World Super Series WSS The Extensive Breaker Series from Mitsubishi Electric
The circuits of the Mitsubishi Electric breaker series are amongst the
smallest compact circuit breakers in the world with electronic overload
indication of this kind.
The system is based, among other things, on the well-known and proven
microprocessor technology.
MITSUBISHI
MITSUBISHI
NO-FUSE BREAKER
MODEL
MCCB Overview
In
OFF
NF250-SEV
250A
POLE
Ui690V
NO-FUSE BREAKER
EN60947-2
40C
Icu/Ics
8/8kA
30/30kA
36/36kA
36/36kA
36/36kA
36/36kA
85/85kA
IEC60947-2
JIS C 8201-2
Ue
690VAC
500VAC
440VAC
415VAC
400VAC
380VAC
230VAC
MODEL
NF400-SEP
50 - 60Hz
8kV
Uimp
MODEL
In
NF1000-SS
1000A
Icu/Ics
25/13kA
65/33kA
85/43kA
85/43kA
125/63kA
Icw 20kA 0.1s
Ir 500-1000A
50kA
85kA
500VAC
250VAC
ON
ON
IEC60947-2
EN60947-2
Ue
690VAC
500VAC
440VAC
400VAC
230VAC
Cat. B
MITSUBISHI
NO-FUSE BREAKER
Icu/Ics
10/10kA
30/30kA
42/42kA
45/45kA
85/85kA
40C
400
690VAC
Ui
Icn
35kA
50kA
85kA
IEC 60947-2
EN 60947-2
3P
POLE
3P
Uimp 8kV
Cat.A
JIS
Ue
550VAC
460VAC
220VAC
OFF
400A
MITSUBISHI ELECTRIC
PUSH TO
TRIP
PUSH TO TRIP
T
TEST
MITSUBISHI ELECTRIC
Ir
Ip
TL
Is
250
Ii
300
220
Ts
200
Ii(X100A)
TEST
T
Is
80
TL
4 5 6
PUSH TO TRIP
10
7 6
8
10 4
12
14
16
Ii(X400A)
IS(xIr)
.2
.3
TS(sec)
TL(sec)
Ts
.1
100 .06
12
Ii
350 3.5
3
2.5
400 2
Ir(A)
60
Ir
Ip
OVER
PAL
70%
.10
.07
Ip(xIr)
250
T
TL
Is
Ts
Ii
200
.7
300
225
Ir
Ip
In(A)
100
60
NF400-SEW, 3p
.2
.1
.06
.3
T S (s)
10
12
14
16
II(400A)
IS (In, Ir )
150
T L (s)
NF250-SEV, 3p
Ir(400A)
12
7 6
8
10 4
3
1
.5
TEST
4 5 6
.8
350
.8
.7
.9
1.0
IP (In, Ir)
NF1000-SEW, 3p
zz 400 to 800 A
zz breaking capacity
zz 1000 to 1600 A
zz 1 model size (3- and 4-pole)
zz electronic trip system
Intelligent Breaking
Technology for Your Safety
kA
200
Breaking
performance
UGV
UEW
RGV
REW
125
85
75
70
HGV
50
45
36
HEW
LGV
SEW
SEW
10
7,5
5
32
SEV
HV
SV
SV
32
63
125/160/250
400/630/800 1000/1250/1600
AF
MCCB Overview
Outline
New breaking technology
With its new breaking technology the circuit
breakers offer greater safety and even faster
circuit-breaking speed through the use of the
Arc-extinguishing device
ov
em
en
t
Switching mechanism
4
MCCB Overview
Ra
pi
d
Magnetic flux
Grid
Magnetic
force
Arc
Handle
zz Trip indication
The automatically tripped condition is indicated
by the handle in the center position between ON
and OFF; the yellow or white line cannot be seen
in this position.
Arc extinction
Arc runner
The arc is instantaneously transferred
to the arc-extinguishing chamber (see
the figure above) by the arc runner,
which reduces damage to contacts
and improves interrupting performance.
zz Resetting
MITSUBISHI
NO-FUSE BREAKER
MODEL
In
OFF
NF250-SEV
250A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
30/30kA
36/36kA
36/36kA
36/36kA
36/36kA
85/85kA
IEC60947-2
JIS C 8201-2
Ue
690VAC
500VAC
440VAC
415VAC
400VAC
380VAC
230VAC
zz Trip-Free
3P
Uimp 8kV
Cat.A
ON
IIIIIII IIIIIII IIIIIII IIIIIII
PUSH TO
TRIP
T
TEST
Ir
Ip
TL
Is
Ts
Ii(X100A)
Ii
33
MCCB Overview
A Microcomputer and Mitsubishi Electrics Original IC fulfill a New High Level of Safety
Alarm function monitors and anticipates interruptions
Current setting Ir
Pre-alarm
current IP
Time [s]
MCCB Overview
High
voltage
Low
voltage
MCCB
Load current
Instantaneous tripping
current II
Current [A]
Current setting Ir
250
300
200
.7
.8
350
225
.5
In(A)
7 6
8
10 4
IS (In, Ir )
100
TEST
4 5 6
Ir(400A)
60
.2
.1
10
12
14
16
II(400A)
.8
.9
150
12
.06
T L (s)
.3
T S (s)
1.0
.7
IP (In, Ir)
NF400-SEW 3P
Long time-delay
operating time TL
34
Short time-delay
operating time TSd
L1
L2
L3
MCCB Overview
MELSHORT2
MS Windows 95/98/NT4.0/2000
CD-ROM
Art. no.
129115
35
4
MCCB Overview
The program calculates the short-circuit levels and currents at all necessary points for all switchgear components, including the power supply
transformer and circuit breakers, the emergency generators, the individual motor and capacitor group branch circuits and all the other power
distribution circuits, down to the last circuit breaker. This makes it possible
to select the ideal breaker for every task, for optimum performance and
cost-efficiency.
MCCB Overview
see page 38
see page 61
see page 61
see page 68
see page 67
see page 67
see page 67
see page 61
see page 61
10
see page 68
11
see page 64
12
see page 64
13
see page 62
14
see page 63
15
see page 66
16
see page 54
17
see page 58
18
see page 56
11
12
16
98
ALc
Circuit Breaker
10
98
ALa
95
c
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
96
b
98
a
14
a
14
AXa
12
b
11
c
12
AXb
11
AXc
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
AUXILIARY SWITCH
MITSUBISHI ELECTRIC
ALAX-2GSWLS
AX AL
ALARM SWITCH
96
ALb
MCCB Overview
13
ON
F
F
I
P
Ir
Ip
TEST
PUSH
TO
TRIP
TL
Is
Ii
Ts
Ii(X100A)
14
17
ON
F
F
I
P
D1
P1
D3 D2
P3 P2
SOURCE
Hi Lo
UVTSA250-2GSWRS
PUS
TO H
TRIP
15
18
Power
P1
Supply
P2
S1
S2
S4
OFF
ON
Uc
Operating
S4
C2
S2
K1
K1
K2
SW1
K2
S1
P2
K1
K2
K3
Uc
K3
Circuit
S2
K3
P1
P1
S1
MODEL
MITSUBISHIMODULE
POWER SUPPLY
MODEL
SERIAL:
S2
S4
MSDBA-NF25GSW
A0106
MDSPSA240-SW
CONTROLL CIRCUIT
Pull
VOLTAGE
AC100-240V/DC100-250V
NO-FUSE BREAKER
MODEL
NF250-SGW
Push to
ON
AUTO
Push to
OPEN
(TRIP)
MANU
36
Ui 690V
Cat.A
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
RATED CURRENT
250 A
ON
50/60Hz
Uimp 8kV
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
MITSUBISHI ELECTRIC
C1
S1
50/60Hz
SHTA240-2GSWRS
P2
SHT
AC100-240V
Control circuit be
voltage should
supplied to P1
and P2 terminals.
(MANU)
Discharge
Push
MCCB Overview
MCCB Overview
MITSUBISHI
NO-FUSE BREAKER
MODEL
In
OFF
NF250-SEV
250A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
30/30kA
36/36kA
36/36kA
36/36kA
36/36kA
85/85kA
IEC60947-2
JIS C 8201-2
Ue
690VAC
500VAC
440VAC
415VAC
400VAC
380VAC
230VAC
Uimp 8kV
ON
IIIIIII IIIIIII IIIIIII IIIIIII
PUSH TO
TRIP
T
TEST
3P
Cat.A
Ir
Ip
TL
Is
Ii
Ts
Ii(X100A)
37
MCCB Overview
S series
IEC 947-2
EN 60 947-2
VDE 0660
AC
AC a
(50/60
Hz)
(Icu / Ics)
Dimensions WxHxD
Type
Rated current In max. [A]
Rated insulation voltage Ui [V]
Number of poles
L series
Rated
breaking
capacity [kA]
IEC 947-2
EN 60 947-2
VDE 0660
AC a
(50/60
Hz)
(Icu / Ics)
H series
Rated
breaking
capacity [kA]
IEC 947-2
EN 60 947-2
VDE 0660
AC a
(50/60
Hz)
(Icu / Ics)
R series
IEC 947-2
EN 60 947-2
VDE 0660
AC a
(50/60
Hz)
(Icu / Ics)
U series
(Icu / Ics)
690 V
500 V
440 V
400 V
230 V
[mm]
690 V
500 V
440 V
400 V
230 V
[mm]
AC
AC a
(50/60
Hz)
690 V
500 V
440 V
400 V
230 V
[mm]
Dimensions WxHxD
Type
Rated current In max. [A]
AC/DC
Rated insulation voltage Ui [V]
AC (50/60 Hz) / DC
Rated voltage Ue [V]
Number of poles
AC/DC
Max. switching current [A] (breaking)
Dimensions WxHxD
[mm]
a DC on request
38
IEC 947-2
EN 60 947-2
VDE 0660
NF63-HV
63
690
3/4
2.5 / 2.5
7.5 / 7.5
10 / 8
10 / 8
25 / 19
75/100x130x68
AC
Dimensions WxHxD
Type
Rated current In max. [A]
Rated insulation voltage Ui [V]
Number of poles
Rated
breaking
capacity [kA]
690 V
500 V
440 V
400 V
230 V
[mm]
AC
Dimensions WxHxD
Type
Rated current In max. [A]
Rated insulation voltage Ui [V]
Number of poles
Rated
breaking
capacity [kA]
NF63-SV
63
600
3/4
7.5 / 7.5
7.5 / 7.5
7.5 / 7.5
15 / 15
75/100x130x68
AC
Dimensions WxHxD
Type
Rated current In max. [A]
Rated insulation voltage Ui [V]
Number of poles
Disconnectors
MCCB Overview
690 V
500 V
440 V
400 V
230 V
[mm]
NF32-SV
32
600
3
2.5 / 2.5
2.5 / 2.5
5/5
7.5 / 7.5
75x130x68
DSN32-SV
32
600
500 / 250
3
256 / 128
75x130x68
DSN63-SV
63
600
500 / 250
3/4
504 / 252
75/120x130x68
* adjustable
NF125-SGV
125*
690
3/4
8/8
30 / 30
36 / 36
36 / 36
85 / 85
105/140x165x68
NF125-LGV
125*
690
3/4
8/8
36 / 36
50 / 50
50 / 50
90 / 90
105/140x165x68
NF125-HGV
125*
690
3/4
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
105/140x165x68
NF125-RGV
125*
690
3
125 / 125
150 / 150
150 / 150
105x165x68
NF125-UV
125
690
3/4
10 / 10
200 / 200
200 / 200
200 / 200
200 / 200
105/140x240x68
DSN125-SGV
125
690
690 / 300
3/4
1000 / 500
105/140x165x68
WS-V series
NF125-SEV
125*
690
3/4
8/8
30 / 30
36 / 36
36 / 36
85 / 85
105/140x165x68
NF125-HEV
125*
690
3/4
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
105/140x165x68
NF160-SGV
160*
690
3/4
8/8
30 / 30
36 / 36
36 / 36
85 / 85
105/140x165x68
NF160-LGV
160*
690
3/4
8/8
36 / 36
50 / 50
50 / 50
90 / 90
105/140x165x68
NF160-HGV
160*
690
3/4
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
105/140x165x68
DSN160-SGV
160
690
690 / 300
3/4
1280 / 640
105/140x165x68
MCCB Overview
WS-V series
NF250-SEV
250*
690
3/4
8/8
30 / 30
36 / 36
36 / 36
85 / 85
105/140x165x68
NF400-SEW
400*
690
3/4
10 / 10 b
30 / 30 b
42 / 42 b
50 / 50 b
85 / 85 b
140/185x257x103
NF630-SEW
630*
690
3/4
10 / 10
30 / 30
42 / 42
50 / 50
85 / 85
140/185x257x103
NF800-SEW
800*
690
3/4
10 / 10
30 / 30
42 / 42
50 / 50
85 / 85
210/280x275x103
WSS series
NF1000-SEW
1000*
690
3/4
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
210/280x406x140
NF1250-SEW
1250*
690
3/4
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
210/280x406x140
NF1600-SEW
1600*
690
3/4
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
210/280x406x140
NF250-HEV
250*
690
3/4
10 / 8
50 / 50
65 / 65
75 / 75
100 / 100
105/140x165x68
NF400-HEW
400*
690
3/4
10 / 10
50 / 50
65 / 65
70 / 70
100 / 100
140/185x257x103
NF400-REW
400*
690
3
15 / 10
70 / 35
125 / 63
125 / 63
150 / 75
140x257x103
NF400-UEW
400*
690
3/4
35 / 35
170 / 170
200 / 200
200 / 200
200 / 200
140/280x297/322x200
DSN400-SW
400
690
690 / 250
3/4
3200 / 1600
140/185x257x103
NF630-HEW
630*
690
3/4
15 / 15
50 / 50
65 / 65
70 / 70
100 / 100
140/185x257x103
NF630-REW
630*
690
3
20 / 15
70 / 35
125 / 63
125 / 63
150 / 75
140x257x103
DSN630-SW
630
690
690 / 250
3/4
5040 / 2520
140/185x257x103
NF800-HEW
800*
690
3/4
15 / 15
50 / 50
65 / 65
70 / 70
100 / 100
210/280x275x103
NF800-REW
800*
690
3
20 / 15
70 / 35
125 / 63
125 / 63
150 / 75
210x275x103
NF800-UEW
800*
690
3/4
35 / 35
170 / 170
200 / 200
200 / 200
200 / 200
210/280x322x200
DSN800-SW
800
690
690 / 250
3/4
6400 / 3200
210/280x275x103
MCCB Overview
NF250-SGV
250*
690
3/4
8/8
30 / 30
36 / 36
36 / 36
85 / 85
105/140x165x68
NF250-LGV
250*
690
3/4
8/8
36 / 36
50 / 50
50 / 50
90 / 90
105/140x165x68
NF250-HGV
250*
690
3/4
10 / 8
50 / 50
65 / 65
75 / 75
100 / 100
105/140x165x68
NF250-RGV
250*
690
3
125 / 125
150 / 150
150 / 150
105x165x68
NF250-UV
250
690
3/4
15 / 15
200 / 200
200 / 200
200 / 200
200 / 200
105/140x240x68
DSN250-SGV
250
690
690 / 300
3/4
2000 / 1000
105/140x165x68
DSN1000-SW
1000
660
660 / 250
3/4
8000 / 14000
210/280x406x140
DSN1250-SW
1250
660
660 / 250
3/4
10000 / 5000
210/280x406x140
DSN1600-SW
1600
660
660 / 250
3/4
12800 / 6400
210/280x406x140
* adjustable
39
MCCB - Specifications
40 C
Rated data
Number of poles
Rated insulation voltage Ui [V]
Rated
breaking
capacity [kA]
IEC/EN 60947-2
(Icu / Ics)
DC
Utilization category
Rated impulse withstand voltage Uimp [kV]
Pollution degree
Reverse connection
Suitable for isolation
ca
c
Dimensions [mm]
a
b
c
ca
Externl accessories
Mechanical data
Weight [kg]
Others
MCCB - Specifications
AC
(50/60 Hz)
AC
690 V
500 V
440 V
400 V
230 V
250 V
Alarm switch
(AL)
Auxiliary switch
(AX)
CassetteShunt
trip
(SHT)
type
Non-synchronous
accessories
Under(UVT-N)
voltage closing
trip
Synchronous closing (UVT-S)
with terminal block
(SLT)
Accessories
connection
with internal terminal type
Screw terminal (standard)
Front
Solderless terminal
Busbar terminal
Installation
and
Rear
(B)
connection
Rear
(PM)
Plug-in
Rear front IP 20
(PM-IP)
with auto trip
a
(PAL)
Pre-alarm-contact output
Built-in
accessories
(OAL)
Overcurrent trip alarm a
(V)
External operating Door mounting
handle
Mounted on breaker
(R)
Electrical operation device
(MDS)
(HL)
Handle lock for use
Handle lock device with padlock
(HL-S)
Lock cover
(LC)
Large
(TC-L)
Small
(TC-S)
Terminal
cover
For rear connection
(BTC)
For plug-in
(PTC)
Mechanical interlock
(MI)
Insulating barrier Between phases (Standard)
(BA-F)
Adapter for IEC 35 mm rail
CE marking
CCC recognition
Automatic tripping device
Trip button
Both PAL and OAL is not available. Only one specified. b Others on request.
Missing specifications accord. to IEC/EN 60947-2 on request.
40
NF32-SV
32
NF63-SV
63
NF63-HV
63
3/4
690
2.5 / 2.5
7.5 / 7.5
10 / 8
10 / 8
25 / 19
7.5 / 7.5d
A
8
3
V
V
75 / 100
130
68
90
0.75 / 1,0
V
V
V
NF125-SGV
125
1620, 2025, 2532,
3240, 3550, 4563,
5680, 70100, 90125
Adjustable
3/4
690
8/8
30 / 30
36 / 36
36 / 36
85 / 85
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3
600
2.5 / 2.5
2.5 / 2.5
5/5
7.5 / 7.5
2.5 / 2.5
A
8
3
V
V
75
130
68
90
0.65
V
V
V
3/4
600
7.5 / 7.5
7.5 / 7.5
7.5 / 7.5
15 / 15
7.5 / 7.5
A
8
3
V
V
75 / 100
130
68
90
0.75 / 1,0
V
V
V
3/4
690
8/8
30 / 30
36 / 36
36 / 36
85 / 85
A
8
3
V
V
105 / 140
165
68
92
1.7 / 2.2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V/
Self-declaration
Recognized
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Electronic
Equipped
On request.
Use of 3- or 4-pole breaker for DC, see wiring diagram on the next page.
NF125-SEV
125
1632, 3263,
63125
Adjustable
MCCB - Specifications
NF125-HGV
125
NF125-HEV
125
NF125-RGV
125
NF125-UV
125
1632, 3263,
63125
Adjustable
3/4
690
8/8
36 / 36
50 / 50
50 / 50
90 / 90
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
40 / 40d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
A
8
3
V
V
105 / 140
165
68
92
1.7 / 2.2
V
V
V
3
690
125 / 125
150 / 150
150 / 150
150 / 150
150 / 150
A
8
3
V
V
105
165
68
92
1.8
V
V
V
3/4
690
10 / 10
200 / 200
200 / 200
200 / 200
200 / 200
A
8
3
V
V
90 / 120
191
68
92
1.5 / 1.9
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
/V
V /
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Electronic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Thermal-magnetic
Equipped
5
MCCB - Specifications
NF125-LGV
125
xdfgb
3-pole
Line
Load
Line
Load
41
MCCB - Specifications
40 C
Rated data
Number of poles
Rated insulation voltage Ui [V]
Rated
breaking
capacity [kA]
IEC/EN 60947-2
(Icu / Ics)
DC
Utilization category
Rated impulse withstand voltage Uimp [kV]
Pollution degree
Reverse connection
Suitable for isolation
ca
c
Dimensions [mm]
a
b
c
ca
Externl accessories
Mechanical data
Weight [kg]
Others
MCCB - Specifications
AC
(50/60 Hz)
AC
690 V
500 V
440 V
400 V
230 V
250 V
Alarm switch
(AL)
Auxiliary switch
(AX)
CassetteShunt
trip
(SHT)
type
Non-synchronous
accessories
Under(UVT-N)
voltage closing
trip
Synchronous closing (UVT-S)
with terminal block
(SLT)
Accessories
connection
with internal terminal type
Screw terminal (standard)
Front
Solderless terminal
Busbar terminal
Installation
and
Rear
(B)
connection
Rear
(PM)
Plug-in
Rear front IP 20
(PM-IP)
with auto trip
a
(PAL)
Pre-alarm-contact output
Built-in
accessories
(OAL)
Overcurrent trip alarm a
(V)
External operating Door mounting
handle
Mounted on breaker
(R)
Electrical operation device
(MDS)
(HL)
Handle lock for use
Handle lock device with padlock
(HL-S)
Lock cover
(LC)
Large
(TC-L)
Small
(TC-S)
Terminal
cover
For rear connection
(BTC)
For plug-in
(PTC)
Mechanical interlock
(MI)
Insulating barrier Between phases (Standard)
(BA-F)
Adapter for IEC 35 mm rail
CE marking
CCC recognition
Automatic tripping device
Trip button
Both PAL and OAL is not available. Only one specified. b Others on request.
Missing specifications accord. to IEC/EN 60947-2 on request.
42
NF160-SGV
160
NF160-LGV
160
NF160-HGV
160
NF250-SGV
250
NF250-SEV
250
125160
Adjustable
125160
Adjustable
125160
Adjustable
125160, 140200,
175250
Adjustable
80160, 125250
Adjustable
3/4
690
8/8
30 / 30
36 / 36
36 / 36
85 / 85
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
8/8
36 / 36
50 / 50
50 / 50
90 / 90
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
40 / 40d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
8/8
30 / 30
36 / 36
36 / 36
85 / 85
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
8/8
30 / 30
36 / 36
36 / 36
85 / 85
A
8
3
V
V
105 / 140
165
68
92
1.7 / 2.2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Electronic
Equipped
On request.
Use of 3- or 4-pole breaker for DC, see wiring diagram on the next page.
MCCB - Specifications
NF250-HGV
250
NF250-HEV
250
NF-250-RGV
250
NF250-UV
250
80160, 125250
Adjustable
3/4
690
8/8
36 / 36
50 / 50
50 / 50
90 / 90
20 / 20d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
40 / 40d
A
8
3
V
V
105 / 140
165
68
92
1.6 / 2.0
V
V
V
3/4
690
10 / 8
50 / 38
65 / 65
75 / 75
100 / 100
A
8
3
V
V
105 / 140
165
68
92
1.7 / 2.2
V
V
V
3
690
125 / 125
150 /150
150 / 150
A
8
3
V
V
105
165
68
92
1.8
V
V
V
3/4
690
15 / 15
200 / 200
200 / 200
200 / 200
200 / 200
A
8
3
V
V
105 / 140
240
68
92
2.7 / 3.7
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V /
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognized
Electronic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Recognition in process
Thermal-magnetic
Equipped
V
V
V
V
V
V
V
V
V
V
V
V
Self-declaration
Thermal-magnetic
Equipped
5
MCCB - Specifications
NF250-LGV
250
3-pole
Line
Load
Line
Load
43
MCCB - Specifications
Rated data
Type
Frame (A)
Rated current In [A]
at ambient temperature
Number of poles
Rated insulation voltage Ui [V]
Rated
breaking
capacity [kA]
40 C
IEC/EN 60947-2
AC a
(50/60 Hz)
(Icu / Ics)
AC
690 V
500 V
440 V
400 V
230 V
Utilization category
Rated short-time withstand current Icw [kA/s]
Rated impulse withstand voltage Uimp [kV]
Pollution degree
Reverse connection
Suitable for isolation
Dimensions [mm]
a
b
c
ca
Mechanical data
Weight [kg]
Cassettetype
accessories
Accessories
connection
Installation
and
connection
Built-in
accessories
Externl accessories
External operating
handle
Others
MCCB - Specifications
ca
c
Alarm switch
(AL)
Auxiliary switch
(AX)
Shunt trip
(SHT)
Non-synchronous
Under(UVT-N)
voltage closing
trip
Synchronous closing (UVT-S)
with terminal block
(SLT)
with internal terminal type c
Front
Busbar terminal (standard)
Rear
(B)
Plug-in
Rear
(PM)
Pre-alarm-contact output
(PAL)
Trip indicator
(TI)
Door mounting
(V)
Mounted on breaker
(R)
Terminal
cover
Large
For rear connection
Mechanical interlock
Insulating barrier Between phases (Standard)
Marine approval d for 3 pole breakers
Automatic tripping device
Trip button
NF400-SEW
400
200400
Adjustable
3/4
690
10 / 10 (5 / 5) b
30 / 30 (25 / 25) b
42 / 42 (36 / 36) b
50 / 50 (36 / 36) b
85 / 85 (65 / 65) b
B
5 / 0.25
8
3
V
V
140 / 185
257
103
155
6.0 / 7.8
V
V
V
NF400-HEW
400
200400
Adjustable
3/4
690
10 / 10
50 / 50
65 / 65
70 / 70
100 / 100
B
5 / 0.25
8
3
V
V
140 / 185
257
103
155
6.0 / 7.8
V
V
V
NF400-REW
400
200400
Adjustable
3
690
15 / 10
70 / 35
125 / 63
125 / 63
150 / 75
B
5 / 0.25
8
3
V
V
140
257
103
155
6.0
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
(MDS)
(HL)
(HL-S)
(TC-L)
(BTC)
(MI)
(BA-F)
V
V
V
V
V
V
LR, GL, BV, DNV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
44
On request.
Others on request.
MCCB - Specifications
NF630-SEW
630
300630
Adjustable
3/4
690
10 / 10
30 / 30
42 / 42
50 / 50
85 / 85
B
7.6 / 0.25
8
3
U
U
140 / 185
257
103
155
6.5 / 8.3
V
V
V
NF630-HEW
630
300630
Adjustable
3/4
690
35 / 18
50 / 50
65 / 65
70 / 70
100 / 100
B
7.6 / 0.25
8
3
U
U
140 / 185
257
103
155
6.5 / 8.3
V
V
V
NF630-REW
630
300630
Adjustable
3
690
20 / 15
70 / 35
125 / 63
125 / 63
150 / 75
B
7.6 / 0.25
8
3
U
U
140
257
103
155
6.5
V
V
V
V
V
V
V
V
V/
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
5
MCCB - Specifications
NF400-UEW
400
200400
Adjustable
3/4
690
35 / 35
170 / 170
200 / 200
200 / 200
200 / 200
B
5 / 0.25
8
3
U
U
140 / 280
297 / 322
200
252
16.7 / 26.1
V
V
V
45
MCCB - Specifications
Rated data
Type
Frame (A)
Rated current In [A]
at ambient temperature
Number of poles
Rated insulation voltage Ui [V]
Rated
breaking
capacity [kA]
NF800-SEW
800
400800
Adjustable
3/4
690
10 / 10
30 / 30
42 / 42
50 / 50
85 / 85
B
9.6 / 0.25
8
3
V
V
210 / 280
275
103
155
10.9 / 14.2
V
V
V
NF800-HEW
800
400800
Adjustable
3/4
690
15 / 15
50 / 50
65 / 65
70 / 70
100 / 100
B
9.6 / 0.25
8
3
V
V
210 / 280
275
103
155
10.9 / 14.2
V
V
V
NF800-REW
800
400800
Adjustable
3
690
70 / 35
125 / 63
125 / 63
150 / 75
B
9.6 / 0.25
8
3
V
V
210
275
103
155
10.9
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
(MDS)
(HL)
(HL-S)
(TC-L)
(BTC)
(MI)
(BA-F)
V
V
V
V
V
V
LR, GL, BV, DNV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
V
V
V
V
V
V
LR, GL, BV, AB
Electronic
Equipped
40 C
IEC/EN 60947-2
AC a
(50/60 Hz)
(Icu / Ics)
AC
690 V
500 V
440 V
400 V
230 V
Utilization category
Rated short-time withstand current Icw [kA/s]
Rated impulse withstand voltage Uimp [kV]
Pollution degree
Reverse connection
Suitable for isolation
Dimensions [mm]
Mechanical data
Weight [kg]
Cassettetype
accessories
Accessories
connection
Installation
and
connection
Built-in
accessories
Externl accessories
External operating
handle
Others
MCCB - Specifications
a
b
c
ca
ca
c
Alarm switch
(AL)
Auxiliary switch
(AX)
Shunt trip
(SHT)
Non-synchronous
Under(UVT-N)
voltage closing
trip
Synchronous closing (UVT-S)
with terminal block
(SLT)
with internal terminal type c
Front
Busbar terminal (standard)
Rear
(B)
Plug-in
Rear
(PM)
Pre-alarm-contact output
(PAL)
Trip indicator
(TI)
Door mounting
(V)
Mounted on breaker
(R)
Terminal
cover
Large
For rear connection
Mechanical interlock
Insulating barrier Between phases (Standard)
Marine approval d for 3 pole breakers
Automatic tripping device
Trip button
a
DC type on request. b On request. c Others on request.
Missing Specifications accord. to IEC/EN 60947-2 on request.
46
Assembly by factory.
MCCB - Specifications
NF1000-SEW
1000
5001000
Adjustable
3/4
690
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
B
20 / 0.3
8
3
V
V
210 / 280
406
140
190
23.5 / 30.7
V
V
V
NF1250-SEW
1250
6001250
Adjustable
3/4
690
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
B
20 / 0.3
8
3
V
V
210 / 280
406
140
190
23.5 / 30.7
V
V
V
NF1600-SEW
1600
8001600
Adjustable
3/4
690
25 / 13
65 / 33
85 / 43
85 / 43
125 / 63
B
20 / 0.3
8
3
V
V
210 / 280
406
140
190
34.5 / 41.2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Electronic
Equipped
V
V
LR, GL, AB
Electronic
Equipped
V
V
LR, GL, AB
Electronic
Equipped
V
V
Electronic
Equipped
5
MCCB - Specifications
NF800-UEW
800
400800
Adjustable
3/4
690
35 / 35
170 / 170
200 / 200
200 / 200
200 / 200
B
9.6 / 0.25
8
3
V
V
210 / 280
322
200
252
27.6 / 33.7
V
V
V
47
MCCB - Specifications
40 C
AC
DC
kV
Rated data
Dimensions [mm]
A
A
Mechanical data
48
DSN250-SGV
250
3/4
690
690
300
8
3
AC-23A, DC-23A
2500 / 1000
3/5
2000 / 1000
3/5
25000
10000 / 1000
1000
1000
2000
3000
4000
1500
1500
3000
4000
6000
378 / 155
12
V
75 / 100
130
68
90
0.6 / 0.7
V
V
V
V
V
Vc
V
V
V
750 / 315
12
V
105 / 140
165
86
110
2.0 / 2.6
V
V
V
V
V
V
Vc
V
V
V
960 / 400
12
V
105 / 140
165
86
110
2.0 / 2.6
V
V
V
V
V
V
Vc
V
V
V
1500 / 625
12
V
105 / 140
165
86
110
2.0 / 2.6
V
V
V
V
V
V
Vc
V
V
V
Alarm switch
(AL)
Auxiliary switch
(AX)
Shunt trip
(SHT)
Undervoltage trip
(UVT)
with terminal block
(SLT)
Accessories
connection
with internal terminal type b
Screw terminal
Front
Solderless terminal
Busbar terminal
Installation
and
Rear
(B)
connection
Rear
(PM)
Plug-in
Rear front IP 20 (PM-IP)
with auto trip
(V)
External operating Door mounting
handle
Mounted on breaker
(R)
Electrical operation device
(MDS)
(HL)
Handle lock for use
Handle lock device with padlock
(HL-S)
Lock cover
(LC)
Large
(TC-L)
Terminal
Small
(TC-S)
cover
For rear connection
(BTC)
Mechanical interlock
(MI)
Insulating barrier Between phases (Standard)
(BA-F)
Adapter for IEC 35 mm rail
Corresponding type of circuit breaker
b
DSN160-SGV
160
3/4
690
690
300
8
3
AC-23A, DC-23A
1600 / 640
3/5
1280 / 640
3/5
40000
20000 / 1000
192 / 80
12
V
75
130
68
90
0.55
V
V
V
V
V
Vc
V
V
V
Cassettetype
accessories
DSN125-SGV
125
3/4
690
690
300
8
3
AC-23A, DC-23A
1250 / 500
3/5
1000 / 500
3/5
50000
30000 / 1000
Weight [kg]
DSN63-SV
63
3/4
600
500
250
6
2
AC-23A, DC-23A
630 / 252
5
504 / 252
5
15000
8000 /
a
b
c
ca
ca
c
Externl accessories
MCCB - Specifications
DSN32-SV
32
3
600
500
250
6
2
AC-23A, DC-23A
320 / 128
5
256 / 128
5
10000
6000 /
On request.
V
V
V
V
V
V
V
V
V
NF32-SV
V
V
V
V
V
V
V
V
V
NF63-SV
V
V
V
V
V
V
V
V/
V/
V
V
NF125-SGV
V
V
V
V
V
V
V
V/
V/
V
V
NF160-SGV
V
V
V
V
V
V
V
V
V
V
V
NF250-SGV
Standard.
Assembly by factory.
TC-N.
MCCB - Specifications
DSN630-SW
630
3/4
690
690
250
8
3
AC-23A, DC-23A
6300 / 2520
3/5
5040 / 2520
3/5
6000
1000
DSN800-SW
800
3/4
690
690
250
8
3
AC-23A, DC-23A
8000 / 3200
3/5
6400 / 3200
3/5
4000
500
DSN1000-SW
1000
3/4
690
690
250
8
3
AC-23A, DC-23A
10000 / 4000
3/5
8000 / 4000
3/5
3000
500
DSN1250-SW
1250
3/4
690
690
250
8
3
AC-23A, DC-23A
12500 / 5000
3/5
10000 / 5000
3/5
2500
500
DSN1600-SW
1600
3/4
690
690
250
8
3
AC-23A, DC-23A
16000 / 6400
3/5
12800 / 6400
3/5
2500
500
6000
8000
10000
12000
12000
16000
10200
13600
17000
24000
24000
32000
2400 / 1000
12
V
140 / 185
257
103
155
5.7 / 7.5
V
V
V
V
V
V
Va
V
V
3780 / 1575
12
V
140 / 185
275
103
155
6.2 / 8.0
V
V
V
V
V
V
Va
V
V
4800 / 2000
12
V
210 / 280
275
103
155
10.9 / 14.2
V
V
V
V
V
V
Va
V
V
6000 / 2500
12
V
210 / 280
406
140
190
23.0 / 30.2
V
V
V
V
V
V
Va
Vd
Vd
7500 / 3125
12
V
210 / 280
406
140
190
23.0 / 30.2
V
V
V
V
V
V
Va
Vd
Vd
9600 / 4000
12
V
210 / 280
406
140
190
34.0 / 40.7
V
V
V
V
V
V
Va
Vd
Vd
V
V
V
V
V
V
V
V
NF400-SW
V
V
V
V
V
V
V
V
NF630-SW
V
V
V
V
V
V
V
V
NF800-SEW
V
V
V
V
V
Ve
V
V
V
NF1000-SEW
V
V
V
V
V
Ve
V
V
V
NF1250-SEW
V
V
V
V
V
V
V
V
NF1600-SEW
5
MCCB - Specifications
DSN400-SW
400
3/4
690
690
250
8
3
AC-23A, DC-23A
4000 / 1600
3/5
3200 / 1600
3/5
6000
1000
49
MCCB - Specifications
Type
254752
254753
254754
254755
254756
254757
254758
254759
254760
254761
254762
254763
254764
254765
254766
254789
254790
254791
254792
254793
254794
254795
254796
254797
254798
254799
NF63-SV
50
3A
4A
5A
6A
10 A
15 A
16 A
20 A
25 A
30 A
32 A
40 A
50 A
60 A
63 A
Art. no.
4 pole type
254739
254740
254741
254742
254743
254744
254745
254746
254747
253075
254748
254749
253073
254750
254751
5
MCCB - Specifications
Art. no.
3 pole type
S series with thermal-magnetic tripping device, AC, DC
1620 A
254908
2025 A
254909
2532 A
254910
3240 A
254911
NF125-SGV
3550 A
254912
4563 A
254913
5680 A
254914
70100 A
254915
90125 A
254916
Type
254917
254918
254919
254920
254921
254922
254923
254924
254925
254935
254936
254937
254938
254939
254940
254941
254942
255195
254943
254944
254945
254946
254947
254948
254949
254950
254951
254970
254971
254972
254973
254974
254975
254976
254977
254978
255033
255034
255035
255015
255016
255017
255018
255019
255020
255021
255022
255023
NF125-LGV
1620 A
2025 A
2532 A
3240 A
3550 A
4563 A
5680 A
70100 A
90125 A
Art. no.
4 pole type
MCCB - Specifications
Art. no.
4 pole type
255041
Art. no.
3 pole type
H series with thermal-magnetic tripping device, adjustable, AC, DC
125160 A
255136
NF250-HGV
140200 A
255137
175250 A
255138
Type
Art. no.
4 pole type
255139
255140
255141
255044
255047
255172
255173
255121
255122
255123
255168
255169
255130
255131
255132
255160
255161
255162
255163
255164
255165
5
MCCB - Specifications
Art. no.
3 pole type
S series with thermal-magnetic tripping device, adjustable, AC, DC
NF160-SGV
125160 A
255040
Type
Type
204781
204790
204798
204783
204792
204800
204786
204803
Type
Art. no.
3 pole type
Type
Art. no.
4 pole type
204811
204813
204815
Art. no.
3 pole type
Art. no.
4 pole type
Art. no.
3 pole type
Art. no.
4 pole type
254669
254722
254897
255037
255113
204778
204787
204794
204804
204806
204808
254723
254898
255038
255114
204779
204788
204795
204805
204807
204809
51
MCCB Accessories
Internal Accessories
Modular cassette type accessories
The new arrangement and design of pluggable
accessories such as indicator and auxiliary contacts allows you to modify the circuit in a way
that saves time and space at any time, even
when built in and ready for operation.
TL
AX AL
98
a
14
a
14
AXa
12
b
11
c
12
AXb
MITSUBISHI ELECTRIC
11
AXc
Is
Ts
Ii
SHTA240-2GSWRS
ALAX-2GSWLS
AUXILIARY SWITCH
50/60Hz
Ir
Ip
Ii(X100A)
95
c
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
98
ALa
AC100-240V
T
TEST
96
b
ALARM SWITCH
96
ALb
98
ALc
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
MCCB Accessories
For the breakers of the Super Series, 1000 A up to 1600 A, please contact your Distributor.
52
MCCB Accessories
Function
Catalogue reference
AL (Alarm switch)
Page 54
AX (Auxiliary switch)
Page 54
The shunt trip SHT trips the breaker automatically by remote. A cut-off switch is integrated.
The allowable tripping voltage is 70% to 110% of the rated voltage for both AC and DC.
The undervoltage trip UVT trips the breaker automatically when the voltage drops. The tripping voltage is 35% to 70% of the
rated voltage. When the voltage recovers to 85% of the rated voltage or above, the UVT can be reset and the breaker closed.
Page 56
Page 58
Application
98
ALa
AX AL
95
c
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
14
AXa
12
b
11
c
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
11
AXc
12
AXb
MITSUBISHI ELECTRIC
AUXILIARY SWITCH
The terminal cover for the lead-wire terminals is available for the safety of live parts.
ALAX-2GSWLS
14
a
98
a
96
b
ALARM SWITCH
96
ALb
98
ALc
Cassette-type accessory
Example:
ALAX, also for SHT, UVT
Application
MITSUBISHI ELECTRIC
ALAX-2GSWLS
Example:
ALAX, also for SHT, UVT
53
MCCB Accessories
MCCB Accessories
AX
11
AXc
11
c
12
b
AC
125V
5A
AC
250V
3A
DC
125V
0.4A
DC
250V
0.2A
AUXILIARY SWITCH
12
AXb
14
AXa
14
a
zz AL, AX and ALAX standard types are for leftside mounting and equipped with lead-wire
terminal block SLT.
Contact plans
TEST
TEST
MCCB Accessories
6
Figure shows Lead-wire terminal block type (SLT).
98
14
96
12
95
11
(1 W)
Alarm switch AL
(1 W)
Auxiliary switch AX
Switching Operation
Alarm switch (AL) operation
Main MCCB conditions
OFF or ON
Trip
Alarm contacts
AXa 14 (open)
AXc 11
(DC+) a
AXb 12 (closed)
AXa 14 (closed)
AXc 11
(DC+) a
AXb 12 (open)
Trip
AL/AX/ALAX-10
a
54
Voltage (V AC)
460
250
125
460
250
125
3
5
5
10
10
2
3
2
10
10
Voltage (V DC) a
250
125
30
250
125
30
MCCB Accessories
Breaker type
Mounted on
Art. no.
AL-05SVLS
1W
Left side
267212
AL-4SWLS
AL2-4SWLS
AL3-8SWLS
AL-10SWL
1W
2W
3W
1W
NF/DSN3263
NF/DSN125250
NF/DSN400800
NF/DSN400800
NF/DSN800
NF/DSN10001600
Left-side
Left-side
Left-side
Left-side
205763
205764
205765
205766
1W
NF/DSN3263
NF/DSN125250
Left side
267210
NF/DSN3263
NF/DSN125250
NF/DSN3263
NF/DSN125250
NF/DSN400800
NF/DSN400800
NF/DSN800
NF400-UEW 4P
NF/DSN800
NF400-UEW 4P
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
Left side
267238
Left-side
146382
Left-side
Left-side
205767
205768
Left-side
205769
Left-side
205770
Left-side
Left-side
Left-side
205771
205772
205773
NF/DSN3263
NF/DSN125250
NF/DSN3263
NF/DSN125250
Left side
267236
Left side
267246
Mounted on
Art. no.
Left side
146381
Left side
205774
Left side
205775
Left side
Left side
205776
205777
Left side
139509
AX2-05SVLS
2W
AX-4SWLS
AX2-4SWLS
1W
2W
AX3-8SWLS
3W
AX4-8SWLS
4W
AX-10SWLS
AX2-10SWLS
AX3-10SWLS
1W
2W
3W
6
MCCB Accessories
AX-05SVLS
1W
AX2-05SVLS
2W
Contacts
Breaker type
AL AX
Alarm switch and Auxiliary switch ALAX with lead-wire terminal block SLT
NF/DSN3263
ALAX-05SVLS
1W+1W
NF/DSN125250
NF/DSN400800
ALAX-4SWLS
1W+1W
NF400-UEW 4P
NF/DSN400800
AL2AX2-4SWLS
2W+2W
NF400-UEW 4P
ALAX-10SWL
1W+1W
NF/DSN10001600
AL1AX2-10SWL
1W+2W
NF/DSN10001600
Type
55
MCCB Accessories
Application
The shunt trip device SHT trips the breaker
automatically by remote. A cut-off switch is
integrated.
The allowable tripping voltage range is 70 % to
110 % of the rated voltage for both AC and DC.
The SHT is mounted on the right side of the
breaker and equipped with lead-wire terminal
block SLT as standard.
50/60Hz
SHTA240-2GSWRS
SHTA240-2GSWRS
Ir
Ip
TL
Is
AC100-240V
C2
S2
50/60Hz
C1
S1
SHT
AC100-240V
Ir
Ip
Ii
TL
Is
Ts
Ts
Ii(X100A)
Ii(X100A)
Ii
Contact plans
C1
MCCB Accessories
SHT
6
Figure shows Lead-wire terminal block type (SLT).
C2
Coil ratings
MCCB type a
Cut-off switch
Voltage (V) b
Input c
AC (VA)
DC (W)
Operating time
(msec) d
NF32-SV
NF63-SV
NF63-HV
Equipped
AC 2448
AC 100240
AC 380550
(50 / 60 Hz)
DC 100125
120
50
15
NF125-SGV/SEV
NF125-HGV/HEV
NF125-RGV/UGV
NF160-SGV/SEV
NF160-HGV/HEV
NF250-SGV/SEV
NF250-HGV/HEV
NF250-RGV/UGV
Equipped
Equipped
NF1000-SEW
NF1250-SEW
NF1600-SEW
Equipped
a
b
c
d
56
60
AC 2448 / DC 2448
AC 100450 / DC 100200
AC 380550
(50 / 60 Hz)
AC 100120
AC 200240
AC 380450
(50 / 60Hz)
DC 100
100 V: 20
200 V: 50
330 V: 120
450 V: 170
100 V: 10
200 V: 35
515
200
70
715
MCCB Accessories
NF/DSN3263
NF/DSN125250
SHT-4SWRS
SHT48-4SWRS
NF/DSN400800
SHTA550-4SWRS
Art. no.
267479
267484
267489
267494
267499
267504
267509
267514
205778
SHT-4SWRFS
205780
SHT48-4SWRFS
205782
SHTA550-4SWRFS
Breaker type
NF/DSN3263
NF/DSN125250
205779
NF/DSN400630
SHTA120-10SWRS
SHTA240-10SWRS
SHTA450-10SWRS
SHTD024-10SWRS
SHTD110-10SWRS
NF/DSN10001600
205787
205789
205791
205793
205795
205781
205783
Rated voltage
AC 2448 V
AC 100240 V
AC 380550 V
DC 12 V
DC 2436 V
DC 3648 V
DC100125 V
DC220250 V
AC 100450 V /
DC100200 V
AC 2448 V /
DC2448V
AC 380550 V
SHTA550-8SWRFS
205786
AC 100450 V /
DC100200 V
AC 2448 V /
DC2448V
AC 380550 V
SHTA120-10SWRFS
SHTA240-10SWRFS
SHTA450-10SWRFS
SHTD024-10SWRFS
SHTD110-10SWRFS
205788
205790
205792
205794
205796
AC 100120 V
AC 200240 V
AC 380450 V
DC 24 V
DC 110 V
SHT-8SWRFS
Art. no.
267480
267485
267490
267495
267500
267505
267510
267515
SHT48-8SWRFS
205784
NF/DSN800
NF400-UEW 4P
NF/DSN10001600
205785
6
MCCB Accessories
Breaker type
NF/DSN3263
NF/DSN125250
Rated voltage
AC 2448 V
AC 100240 V
AC 380550 V
DC 12 V
DC 2436 V
DC 3648 V
DC 100125 V
DC 220250 V
Art. no.
139529
139530
139531
139532
139533
139534
139535
139536
57
MCCB Accessories
Application
The undervoltage tripping device UVT trips
the breaker automatically when the voltage
drops. The tripping voltage is 35 % to 70 % of
the rated voltage. When the voltage recovers
to 85 % of the rated voltage or above, the UVT
can be reset and the breaker closed.
The UVT is mounted on the right side of the
breaker and equipped with lead-wire terminal
block SLT as standard.
D1
P1
D3 D2
P3 P2
SOURCE
Hi Lo
UVTSA-250GSWR
UVTSA-250GSWR
Ir
Ip
TL
Is
Ir
Ip
Ii
TL
Is
Ii
Ts
Ts
Ii(X100A)
Ii(X100A)
6
MCCB Accessories
Contact plans
J2
J2
J1
MITSUBISHI
J1
OFF
D2
D2
D1
D1
Coil ratings
Breaker type a
NF32-SV
NF63-SV
NF125-SGV / REV
NF125-HGV / HEV
NF125-RGV / UV
NF160-SGV / REV
NF160-HGV / HEV
NF250-SGV / REV
NF250-HGV / REV
NF250-RGV / UV
NF400-SEW / HEW / REW / UEW
NF630-SEW / HEW / REW
NF800-CEW / SEW / HEW / REW / UEW
NF1000-SEW
NF1250-SEW
NF1600-SEW
a
b
c
d
58
Voltage (V)
Standard
AC 100120
AC 200240
AC 220240
AC 380450
AC 400440
(50 / 60 Hz)
Input (VA)
Operating time c
(msec)
Making/breaking data
Breaker OFF
Breaker ON
30
3570 % UN
min. 85 % UN
530
(Instantaneous type)
3570 % UN
min. 85 % UN
535
(Time delay type with
3 voltage inputs)
3570 % UN
min. 85 % UN
DC 24, DC 110
Ud
AC 100110/120130
AC 200220/230250
AC 380415/440480
(50 / 60 Hz)
DC100/110
AC 100120/200240/380450
AC 200250/380450/460550
(50 / 60 Hz)
MCCB Accessories
Types of UVTs
Breaker type
AC 48 V
DC 48 V
AC 100130 V
DC 100130 V
AC 200220 V /
AC 230250 V
AC 380415 V /
AC 440480 V
AC 500550 V /
AC 600 V
UVTSAD048-05SVRS
UVTSAD048-05SVRFS
UVTSAD130-05SVRS
UVTSAD130-05SVRFS
UVTSA250-05SVRS
UVTSA250-05SVRFS
UVTSA480-05SVRS
UVTSA480-05SVRFS
UVTSA600-05SVRS
UVTSA600-05SVRFS
AC 200220 V /
AC 230250 V
AC 380415 V /
AC 440480 V
DC 24 / 48 V
DC 100 / 110 V
UVTSA250-4SWS
UVTSA250-4SWRFS
UVTSA250-8SWRFS
UVTSA250-10SWRS
UVTSA250-10SWRFS
UVTSA480-4SWS
UVTSA480-4SWRFS
UVTSA480-8SWRFS
UVTSA480-10SWRS
UVTSA480-10SWRFS
UVTSD048-4SWS
UVTSD048-4SWRFS
UVTSD048-8SWRFS
UVTND048-10SWRS
UVTND048-10SWRFS
UVTSD110-4SWS
UVTSD110-4SWRFS
UVTSD110-8SWRFS
UVTND110-10SWRS
UVTND110-10SWRFS
DC 24 / 48 V
DC 100 110 V
UVTSA690-05SVRSU05
UVTSA690-05SVRFSU05
UVTSD048-05SVRSU05
UVTSD048-05SVRFSU05
UVTSD110-05SVRSU05
UVTSD110-05SVRFSU05
DC 24 / 48 V
DC 100 110 V
UVTSA690-05SVRSU30
UVTSA690-05SVRFSU30
UVTSD048-05SVRSU30
UVTSD048-05SVRFSU30
UVTSD110-05SVRSU30
UVTSD110-05SVRFSU30
6
MCCB Accessories
59
MCCB Accessories
MCCB Accessories
267610
Art. no.
267615
267620
267625
267600
267605
Art. no.
267616
267621
267626
267601
267606
267611
UVTSA130-4SWS
UVTSA250-4SWS
UVTSA480-4SWS
UVTSD048-4SWS
UVTSD110-4SWS
NF/DSN400800
NF/DSN400800
NF/DSN400800
NF/DSN400800
NF/DSN400800
AC 100110 / 120130 V
AC 200220 / 230250 V
AC 380415 / 440480 V
DC 24 / 48 V
DC 100 / 110 V
205951
205953
205828
205932
205934
UVTSA130-4SWRFS
UVTSA250-4SWRFS
UVTSA480-4SWRFS
UVTSD048-4SWRFS
UVTSD110-4SWRFS
NF/DSN400630
NF/DSN400630
NF/DSN400630
NF/DSN400630
NF/DSN400630
AC 100110 / 120130 V
AC 200220 / 230250 V
AC 380415 / 440480 V
DC 24 / 48 V
DC 100 / 110 V
205952
205954
205955
205933
205935
UVTSA130-10SWRS
UVTSA250-10SWRS
UVTSA480-10SWRS
UVTND048-10SWRS
UVTND110-10SWRS
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
AC 100110 / 120130 V
AC 200220 / 230250 V
AC 380415 / 440480 V
DC 24 / 48 V
DC 100 / 110 V
205941
205943
205945
205947
205949
UVTSA130-8SWRFS
UVTSA250-8SWRFS
UVTSA480-8SWRFS
UVTSD048-8SWRFS
UVTSD110-8SWRFS
NF/DSN800
NF/DSN800
NF/DSN800
NF/DSN800
NF/DSN800
AC 100110 / 120130 V
AC 200220 / 230250 V
AC 380415 / 440480 V
DC 24 / 48 V
DC 100 / 110 V
205936
205937
205938
205939
205940
UVTSA130-10SWRFS
UVTSA240-10SWRFS
UVTSA480-10SWRFS
UVTND048-10SWRFS
UVTND110-10SWRFS
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
AC 100110 / 120130 V
AC 200220 / 230250 V
AC 380415 / 440480 V
DC 24 / 48 V
DC 100 / 110 V
205942
205944
205946
205948
205950
Undervoltage tripping device UVT, short-time delay type, non-synchronous closing, mounted on right-side
with lead-wire terminal block SLT, for 3-pole breakers
Type
Breaker type
Rated voltage
UVTSA048-05SVRSU05
NF/DSN32250
AC 24 / 48 V
UVTSA450-05SVRSU05
NF/DSN32250
AC 120 / 240 / 450 V
UVTSA550-05SVRSU05
NF/DSN32250
AC 250 / 450 / 550 V
UVTSA690-05SVRSU05
NF/DSN32250
AC 450 / 550 / 690 V
UVTSD048-05SVRSU05
NF/DSN32250
DC 24 / 48 V
UVTSD110-05SVRSU05
NF/DSN32250
DC 100 110 V
Art. no.
267690
267695
267700
267705
267710
267715
Art. no.
267691
267696
267701
267706
267711
267716
Undervoltage tripping device UVT, long-time delay type, non-synchronous closing, mounted on right-side
with lead-wire terminal block SLT, for 3-pole breakers
Type
Breaker type
Rated voltage
UVTSA048-05SVRSU30
NF/DSN32250
AC 24 / 48 V
UVTSA450-05SVRSU30
NF/DSN32250
AC 120 / 240 / 450 V
UVTSA550-05SVRSU30
NF/DSN32250
AC 250 / 450 / 550 V
UVTSA690-05SVRSU30
NF/DSN32250
AC 450 / 550 / 690 V
UVTSD048-05SVRSU30
NF/DSN32250
DC 24 / 48 V
UVTSD110-05SVRSU30
NF/DSN32250
DC 100 110 V
60
Art. no.
267720
267725
267730
267735
267740
267745
Art. no.
267721
267726
267731
267736
267741
267746
MCCB Accessories
Fixed
Front (F)
MITSUBISHI
NO-FUSE BREAKER
Appearance
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
OFF
MODEL
In
100A
Ir 63-100A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
MITSUBISHI
In
MITSUBISHI ELECTRIC
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
100A
Ir 63-100A
POLE
T
Ir
Ip
TL
Is
Ui690V
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
OFF
MODEL
3P
Uimp 8kV
ON
Cat.A
Ii
Ts
Ii(X100A)
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
IEC60947-2
JIS C 8201-2
MODEL
ON
PUSH TO TRIP
TEST
OFF
NO-FUSE BREAKER
3P
Uimp 8kV
Cat.A
Plug-in
Rear (PM)
Rear (B)
In
100A
Ir 63-100A
MITSUBISHI ELECTRIC
PUSH TO TRIP
POLE
Ui690V
ON
MITSUBISHI ELECTRIC
PUSH TO TRIP
TEST
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
3P
Uimp 8kV
Cat.A
Ir
Ip
TL
Is
Ii
Ts
T
TEST
Ii(X100A)
Ir
Ip
TL
Is
Ii
Ts
Ii(X100A)
Standard
Option
Option
Front (Standard)
U
U
U
Rear
U
U
b
Solderless terminals
Ua
Plug-in
U
U
b
6
MCCB Accessories
Frame size
32250 A
400800 A
10001600 A
Connection Accessories
Rear studs ST
Type
ST-05SV3
ST-05SV4
ST-1SV3
ST-1SV4
ST-2SV3
ST-2SV4
ST-4SW3
ST-4SW4
ST-6SW3
ST-6SW4
ST-8SW3
ST-8SW4
Plug-in sets PM
No. of Poles
3
4
3
4
3
4
3
4
3
4
3
4
Breaker type
For W75 models
NF/DSN32250
NF/DSN400
NF/DSN630
NF/DSN800
Art. no.
267533
267534
267537
267538
267540
267541
205956
205957
205958
205959
205960
205961
Solderless terminals SL
Type
No. of Poles
SL-1SV3L
SL-1SV3G
SL-1SV4L
SL-1SV4G
SL-2SV3B
SL-2SV3L
SL-2SV3G
SL-2SV4B
SL-2SV4L
SL-2SV4G
SL-2UV3B
SL-2UV3L
SL-2UV3G
SL-2UV4B
SL-2UV4L
SL-2UV4G
3
3
4
4
3
3
3
4
4
4
3
3
3
4
4
4
Breaker type
NF-UV
Connected wire
size
2.525 mm
2570 mm
2.525 mm
2570 mm
2.516 mm
1495 mm
70125 mm
2.516 mm
1495 mm
70125 mm
2.516 mm
1495 mm
70125 mm
2.516 mm
1495 mm
70125 mm
Art. no.
267516
267517
267518
267519
267520
267521
267522
267523
267524
267525
267526
267527
267528
267529
267530
267531
Type
PLT-05SV
PLT-2RV
PMD-05SV3
PMD-05SV4
PMDN-05SV3H
PMDN-1SV3
PMDN-1SV4
PMDN-2SV3
PMDN-2SV4
PMN-05SV3H
PMN-05SV3L
PMN-05SV4H
PMN-05SV4L
PMN-1SV3
PMN-1SV4
PMN-2SV3
PMN-2SV4
PMN-2UV3
PM-4SW3
PM-4SW4
PM-6SW3
PM-6SW4
PM-8SW3
PM-8SW4
No. of Poles
3
4
3
3
4
3
4
3
3
4
4
3
4
3
4
3
3
4
3
4
3
4
Breaker type
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF/DSN32250
NF-UV
NF/DSN400
NF/DSN630
NF/DSN800
Art. no.
267426
267427
267429
267430
267441
267447
267448
267450
267451
267456
267457
267458
267459
267461
267462
267464
267465
267467
205962
205963
205964
205965
205966
205967
61
MCCB Accessories
Application
MITSUBISHI
MODEL
In
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
OFF
NO-FUSE BREAKER
NF125-SGW
100A
Ir 63-100A
POLE
MITSUBISHI ELECTRIC
PUSH TO TRIP
MODEL
60
50/60Hz
100
3.5
3
2.5
2
4 5 6
.1
7
8
10 .06
Is
Ii
70%
Ts
.3
PAL
OVER
Ip(xIr)
Ii(X100A)
8
10
.2
Ir
TL
TS(S)
IS(xIr)
80
100 12
Ip
In 100A
RE100
TL(S)
Ir(A)
80
The door is locked when the breaker is ON and can only be opened when
the breaker is in OFF position.
ON
Cat.A
63
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
3P
Uimp 8kV
Ui690V
12
14 .07
.10
Handle and front in black/black and handle and front in red/yellow, or red/
black, see also the following table.
D
I
P
ON
F
F
MCCB Accessories
Example:
cabinet door
PUSH
TO
TRIP
V-2SV
V-2SVE
NF/DSN125-250
black
red/yellow
V-2UV
V-2UVE
NF/DSN125-250-UV
black
red/yellow
V-4S
V-4SE
NF/DSN400-630
black
red/yellow
V-8S
NF/DSN800
black
V-8SE
Breaker type
Colour: handle/front
Art. no.
267747
267755
267757
225420
225424
225425
Specifications
267749
267756
Breaker type
Lenght (mm)
Adjustment unit
V-AD3S
V-AD3L
NF/DSN32-250
318
518
V-AD5S
V-AD5L
NF/DSN400-800
300
539
Art. No.
225426
235194
Spcifications
62
225427
235235
267758
225421
red/yellow
MCCB Accessories
Application
The F-type operating handles are to be mounted directly on the breaker.
With the installed operating handle the breaker can be locked (with up to
3padlocks, 8 mm max., padlocks are not included) in OFF position only.
The operating handle is available in the following colour combinations:
MITSUBISHI
OFF
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
D
E 100A
Ir 63-100A
POLE
Handle and front in black/black and handle and front in red/yellow, or red/
black, see also the following table.
3P
Uimp 8kV
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
ON
Cat.A
F
F
ON
In
I
P
NO-FUSE BREAKER
MODEL
NF125-SGW
MITSUBISHI ELECTRIC
PUSH TO TRIP
60
100 12
80
100
3.5
3
2.5
2
4 5 6
50/60Hz
TL
PU
TS(S)
SH
TO
TRIP .2
.1
7
8
10 .06
Ir
Ip
In 100A
IS(xIr)
TL(S)
Ir(A)
80
63
RE100
MODEL
.3
Is
Ii
70%
Ts
PAL
OVER
Ip(xIr)
Ii(X100A)
8
10
6
12
14 .07
.10
F-05SVE LF DF
F-05SVE LF DF Y
F-05SVE LF DF Z
F-05SVE LF DR
F-05SVE LF DR Y
F-05SVE LF DR Z
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is left
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is right
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is left
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is right
F-2SV LF DF
F-2SV LF DF Y
F-2SV LF DF Z
F-2SV LF DR
F-2SV LF DR Y
F-2SV LF DR Z
Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper
Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is left
Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is right
Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is upper
Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is left
Operating handle Type F. OFF position lock, RESET position open, ON side of breaker is right
F-2SVE LF DF
F-2SVE LF DF Y
F-2SVE LF DF Z
F-2SVE LF DR
F-2SVE LF DR Y
F-2SVE LF DR Z
Breaker type
NF/DSN32-63
3P / 4P
Art. No.
267263
267264
267265
267266
267267
267268
NF/DSN32-63
3P / 4P
267287
267288
267289
267290
267291
267292
NF/DSN125-250
3P / 4P
267359
267360
267361
267362
267363
267364
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is left
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is right
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is left
Operating handle Type F Emergency. OFF position lock, RESET position open, ON side of breaker is right
NF/DSN125-250
3P / 4P
267371
267372
267373
267374
267375
267376
F-4S LF DF
F-4SE LF DF
Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper
NF/DSN400-630
3P / 4P
225402
225403
F-8S LF DF
F-8SE LF DF
Operating handle Type F. OFF position lock, OFF position open, ON side of breaker is upper
Operating handle Type F Emergency. OFF position lock, OFF position open, ON side of breaker is upper
NF/DSN800
3P / 4P
225404
225405
F-RCS
267385
MCCB Accessories
Name
F-05SV LF DF
F-05SV LF DF Y
F-05SV LF DF Z
F-05SV LF DR
F-05SV LF DR Y
F-05SV LF DR Z
63
MCCB Accessories
Application
The handle lock device HL is used to lock the handle of the breaker against
switching by not-allowed persons. The function of protection is given
every time.
Different types are available.
LC-05SV
MCCB Accessories
zz The handle lock HL type can be used for 3- and 4-pole breaker types.
zz The handle locks can be used without padlock as lock covers.
zz The HLF types are used for OFF-lock and the HLN types are used for
ON-lock.
zz The handle lock HLF3 type enables the user to lock the handle with up
to three padlocks against switching.
zz The HLS types are used for OFF-lock only.
HLS-05SW
HLS-05SW
HL-4SW
64
Type
LC-05SV
Breaker type
NF/DSN32250
Art. no.
267761
HLF-05SV
NF/DSN32250
267396
HLN-05SV
NF/DSN32250
267397
HLS-05SW
HLS-05SV2
267398
267399
HL-4SW
HL-10SW
NF/DSN400800
NF/DSN1001600
205975
205976
MCCB Accessories
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
OFF
MODEL
100A
MITSUBISHI
NO-FUSE BREAKER
MODEL
3P
Power
P1
Supply
P2
S1
S2
S4
OFF
ON
K1
K1
K2
SW1
K2
P2
P1
K1
K2
K3
Uc
K3
S1
K3
MITSUBISHI ELECTRIC
PUSH TO TRIP
NF400-SEP
JIS
Ue
550VAC
460VAC
220VAC
OFF
Icn
35kA
50kA
85kA
IEC 60947-2
EN 60947-2
400A
Icu/Ics
10/10kA
30/30kA
42/42kA
45/45kA
85/85kA
40C
Uc
ON
Circuit
Uimp 8kV
Cat.A
S2
Ui690V
S4
Ir 63-100A
POLE
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
Operating
In
3P
POLE
400
690VAC
Ui
50 - 60Hz
8kV
Uimp
Ir
Ip
TEST
TL
Is
PUSH TO TRIP
P1
S1
P2
S2
MITSUBISHI ELECTRIC
S4
250
300
220
200
TL
MODEL
MITSUBISHIMODULE
POWER SUPPLY
MODEL
SERIAL:
MSDBA-NF25GSW
A0106
MDSPSA240-SW
CONTROLL CIRCUIT
60
80
Ir
Ip
Is
350 3.5
3
2.5
400 2
Ir(A)
TEST
T
50kA
85kA
500VAC
250VAC
ON
Control circuit
voltage should be
supplied to P1
and P2 terminals.
Ii
Ts
Ii(X100A)
Ts
4 5 6
TL(sec)
10
7 6
8
10 4
12
14
16
Ii(X400A)
IS(xIr)
.2
.3
100 .06
12
Ii
.1
TS(sec)
.10
.07
Ip(xIr)
Pull
VOLTAGE
AC100-240V/DC100-250V
NO-FUSE BREAKER
MODEL
NF250-SGW
Push to
ON
AUTO
Push to
OPEN
(TRIP)
MANU
Ui 690V
Cat.A
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
ON
50/60Hz
Uimp 8kV
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
(MANU)
Discharge
Push
MITSUBISHI ELECTRIC
RATED CURRENT
250 A
OFF
Specifications
Breaker type a
MDSD.../MDSA...
NF-S/H series
NF-R/U series
NF125-RGV / REV / UV
NF250-RGV / REV / UV
DC 24 V
Compatible with 100240 V AC /
100250 V DC
DC
AC
100 / 110 V
100 / 110 V
200 / 200 V
ON operating
OFF operating
Spring charging
Transformer capacity required (VA)
Endurance voltage (V)
Operating time (sec.)
a
b
c
MDS-4.../8...
NF400-SEW / HEW / REW
NF630-SEW / HEW / REW
NF800-SEW / HEW / REW
MDS-16...
NF1000-SEW
NF1250-SEW
NF1600-SEW
NF400-UEW, NF800-UEW
700
1500
700
1500
MCCB Accessories
Automatic Reset
The motor operated types should not be operated 10 times consecutively (one on/off counts
as an operation).
The dielectric strength of the electrical operating circuits is 1500 V. When performing a dielectric strength test simultaneously with another
device at a voltage over 1500 V, the operating
circuit terminal should be disconnected.
65
MCCB Accessories
Power
P1
Supply
P2
S1
S2
S4
OFF
ON
Uc
Operating
S4
K1
K1
K1
K2
K2
SW1
K2
K3
Uc
K3
K3
Circuit
S2
S1
P2
P1
Control circuit be
voltage should
supplied to P1
and P2 terminals.
MITSUBISHI
In
MITSUBISHIMODULE
POWER SUPPLY
100A
Ir 63-100A
MODEL
CONTROLL CIRCUIT
VOLTAGE
RE100
TL(S)
Ir(A)
80
63
60
100 12
3.5
3
2.5
100 2
80
In 100A
50/60Hz
AUTO
TS(S)
IS(xIr)
4 5 6
Ui 690V MITSUBISHI
Cat.A
EN60947-2
IEC60947-2
40C
JIS C 8201-2
Icu/Ics
Ue
8/8kA
690VAC
Ir
22/22kA
Ip
OVER
PAL
Is 525VAC
70%
30/30kA
Ii
500VAC
TL
36/36kA
Ts
440VAC Ip(xIr)
36/36kA
Ii(X100A)
380/415VAC
8
10
85/85kA
230VAC
6
12
Push to
OPEN
.1
7
8
10 .06
MANU
.2
4
.3
(TRIP)
MODEL
NF400-SEP
400A
JIS
Ue
550VAC
460VAC
220VAC
OFF
OFF
3P
POLE
ON
Icu/Ics
10/10kA
30/30kA
42/42kA
45/45kA
85/85kA
40C
400
690VAC
8kV
Uimp
50kA
85kA
500VAC
250VAC
ON
14 .07
PUSH TO TRIP
(MANU)
MITSUBISHI ELECTRIC
Discharge
250
300
350 3.5
3
2.5
400 2
220
200
Push
MITSUBISHI ELECTRIC
T
Ip
.10
TL
RATED CURRENT
OFF
Ir
Is
TEST
Ir(A)
60
80
.1
100 .06
12
Ii
Ts
TL(sec)
4 5 6
10
7 6
8
10 4
12
14
16
Ii(X400A)
IS(xIr)
.2
.3
TS(sec)
.10
.07
Ip(xIr)
250 A
6
MCCB Accessories
Icn
35kA
50kA
85kA
IEC 60947-2
EN 60947-2
50 - 60Hz
ON
MODEL
MITSUBISHI
NO-FUSE BREAKER
Pull
50/60Hz
Uimp 8kV
ELECTRIC
Push to
PUSH TO TRIP
Spring-charged type
MDS-4SW.... and
breaker type NF400-SEW
Spring-charged type
MDS.....-NF2GSWE
and breaker type NF250-SGV
S4
Ui
NO-FUSE BREAKER
MODEL
NF250-SGW
ON
Cat.A
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
50V
AC100-240V/DC100-2
3P
Uimp 8kV
Ui690V
MDSPSA240-SW
S2
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
GSW
MODEL MSDBA-NF25
30/30kA
36/36kA
SERIAL: A0106
36/36kA
85/85kA
20/20kA
IEC60947-2
JIS C 8201-2
OFF
NO-FUSE BREAKER
MODEL
NF125-SGW
POLE
S1
P2
P1
P2
(DC-)
P1
Spring-Charged
S4
S1
P2
(DC-)
Alarm switch
AL (AL-a contact)
ON
OFF
P1
Spring-Charged Type
When the ON switch is closed, the coil is releasing the latch mechanism, and the breaker is
turned to ON.
Manual operation
When the ON button (on the front of the springcharged type) is pressed, the latch mechanism is
cancelled and the circuit breaker set momentarily to ON by the force of spring.
Since it takes 3 sec to switch off a breaker provided with this device, if the breaker needs to be
opened urgently by remote control, a breaker
fitted with an SHT or UVT should be used.
The breaker is equipped with a relay for the
prevention of pumping.
Control circuit
Type
MDSAD240-NF1SVE
MDSAD240-NF2SVE
MDSAD240-NF2UVE
MDSD024-NF1SVE
MDSD024-NF2SVE
MDSD060-NF1SVE
MDSD060-NF2SVE
MDSD060-NF2UVE
Breaker type
NF/DSN125250 W90
NF/DSN125250 W105
NF250-UV W105
NF/DSN125250 W90
NF/DSN125250 W105
NF/DSN125250 W90
NF/DSN125250 W105
NF250-UV W105
Rated voltage
AC 100-240V / DC 100-250V
AC 100-240V / DC 100-250V
AC 100-240V / DC 100-250V
DC 24V
DC 24V
DC 48-60V
DC 48-60V
DC 48-60V
Art. no.
267401
267402
267403
267406
267407
267410
267411
267412
MDS-4SWA110
MDS-4SWA240
MDS-4SWD110
NF/DSN400630
NF/DSN400
NF/DSN400
AC 100110 V
AC 230 V
DC 100110 V
205968
205969
205970
MDS-8SWA110
MDS-8SWA240
MDS-8SWD110
NF/DSN800
NF/DSN630800
NF/DSN630800
DC 100110 V
AC 230 V
DC 100110 V
205971
205972
205973
MDS-16SSA110
MDS-16SSA220
MDS-16SSD110
NF/DSN10001600
NF/DSN10001600
NF/DSN10001600
AC 100110 V
AC 230 V
DC 100110 V
11463
9430
11464
66
OFF
Reset
Electrical operation
Alarm switch
AL (AL-a contact)
ON
Reset
S4
S1
MCCB Accessories
Terminal Covers
Application
TCS type terminal covers
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
JIS C 8201-2
OFF
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
MODEL
In
100A
Ir 63-100A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
3P
Uimp 8kV
Cat.A
ON
MITSUBISHI ELECTRIC
PUSH TO TRIP
T
TEST
Ir
Ip
TL
Is
Ii
Ts
Ii(X100A)
No. of
poles
3
4
3
4
3
4
Breaker type
Protection
degree
NF/DSN32250 W75
NF/DSN32250 W90
NF/DSN32250 W105
Art. no.
Type
267552
267553
267555
267556
267557
267558
TTC-05SV3
TTC-05SV4
TTC-1SV3
TTC-1SV4
TTC-2SV3
TTC-2SV4
No. of
poles
3
4
3
4
TCL-2SV3
TCL-2SV3L
TCL-2SV4
TCL-4SW3
TCL-4SW4
TCL-8SW3
TCL-8SW4
TCL-8UW3
TCL-8UW4
TCL-10SW3
TCL-10SW4
4
3
4
3
4
3
4
3
4
Type
Breaker type
No. of
poles
3
4
3
4
3
4
Breaker type
Colour
Protection
degree
267560
267561
267563
267564
267565
267566
NF/DSN32250 W75
NF/DSN32250 W90
Art. no.
transparent
NF/DSN32250 W105
NF/DSN32250 W75
NF/DSN32250 W75
NF/DSN32250 W90
NF/DSN32250 W90
NF/DSN32250 W105 3-pole up to
200A max 100mm
NF/DSN32250 W105 3-pole up to
250A max 150mm
NF/DSN32250 W105
black
NF/DSN400630
transparent
Protection
degree
IP20
NF/DSN800
transparent
IP20
NF/DSN800
transparent
IP20
NF/DSN10001250
(fixed with screws)
MCCB Accessories
transparent
IP20
Art. no.
Type
267543
267544
267546
267547
BTC-05SV3
BTC-05SV4
BTC-1SV3
BTC-1SV4
No. of
poles
3
4
3
4
267548
BTC-2SV3
267549
BTC-2SV4
267550
205977
205978
205979
205980
205981
205982
205983
205984
BTC-4SW3
BTC-4SW4
BTC-8SW3
BTC-8SW4
3
4
3
4
Breaker type
Colour
Protection
degree
Art. no.
267254
267255
267257
267258
NF/DSN32/63 3P W75
NF/DSN32/63 4P W75
NF/DSN125 3P W90
NF/DSN125 4P W90
NF/DSN125/160/250
2,3P W105
NF/DSN125/160/250
4P W105
267259
267260
NF/DSN400630
transparent
IP20
NF/DSN800
transparent
IP20
205985
205986
205987
205988
No. of
poles
3
4
3
4
3
4
Breaker type
NF/DSN32250 W75
NF/DSN32250 W75
NF/DSN32250 W90
NF/DSN32250 W90
NF/DSN32250 W105
NF/DSN32250 W105
Colour
Protection
degree
Art. no.
267469
267470
267472
267473
267474
267475
67
MCCB Accessories
Mechanical Interlock MI
MITSUBISHI
NO-FUSE BREAKER
MODEL
In
100A
Ir 63-100A
POLE
Ui690V
3P
MITSUBISHI
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
NO-FUSE BREAKER
MODEL
In
Ir 63-100A
POLE
Ui690V
Uimp 8kV
3P
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
Uimp 8kV
Cat.A
Cat.A
PUSH TO TRIP
PUSH TO TRIP
MITSUBISHI ELECTRIC
6
MCCB Accessories
100A
MITSUBISHI ELECTRIC
Type
MI-05SV3
MI-05SV4
MI-05SVFB3
MI-1SV4
MI-1SVFB3
MI-2SV4
MI-2SVFB3
MI-4SW3
MI-4SW4
MI-8SW3
MI-8SW4
MI-10SW3
MI-10SW4
MI-16SW3
MI-16SW4
No. of
poles
3
4
3
4
3
4
3
3
4
3
4
3
4
3
4
NF/DSN32250
Art. no.
400 AF
630800 AF
10001250 AF
1600 AF
267418
267419
267421
267422
267423
267424
267425
205989
205990
205991
205992
205993
205994
205995
205996
Application
The isolation barriers are used to avoid short-circuits between the terminals of the breaker due to
dust or leakage current.
Every breaker is equipped with isolation barriers as standard.
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
JIS C 8201-2
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
OFF
MODEL
In
100A
Ir 63-100A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
3P
Uimp 8kV
Cat.A
ON
MITSUBISHI ELECTRIC
PUSH TO TRIP
T
TEST
Ir
Ip
TL
Is
Ts
Ii(X100A)
Ii
Specifications
For breaker type
Connection type
Order information
BAF-05SV
V series W75 type
For front connection
Art. no. 267248
BAF-2SV
V series W90/105 type
For front connection
267249
Application
The IEC 35 mm rail mounting adapter is used to mount the breaker on a IEC 35 mm mounting rail.
It is available for 3-pole breakers NF/DSN3263.
Specifications
For 3-pole breakers
Order information
68
DIN-05SW
NF/DSN3263
Art. no. 146459 (packing unit: 10 pcs)
MCCB Accessories
Application
The portable tester unit can be used to check the tripping characteristics
of the electronic breakers from 125 A up to 1600 A.
zz More details on request.
MITSUBISHI
NO-FUSE BREAKER
IEC60947-2
JIS C 8201-2
OFF
Ue
690VAC
525VAC
500VAC
440VAC
380/415VAC
230VAC
300VAC
MODEL
In 100A
Ir 63-100A
POLE
Ui690V
EN60947-2
40C
Icu/Ics
8/8kA
22/22kA
30/30kA
36/36kA
36/36kA
85/85kA
20/20kA
3P
Uimp 8kV
Cat.A
ON
MITSUBISHI ELECTRIC
PUSH TO TRIP
T
TEST
Specifications
For electronic breakers
Order information
Y-250
W series 125 A 1600 A
Art. no. 68181
Y-350
V series 125 A 250 A
267770
Ir
Ip
TL
Is
Ii
Ts
Ii(X100A)
000
L 30
POWER
ON
MCCB Accessories
69
NF63-SV
NF63-CV
3, 4, (5), 6, 10,
3, 4, (5), 6, 10,
(15), 16, 20, 25, (15), 16, 20, 25,
(30), 32, 40, 50, (30), 32, 40, 50,
(60), 63
(60), 63
3
3
3
4
600
600
600
690V
500V
2.5/2.5
2.5/2.5
7.5/7.5
440V
2.5/2.5
2.5/2.5
7.5/7.5
415V
2.5/2.5
2.5/2.5
7.5/7.5
400V
5/5
5/5
7.5/7.5
380V
5/5
5/5
7.5/7.5
230V
7.5/7.5
7.5/7.5
15/15
250V *1 2.5/2.5
2.5/2.5
7.5/7.5
Mounting screw: M40.755 (2 and 3P: 2pcs, 4P: 4pcs)
Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) (*2)
AC
DC
Standard attached parts
(front connection)
NF63-SV
1h
30min
20min
14min
10min
1h
30min
20min
14min
10min
6min
4min
2min
2min
Max. (3A5A)
Max. (7.1A8A)
10s
5s
5s
30s
20s
10s
5s
Min.
AC
0.1s
DC
0.05s
1s
Time-delay trip
100 125
200
300
1000
DC
0.1s
3000 4000
1500 2000
Time-delay trip
100 125
200
300
500 700
400
600
0.02s
Instantaneous trip
1000
0.01s
5 0 0 0 7 0 0 0 10000
4000 6000
Time-delay trip
100 125
200
Internal Accessories
Max. total
breaking
time
300
400
Instantaneous trip
500 7 0 0 1 0 0 0
600
1500 2000
3000 4000
Operating handle
AL
AX
SHT or UVT
Lead-wire
direction
130
Right-side mounting
Left-side mounting
DC
0.1s
0.05s
0.02s
0.01s
AC
0.2s
Max. total
breaking
time
0.05s
Instantaneous trip
500 700
400
600
0.5s
AC
0.2s
2-pole
3, 4-pole
Rated ambient
temperature
0.02s
Min.
2s
0.5s
Max. total
breaking
time
Max. (40A50A)
1min
1s
0.2s
Max. (60A63A)
2min
10s
2s
0.5s
0.01s
Max.
30s
20s
1s
Operating characteristics
NF63-CV
40A63A
NF63-SV
40A63A
NF63-HV
40A63A
1h
30min
20min
14min
10min
6min
4min
1min
Min.
2s
2h
Operating characteristics
NF32-SV 10A32A
NF63-CV 10A30A
NF63-SV 10A32A
NF63-HV 10A30A
6min
4min
30s
20s
3
4
600
2.5/2.5
7.5/7.5
10/8
10/8
10/8
10/8
25/19
7.5/7.5
4h
2h
Operating time
Operating time
4h
Operating characteristics
NF32-SV 3A6A
NF63-CV 3A6A
NF63-SV
3A6A
2h
Operating time
4h
NF63-HV
10, (15), 16, 20,
25, (30), 32, 40,
50, (60), 63
Notes: *1 Use two poles for three- and four-pole products. Not available for use with connection as shown at the bottom of page 41.
*2 Supplied with NF63-SV and NF63-HV.
Operating Characteristics
1min
NF32-SV
3, 4, (5), 6, 10,
(15), 16, 20, 25,
(30), 32
120
110
100
90
(Rated ambient 80
10
temperature 40 C)
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
F
V
LC
HL (*1)
HL-S
3, 4P
3, 4P
Type name
F-1SV
V-1SV
LC-05SV
HLF-05SV
HLN-05SV
HLS-1SV
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
70
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
64
Accessories
Mechanical interlock
Terminal
cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
3P
4P
3P
3P
4P
3P
3P
3P
Type name
MI-05SV3
MI-05SV4
TCS-1SV3
TCL-1SV3
TCL-1SV4
TTC-1SV3
BTC-1SV3
PTC-1SV3
MDS (2*)
Reference page
68
62
66
Front connection
M8 screw
Solderless terminal
for wire size
14~2/0AWG CU/AL
Wire connection
4.5
50
84
Breaker
8.5
60
22
30
60
90
90
120
8.5
Trip
button
30
130
112
50
24
111
Insulation barrier
(removable)
Mounting hole
61
68
Neutral pole
4
19 max.
Comb conductor
16.5 max.
(Conductor thickness t
= 5 max.)
72
90
2-pole
4-pole
3-pole
30
30
45
M40.7 taps
or 5
2-pole
4-pole
3-pole
Conductor drilling
for direct connection
Drilling plan
Rear connection
4-pole
4-pole
Stud can be
rotated 90
Breaker
30
8.5
30
68
72
2.5
M8 bolt
15
2.5
54.5
52
R1
112
16
15 connection
allowance
R1
7
112
52
Breaker
3-pole
2-pole
111
102
2-pole
Mounting plate
t = 3.2 max.
3-pole
Insulation tube
15
90
28
30
18
60
M40.7 breaker
mounting screw
60
Insulation
tube
30
57
90
M40.7 taps
or 5
2-pole
86
3-pole
4-pole
104.5
Front-panel cutout
Drilling plan
Plug-in
Mounting
plate
Plug-in
terminal block
M50.8
Terminal block mounting nut
or screw mounted directly
3-pole
4-pole
95
125
60
90
M8 screw
21
8.5
Details of
terminal
Remarks:
30
2-pole
56
12
30
65
89
80
54
116
20 max.
85
5.5
170
11
83.5
56
30
67
97
127
2-pole
3-pole
4-pole
6 hole
or M50.8 tabs
Conductor drilling
1. The two-pole models of NF125-HV are three-pole models with the central pole removed.
2. Only two- and three-pole models are available for NF125-CV.
Drilling plan
[mm]
71
690V
500V
440V
415V
IEC/EN
AC
60947-2
400V
(Icu/Ics)
380V
230V
200 V
DC *1 300 V
Standard attached parts
(front connection)
NF250-SGV
Note: *1 When wired as shown at the bottom of page 41, three-pole models can be used for up to 500VDC, and 4-pole models for up to
600VDC.
6min
4min
6min
4min
2min
1min
Operating time
30s
20s
10s
Max.
5s
Max. total
breaking
time
Min.
1min
30s
20s
10s
6min
4min
2min
1s
1s
0.5s
0.5s
0.2s
30s
20s
10s
0.05s
0.02s
1 1.25
5 6 7
10
15 20
30
40 50 6070
2min
1min
Time-delay trip
10s
Max. total
breaking
time
DC
1 1.25
5 6 7
10
15
20
30
Internal Accessories
40
Min.
5s
AC
0.2s
DC
0.1s
Max. total
breaking
time
0.05s
0.02s
0.01s
Instantaneous trip
current ratio
AC
DC
In(%)
In(%)
1000 200 1300 260
1s
0.1s
Instantaneous trip
Max.
30s
20s
0.5s
AC
0.05s
0.02s
0.01s
6min
4min
2s
0.2s
DC
NF125-SGV NF125-LGV
Current setting Ir = 70-100A(Rated current In=100A)
Current setting Ir = 90-125A(Rated current In=125A)
NF160-SGV NF160-LGV
Current setting Ir = 125-160A(Rated current In=160A)
NF250-SGV NF250-LGV
Current setting Ir = 125-160A(Rated current In=160A)
Current setting Ir = 140-200A(Rated current In=200A)
Current setting Ir = 175-250A(Rated current In=250A)
30min
20min
14min
10min
1s
0.05s
Instantaneous trip
Time-delay trip
Min.
5s
0.5s
AC
0.1s
DC
Instantaneous trip
current ratio
AC
DC
In(%)
In(%)
1000 200 1300 260
Thermal-Adjustable types
1h
2s
0.2s
AC
0.1s
Max.
1min
2s
2s
0.01s
Max. total
breaking
time
Min.
5s
30min
20min
14min
10min
Instantaneous trip
current
AC
DC
600A 120A 850A 170A
Max.
NF125-SGV NF125-LGV
Current setting Ir = 45-63A(Rated current In=63A)
Current setting Ir = 56-80A(Rated current In=80A)
1 1.25
0.02s
Instantaneous trip
Time-delay trip
5 6 7
10
15 20
30
40
0.01s
Time-delay trip
1 1.25
Instantaneous trip
5 6 7
10
15 20
30
Operating handle
Right-side
mounting
SHT or UVT
130
AL
AX
Current rating (%)
Left-side
mounting
Lead-wire direction
Rated ambient
temperature
Operating time
2min
30min
20min
14min
10min
Instantaneous trip
current
AC
DC
600A 120A 850A 170A
Operating time
30min
20min
14min
10min
Operating characteristics
2h
Thermal-Adjustable types
1h
NF125-SGV NF125-LGV
Current setting Ir = 32-40A(Rated current In=40A)
Current setting Ir = 35-50A(Rated current In=50A)
4h
Operating characteristics
2h
Thermal-Adjustable types
1h
NF125-SGV NF125-LGV
Current setting Ir = 16-20A(Rated current In=20A)
Current setting Ir = 20-25A(Rated current In=25A)
Current setting Ir = 25-32A(Rated current In=32A)
4h
Operating characteristics
2h
Thermal-Adjustable types
1h
4h
Operating characteristics
2h
Operating time
Operating Characteristics
4h
NF160-LGV NF250-LGV
125160
125160
140200
175250
3
4
3
4
690
690
8/8
8/8
36/36
36/36
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
90/90
90/90
90/90
90/90
20/20
20/20
120
110
100
90
80
10
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
F
V
LC
HL (*1)
HL-S
Type name
F-2SV
V-2SV
LC-05SV
HLF-05SV
HLN-05SV
HLS-2SV
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
72
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
Accessories
Mechanical interlock
64
Terminal
cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
3P
4P
3P
3P
4P
3P
3P
3P
Type name
MI-05SV3
MI-2SV4
TCS-2SV3
TCL-2SV3
TCL-2SV3L
TCL-2SV4
TTC-2SV3
BTC-2SV3
PTC-2SV3
MDS (*2)
Reference page
68
67
66
40
30
Front connection
Insulation barrier
(removable)
24
M8 bolt
(hex-socket)
126
10
8
.5
C1
4.5
50
102
165
144
Breaker
Solderless terminal for wire size
125~175A 14~95mm
200 ~250A 70~125mm
Wire connection
100
Mounting hole
100
8.5
C1
Trip button
35
70
105
105
140
3-pole
61
Neutral pole
8.5
72
35
M40.7 taps
or 5
68
4
35
Or
3-pole
22
25 max.
45
4-pole
25 max.
92
4-pole
Drilling plan
Rear connection
4-pole
3-pole
4-pole
Stud can be
rotated 90
Breaker
3-pole
Breaker
7
MCCB Characteristics & Dimensions
20
52
R1
144
Connection
allowance
22
126
144
Mounting plate
t = 3.2 max.
Insulation
tube
M40.7 breaker
mounting screw
15
68
24
15
9
M8 bolt
35
70
105
71
72
Insulation tube
70
M40.7 taps
or 5
3-pole
106
32.5
35
35
100
105
4-pole
Drilling plan
Front-panel cutout
Plug-in
4-pole 145
31
30
56.5
3-pole 70
Insulating
barrier
112
4-pole 105
3-pole 105
4-pole 140
56.5
80
54
20
M5
terminal block mounting screw
21
89
15
28
151
144
11
70
165
190
Mounting plate
3-pole 110
24 connection allowance
34.5
Plug-in
terminal block
9
M8 bolt
Stud attachable in this
direction only
70
105
107
142
3-pole
6 hole
or M50.8 tabs
4-pole
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
73
NF125-HGV
NF250-HGV
125160
125160
140200
175250
3
4
3
4
3
4
690
690
690
10/8
10/8
10/8
50/38
50/38
50/38
65/65
65/65
65/65
70/70
70/70
70/70
75/75
75/75
75/75
75/75
75/75
75/75
100/100
100/100
100/100
100/100
100/100
100/100
40/40
40/40
40/40
Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs)
Insulation barrier: (3P: 4pcs, 4P: 6pcs)
690V
500V
440V
415V
IEC/EN
AC
60947-2
400V
(Icu/Ics)
380V
230V
200 V
DC *1 300 V
Standard attached parts
(front connection)
NF250-HGV
NF160-HGV
NF125-RGV
NF250-RGV
125160
3
690
125/125
150/150
150/150
150/150
150/150
150/150
3
690
125/125
150/150
150/150
150/150
150/150
150/150
Note: *1 When wired as shown at the bottom of page 41, three-pole models can be used for up to 500VDC, and 4-pole models for up to
Operating Characteristics
6min
4min
2min
1min
30s
20s
Max.
5s
Max. total
breaking
time
Min.
1min
30s
20s
10s
1s
1s
0.5s
0.5s
0.2s
30s
20s
10s
0.05s
0.02s
1 1.25
5 6 7
10
15 20
30
40 50 6070
2min
1min
10s
Max. total
breaking
time
DC
1 1.25
5 6 7
10
15
20
30
Internal Accessories
40
AC
0.2s
DC
0.1s
Max. total
breaking
time
0.05s
0.02s
0.01s
Min.
5s
1s
0.1s
Instantaneous trip
Instantaneous trip
current ratio
DC
AC
In(%)
In(%)
1000 200 1300 260
0.5s
AC
0.05s
Time-delay trip
Max.
30s
20s
2s
0.2s
DC
0.02s
0.01s
6min
4min
1s
0.05s
Instantaneous trip
Time-delay trip
Min.
5s
0.5s
AC
0.1s
DC
Instantaneous trip
current ratio
DC
AC
In(%)
In(%)
1000 200 1300 260
NF125-HGV
Current setting Ir = 70-100A(Rated current In=100A)
Current setting Ir = 90-125A(Rated current In=125A)
NF160-HGV
Current setting Ir = 125-160A(Rated current In=160A)
NF250-HGV
Current setting Ir = 125-160A(Rated current In=160A)
Current setting Ir = 140-200A(Rated current In=200A)
Current setting Ir = 175-250A(Rated current In=250A)
NF125-RGV
Current setting Ir = 80-100A(Rated current In=100A)
Current setting Ir = 100-125A(Rated current In=125A)
NF250-RGV
Current setting Ir = 125-160A(Rated current In=160A)
Current setting Ir = 160-200A(Rated current In=200A)
Current setting Ir = 200-250A(Rated current In=250A)
30min
20min
14min
10min
2s
0.2s
AC
0.1s
Max.
1min
2s
2s
0.01s
Max. total
breaking
time
Min.
5s
2min
Thermal-Adjustable types
1h
6min
4min
Instantaneous trip
current
AC
DC
600A 120A 850A 170A
Operating characteristics
2h
1 1.25
0.02s
Instantaneous trip
Time-delay trip
5 6 7
10
15 20
30
40
0.01s
Time-delay trip
1 1.25
Instantaneous trip
5 6 7
10
15 20
30
Operating handle
Right-side
mounting
SHT or UVT
130
AL
AX
Current rating (%)
Left-side
mounting
Lead-wire direction
Rated ambient
temperature
10s
Max.
NF125-HGV
Current setting Ir =
Current setting Ir =
NF125-RGV
Current setting Ir =
Current setting Ir =
30min
20min
14min
10min
6min
4min
Operating time
Operating time
2min
30min
20min
14min
10min
Instantaneous trip
current
AC
DC
600A 120A 850A 170A
4h
Thermal-Adjustable types
1h
Operating time
30min
20min
14min
10min
NF125-HGV
Current setting Ir =
Current setting Ir =
NF125-RGV
Current setting Ir =
Current setting Ir =
Operating characteristics
2h
Thermal-Adjustable types
1h
NF125-HGV NF125-RGV
Current setting Ir = 16-20A(Rated current In=20A)
Current setting Ir = 20-25A(Rated current In=25A)
Current setting Ir = 25-32A(Rated current In=32A)
4h
Operating characteristics
2h
Thermal-Adjustable types
1h
4h
Operating characteristics
2h
Operating time
4h
120
110
100
90
80
10
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
F
V
LC
HL (*1)
HL-S
Type name
F-2SV
V-2SV
LC-05SV
HLF-05SV
HLN-05SV
HLS-2SV
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
74
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
Accessories
Mechanical interlock
64
Terminal
cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
3P
4P
3P
3P
4P
3P
3P
3P
Type name
MI-05SV3
MI-2SV4
TCS-2SV3
TCL-2SV3
TCL-2SV3L
TCL-2SV4
TTC-2SV3
BTC-2SV3
PTC-2SV3
MDS (*2)
Reference page
68
67
66
40
30
Front connection
Insulation barrier
(removable)
24
M8 bolt
(hex-socket)
126
10
8
.5
C1
4.5
50
102
165
144
Breaker
Solderless terminal for wire size
125~175A 14~95mm
200 ~250A 70~125mm
Wire connection
100
Mounting hole
100
8.5
C1
Trip button
35
70
105
105
140
3-pole
61
Neutral pole
8.5
72
35
M40.7 taps
or 5
68
4
35
Or
3-pole
22
25 max.
45
4-pole
25 max.
92
4-pole
Drilling plan
Rear connection
4-pole
3-pole
4-pole
Stud can be
rotated 90
Breaker
3-pole
Breaker
7
MCCB Characteristics & Dimensions
20
52
R1
144
Connection
allowance
22
126
144
Mounting plate
t = 3.2 max.
Insulation
tube
M40.7 breaker
mounting screw
15
68
24
15
9
M8 bolt
35
70
105
71
72
Insulation tube
70
M40.7 taps
or 5
3-pole
106
32.5
35
35
100
105
4-pole
Drilling plan
Front-panel cutout
Plug-in
4-pole 145
31
30
56.5
3-pole 70
Insulating
barrier
112
4-pole 105
3-pole 105
4-pole 140
56.5
80
54
20
M5
terminal block mounting screw
21
89
15
28
151
144
11
70
165
190
Mounting plate
3-pole 110
24 connection allowance
34.5
Plug-in
terminal block
9
M8 bolt
Stud attachable in this
direction only
70
105
107
142
3-pole
6 hole
or M50.8 tabs
4-pole
Drilling plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
75
NF125-SEV
NF250-SEV
NF125-HEV
1632, 3263,
80160,
1632, 3263,
63125
125250
63125
3
4
3
4
3
4
690
690
690
8/8
10/8
8/8
30/30
50/38
30/30
36/36
65/65
36/36
36/36
70/70
36/36
36/36
75/75
36/36
36/36
75/75
36/36
85/85
100/100
85/85
690V
500V
440V
IEC/EN
AC
415V
60947-2
400V
(Icu/Ics)
380V
230V
DC *1 300 V
Standard attached parts
(front connection)
NF250-HE
80160,
125250
3
4
690
10/8
50/38
65/65
70/70
75/75
75/75
100/100
NF125-SEV
Operating Characteristics
10h
10h
5h
5h
Operating characteristics
2h
NF125-SEV NF125-HEV
Current setting Ir
16-32
32-63
LTD operating time at 125% (I6t ON)
63-125
670s (TL = 100s set)
540s (TL = 80s set)
400s (TL = 60s set)
80s (TL = 12s set)
1h
30min
20min
14min
10min
6min
4min
Rated current In
32A
63A
125A
I t OFF
6
5s
2s
Operating time
Operating time
10s
2min
LTD operating time TL
126080100s 20%
(at 200%)
I6t ON
1min
I6t ON
30s
20s
I t OFF
6
10s
5s
2s
1s
1s
0.5s
0.5s
0.2s
0.1s
0.1s
0.10-03s
I2t ON
0.2s
0.05s
0.10-03s
I2t ON
0.05s
I2t OFF
0.02s
0.01s
0.6
0.7
1 1.25
5 6 7
10
20
I2t OFF
0.02s
0.01s
30 40
0.6
0.7
1 1.25
Internal Accessories
10 5
20
3 0 40
AL
Right-side
mounting
AX
SHT or UVT
Lead-wire direction
PAL
Rated ambient
temperature
130
Operating handle
Left-side
mounting
6 7
30s
20s
NF250-SEV NF250-HEV
1h
30min
20min
14min
10min
6min
4min
2min
1min
Operating characteristics
2h
120
110
100
90
80
70
10
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
F
V
LC
HL (*1)
HL-S
Type name
F-2SV
V-2SV
LC-05SV
HLF-05SV
HLN-05SV
HLS-2SV
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
76
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
Accessories
Mechanical interlock
64
Terminal
cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
3P
4P
3P
3P
4P
3P
3P
3P
Type name
MI-05SV3
MI-2SV4
TCS-2SV3
TCL-2SV3
TCL-2SV3L
TCL-2SV4
TTC-2SV3
BTC-2SV3
PTC-2SV3
MDS (*2)
Reference page
68
67
66
30
Front connection
Insulation barrier
(removable)
M8 bolt
(hex-socket)
24
100
Mounting hole
Breaker
126
10
C1
C1
4.5
50
102
165
144
8
.5
Trip button
25 max.
35
70
105
105
140
Neutral pole
Or
Or
8.5
45
61
35
M40.7 taps
or 5
68
25 max.
72
92
3-pole
35
22
8.5
100
Trip characteristics
selector
3-pole
4-pole
4-pole
Conductor drilling
for direct connection
Drilling plan
Rear connection
4-pole
Mounting plate
t = 3.2 max.
Insulation
tube
Stud can be
rotated 90
3-pole
4-pole
Breaker
Breaker
3-pole
52
R1
144
126
20
22 connection
allowance
144
7
M40.7 breaker
mounting screw
15
15
68
71
72
106
9
M8 bolt
70
Insulation
tube
105
70
32.5
35
24
35
35
M40.7 taps
or 5
100
105
4-pole
3-pole
Front-panel cutout
Drilling plan
M5
terminal block
mounting screw
31
89
112
30
56.5
20
3-pole 70
Insulation
barrier
56.5
151
15
28
21
9
M8 bolt
4-pole 105
3-pole 105
4-pole 140
80
70
144
11
4-pole 145
3-pole 110
54
34.5
Plug-in
terminal block
165
190
Mounting
plate
24 connection allowance
Plug-in
70
105
107
142
3-pole
4-pole
6 hole
or M50.8 tabs
Drilling plan
Remark: 1. Products with data parenthesized come with PAL; built-in models with PAL have different external dimensions from the standard models.
[mm]
77
NF125-UV, NF250-UV
Type name
NF125-UGV
NF250-UGV
15, 20, 30, 40, 50,
125, 150, 175,
60, 75, 100, 125
200, 225, 250
3
4
3
690
690
10/10
15/15
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
200/200
Number of poles
Rated insulation voltage Ui [V]
690V
500V
440V
415V
AC
400V
380V
230V
200V
DC *1 300 V
IEC/EN
60947-2
(Icu/Ics)
NF125-UV
Operating Characteristics
4h
30min
20min
14min
10min
6min
4min
2min
10s
5s
Min.
2s
Min.
2s
30s
20s
10s
5s
Min.
2s
1s
1s
1s
0.5s
0.5s
0.5s
Max. total
breaking
time
0.2s
0.1s
0.2s
0.05s
0.02s
Time-delay trip
0.01s
100 125
200
3 0 0 4 0 0 500 700
600
0.02s
Instantaneous trip
0.01s
1000
Time-delay trip
100 125
200
300
0.02s
Instantaneous trip
500 7 0 0 1 0 0 0
600
400
1500 2000
Max. total
breaking
time
0.1s
0.05s
0.01s
3000 4000
Time-delay trip
100 125
200
300
400
500 7 0 0
600
Instantaneous trip
1000
1500 2000
3000 4000
4h
4h
2h
2h
Operating characteristics
NF250-UV 125A 225A
1h
2min
30min
20min
14min
10min
6min
4min
2min
Max.
1min
30s
20s
30s
20s
Operating time
1min
10s
5s
Min.
2s
5s
1s
0.5s
0.2s
0.2s
Max. total
breaking
time
0.1s
0.05s
Time-delay trip
200
300
Min.
2s
0.5s
100 125
Max.
10s
1s
0.02s
Operating characteristics
NF250-UV 250A
NF250-UV
250A
1h
NF250-UV 125A225A
30min
20min
14min
10min
6min
4min
0.01s
0.2s
Max. total
breaking
time
0.1s
0.05s
Operating time
1min
10s
5s
Max.
2min
30s
20s
Operating time
30s
20s
6min
4min
(40A50A)
Max.
40A50A
1min
Operating time
Operating time
Instantaneous trip
Instantaneous
trip current
current
isisfixed
120A.
fixedtoto600A
600A
120A
Max.
Operating characteristics
NF125-UV
NF125-UV
125A
125A
1h
30min
20min
14min
10min
(60A100A)
Max.
60A100A
2min
1min
400
500 700
600
0.02s
Instantaneous trip
1000
1500 2000
Max. total
breaking
time
0.1s
0.05s
0.01s
3000 4000
Time-delay trip
100 125
200
300
400
500 700
600
Instantaneous trip
1000
1500 2000
3000 4000
Internal Accessories
SHT or UVT
130
AL
AX
Current rating (%)
Left-side
mounting
Lead-wire direction
Rated ambient
temperature
Operating characteristics
NF125-UV
NF125-UV
40A100A
40A100A
1h
NF125-UV 15A30A
30min
20min
14min
10min
6min
4min
2h
2h
Operating characteristics
NF125-UV 15A 30A
1h
4h
4h
2h
120
110
100
90
80
10
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
F
V
LC
HL (*1)
HL-S
Type name
F-1UV
V-1UV
LC-05SV
HLF-05SV
HLN-05SV
HLS-05SV
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
78
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
64
Accessories
Mechanical interlock
Terminal
cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
3P
4P
3P
3P
4P
3P
3P
3P
Type name
MI-05SV3
MI-05SV4
TCS-1SV3
TCL-1SV3
TCL-1SV4
TCL-1SV3
BTC-1SV3
PTC-1SV3
MDS (*2)
Reference page
68
67
66
Front connection
24
126
.5
10
f 8
C1
f 4.5
50
102
165
144
Breaker
Breaker
Solderless
terminal
Solderless terminal
for wire
for
wiresize
size
2
125-175A
14-95mm
125~175A 14~95mm
2
200-250A
70-125mm
200
~250A
70~125mm
Wire connection
Wire
connection
100
Mounting hole
30
M8
M8 bolt
bolt
(hex-socket)
(hex-socket)
Insulation
Insulationbarrier
barrier
(removable)
(removable)
C1
35
70
105
105
140
3-pole
3-pole
45
OderOr
Neutral pole
68
4
35
M4 0.7taps
taps
M40.7
or 5
f5
3-pole
3-pole
25
max.
25 max.
72
92
4-pole
4-pole
35
5.5
.
f88
61
22
25
max.
25 max.
f 8.5
8.5
100
Trip button
4-pole
4-pole
(Conductor thickness
(Conductor
thickness
tt=7
= 7max.)
max.)
Conductor
drilling
Conductor drilling
for direct
direct connection
for
connection
Drilling plan
plan
Drilling
Rear connection
4-pole
Mounting base
4-pole
Stud can be
rotated 90
Mounting plate
t = 3.2 max.
3-pole
Breaker
Breaker
3-pole
3-pole
15
Insulation
Insulation
tube
tube
105
70
M4
0.7taps
taps
M40.7
or f55
52
R1
35
100
105
4-pole
4-pole
3-pole
3-pole
106
32.5
35
f24
24
35
70
f9
9
M8 bolt
bolt
71
72
0.7breaker
breaker
M4
M40.7
mounting screw
15
68
144
20
Connection
Connection
allowance
allowance
22
126
144
Front-panel
cutout
Front-panel
cutout
Drilling
Drillingplan
plan
Plug-in
4-pole
4-pole 145
24 connection allowance
3-pole 110
110
3-pole
Breaker (plug-in
(plug-in terminal
terminal block)
block)
Breaker
M5 terminal block
terminal
block
mounting
screw
mounting screw
21
31
89
30
56.5
54
56.5
15
28
151
144
11
70
165
190
Connection
allowance
20
3-pole 70
Insulation
Insulation
barrier
barrier
112
4-pole 105
3-pole 105
4-pole 140
80
34.5
Mounting
plate
Plug-in
terminal block
f9
9
M8 bolt
bolt
Stud attachable
attachablein
inthis
this
direction only
direction
only
70
105
107
142
3-pole
3-pole
4-pole
4-pole
6
f 6 hole
or
or M5
M5 screw
0.8 taps
Drilling
Drillingplan
plan
Remark: 1. Two-pole models are three-pole models with the central pole removed.
[mm]
79
NF400-SEW
NF400-HEW
200, 225, 250,
200, 225, 250,
300, 350, 400
300, 350, 400
3
4
3
4
690
690
10/10
35/18
30/30
50/50
42/42
65/65
50/50
70/70
50/50
70/70
50/50
70/70
85/85
100/100
85/85
100/100
Number of poles
Rated insulation voltage Ui [V]
IEC/EN
60947-2
(Icu/Ics)
AC
DC
Standard attached parts
(front connection)
NF400-SEW
690V
500V
440V
415V
400V
380V
230V
200V
250V
NF400-REW
200, 225, 250,
300, 350, 400
3
690
70/35
125/63
125/63
125/63
125/63
150/75
150/75
Operating Characteristics
10h
Operating characteristics
5h
2h
1h
30min
20min
14min
10min
6min
4min
2min
126080100s 20%
(at 200%)
(at
200%)
1min
Operating time
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 16 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
AL
AL
Right-side
mounting
Left-side
mounting
AX
AX
SHT or UVT
EAL
EAL
TBL
TBL
MG
MG
TBM
TBM
130
Lead-wire direction
PAL
PAL
ATU
ATU
Note 1
Rated ambient
temperature
0.5s
NF400-SEW NF400-HEW
NF400-REW
Current
Rated
setting Ir
current In
200, 225, 250,
400 A
300, 350, 400
Adjustable
120
110
100
90
80
Note 1
Note 1
70
10
Note 1
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
Type name
Reference page
F-4S
63
V-4S
62
HL (*1)
HLF-4SW
HL-S
HLN-4SW
64
HLS-4SW
*1 HLF types are used for OFF-lock and HLN types for ON-lock.
*2 Specify the working voltage. Refer to the reference page for type name.
Accessories
Mechanical interlock
Large
Type name
MI
TC-L
Skeleton
TTC
Rear
BTC
80
3P
MI-4SW3
4P
MI-4SW4
3P
TCL-4SW3
4P
TCL-4SW4
3P
TTC-4SW3
4P
TTC-4SW4
3P
4P
BTC-4SW3
BTC-4SW4
MDS (*2)
Reference page
68
67
66
Front connection
Insulation barrier
(Conductor
thickness
t=8thickness
max.)
Conductor
Insulating
barrier (removable)
(removable)
28
44
4-pole
4-pole
3-pole
3-pole
Breaker
Breaker
Breaker
Breaker
39
43
110
16
t=8 max.
94.5
92
f7
7
39
25
44
97
56
51
168
112
185
140
f10.5
10.5
44
118
Conductor
drilling
Conductor drilling
for
direct connection
for direct
connection
103
5
Conductor thickness
(Conductor
thicknesst=8
t =max.
8 max.)
107
3-pole
3-pole
155
196
3-pole
3-pole
M6 tap
M6
tapsororf 7
7 hole
44
Neutral pole
Neutral
pole
f 14 for
14
M12 bolt
M12
bolt
194
12
59
f 12.5
12.5
257
Trip button
button
Trip
R6
102
Mounting hole
Mounting
hole
1.0mm
sideof
1.0mmclearance
clearanceon
on each
each side
ofthe
thehandle
handleframe.
frame
4-pole
4-pole
Front-panel cutout
Drilling plan
Drilling
plan
Front-panel cutout
4-pole
4-pole
Boring
dimensions
rearconnection
connection
Boring
dimensions
forforrear
type
barriers (3-pole)
type barriers
(3-pole)
Rear connection
4-pole
4-pole
Stud
canbe
be
Stud can
rotated 90
rotated
90
Breaker
Breaker
3-pole
3-pole
Groove
forreducing
reducing
Groove for
heat
byovercurrent
overcurrent
heat by
Line
side
Line side
6 35
35
6-f
Connection
Connection
allowance
allowance
M6M6
taptaps
or for
7
44
Insulation
Insulationtube
87
f 35
35
44
87
tube
130.5
225
194
225
24 24
M6 screw
screwfor
for
mounting breaker
mounting
breaker
13
f 13 for
M12 bolt
bolt
113
194
14
128
83
225
265
26
10
44-M6
M6
taps
tap
or or
f 7 7
7 hole
25 20 20
11
43.5
11
44
130.5
87
4-pole
3-pole
3-pole
4-pole
Drillingplan
plan
Drilling
8-M4 screw
8-M4
screw
Add these
tapped
holes
in in
Add
these
tapped
holes
to to
standard
boring.
88 positions
positions
standard
boring.
Load
side
Load side
Plug-in
Plug-in
4-pole
4-pole
3-pole
3-pole
Mounting
plate
Mounting plate
Breaker
Breaker
163
24
55
79
160
28
18
135
Connection
Connection
allowance
allowance
15
M8 terminal
terminalblock
block
mounting screw
mounting
screw
8
24
225
280
55
35
Plug-in
terminal
block
terminal
block
10
f 10
28
121
f13
13 for
M12
M12 bolt
bolt
Stud
Studattachable
attachableinin
this
this direction
directiononly
only
87
130.5
Insulating
Insulationbarrier
barrier
44
87
136
181
3-pole
3-pole
4-pole
4-pole
Drilling
Drilling plan
plan
[mm]
81
24 24
Mounting plate
Mounting
plate
NF400-UEW
Type name
Rated current In [A]
Number of poles
Rated insulation voltage Ui [V]
IEC/EN
60947-2
(Icu/Ics)
AC
DC
Standard attached parts
(front connection)
NF400-UEW
NF400-UEW
200, 225, 250, 300, 350, 400
3
690
170/170
200/200
200/200
200/200
200/200
200/200
200/200
690V
500V
440V
415V
400V
380V
230V
200V
250 V
Operating Characteristics
10h
Operating characteristics
5h
NF400-UEW
2h
1h
30min
20min
14min
10min
6min
4min
126080100s 20%
(at 200%)
(at
200%)
1min
Operating time
Rated
current In
400 A
2min
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.750.80-0.85-0.900.95-1.0) 10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 16 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
AL
AL
Right-side
mounting
Left-side
mounting
AX
AX
SHT or UVT
EAL
EAL
TBL
TBL
MG
MG
TBM
TBM
130
Lead-wire direction
PAL
PAL
ATU
ATU
Note 1
Rated ambient
temperature
0.5s
Current
setting Ir
200, 225, 250,
300, 350, 400
Adjustable
120
110
100
90
80
Note 1
Note 1
70
10
Note 1
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
Type name
Reference page
Accessories
F-4U
63
Mechanical interlock
V-4U
62
HL (*1)
HL-S
Notes
82
HLF-4SW
HLN-4SW
64
HLS-4SW
*1 HLF types are used for OFF-lock and HLN types for ON-lock.
*2 Specify the working voltage. Refer to the reference page for type name.
Terminal
cover
Type name
Reference page
MI
3P
MI-4SW3
68
Large
TC-L
3P
TCL-4SW3
Skeleton
TTC
3P
TTC-4SW3
Rear
BTC
3P
BTC-4SW3
MDS (*2)
67
66
Front connection
127.5
Breaker
Breaker
78
8
12.5
10.5
10.5
43
39
25
16
28
200
5
140
118
1.0mmclearance
clearance onon
each
side side
1.0mm
each
of the
handle frame.
of the
handle
frame
3-pole
3-pole
204
252
3-pole
3-pole
M6 tap
or for
7
M6
taps
7 hole
Conductor drilling
Conductor
drilling
for direct connection
for direct connection
194
112
44
Conductor thickness
t=8 max.
(Conductor
thickness
t = 8 max.)
141
191.5
14 for
14
M12 bolt
M12 bolt
51
92
156
12.5
234
47
11.5
31
257
102
297
button
Trip Trip
button
R6
Mounting hole
Mounting
hole
26
Breaker
Breaker
43
110
Insulating barrier
(removable)
Insulation
barrier
(removable)
(Conductor
Conductor
thickness
t=8 max. thickness
t=8 max.)
Front-panel
cutout
Front-panel cutout
Drilling
plan
Drilling plan
Boring
dimensionsfor
forrear
rearconnection
connection
Boring
dimensions
type
barriers (3-pole)
type barriers
(3-pole)
Line
Lineside
side
Groove
reducing
Groove forfor
reducing
heat byby
overcurrent
heat
overcurrent
Breaker
Breaker
M6
screw
or or
f7
M6
taps
4 M6
or 7
4-M6
taptaps
or 7
234
11
M6
for for
M6screw
screw
mounting
breaker
mounting
breaker
10
13 for
13
M12 bolt
M12 bolt
24 24
83
128
26
14
25 20 20
265
234
305
265
7 hole
8
87
3-pole
3-pole
265
Connection
Connection
allowance
allowance
210
66-35
35
rotated
90
Stud
can be
rotated 90
24 24
Stud can be
Mounting
plate
Mounting
plate
35
44
44
87
87
Insulation
tube
Insulation
tube
11
8-M4
8-M4screw
screw
Add
tapped
holesholes
in in
Addthese
these
tapped
88 positions
to standard
boring.
positions
to standard
boring.
Loadside
side
Load
Drilling plan
Drilling
plan
Note
NoteThe
Thebore
boredimensional
dimensionaldrawing
drawingshows
shows
thebreaker
breakerviewed
viewedfrom
fromthe
therear.
rear.
the
Plug-in
Plug-in
Plug-in terminal
block
terminal
block
Breaker
Breaker
3-pole
3-pole
175
24
15
79
218
160
28
18
203
max.max.
203
Connection
Connection
allowance
allowance
24
Mounting angle
Mounting
angle
M8M8
terminal
block
terminal block
mountingscrew
screw
mounting
265
297
320
35
Mounting
angle
Mounting
angle
Stud
Studattachable
attachable in 10
in this direction only
28
13
13
for
M12 bolt
M12
bolt
87
Insulating
barrier
Insulation
barrier
44
3-pole
3-pole
Drilling
plan
Drilling plan
[mm]
83
Rear connection
NF630-SEW
NF630-HEW
300, 350, 400,
300, 350, 400,
500, 600, 630
500, 600, 630
3
4
3
4
690
690
10/10
35/18
30/30
50/50
42/42
65/65
50/50
70/70
50/50
70/70
50/50
70/70
85/85
100/100
85/85
100/100
Number of poles
Rated insulation voltage Ui [V]
IEC/EN
60947-2
(Icu/Ics)
AC
DC
Standard attached parts
(front connection)
NF630-SEW
690V
500V
440V
415V
400V
380V
230V
200V
250 V
NF630-REW
300, 350, 400
500, 600, 630
3
690
70/35
125/63
125/63
125/63
125/63
150/75
150/75
Operating Characteristics
10h
Operating characteristics
5h
2h
1h
30min
20min
14min
10min
6min
4min
2min
126080100s 20%
(at 200%)
(at
200%)
1min
Operating time
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 15 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
AL
AL
Right-side
mounting
Left-side
mounting
AX
AX
SHT or UVT
EAL
EAL
TBL
TBL
MG
MG
TBM
TBM
130
Lead-wire direction
PAL
PAL
ATU
ATU
Note 1
Rated ambient
temperature
0.5s
NF630-SEW NF630-HEW
NF630-REW
Current
Rated
setting Ir
current In
300, 350, 400,
630 A
500, 600, 630 A
Adjustable
120
110
100
90
80
Note 1
Note 1
70
10
Note 1
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
Handle lock device
Notes
Type name
Reference page
F-4S
63
V-4S
62
HL (*1)
HLF-4SW
HL-S
HLS-4SW
Accessories
Mechanical interlock
Large
64
*1 HLF types are used for OFF-lock and HLN types for ON-lock.
*2 Specify the working voltage. Refer to the reference page for type name.
Terminal
cover
Skeleton
Rear
Type name
MI
TC-L
TTC
BTC
84
3P
MI-4SW3
4P
MI-4SW4
3P
TCL-4SW3
3P
TTC-4SW3
4P
TTC-4SW4
3P
BTC-4SW3
4P
Reference page
68
67
BTC-4SW4
MDS (*2)
66
12
Front connection
28
4-pole
4-pole
44
30
Breaker
Breaker
16
39
102
CL
59
12.5
Trip
button
39
Trip button
CL
Neutral pole
Neutral
pole
194
257
CL
R6
CL
118
44
97
f 14 for
14
M12 bolt
M12
bolt
56
51
168
112
185
140
196
3-pole
3-pole
4-pole
4-pole
Breaker
Breaker
CL
Conductor
drilling
for
direct connection
for direct connection
Mounting hole
Mounting
hole
CL
3-pole
3-pole
10.5
Conductor thickness
t=10 max.
(Conductor
thickness
t = 10 max.)
Conductor
drilling
43
103
107
1.0mm1.0mm
clearance
ononeach
clearance
each side
side of handle.
of the handle
frame
M6 screw
M6
taps or
or f 7
7
hole
44
44
3-pole
3-pole
155
Front-plate cutout
Front-panel
cutout
4-pole
4-pole
Drilling
Drilling
plan plan
Boringdimensions
dimensions for
for rear
rear connection
connection
Boring
type(3-pole)
barriers (3-pole)
type barriers
Rear connection
Breaker
Breaker
3-pole
3-pole
Line side
Line
side
Eddy-current
heat by overcurrent
heat-reducing slit
Connection
Connection
allowance
allowance
225
225
194
14
4-M6
taptaps
4 M6
or
7
or f7
breaker
f13
13 for
M12
M12bolt
bolt
Insulating tubetube
Insulating
attached to
attached
to
3P:Center pole
3P:
Center
4P:Center
and pole
4P:neutral
Center
and
poles
87
130.5
neutral poles
24 24
M6
M6breaker
screw
mounting
screw
for mounting
8
10
113
CL
83
128
225
20
32
25 20
screw
M6M6
taps
or
f7
7orhole
265
CL
6 35
CL
8
CL
35
44
44
11
87
43.5
3-pole
3-pole
4-pole
4-pole
11
44
130.5
87
8 M4
screws
8-M4
screw
Add
Addthese
thesetapped
tapped
holes
holesinin8 8positions
positions
to
boring.
tostandard
standard
boring.
Load side
Load
side
Drilling plan
Drilling
plan
Note The
Thebore
boredimensional
dimensional drawing
drawing shows
thebreaker
breakerviewed
viewedfrom
from the
the rear.
rear.
the
Plug-in
Mounting
plate
Mounting plate
4-pole
4-pole
3-pole
3-pole
CL
CL
Breaker
Breaker
CL
55
93
160
28
18
CL
163
Connectionallowance
allowance
Connection
135
mounting screw
25
M8 terminal block
M8 terminalscrew
block
mounting
10
20
25
225
CL
10
280
55
35
Plug-in
Plug-in terminal
block
terminal
block
Stud attachable
in
Stud
attachable
in
this direction only
this direction only
30
121
13f 13
for
M12
bolt
M12
bolt
110
165.5
Insulating barrier
Insulation
barrier
44
87
136
181
3-pole
3-pole
4-pole
4-pole
Drilling plan
plan
Drilling
[mm]
85
Stud
be be
Studcancan
rotated
9090
rotated
24 24
4-pole
4-pole
Mounting
plate
Mounting plate
194
110
CL
94.5
(Conductor
Conductor
thickness
thickness
t=10 max.)
max.
t=10
CL
92
Insulation
barrier
Insulating barrier
(removable)
(removable)
NF800-SEW
NF800-HEW
400, 450, 500,
400, 450, 500,
600, 700, 800
600, 700, 800
3
4
3
4
690
690
10/10
15/15
30/30
50/50
42/42
65/65
50/50
70/70
50/50
70/70
50/50
70/70
85/85
100/100
85/85
100/100
Number of poles
Rated insulation voltage Ui [V]
NF800-SEV
IEC/EN
60947-2
(Icu/Ics)
AC
DC
Standard attached parts
(front connection)
690V
500V
440V
415V
400V
380V
230V
200V
250 V
NF800-REW
400, 450, 500,
600, 700, 800
3
690
70/35
125/63
125/63
125/63
125/63
150/75
150/75
Operating Characteristics
10h
Operating characteristics
5h
2h
1h
30min
20min
14min
10min
6min
4min
2min
126080100s 20%
(at 200%)
(at
200%)
1min
Operating time
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 12 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
Left-side
mounting
Right-side
mounting
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
130
Lead-wire direction
Note 1
Rated ambient
temperature
0.5s
NF800-SEW NF800-HEW
NF800-REW
Current
Rated
setting Ir
current In
400, 450, 500,
800 A
600, 700, 800 A
Adjustable
120
110
100
90
80
Note 1
Note 1
70
10
Note 1
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
Handle lock device
F
V
HL (*1)
HL-S
Type name
F-8S
V-8S
HLF-4SW
HLN-4SW
HLS-8SW
Notes *1 HLF types are used for OFF-lock and HLN types for ON-lock.
*2 Specify the working voltage. Refer to the reference page for type name.
Reference page
63
62
Accessories
Mechanical interlock
64
Terminal
cover
MI
Large
TC-L
Skeleton
TTC
Rear
BTC
86
3P
4P
3P
4P
3P
4P
3P
4P
Type name
MI-8SW3
MI-8SW4
TCL-8SW3
TCL-8SW4
TTC-8SW3
TTC-8SW4
BTC-8SW3
BTC-8SW4
MDS (*2)
Reference page
68
67
66
Front connection
Auxiliary
handle
Auxiliary handle
(removable)
(removable)
8.5
51
70
40
140
210
210
280
3-pole
3-pole
97
f14
14 for
M12 bolt
(Conductor thickness
t = 10 max.)
107
51
70
3-pole
3-pole
Conductor drilling
Conductor
drilling
for direct
direct connection
for
connection
155
M12 bolt
M6 tap
M6
taps or
or f hole
7
7
70
172
40
103
Neutral
pole
Neutral
pole
4-pole
4-pole
22
217
1.0mm
clearance
each side
1.0mm
clearance onon
each
of the
frame
sidehandle
of the handle
frame.
4-pole
4-pole
Front-panel cutout
Drillingplan
plan
Drilling
Front-panel cutout
Boring
Boringdimensions
dimensionsfor
forrear
rearconnection
connection
type(3-pole)
barriers (3-pole)
type barriers
Rear connection
7tap
hole
M6
or f 7
Breaker
Breaker
Groove
reducing
Groove forfor
reducing
heat
byovercurrent
overcurrent
heat by
6-f
6 48
48
10
24 24
25
Mounting
plate
Mounting
plate
M6 taps or
Stud can be
rotated
90
Stud can be
rotated 90
Connection
Connectionallowance
allowance
243
243
tap or f 7
44-M6
M6
taps or 7
10
8
113
32
24 24
45
13
12.5
295
243
10
13 for
M12 bolt
15
70
70
140
f 13 for
13
M12 bolt
M12
bolt
110
M6 screw
for
M6
screw
mounting
breaker
for
mounting
breaker
140
3-pole
3-pole
48
Drilling plan
Drilling
plan
11
70
11
70
210
to standard boring.
140
4-pole
4-pole
8-M4
screw
8 M4
screws
Add
these
tapped
holes in
Add
these
tapped
8holes
positions
boring.
into8standard
positions
Plug-in
Mounting
plate
Plug-in
can
be rotated
90
StudStud
can be
rotated
90
Mounting
plate
terminal
block
Plug-in terminal block
23
126
40
M8
blockblock
mounting screw
M8terminal
terminal
mounting screw
140
187
155
15
f 13 for
13
M12 bolt
M12
bolt
56
112
32
13
25
243
10
301
20
Connection
Connectionallowance
allowance
56
Breaker
Breaker
70
208
3-pole
3-pole
10
Drilling plan
Drilling
plan
140
278
4-pole
4-pole
[mm]
87
button
15
46
Trip
button
Trip
243
Breaker
Breaker
R6
conductor
12
15
8
102
Terminal dimension
dimension
for
forTerminal
directly
connectconnecting
ingdirectly
conductor
14
32
14
4-pole
4-pole
3-pole
3-pole
Breaker
Breaker
275
87
26
46
87
32
32
110
94.5
(Conductor
thickness
Conductor
thickness
t=12
max.
t=12
max.)
92
Insulation barrier
(removable)
Insulating
barrier (removable)
Mounting
hole
Mounting
hole
NF800-UEW
Type name
Rated current In [A]
Number of poles
Rated insulation voltage Ui [V]
NF800-UEW
IEC/EN
60947-2
(Icu/Ics)
AC
DC
NF800-UEW
400, 450, 500, 600, 700, 800
3
4
690
35/35
170/170
200/200
200/200
200/200
200/200
200/200
200/200
690V
500V
440V
415V
400V
380V
230V
200V
300 V
Operating Characteristics
10h
Operating characteristics
5h
NF800-UEW
2h
1h
30min
20min
14min
10min
6min
4min
126080100s 20%
(at 200%)
(at
200%)
1min
Operating time
Rated
current In
800 A
2min
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 12 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
Right-side
mounting
Left-side
mounting
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
130
Lead-wire direction
Note 1
Note 1
Rated ambient
temperature
0.5s
Current
setting Ir
400, 450, 500,
600, 700, 800 A
Adjustable
120
110
100
90
80
Note 1
70
10
Note 1
10
20
30
40
50
60
External Accessories
Accessories
Operating handle
Handle lock device
Mechanical interlock
F
HL
HL-S
MI
3P
4P
Type name
F-8U
HL-4SW
HLS-8UW
MI-8SW3
MI-8SW4
Notes *1 Specify the working voltage. Refer to the reference page for type name.
88
Reference page
63
Accessories
64
Terminal
cover
68
Large
TC-L
Rear
BTC
3P
4P
3P
4P
Type name
TCL-8UW3
TCL-8UW4
BTC-8SW3
BTC-8SW4
MDS (*1)
Reference page
67
66
Front connection
(Conductor
thickness
87
64
8
Handle
Auxiliary handle
(removable)
(removable)
14
110
44(ON
(ONside)
position)
44
123.5
123,5(OFF
(OFFside)
position)
143
Conductor thickness
t=12
t=12
max. max.)
27.5
Insulation
barrier
Insulating
barrier (removable)
(removable)
Mounting
holehole
Mounting
102
12
Conductor drilling
Conductor
drilling
for direct
for
directconnection
connection
252
f 14 for
14
M12 bolt
M12
bolt
314
Conductor
(Conductor
thickness
Insulating barrier
(removable)
Insulation
barrier
(removable) thickness
t=8 max.)
max.
t=8
Mounting
Mounting
holehole
48
110
70
Breaker
Breaker
R6
143
97
6.5
Handle
Auxiliary
handle
(removable)
(removable)
51
3-pole
3-pole
M6
or or
f 7 7
M6screw
screw
Drilling plan
6.5
35
141
Neutral pole
Neutral
pole
70
Drilling plan
194
f 14 for
14
M12 bolt
M12 bolt
210
280
275
48
51
4-pole
4-pole
14
70
70
Front-panel cutout
Front-panel
cutout
112
16
Trip
Trip
button
button
1.0mm
clearance
each side
1.0mm
clearance onon
each
side handle
of the handle
frame.
of the
frame
15
102
290
322
27.5
172
280
4-pole
4-pole
t = 10 max.)
22.5
210
3-pole
3-pole
Breaker
Breaker
(Conductor
thickness
(Conductor
thickness
t=10 max.)
204
92
14
200
5
Neutral
pole
Neutral
pole
4-pole
4-pole
3-pole
3-pole
40
194
14
210
22
f7
40
8
143
15
70
140
275
322
87
32
14
51
conductor
8.5
Trip
Trip
button
button
Terminal
dimension
Terminal
dimension
for for
directly
connecting
directly
connecting
conductor
15
112
200
204
4-pole
252
NF400-UEW
4-pole
NF400-UEW
314
Rear connection
Boring dimensions
dimensionsfor
forrear
rearconnection
connection
type (3-pole)
barriers (3-pole)
type barriers
M6 tap
M6 or
tap7
or f 7 Groove for reducing
Groove for reducing
heat
overcurrent
heat
byby
overcurrent
Breaker
Breaker
Connection
Connection
Mounting allowance
can
allowance Stud
Stud can
bebe
rotated 9090
plate
rotated
25
6-f 48
32
f 13 for
13
M12 bolt
M12
bolt
140
M6 screw
M6
for for
mounting
breaker
breaker
mounting
290
342
290
3-pole
3-pole
10
70
48
140
210
4-pole
4-pole
Drilling
Drillingplan
plan
24 24
26
20
70
70
10
110
4-M6
tap or
f 7or 7
4 M6
tap
290
15
10
210
12.5
342
45
13
290
10
10
24 24
Mounting plate
5
210
83
f 13 for
13
M12 bolt
M12 bolt
11
70
140
11
8-M4
screw
8 M4
screws
Add
tapped
holes in
Addthese
these
tapped
8holes
positions
boring.
into8 standard
positions
to standard boring.
4-pole 4-pole
NF400-UEW
NF400-UEW
[mm]
89
NF1000-SEW, NF1250-SEW
Type name
NF1000-SEW
NF1250-SEW
500, 600, 700,
600, 700, 800,
800, 900, 1000
1000, 1200, 1250
3
4
3
4
690
690
25/13
25/13
65/33
65/33
85/43
85/43
85/43
85/43
85/43
85/43
85/43
85/43
125/63
125/63
125/63
125/63
Number of poles
Rated insulation voltage Ui [V]
IEC/EN
60947-2
(Icu/Ics)
690V
500V
440V
415V
400V
380V
230V
200V
250 V
AC
DC
Standard attached parts
(front connection)
NF1000-SEW
Operating Characteristics
10h
1h
30min
20min
14min
10min
6min
4min
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
Current
Rated
setting Ir
current In
600, 700, 800,
1250 A
1000, 1200, 1250A
Adjustable
2min
126080100s 20%
Operating time
Operating time
1h
30min
20min
14min
10min
6min
4min
(at 200%)
(at
200%)
1min
NF1250-SEW
2h
Rated
current In
1000 A
2min
126080100s 20%
(at 200%)
(at
200%)
1min
30s
20s
10s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
5s
2s
1s
1s
0.2s
0.1s
i
INST pick up current li
Note x 4 x 12 15 %
(Magnification to reference current)
0.01s
60 70
100 125
200
0.1s
1000
1500 2000
i
INST pick up current li
Note x 4 x 12 15 %
(Magnification to reference current)
0.02s
0.01s
3000 4000
60 70
Internal Accessories
100 125
200
1000
1500 2000
3000 4000
Operating handle
Right-side
mounting
Left-side
mounting
0.10.03s
0.060.02s
0.05s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.10.03s
0.060.02s
0.05s
0.02s
0.5s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
Lead-wire
direction
130
Rated ambient
temperature
0.5s
Current
setting Ir
500, 600, 700,
800, 900, 1000 A
Adjustable
Operating characteristics
5h
NF1000-SEW
2h
10h
Operating characteristics
5h
120
110
100
90
80
70
10
10
20
30
40
50
60
External Accessories
Accessories
Handle lock device
HL
Mechanical interlock
MI
3P
4P
Type name
HL (on request)
MI-10SW3
MI-10SW4
Notes *1 Specify the working voltage. Refer to the reference page for type name.
90
Reference page
64
68
Accessories
Terminal
cover
Large
TC-L
3P
4P
Type name
TCL-10SW3
TCL-10SW4
MDS (*1)
Reference page
67
66
Front connection
(Conductor
thickness
Conductor
thickness
= 8, max.
2 pcs)
t=8 t2pcs
110
Insulation
Insulatingbarrier
barrier (removable)
(removable)
15 40
50
BoltM12
M12 50
Bolt
Mounting
Mounting
hole
hole
Breaker
Breaker
375
9.5
406
346
Auxiliary
handle
Handle
(removable)
(removable)
17.5
80
15 32 8
13
Neutral
Neutral pole
pole
70
210
280
43
140
210
f 13 M12
13bolt
for
M12 bolt
4-pole
4-pole
3-pole
3-pole
18.5
70 M8
M8taps
tap or 10
f 10
15 44
133.5
17
140
190
280
70
3-pole
3-pole
4-pole
4-pole
Drilling
plan
Drilling plan
Rear connection
4-pole
4-pole
Mountingplate
hole
Mounting
3-pole
3-pole
97
39.5
81.5
273
12
140
8 32 15
97
Bolt
Bolt M12
M12 45
45
86
(Conductor
Conductor
thickness
thickness
t = 6,2pcs
2 pcs)
max.
t=6
45
13
140
R11.5
269
109
86
Studcan
canbe
berotated
rotated90
90
Stud
Connection
18 Connection
allowance
allowance
13
22
Breaker
Breaker
M8
for mounting
breaker
M8screw
for breaker
mounting
35.5
Breaker
Breaker
70
230
Insulation
Insulationcover
barrier
(removable)
(removable)
80
70
300
1.0mmclearance
clearance on each
1.0mm
each side
the handle
ofside
theofhandle
frameframe.
M8
M8taps
tap or 10
f 10
Front-panel cutout
Front-panel
cutout
3-pole
4-pole
3-pole
4-pole
Drilling plan
Drilling
plan
Plug-in
Mounting
Mountingplate
holes
Breaker
M10
breaker
mounting
M10 for
terminal
block
mounting screw
136
269
100.5
105
13
68
208
134
43
140
15
136
12
Connection
Connection
allowance
allowance
(Conductor
13
Conductor
thickness thickness
Insulation
Insulating
t = 6, 2pcs
2 pcs)
t=6
max.
barrier
barrier
Bolt
Bolt M12
M12 45
45
32 8
104
30
225
25.5
269
28.5
Stud
Stud can
canbe
berotated
rotated90
90
28.5
Plug-in
Plug-interminal
terminalblock
block
12
70
204
3-pole
3-pole
140
274
Drilling
plan
Drilling plan
4-pole
4-pole
[mm]
91
NF1600-SEW
Type name
Rated current In [A]
Number of poles
Rated insulation voltage Ui [V]
IEC/EN
60947-2
(Icu/Ics)
AC
DC
Standard attached parts
(front connection)
NF1600-SEW
NF1600-SEW
800, 1000, 1200, 1400, 1500, 1600
3
4
690
25/13
65/33
85/43
85/43
85/43
85/43
125/63
125/63
690V
500V
440V
415V
400V
380V
230V
200V
250 V
Operating Characteristics
10h
Operating characteristics
5h
NF1600-SEW
2h
1h
30min
20min
14min
10min
6min
4min
2min
Operating time
126080100s 20%
(at 200%)
(at
200%)
1min
30s
20s
10s
5s
2s
Pre-alarm pickup
current Ip
Ir x ( 0.70-0.75-0.800.85-0.90-0.95-1.0)
10 %
1s
STD operating time Ts
0.30.06s
0.20.04s
Pre-alarm operating
time Tp
TL
Tp = Tl 20 %
2
(at 200 %)
0.2s
0.1s
0.10.03s
0.060.02s
0.05s
i
INST pick up current li
Note x 4 x 12 15 %
(Magnification to reference current)
0.02s
0.01s
60 70
100 125
200
1000
1500 2000
3000 4000
Internal Accessories
Operating handle
Right-side
mounting
Left-side
mounting
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
Lead-wire
direction
130
Rated ambient
temperature
0.5s
Current
Rated
setting Ir
current In
800, 1000, 1200,
1600 A
1400, 1500, 1600 A
Adjustable
120
110
100
90
80
70
10
10
20
30
40
External Accessories
Accessories
Handle lock device
HL
Mechanical interlock
MI
3P
4P
Type name
HL (on request)
MI-16SW3
MI-16SW4
MDS (*1)
Notes *1 Specify the working voltage. Refer to the reference page for type name.
92
Reference page
64
68
66
50
60
Front connection
11
2035
4-pole
3-pole
Bolt M10 65
Mounting hole
18.5
280
375
130
115
203
101.5
304.5
364.5
263
3-pole
9.5
Trip button
17.5
406
R11.5
346
210
Breaker
Breaker
Handle
(removable)
97
(185.5)
Conductor
thickness
t = 6 W75
(185.5)
60
38
38 15
Insulation barrier
(removable)
20
49.5
133.5
140
190
280
Neutral 17
pole
4-pole
Rear connection
80
M8 taps or
10 hole
7070
3-pole
4-pole
Drilling plan
Front-panel cutout
38
Stud can be
rotated 90
Breaker
Mounting angle
Mounting angle
38
125
273
11
70
70
Bolt M10 50
210
4-pole
3-pole
11
Bolt M10 50
140125
M8 taps or
10 hole
70
4-pole
Drilling plan
269
506
81.5
273
36
60
54 18
38
273
534
109
109
20
3-pole 140
15
38
15
200
54
140
60
36
38
18
160 min.
269
109
20
109
273
15
Conductor
t = 6 75
20
Conductor thickness
t = 6 75
100 max.
Mounting angle
81.5
212
Stud can be
rotated 90
106106
318
18
60
Connection allowance 15 3 8 1 5
38
15.5
53
138
125
200
38 15
15
11
20 70
210
438
70
292
20
140
332
53
15.5
138
70
398
125
[mm]
93