4
12
4
6
4
11
2
11
1-33 6,8
4
12
4
6
4
11
2
11
100
2-24
4
8
8
4
8
4
10
2
10
1-30 6,8
8
8
4
8
4
10
2
10

Full- 1/2
A/B
Dist. Cir/Dist.
1/1
8/4
1/1

12/6

10

11

2/2

12/6

3
3

8
11

2/2
3

12/6
11

6
3

8
10

1/2-Full
B/A
Dist. Cir/Dist.
1/1

4/8

1/1

6/12

3
3

10
10

11

2/2

6/12

3
3

8
11

2/2
3

6/12
11

6
3

8
10

VERTICAL SPLIT
1/2- 1/4

80

1/4- 1/2

Dist. Cir/Dist. Dist. Cir/Dist.


1/1
4/2
1/1
2/4
1/1
6/3
1/1
3/6
1/1
8/4
1/1
4/8
1/1
10/5
1/1
5/10
1/1
5/10
1/1
11/7
1/1
7/11
2/2
6/3
2/2
3/6
2/2
8/4
2/2
4/8
1/1
8/4
1/1
11/7
1/1
4/8
1/1
7/11
2/2
6/3
1/1
11/7
2/2
3/6
1/1
7/11
2/2
8/4
1/1
10/5
2/2
4/8
1/1
5/10

1/4- 1/4
Dist. Cir/Dist.
2
2
2
2
2
3
2
3
2
4
2
4
2
5
2
5
2
5
2
7
2
7
4
3
4
3
4
4
4
4
2
4
2
7
2
4
2
7
4
3
2
7
4
3
2
7
4
4
2
5
4
4
2
5

1/4- 1/8
Dist. Cir/Dist.

1/1

5/4

1/8- 1/8
Dist. Cir/Dist.

2
2

4
4

Jobsite
Connections
TSC Economizer

UNIT SIZE
L
W
3
49
31
6
49
44
8
49
48
10
60.5
60
12
60.5
64
14
60.5
68
17
60.5
74
21
60.5
76
25
60.5
78
30
72
91
35
72
96
40
84
109
50
84
120
66
96
135
80
96
135
100
96
150
All Dimensions are in Inches

81

H
28.75
31.25
35
38
42
44
48
52.5
58.75
58.75
68
68
80
92
107
119.5

C
17
17
17
22.75
22.75
22.75
22.75
22.75
22.75
28.50
28.50
34.25
34.25
40
40
40

WITH DAMPER
D
M
12
3.88
18
5.13
22
7.00
21
8.00
25
8.00
29
8.00
33
8.00
38
8.00
44
8.63
44
8.00
51
9.75
48
6.88
60
6.88
68
4.50
81
7.00
99
10.00

V
13.63
10.13
9.88
13.88
13.88
11.88
11.88
11.38
11.63
11.63
13.63
16.63
16.63
20.63
22.63
17.13

K
4
4
4
4
4
4
4
4
4
4
6
6
6
8
8
8

J
3.75
3.75
3.75
3.75
3.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
5
5
5
5

Jobsite
Connections
TSC Fan

Note: Motor location may be right or left; right hand shown.

UNIT SIZE
FAN SIZE
3A
9 1/2 FC
3B
9 1/2 FC
6A
12 1/4 FC
6B
10 1/2 FC
8A
13 1/2 FC
10A
15 FC
10B
13 1/2 FC
10C
13 1/2 BI
12A
16 1/2 FC
12B
15 FC
12C
15 BI
14A
18 1/4 FC
14B
16 1/2 FC
14C
16 1/2 BI
17A
20 FC
17B
18 1/4 FC
17C
18 1/4 BI
21A
22 3/8 FC
21B
20 FC
21C
20 BI
25A
25 FC
25B
22 3/8 FC
25C
22 1/4 BI
30A
25 FC
30B
22 3/8 FC
30C
22 1/4 BI
35A
27 5/8 FC
35B
25 FC
35C
24 1/2 AF
40A
30 1/4 FC
40B
27 5/8 FC
40C
27 AF
50A
33 FC
50B
30 1/4 FC
50C
30 AF
66A
33 FC
66B
36 1/2 FC
66C
33 AF
80A
40 1/4 AF
80B
36 1/2 AF
80C
33 AF
100A
44 1/2 AF
100B
40 1/4 AF
100C
36 1/2 AF
All Dimensions are in Inches

A
12
9.5
16.63
14.5
18.5
20.5
18.5
18.5
22.5
20.63
20.5
24.63
22.5
22.5
27.0
24.63
24.63
27.5
27.0
27.0
31.5
27.5
30.0
31.5
27.63
30.13
34.63
31.5
35.5
37.88
25.63
39
41.38
37.88
43.25
41.5
52.38
47.5
57.88
52.5
47.5
63.88
58
52.5

B
11.5
12.75
15.83
16.75
16.75
14.88
14.38
13.88
15.25
14.88
14
15.88
15.38
14.13
16.38
15.88
14.75
15.38
16.38
14.88
16.5
15.5
14.88
22
25.88
23.38
18.88
20.38
18.5
21.5
23.13
20
25.5
27.38
24.5
39.75
34.38
36.75
31.63
34.25
36.75
36
39
41.75

C
10.5
10.5
16.88
14.5
18.5
20.0
18.5
18.5
22.25
20.0
20.0
24.63
22.38
22.38
27.38
24.63
24.63
27.38
27.38
27.38
31.5
27.38
30.5
31.5
27.38
30.5
34.38
31.5
31.13
37.88
34.38
34.25
41.38
37.88
38.0
41.5
45
41.63
50.75
46.13
41.63
56
50.88
46.13

D
8.13
8.13
4.88
6.5
6
6.25
6.38
6.13
6.13
6.13
6.13
6.38
6.38
6.25
6.38
6.38
6.25
6.25
6.13
6.13
6.38
6.38
6.25
6.25
6.25
6.25
8.13
12
12
7.13
8.25
8.88
121
14
15
13.5
7.13
12.5
16.25
22.13
27.5
22.13
28.75
34.63

E
29.63
29.63
32.5
32.5
37
31.63
32.5
32.13
32.75
33
33.38
32.38
34.5
33.5
32.5
32.88
33.25
34.38
34.75
32.88
10
10.5
10.88
10
10.38
11
7.00
9.25
9.25
6.63
7.00
6.75
7
11.25
11.63
20.13
13.63
19.13
15.13
21.50
26
10.25
18.13
24.5

G
9.5
10.75
13.63
14.75
14.75
12.88
12.38
11.88
13.25
12.8
12.0
13.88
13.38
12.13
14.38
13.88
12.75
13.38
14.38
12.88
14.5
13.5
12.88
20.0
23.88
21.38
16.88
18.38
16.5
19.5
21.13
18
23.5
25.38
22.5
37.75
32.38
34.75
29.63
32.25
34.75
34
37
39.75

82

F
60.75
60.75
68.25
68.25
75
58.5
58.5
58.5
62.5
62.5
62.5
64.5
64.5
64.5
68.5
68.5
68.5
73
73
73
54.75
54.75
54.75
54.75
54.75
54.75
62
62
62
62
62
62
68.5
68.5
68.5
84
84
84
92
92
92
96
96
96

L
60.75
60.75
68.25
68.25
75
69.5
69.5
69.5
73.5
73.5
73.5
75.5
75.5
75.5
79.5
79.5
79.5
84
84
84
65.75
65.75
65.75
65.75
65.75
65.75
73.5
73.5
73.5
73.5
73.5
73.5
83
83
83
84
84
84
92
92
92
96
96
96

W
31
31
44
44
48
60
60
60
64
64
64
68
68
68
74
74
74
76
76
76
78
78
78
91
91
91
96
96
96
109
109
109
120
120
120
135
135
135
135
135
135
150
150
150

H
28.75
28.75
31.25
31.25
35
38
38
38
42
42
42
44
44
44
48
48
48
52.50
52.50
52.50
58.75
58.75
58.75
58.75
58.75
58.75
68
68
68
68
68
68
80
80
80
92
92
92
107
107
107
119.5
119.5
119.5

J
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
37.5
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
5
5
5
5
5
5
5
5
5
5
5
5

K
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
6
6
6
8
8
8
8
8
8
8
8
8

X
10.125
10.125
9.5
10.25
10.5
11.75
13.125
13.375
13.625
15.875
15.875
13
15.25
15.375
14.25
17
17.125
18.875
19
19
20.875
25
22
21
25.125
22
25.5
24.5
24.875
23
25.375
24.875
26.625
28.125
27
37
39.875
37.875
40
38.75
37.875
41.375
39.875
38.75

Jobsite
Connections
TSC Front Plenum

UNIT SIZE
A
B
3
12
11.5
6
16.63 15.69
8
18.5 15.75
10
20.56 14.81
12
22.44 15.25
14
24.63 15.88
17
27.06 16.38
21
27.56 15.38
25
31.44 16.44
30
31.5
22
35
34.63 18.81
40
37.88 21.5
50
41.41 25.5
66
41.44 38.75
80
57.81 30.63
100
63.88 35.13
All Dimensions are in Inches.

C
10.56
16.86
18.5
20
22.25
24.63
27.38
27.38
31.44
31.44
34.38
37.88
41.41
41.44
50.72
56.06

D
8.13
4.75
6.00
6.25
6.13
6.38
6.38
6.25
6.38
6.25
8.13
7.13
1.00
13.50
16.25
22.13

L
24.75
27.25
31
34
34
34
34
34
40
40
48
48
48
49
54
60

W
31
44
48
60
64
68
74
76
78
91
96
109
120
135
135
150

H
28.75
31.25
35
38
42
44
48
52.5
58.75
58.75
68
68
80
92
107
119.5

K
4
4
4
4
4
4
4
4
4
4
6
6
6
8
8
8

J
3.75
3.75
3.75
3.75
3.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
5
5
5
5

83

F
9.13
4.63
3.50
2.50
2.50
2.50
1.75
2.50
2.50
2.50
3
3
3
2.75
2.38
2.50

M
13.88
13.88
13.88
19.63
19.63
19.63
23.38
25.38
31.13
31.13
36.88
36.88
36.88
43.50
49.25
55

N
17.63
30.63
34.63
55.13
59.13
63.13
69.13
71.13
73.13
86.13
90.13
103.13
114.13
130.25
130.25
145.25

P
6.63
6.63
6.63
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3
3
3
2.38
2.38
2.38

G
14.25
14.25
14.25
20.00
20.00
20.00
20.00
20.00
20.00
25.75
26.25
32.00
32.00
37.75
37.75
37.75

Q
9.25
15.25
19.25
18.25
22.25
26.25
30.25
35.25
41.25
41.25
48.50
45.50
57.50
65.50
78.50
96.50

E
7.25
8.50
10.38
6.63
6.63
6.63
6.63
6.63
12
6.88
12.88
10
10
7.63
10.13
13.13

V
13.63
10.13
9.88
13.88
13.88
17.88
11.88
11.38
11.63
11.63
13.63
16.63
16.63
20.63
22.63
17.13

Jobsite
Connections
TSC plug fan

Note: Motor location may be right or left; right hand shown.

Unit Size
21
25
30
35
40
50
66
80
100

Unit Size
21
25
30
35
40
50
66
80
100

A
27.56
31.44
31.5
34.63
37.88
41.41
41.44
57.81
63.88

E
4
4
4
6
6
6
8
8
8

Front-Top
B
15.38
16.44
22
18.81
21.5
25.5
38.75
30.63
35.13

Discharge Dimensions
C
D
27.38
6.25
31.44
6.38
31.44
6.25
34.38
8.13
37.88
7.13
41.41
12
41.44
13.5
50.72
16.25
56.06
22.13

Module Dimension
J
H
4.75
52.5
4.75
58.75
4.75
58.75
4.75
68
4.75
68
5
80
5
92
5
107
5
119.5

L
73
54.75
54.75
62
62
68.5
84
92
96

W
76
78
91
96
109
120
135
135
150

F
34
9.5
9.5
12.5
12.5
12.5
5.25
4.88
5

R
35.5
41.63
41.75
43.75
43.75
55.75
63.88
78.63
91.38

84

Bottom-Front Discharge Dimensions


L
M
N
84
25.38
71.13
65.75
31.13
73.13
65.75
31.13
86.13
73.5
33.85
90.13
73.5
33.85
103.13
83
36.88
114.13
84
43.5
130.25
92
49.25
130.25
96
55
145.25

S
8.63
8.63
8.63
12
12
12
7.75
7.75
7.75

T
35.88
37.88
46.5
46.75
51.75
59.38
69
73
84.5

Fan Inlet Dimensions


U
30.38
30.38
32.88
33.75
33.75
34.38
47.38
47.38
47.38

P
2.5
2.5
2.5
3
3
3
2.38
2.38
2.38

V
13.88
13.88
15.63
19.5
27.5
30.38
22.5
18.5
22

Jobsite
Connections
TSC Q-Fan

Note: Motor location may be right or left; right hand shown.

UNIT SIZE
FAN SIZE
12 Q
19
12 R
21
14 Q
19
14 R
21
17 Q
21
17 R
24
21 Q
24
25 Q
27
25 R
27
30 Q
30
30 R
33
35 Q
33
35 R
36
40 Q
33
40 R
36
50 Q
36
50 R
40
66 Q
40
66 R
44
80 Q
44
All Dimensions are in Inches.

C
32
32.50
34
34
37
37
38
39
39
45.50
45.50
48
48
54.50
54.50
60
60
72
72
72

D
20
23
20
23
23
26
26
29
29
32
35.88
35.88
40
38.55
40
40
44
44
48
48

E
19.50
20.75
21.50
22.13
23.63
24
25.88
29
29
29.13
29.75
33.75
36.25
33.75
36.25
40.25
40
52.13
52.13
59.75

L
62.50
62.50
64.50
64.50
68.50
68.50
73
54.75
54.75
54.75
54.75
62
62
62
62
68.50
68.50
84
84
92

85

W
64
64
68
68
74
74
76
78
78
91
91
96
96
109
109
120
120
135
135
135

H
42
42
44
44
48
48
52.5
58.75
58.75
58.75
58.75
68
68
68
68
80
80
92
92
107

J
3.75
3.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
5
5
5
5
5
5
5

K
4
4
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
7
8

Jobsite
Connections
Return/Exhaust Fan Opening
Dimensions
The drawings below are to be used for
determining opening sizes and
dimension locations for housed return
or exhaust fans. Bottom opening is
available on return or exhaust fan
modules; back opening is available
only on a return fan module. When
using a plug fan as a return fan, use
page 84 when return air is to be
brought horizontally into the unit. If
return air is being brought vertically
into the unit, and then into the plug
return fan, a mixing module with a
bottom opening must be included
upstream of the plug return fan.

Unit/ Fan Size


3A,B
6A,B
8A,B
10A,B,C
12A,B,C
14A,B,C
17A,B,C
21A,B,C
25A,B,C
30A,B,C
35A,B,C
40A,B,C
50A,B,C
66A,B,C
80A,B,C
100A,B,C

H
28
31
35
38
42
44
48
52
58
58
68
68
80
92
107
119

K
4
4
4
4
4
4
4
4
4
4
6
6
6
8
8
8

86

L
60
68
75
58
62
64
68
73
54
54
62
62
68
84
92
96

P
18
31
35
56
60
64
70
72
74
87
91
104
115
130
136
145

Q
14
14
14
20
20
20
26
26
32
32
37
37
37
43
49
55

R
8 3/8
8 3/8
8 3/8
3 7/8
3 7/8
3 7/8
3 7/8
3 7/8
3 7/8
3 7/8
4 3/8
4 3/8
4 3/8
4 3/8
4 3/8
4 3/8

S
4 7/8
4 7/8
4 7/8
7
7
7
7
7
7
7
6
6
6
2
2
2

U
26
31
34
20
24
26
30
34
40
40
49
49
55
79
87
91

W
31
44
48
60
64
68
74
76
78
91
96
109
120
135
135
150

Y
8
11
14
11
15
17
16
20
21
21
24
24
36
42
52
58

Jobsite
Connections
TSC Mixing Box

UNIT SIZE
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

L
24.75
27.25
31
34
34
34
34
34
40
40
48
48
48
49
54
60

W
31
44
48
60
64
68
74
76
78
91
96
109
120
135
135
150

H
28.75
31.25
35
38
42
44
48
52.5
58.75
58.75
68
68
80
92
107
119.5

WITHOUT DAMPERS
A
B
E
13.88 17.63 9.13
13.88 30.63
4.5
13.88 34.63
3.5
19.63 55.13
2.5
19.63 59.13
2.5
19.63 63.13
2.5
25.38 69.13 1.75
25.38 71.13
2.5
31.13 73.13
2.5
31.13 86.13
2.5
36.88 90.13
3.0
36.88 103.13 3.0
36.88 114.13 3.0
43.5 130.25 2.75
49.25 130.25 2.38
55.00 145.25 2.50

WITHOUT DAMPERS
UNIT SIZE
P
Q
F
Y
3
18.25
14.5
6.63
8.5
6
31.25
14.5
6.63
11
8
35.25
14.5
6.63
14.75
10
56.25
20.5
2.5
11.75
12
60.25
20.5
2.5
15.75
14
64.25
20.5
2.5
17.75
17
70.25 26.25
2.5
16
21
72.25 26.25
2.5
20.5
25
74.25
32
2.5
21.5
30
87.25
32
2.5
21.5
35
91.25 37.75
3
24.5
40
104.25 37.75
3
24.5
50
115.25 37.75
3
36.5
66
130.25 43.5
2.38
42.75
80
136.25 49.25
2.38
52
100
145.25
55
2.38
58.75
All Dimensions are in Inches.

R
8.38
8.38
8.38
3.88
3.88
3.88
3.88
3.88
3.88
3.88
4.38
4.38
4.38
4.38
4.38
4.38

WITH DAMPERS
A
B
E
13.88 17.63
9.13
13.88 30.63
4.5
13.88 34.63
3.5
19.63 55.13
2.5
19.63 59.13
2.5
19.63 63.13
2.5
23.38 69.13
1.75
23.38 71.13
2.5
31.13 73.13
2.5
31.13 86.13
2.5
36.88 90.13
3.0
36.88 103.13
3.0
36.88 114.13
3.0
43.5 130.25 2.75
49.25 130.25 2.38
55.00 145.25 2.50

P
21
34
38
58.5
62.5
66.5
72.5
74.5
76.5
89.5
93.5
106.5
117.5
132.5
132.5
147.5

Q
17
17
17
22.75
22.75
22.75
28.5
28.5
34.25
34.25
40
40
40
45.75
51.5
57.25

J
3.75
3.75
3.75
3.75
3.75
4.75
4.75
4.75
4.75
4.75
4.75
4.75
5
5
5
5

K
4
4
4
4
4
4
4
4
4
4
6
6
6
8
8
8

WITH DAMPERS
F
Y
6.63
8.38
6.63
10.88
6.63
14.63
2.5
11.63
2.5
15.63
2.5
17.63
2.5
15.88
2.5
20.38
2.5
20.88
2.5
20.88
3
24.38
3
24.38
3
36.38
2.38
42.63
2.38
51.88
2.38
58.63

87

WITHOUT DAMPERS
C
D
M
V
14.25 12.25
5.25 15.13
14.25 18.25
6.5
11.63
14.25 22.25
8.38 11.38
20
21.25
9.38 15.38
20
25.25
9.38 15.38
20
29.25
9.38 13.38
20
33.25
9.38 13.38
20
38.25
9.38 12.88
20
44.25
10
13.13
25.75 44.25
9.38 13.13
26.25 51.25 10.88 15.13
32
48.25
8
18.13
32
60.25
8
18.13
37.75 68.25
5.63 22.13
37.75 81.25
8.13 24.13
37.75 99.25 11.13 18.63

R
5.63
5.63
5.63
1.13
1.13
1.13
1.13
1.13
1.13
1.13
2.13
2.13
2.13
2.13
2.13
2.13

WITH DAMPERS
C
D
M
V
17
12
3.88 13.63
17
18
5.13 10.13
17
22
7
9.88
22.75
21
8
13.88
22.75
25
8
13.88
22.75
29
8
11.88
22.75
33
8
11.88
22.75
38
8
11.38
22.75
44
8.63 11.63
28.5
44
8
11.63
28.5
51
8
11.63
34.25
48
6.88 16.63
34.25
60
6.88 16.63
40
68
4.5 20.63
40
81
7
22.63
40
99
10 17.13

Jobsite
Connections
T-Series External Cabinet Drawing

Table JC-1 Pipe Cabinet Dimensions


Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

Standard
31
31
31
31
31
31
31
31
31
31
32
32
38
38
38
38

Cabinet Depth - CW
Reduced
15
15
15
15
15
15
15
15
15
15
16
16
19
19
19
19

Extended
46
46
46
46
46
46
46
46
46
46
48
48
52
52
52
52

F
24
27
31
34
38
40
44
48
54
54
62
62
74
84
99
111

Note:
1. All dimension are in inches
2. L = Length of section or consecutive sections which have cabinets.
3. External cabinet optional only on coil, access, bypass and eliminator modules.
4. Single section cabinet shown with optional access door. See unit drawing for door size(s).
Optional access door available for each section area, hinged toward air leaving side.

88

G
28
31
35
38
42
44
48
52
58
58
68
68
78
92
107
119

Jobsite
Connections
Electrical Location Sizes 3 to 50

Unit Size
3
6
8
10
12
14
17
21
25

30

35

40

50

Front Top Discharge


A
B
18 7/8
5 7/8
20 1/8
7 1/8
22
9
18
5
18
5
18
5
18
5
18
5
13
13
A,B,C Fan
A,B,C Fan
41
41
P,Q,R Fan
P,Q,R Fan
13
13
A,B,C Fan
A,B,C Fan
41
41
P,Q,R Fan
P,Q,R Fan
15
15
A,B,C Fan
A,B,C Fan
46
46
P,Q,R Fan
P,Q,R Fan
15
15
A,B,C Fan
A,B,C Fan
46
46
P,Q,R Fan
P,Q,R Fan
1
17 /8
17 1/8
A,B,C Fan
A,B,C Fan
51 3/8
51 3/8
P,Q,R Fan
P,Q,R Fan

C
5
5
5
5
5
5
5
5
5
A,B,C Fan
12
P,Q,R Fan
6
A,B,C Fan
12
P,Q,R Fan
16

18

21

Unit Size
3
6
8
10
12
14
17
21
25

30

35

40

50

Dimension are in inches. High voltage connection on drive side of fan module.

89

Bottom Front Discharge


A
B
18 7/8
5 7/8
20 1/8
7 1/8
22
9
18
5
18
5
18
5
18
5
18
5
43
43
A,B,C Fan A,B,C Fan
44 1/8
44 1/8
P Fan
P Fan
43
43
A,B,C Fan A,B,C Fan
44 1/8
44 1/8
P Fan
P Fan
46
46
A,B,C Fan A,B,C Fan
49 3/8
49 3/8
P Fan
P Fan
46
46
A,B,C Fan A,B,C Fan
3
49 3/8
49 /8
P Fan
P Fan
52
52
A,B,C Fan A,B,C Fan
5
53 /8
53 5/8
P Fan
P Fan

C
5
5
5
5
5
5
5
5
5
A,B,C Fan
9
P Fan
6
A,B,C Fan
9
P Fan
16
A,B,C Fan
11
P Fan
18
A,B,C Fan
11
P Fan
21
A,B,C Fan
10
P Fan

Jobsite
Connections
Electrical Location Sizes 66 to 100

Unit Size
66

80

100

Front Top Discharge


A
B
9
A,B,C Fan
23
51
P,Q,R Fan
11
A,B,C Fan
23
57
P,Q Fan
13
A,B,C Fan
23
59
P Fan

Unit Size

66

51
A,B,C Fan

23
A,B,C Fan

5
A,B,C Fan

80

57
A,B,C Fan

23
A,B,C Fan

5
A,B,C Fan

100

59
A,B,C Fan

23
A,B,C Fan

5
A,B,C Fan

Unit Size
66

E
60
P Fan
71
P Fan
76 5/8
P Fan

D
7
P Fan
7
P Fan
7
P Fan

C
19
P Fan
20
P Fan
19
P Fan

80
1. Dimension are in inches.
2. For RH drive, high voltage on air entering side of module.
3. For LH drive, high voltage on air leaving side of module.

90

Bottom Front Discharge


A
B

100

Jobsite
Connections
Table JC-2 and JC-3 T-Series Electrical Connection Sizes
The following tables list the size of the electrical pipe nipples protruding from the
floor of T-Series fan modules. All electrical pipe nipples are threaded on both ends.
Table JC-2 Electrical Connection Sizes (200 and 230 volt) by Motor Horsepower
Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

1
Nipple
1 to 5
1 to 5
1 to 7.5
1 to 7.5
1 to 15
1 to 15
1 to 15
1 to 15
1 to 15
1 to 15
1 to 15
1 to 15
1 to 15
1.5 to 15
2 to 15
10, 15

200 Volts
2
2
Nipple
Nipple

3
Nipple

20
20, 25
20, 25
20 to 30
20 to 40
20 to 40
20 to 40
20 to 40
20 to 40
20 to 40

1
Nipple
1 to 5
1 to 5
1 to 7.5
1 to 7.5
1 to 15
1 to 15
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
1.5 to 20
2 to 20
10 to 20

230 Volts
2
2
Nipple
Nipple

3
Nipple

25
25
25, 30
25 to 40
25 to 50
25 to 50
25 to 50
25 to 50
25 to 50

Table JC-3 Electrical Connection Sizes (460 and 575 volt) by Motor Horsepower
Unit Size
3
6
8
10
12
14
17
21
25
30
35
40
50
66
80
100

460 Volts
1
2
2
Nipple
Nipple
Nipple
1 to 5
1 to 5
1 to 7.5
1 to 7.5
1 to 15
1 to 15
1 to 20
1 to 25
1 to 25
1 to 30
1 to 40
1 to 40
50
1 to 40
50, 60
1.5 to 40 50 to 75
2 to 40 50 to 75
10 to 40 50 to 100

NOTE
(1) All low voltage (control) pipes are 1.
(2) All pipes have external threads.

91

3
Nipple

1
Nipple
1 to 5
1 to 5
1 to 7.5
1 to 7.5
1 to 15
1 to 15
1 to 20
1 to 25
1 to 25
1 to 30
1 to 40
1 to 50
1 to 60
1.5 to 60
2 to 60
10 to 60

575 Volts
2
2
Nipple
Nipple

75
75
75, 100

3
Nipple

Mechanical
Specifications
General

The units must be rigged and lifted in


strict accordance with the Installation
Operation and Maintenance manual
(TSC-IM-1). The units are to be installed
in strict accordance with the
specifications. Unit shall be UL and
CUL Listed. Units may be shipped fully
assembled up to size 80 or
disassembled to the minimum
component size according to shipping
or jobsite requirements. Units shipped
in one piece will have a minimum of
six points of lift. These lift points will be
permanently attached to the unit base
and be designed to accept standard
rigging devices. Units shipped in
sections will a minimum of four points
of lift.
Unit Construction
Unit panels shall be solid double-wall
construction. Fiberglass insulation with
a perforated liner can be added to
sections as specified on the schedule.
All exterior wall panels shall be made
of galvanized steel. The casing shall be
able to withstand up to 1.5 times
design static pressure, or 8" WC,
whichever is less, with no more than
0.005 inch deflection per inch of panel
span.
The unit base design will allow unit to
rest on top of roofcurb when field
installed. Entire length and width under
base will be sealed for additional water
management protection.
Insulation
Unit shall be factory insulated. Panels
and unit roof shall be of double-wall
construction with interior and exterior
panels and insulation. Panel insulation
system shall provide a minimum
R value of 12. Insulation shall conform
to NFPA 90 requirements.
Unit Paint
External surface of unit casing shall be
prepared and coated with a minimum
1.5 mil enamel finish or equal. Units
supplied with casing exterior factory
painted shall be able to withstand a salt
spray test in accordance with ASTM
B117 for a minimum of 500
consecutive hours. Unit casing exterior
will be provided with manufacturers
standard color, or alternative color
when required.

Unit Roof
Unit roof will be constructed of two
pieces. Inner roof will be installed in
such a manner as to prevent air bypass
between internal components. Outer
roof will be sloped a minimum .25" per
foot either from one side of unit to
other, or from center to sides of the
unit. Roof assembly will overhang all
walls of units by 2" minimum.
External Pipe Cabinet
Piping cabinet shall be supplied by the
manufacturer (factory assembled) and
shall be of the same construction as the
main unit casing. Piping cabinet shall
be mounted external to the unit and
shipped separate to be field installed.
Piping cabinet shall have removable
panels or optional access door of the
same construction as the unit door.
Drain Pans
Coils and moisture eliminators shall be
provided with a galvanized or stainless
steel, two-way sloping IAQ drain pan to
allow for proper condensate removal.
Access or blank sections may be
provided with an IAQ drain pan when
specified.
Access Doors
Access doors shall be constructed with
a double-wall of solid G90 galvanized
steel interior panel. Automotive style
gasketing around the full perimeter of
the access door shall be used to
prevent air leakage. Door gasketing
shall be mounted to the perimeter of
the door and shall seal against a raised
door frame. Door frame shall channel
water away from gasket. Door shall
have a protective flange to shield
gasket from exposure. Preferred door
handle shall not penetrate door casing.
Door shall have a single handle latch.
View Window
A view window made of tempered
glass in door shall be provided by
section as specified on the schedule.
Marine Light
A factory-mounted, 120-volt, weather
resistant (enclosed and gasketed),
UL listed wet location fluorescent light
fixture shall be provided in sections of
unit as specified. Fixture shall be
complete with junction box, Lexan
housing and lens, magnetic ballast and
70 watt bulb.

92

Fans

The vibration levels of the complete fan


assembly shall be checked and
excessive vibration (including that
caused by fan imbalance) shall be
eliminated in the factory. Fan shaft shall
be properly sized and protectively
coated with lubricating oil. Fan wheels
shall be keyed to fan shaft to prevent
slipping. Fan shafts shall be solid and
designed so that fan shaft does not
pass through its first critical speed as
the unit comes up to its rated rpm. Fan
shafts shall not exceed 75 percent of
their first critical speed at any cataloged
rpm. Fan shall be provided with an
access door on the drive side of the fan.
a
FC Fans Fan shall be double-width,
double-inlet, multiblade type as
produced by the unit manufacturer. Fan
shall be forward curved (FC) as
required for stable operation and
optimum energy efficiency. Fan shall
be equipped with self-aligning,
antifriction bearings with an L-50 life of
200,000 hours. Fan performance shall
be certified as complying with ARI
Standard 430-89.
b
BI Fans Fan shall be double-width,
double-inlet, multiblade type as
produced by the unit manufacturer. Fan
shall be backward inclined (BI) as
required for stable operation and
optimum energy efficiency. Fan shall
be equipped with self-aligning,
antifriction bearings with an L-50 life of
200,000 hours. Fan performance shall
be certified as complying with ARI
Standard 430-89.
c
AF Fans Fan shall be double-width,
double-inlet, multiblade type as
produced by the unit manufacturer. Fan
shall be backward-inclined airfoil (AF)
as required for stable operation and
optimum energy efficiency. Fan shall
be equipped with self-aligning,
antifriction bearings with an L-50 life of
200,000 hours. Fan performance shall
be certified as complying with ARI
Standard 430-89.
d
Plug Fans Fan shall be single-width,
single-inlet, multiblade type plug fan.
The fan blades shall be backward
inclined airfoil (AF). Plug fans shall be
equipped with self-aligning, antifriction
pillow block bearings with an L-50 life
of 400,000 hours. Fan performance
shall be tested in accordance with
AMCA 210.

Mechanical
Specifications
e
Vaneaxial Fans Fan shall be a
vaneaxial type fan as produced by the
manufacturer. Fan shall have tapered
inlet and outlet shells over fan hub
assemblies for uniformly accelerating
air through the blade area. A cast
aluminum diffuser, consisting of
radially-projected straightening vanes
with airfoil cross sections, shall
straighten air as it leaves the blades.
The leading edge of the vanes shall be
curved to reduce tonal noise
generation. Vaneaxial fans shall be
equipped with self-aligning, antifriction
bearings with an L-50 life of 200,000
hours at maximum cataloged
operating conditions. Bearing grease
lines shall extend through fan shell for
easy servicing. Fan performance
shall be tested in accordance with
AMCA 210.
Fan Modulation
a
Inlet Guide Vanes For variable air
volume applications, airflow of
centrifugal type fans shall be
modulated by inlet guide vanes.
b
Variable Frequency Drive For
variable air volume applications,
airflow shall be modulated by a
variable frequency drive controlling fan
speed.
Fan Isolation
Fan connection shall be isolated from
unit casing by a flexible canvas duct.
a
One-Inch Spring Isolators Fan and
motor assembly (sizes 3-8) shall be
internally isolated from the unit casing
with 1-inch deflection spring isolators,
furnished and installed by the unit
manufacturer.
b
Two-inch Spring Isolators Fan and
motor assembly (sizes 10-100) shall be
internally isolated from the unit casing
with two-inch deflection spring
isolators, furnished and installed by the
unit manufacturer. The isolation system
shall be designed to resist loads
produced by external forces such as
earthquakes and conform to the
current requirements for Seismic
Zone IV.

Drives

a
Variable Pitch - Drives shall be
variable pitch, suitable for
adjustment within 5 percent of
specified rpm.
b
Fixed Pitch - Drives shall be
constant speed with fixed pitch
sheaves.
c
1.2 Service Factor - Drives shall be
selected at 1.2 service factor.
d
1.5 Service Factor - Drives shall be
selected at 1.5 service factor.

Motors

Motor shall be mounted integral to an


isolated fan assembly furnished by the
unit manufacturer. Motor shall be
mounted inside the unit casing on a
slide base to permit adjustment of
drive belt tension. Motors shall comply
with NEMA MG-1.
a
High Efficiency E+ Open Drip-Proof Motor shall be a T-frame, squirrel cage,
open drip-proof with size, type and
electrical characteristics as shown on
equipment schedule.
b
High Efficiency E+ Totally-Enclosed
Fan-Cooled - Motor shall be T-frame,
squirrel cage, totally-enclosed
fan-cooled with size, type and electrical
characteristics as shown on equipment
schedule.
Motor Options
a
200 or 230 Volt/3 Ph/60 Hz
b
460 Volt/3 Ph/60 Hz
c
75 Volt/3 Ph/60 Hz
d
115 Volt/l Ph/60 Hz
e
High efficiency E+3 motors
Fan Options
a
Grease Lines Grease lines of both
bearings shall be extended to the fan
support bracket on the drive side.
b
Inverter test shall be performance to
check vibration at unloaded conditions.
Fan vibration levels shall be checked
from 100% to 30% of required
operating rpm.

93

c
Door Guards Expanded metal
screen shall be mounted on door
opening to prevent unauthorized entry
to fan.

Coils

Coils shall be manufactured by the


supplier of the air handling unit. Coils
shall be installed such that headers and
return bends are enclosed by unit
casings. Coils shall be removable by
unbolting the wall panels in the coil
section. Coil connections shall be
clearly labeled on outside of units. Coils
shall have aluminum plate fins and
seamless copper tubes. Fins shall have
collars drawn, belled and firmly
bonded to tubes by mechanical
expansion of the tubes. Soldering or
tinning shall not be used in the
bonding process. Fin surfaces shall be
cleaned prior to installation in the unit
to remove any oil or dirt that may have
accumulated on the fin surfaces during
manufacturing of the coil. Capacities,
pressure drops and selection
procedure shall be certified in
accordance with ARI Standard 410.
Coil casing shall be a minimum
16-gauge G90 galvanized or 304
stainless steel with formed end
supports and top and bottom channels.
If two or more coils are stacked in the
unit, intermediate drain channels shall
be installed between coils to drain
condensate to the main drain pans
without flooding the lower coils or
passing condensate through the
airstream of the lower coil.
Water Coils
Coils shall be burst tested to 300 psig
and proof tested under water to 200
psig.
1/2" Unit Coils (UW or UU)
Headers are to be constructed of round
copper pipe with steel pipe
connections. The steel pipe shall be
attached to the copper pipe in such a
manner as to inhibit galvanic corrosion
of header system. Fin surface shall be
Delta-FIo .005 aluminum fins.
Options
a
Tubes shall be 1/2 inch OD, .016 inch
copper.
b
Tubes shall be 1/2 inch OD, 0.025 inch
copper.

Mechanical
Specifications
5/8" Shipping Coils
(W, WA, WD, D, DD, K, P or WC)
Headers are to be constructed cast iron.
Tubes shall be mechanically bonded to
prevent water leakage due to thermal
stresses and water pressure.

Options
a
Tubes shall be 5/8 inch OD, 0.020
inch copper.
b
Tubes shall be 5/8 inch OD, 0.024
inch copper.
c
Tubes shall be 5/8 inch OD, 0.035
inch copper.
d
Tubes shall be 5/8 inch OD, 0.049
inch red brass.
e
Fin surface shall be Sigma Flo
.0075 aluminum.
f
Fin surface shall be Prima Flo
.0075 aluminum.
g
Fin surface shall be Sigma Flo
.0045 copper.

Filter sections shall have filter racks, an


access door for filter removal and
block-offs as required to prevent air
bypass around filters. Units shall be
supplied with two-inch or four-inch flat,
two-inch angled, cartridge or bag
filters.
a
Throwaway Filters shall be of
throwaway type and shall have
two-inch fiberglass media contained in
a rigid frame. Filters shall have a rigid
supporting maze across both the
entering and leaving faces of the
media. Filters shall be sized so as not to
exceed scheduled face velocities.
b
Pleated Media Filters shall be
two-inch or four-inch thick non-woven
fabric, treated with adhesive and
continuously laminated to a supported
steel wire grid. Filters shall have a rated
average dust spot efficiency of not less
than 25 to 35 percent when tested in
accordance with ASHRAE 52-76
atmospheric dust spot method.
c
Permanent Filters shall be two-inch
all metal, viscous-imprisonment type,
capable of operating up to 600 fpm face
velocity without loss of filter efficiency
and holding capacity. Filter media shall
be layers of cleanable wire maze. Filter
frame shall be constructed of
galvanized steel.

Refrigerant Cooling Coils (UF or F)


Coils shall be burst tested to 450 psig
and proof tested to 300 psig air
pressure under water. After testing, coil
circuiting will be air dried, charged with
dry nitrogen, and sealed to ensure that
circuiting is free of any water or
contaminants. Liquid and suction
headers shall be constructed of copper
and shall penetrate unit casings to
allow for sweat connections to
refrigerant lines. Coils shall have
equalizing vertical distributors sized
according to the capacities of the coils.
Steam Heating Coils (NS)
Non-freeze steam-distributing type
coils shall be provided. Steam coils
shall be pitched in the unit for proper
drainage of steam condensate from
coils. Coils shall be burst tested to 300
psig and proof tested to 200 psig air
pressure under water. Headers are to
be constructed of cast iron or round
copper pipe. Inner tubes shall have
orifices that ensure even steam
distribution across the coil face. Orifices
shall be directed toward the return
connections to ensure that the steam
condensate is adequately removed
from the coil.
a
Tube construction shall be 5/8 inch OD
copper inner tube and 1 inch OD .031
inch copper outer tube.

Tube construction shall be 5/8 inch OD


copper inner tube and one inch OD
.049 inch red brass outer tube.

Filters

Throwaway or Pleated Media Options


I
Anti-Microbial Filters shall be
provided with a antimicrobial coating
to inhibit the growth of microbes.
a
Cartridge Filters Filter shall be
constructed by pleating a continuous
sheet of fine-fiber media into closely
spaced pleats with safe-edged
aluminum separators. This filter shall
be sealed into a metal frame
assembled in a rigid manner. All
cartridge filters shall be furnished with
a two-inch prefilter to provide extended
cartridge life. Manufacturer shall supply
side access filter rack capable of
holding cartridge filters and prefilters.

94

b
Bag Filters Filters shall be fine fiber,
all glass media with spun backing to
keep glass fibers from eroding
downstream. Stitching method shall
permit bag to retain pleat shape
without the use of wire basket support.
Manufacturer shall supply two-inch
prefilters and side access filter rack
capable of holding bag filters and
prefilters.
Bag or Cartridge Filter Options
I
Percent Efficiency Efficiency of filter
shall be in the range of 60 to 65 percent
as determined by ASHRAE Standard
52-76.
Il
Percent Efficiency Efficiency of filter
shall be in the range of 80 to 85 percent
as determined by ASHRAE Standard
52-76.
lll
Percent Efficiency Efficiency of filter
shall be in the range of 90 to 95 percent
as determined by ASHRAE Standard
52-76.
Blank/Access/Inspection
Unit length shall be extended at
specified points of the unit allowing
additional access/inspection for unit
components and space for field
installed components as needed.
Removable panels or optional access
door shall be provided for easy access.
Traq Damper Mixing Box, Mixing
Box, Filter Mixing Box and Economizer
A section shall be provided that
supports damper assembly for outside,
return and/or exhaust air.
Dampers
Dampers shall modulate the volume of
outside, return or exhaust air. Dampers
shall be Ruskin CD60 type double-skin
ultra low-leak airfoil design or
equivalent with metal compressible
jamb seals and extruded blade edge
seals on all blades. The dampers shall
be rated for a maximum leakage rate of
less than 1 percent of nominal airflow
at 1 inch wg. Blades shall rotate on
stainless steel sleeve bearings.
Dampers shall be arranged in parallel
or opposed blade configuration.

Mechanical
Specifications
Traq Dampers Airflow Monitoring
Station
A factory-mounted damper shall be
provided in the outdoor air opening to
measure airflow. Damper blades shall
be galvanized steel, housed in a
galvanized steel frame and
mechanically fastened to a rotating
axle rod. The dampers shall be rated
for a maximum leakage rate of less
than one percent of nominal airflow at
one inch wg. The airflow measurement
station shall measure up to 100 percent
of total outside air and/or return air. The
airflow monitoring device shall adjust
for temperature variations. The airflow
monitoring output shall be a 2-10 VDC
signal proportional to velocity. The
accuracy of the airflow measurement
station shall be 5 percent.
Air Blenders
An Air Blender brand blender shall be
provided by unit manufacturer for
properly mixing outside and return air,
to prevent air stratification and reduce
the risk of coil freeze-up. The proper
blender size and space upstream and
downstream shall conform to the
manufacturers recommendation to
allow for proper performance.
Turning and Discharge Plenums
Plenums shall be provided to efficiently
turn air and provide for sound
attenuation.
Diffusers
A diffuser shall be provided
immediately downstream of the fan to
provide equal air distribution to
blow-thru components immediately
downstream of diffuser. Diffuser shall
be installed at an angle in order to
smooth out the velocity profile of
housed fan.
Moisture Eliminator
A section consisting of a verticallymounted, maintenance-free moisture
eliminator shall be provided. Eliminator
shall have G90 galvanized steel sine
wave fins for effective moisture
removal.
Face or Face and Bypass
Ultra low-leakage face and bypass
dampers shall be provided as
scheduled on drawings. Dampers shall
be Ruskin CD60 type double-skin airfoil
design or equivalent. Damper blades
shall be of minimum 14-gauge
galvanized steel and damper frames of
minimum 16-gauge galvanized steel.
Blades shall be of opposed blade
action, with metal compressible jamb
seals and extruded vinyl blade edge

seals. Blades shall rotate on stainless


steel sleeve bearings. Face damper and
bypass damper shall be mechanically
linked together and provide end driven
control shafts. Leakage rate shall not
exceed 5 cfm/foot2 at 1 inch wg and 9
cfm/foot2 at 4 inch wg. Damper section
shall be supplied with an access door.
Inlet Hood
For units with outside air requirements,
manufacturer shall provide inlet hood
for each outside air damper with high
performance moisture eliminator to
prevent water carryover into unit
casing from outside air. Hoods shall be
sized for 100% of nominal damper
capacities. Outlet hood shall be
provided on exhaust air openings.
Exhaust Damper
For units supplied with an exhaust fan
economizer cycle, a section shall be
supplied to house the exhaust damper.
Dampers shall be Ruskin CD60 type
double-skin airfoil design or equivalent.
Damper blades shall be of minimum
14-gauge galvanized steel and damper
frames of minimum 16-gauge
galvanized steel. Blades shall rotate on
stainless steel sleeve bearings. Leakage
rate shall not exceed 5 cfm/foot2 at 1
inch wg and 9 cfm/foot2 at 4 inch wg.
Section shall be supplied with an
access door, and an exhaust hood.
Combination Starter / Line Break
Switch
Combination starter/ Line Break Switch
packages shall be factory mounted and
wired by the air handling unit
manufacturer. The package shall
include:
a
Line break switch
b
Hand-Off-Auto (HOA) selector switch
c
Control transformer
d
Overload shall be factory-set for the
exact motor used in the air handler
e
Starter shall include adjustable trip
switch which opens the contacts if a
short-circuit occurs
When ordered with an optional factory
mounted control system, an oversized
control transformer shall be provided
to power the temperature controls.
Power wiring from the transformer to
the controls, start/stop relay and start/
stop wiring to the HOA switch shall be
factory wired and tested.

95

Factory-mounted controls shall be


covered by the air handler
manufacturers standard warranty.
Combination Variable Frequency Drive
/Disconnects
A combination VFD/disconnect
packages shall be factory mounted and
wired by the air handling unit
manufacturer. The package shall
include:
a
Variable frequency drive
Pulse Width Modulated Drive w/IGBT
transistors
LCD display and keypad
English language electrical values,
parameters, self test, faults and
diagnostics
Power, pending fault, and fault LED
indicator lights
Form C fault contacts
4-20 mA or 0-10 V speed input signal
b
Circuit breaker disconnect
c
Hand-Off-Auto (HOA) selector switch
d
Current limiting NEMA Class T fuses
e
NEMA 1 enclosure
f
Auto restart after momentary power
loss
g
Critical frequency avoidance
h
Voltage and FLA shall be factory-set for
the exact motor used in the air handler
An optional three contactor bypass
with a key operated drive-off-bypass
selector switch is available.
When ordered with an optional factory
mounted control system, an oversized
control transformer shall be provided
to power the temperature controls.
Power wiring from this transformer to
the controls, start/stop relay, start/stop
wiring to the HOA switch and analog
speed signal wiring to the VFD is to be
wired and tested at the factory.
Factory-mounted controls shall be
covered by the air handler
manufacturers standard warranty.
When the optional start-up service is
performed by a certified Square D
technician, Square D will extend the
warranty to three year parts and labor.

Mechanical
Specifications
Factory-Mounted Direct
Digital Control (DDC)
Systems

Factory-mounted DDC systems shall be


engineered, mounted, wired and tested
by the air handling unit manufacturer
to reduce installed costs, save time,
and improve reliability. Each control
system shall be fully functional in a
standalone mode or can be tied to a
building automation system with a
simple pair of wires.
Direct Digital Controller
A dedicated programmable direct
digital controller with the appropriate
point capabilities shall be unit mounted
(remote mounting is also available) on
each air handling unit. A screen and
keypad shall be provided to facilitate
local monitoring, trouble shooting and
changing of setpoints.
Factory-Mounted Control Options
a
Mixing Box Damper Actuators Spring
return actuators shall be mounted with
the outside air damper linked normally
closed and the return air damper linked
normally open.
b
Traq Dampers with Airflow Measuring
Stations Velocity Control Modules
(VCM) shall provide a 2-10 VDC signal
which corresponds to cfm for
controlling and documenting airflow.
c
Face / Bypass and Multizone Damper
Actuators Non-spring return
actuators shall linked as indicated on
the order and control drawings.

d
Inlet Guide Vane Actuators Spring
return actuators shall be mounted with
the IGVs linked normally closed. On
units larger than #66, non spring return
is acceptable, but a high static switch
shall be provided to protect the
ductwork.
e
Fan Discharge Temperature Sensors
Thermister type sensor shall be
mounted in the fan discharge.
f
Averaging Temperature Sensors A
20' capillary tube averaging RTD sensor
shall be serpentined with capillary clips
across the unit as engineered by the air
handling unit manufacturer.
g
Low-Limit Switches A 20' capillary
tube manual-reset low limit switch
shall be serpentined with capillary clips
across the unit as engineered by the air
handling unit manufacturer.
h
Airflow Switches A differential
pressure switch piped to the discharge
and suction sides of the fan shall
indicate fan status.
i
Dirty Filter Switches A differential
pressure switch piped to both sides of
the filter shall indicate filter status.
j
Customer Interface Relays 10 amp
DPDT relays shall be provided as
required for each binary output of the
controller for customer interface to:
supply, return and exhaust fan motor
starters; relief dampers; pumps;
condensing units; etc.
k
Electronic or pneumatic end devices.

Field-Mounted Control Options


a
Control Valves Control valves shall
be provided by the air handling unit
manufacturer and field piped by the
piping contractor. Power and signal
wiring shall be by a simple quick
connect.
b
Space Temperature Sensors
Thermister type sensors shall be
provided as required for field wiring.
c
Outside Air Sensors Thermistor type
sensors shall be provided as required
for field wiring.
All factory-mounted controls shall be
covered by the air handling
manufacturers standard warranty.

Worldwide Applied Systems Group


The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com

Library

Product Literature

Product Section
Product
Model

Air Handling
Climate Changer Air Handler
000

An American Standard Company

Literature Type
Sequence
Date

Data Sales Catalog


9
February 1999

File No.
Supersedes
Ordering No.

PL-AH-CLCH-000-DS-9-299
CLCH-DS-9 697
CLCH-DS-9

Since The Trane Company has a policy of continuous


product improvement, it reserves the right to change
design and specification without notice.

96